for vlt 6000 hvac only

50
Global Global Global HVAC HVAC HVAC Danfoss Taiwan Cascade Controller Option For VLT 6000 HVAC Only

Upload: others

Post on 03-Nov-2021

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Cascade Controller Option

For VLT 6000 HVAC

Only

Page 2: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Cascade Controller Option

An option card with 4 additional form C250V relays, software, connectors etc. mounted inside the VLT Standard Cascade control with fixed speed and variable speed or Master/Slave with variable speed only selectableTrue feedback based PI(D) controlBest Efficiency Master/Slave control

Page 3: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Applications

Pressure booster sets / booster stationsSecondary chilled water and variable primary flow pump setsLevel controlled pumps sets(District) Heating Circulating pumpsCondenser fans / cooling tower fans Blowers for Clarifier aeration

Page 4: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Standard Cascade Control

The system consists of 1 variable speed and up to 4 fixed speed pumps/fans

Page 5: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Level Control

Using the built-in PID controller allows easy inverse control

Page 6: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Master/Slave Operation

All pumps orfans aredrive controlled

Page 7: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

.

Basic System Layout

Up to 5 Pumps or Fans1 variable speed pump or fan and up to 4 fixed speed pumps or fans in standard cascade control

Equal and unequal pump/fan capacityOperation hours dependant cycling

Software selectableAll fixed speed pumps or fans and all slaves can be cycled Hours run determine which pump or fan to be switched on or off next.

Page 8: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

The NEW solution

VLT Drive

PIDControl-ler.

CascadeController

With 4additionalrelays.

ContactorArrangement

Page 9: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Capacity Combinations

A predetermined pattern, will make programming easy.

Choice Connected tothe VLT(100%capacity)

No. of additional100% Capacity

No. of additional200% Capacity

No. of additional300% Capacity

1 1 1 (Pump 2) - -2 1 2 (Pumps 2 & 3) - -3 1 3 (Pumps 2,3 & 4) - -4 1 4 (Pumps 2,3,4 &5) - -5 1 1 (Pump 2) 1 (Pump 3) -6 1 1 (Pump 2) 2 (Pumps 3 & 4) -7 1 2 (Pumps 2 & 3) - 1 (Pump 4)8 1 2 (Pumps 2 & 3) - 2 (Pumps 4 & 5)

equal capacity unequal capacity (not suitable for M/S)

Page 10: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

8 pre-determined combinations

Flow Demand

VLT

VLT Pump 2

VLT Pump 1 Pump 1

VLT

VLT Pump 2

VLT Pump 1 Pump 1 Pump 4 Pump 4 Pump 4

VLT

VLT Pump 2

VLT Pump 1 Pump 1 Pump 3 Pump 3 Pump 3 Pump 3 Pump 3 Pump 3

Number of stages is determined by difference between max. and min. flow requirement.

Represented here is choice no. 8 = 1 V/S (100%) + 2 x 100% C/S + 2 x 300% C/S pumps

Page 11: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

PID Controller

Full functionality of the VLT 6000 HVAC built-in PID controller

Anti-wind upLow pass filterNormal / Inverse control2 feedback calculation2 zone controletc.

Page 12: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Control Curve ApproximationStandard Cascade control setpoint correction

H1 = Setpoint (pressure) at full capacity / flow

H0 = Setpoint (pressure) with the variable speed device running only.Hm’s = Intermediate points (calculated automatically)

8000

10000

12000

14000

16000

18000

20000

22000

Ideal

Approximate

Example with 8 stages.

H1

H0

H1 = H0 if sensor can be placed correctly

.

Page 13: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Control Bandwidth’s / Timers

Control bandwidth (% of set point)2 Programmable timers (ON/OFF) determine when to react on feedback to avoid frequent switching

Override Bandwidth (% of set point)A programmable timer to determine reaction time to feedback signal

Override FB highOBW

FB High FBW Set-point

FB Low

Override FB Low

Page 14: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Transition Frequency

It is possible to program at what frequency the constant speed pump/fan is started, when ramping down the variable speed pump/fan

Frequency

Fmax.

Transition frequency

Fmin.

C/S device Cut in.

V/S device

.

Page 15: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

De-Stage Timer

Programmable De-stage timer Like a sleep mode function but for the fixed speed pumps/fans. It switched off a fixed speed pump when the variable speed pump runs at minimum speed for a programmed time.

Optimized energy consumption

Avoids “cooking” of the pump

Page 16: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

User friendly Operation

Guided programming Structure Completely NEW “Quick” Menu (35 parameters)

First perform “Drive set-up” (= Old Quick Menu)Secondly, initialize PID controller.Then Set up the Cascade Controller parameters.Finally, Fine tune the PID controller.

Changed Factory Settings

Page 17: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Protected against drive tripping

The Cascade Controller will maintain operation as a C/S controller, should drive trip.

Redundancy is possible in a Master/Slave arrangement

(Designate an AUX master)

.

Page 18: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Service Parameters

Operation hour counters for each pump Counts the hours for maintenance purposesResettable in case the pump is replacedReset does not affect the counters for pump cycling

Cycle counters for each pumpAdditional counters that count the number of start/stop for maintenance purpose

Relay status readoutAllows to see on the LCP how many pumps are presently in operation

.

Page 19: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Serial Communication?

Possible to combine cascade controller with Serial communication option (N2, FLN, Profibus, LonWorks)

Page 20: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

VLT® Software Dialog

Supports the Basic (VLT 6000 HVAC) parameters.Will from Version 2.30-3 include the new 700 group parameters in the “Parameter Set Up” tool.Can not support the “Test Run / Logging modules with the present VLT(R) dialog Software.

Page 21: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Master / Slave SystemsAll pumps/fans are VLT speed controlled1 VLT hosts the Cascade Controller Option, it’s called the MasterUp to 4 VLT’s act as Slaves following the Masters speed referenceAll pumps/fans are of equal sizeBest Efficiency control pattern

Page 22: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Superiority of Master/Slave Control

Less energy consumption

Complete elimination of pressure surge and water

hammer

Accurate control to a fixed Setpoint

(not within a bandwidth)

Page 23: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Master / Slave Operation

Best Efficiency Control

.

Page 24: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

An excursion to the pumping basics

To examine why Master/Slave is superior, we look at a “real” applicationHere we have a system design point of

680 m3/h or GPM flow

@ 30 m or Ft. head (pressure)

We have a setpoint of 10 m or Ft. head (pressure)

Page 25: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Pump Curve

Lines of different impeller diameters

0 100 200 300 400 500 600

Flow

05

101520253035404550

Tota

l Hea

d (P

ress

ure)

7.0

6.5

6.0

5.55.0

Page 26: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Efficiencies

0 100 200 300 400 500 600

Flow

05

101520253035404550

Tota

l Hea

d (P

ress

ure)

40%

50%

60%

70%

75%

77%

79%

80%

80%

79%

77%

75%

70%

50%60%

Page 27: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Variable Speed

Lines of different speed

0 100 200 300 400 500 600

Flow

05

101520253035404550

Tota

l Hea

d (P

ress

ure)

100%

90%

80%

70%

60%50%40%

30%

Page 28: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Variable Speed Efficiencies

0 100 200 300 400 500 600

Flow

05

101520253035404550

Tota

l Hea

d (P

ress

ure)

40%

50%

60%

70%

75%

77%

79%

80%

80%

79%

77%

75%

70%

50%60%

Page 29: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Adding a Parallel Pump

0 100 200 300 400 500 600

Flow

05

101520253035404550

Tota

l Hea

d (P

ress

ure)

700 800 900 1000

Page 30: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Traditional Staging

0 100 200 300 400 500 600

Flow

05

101520253035404550

Tota

l Hea

d (P

ress

ure)

700 800 900 1000

1 PUMP

2 PUMPS

Page 31: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Mixing Constant and Variable Speed

0 100 200 300 400 500 600

Flow

05

101520253035404550

Tota

l Hea

d (P

ress

ure)

700 800 900 1000

1 PUMP

2 PUMPSMinimum Head

Hzmin= HzfundMin. HeadDeadhead

Page 32: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Traditional Staging

Time

Feed

back

Set PointStagingBandwidth

Page 33: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Full Speed Pump Efficiency

0 100 200 300 400 500 600

Flow

05

101520253035404550

Tota

l Hea

d (P

ress

ure)

700 800 900 1000

40%

50%

60%

70%

75%

77%

77%

75%

70%

50%60%

Page 34: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Variable speed system

0 100 200 300 400 500 600

Flow

05

101520253035404550To

tal H

ead

(Pre

ssur

e)

Page 35: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Variable Speed Pump Efficiency

0 100 200 300 400 500 600

Flow

05

101520253035404550To

tal H

ead

(Pre

ssur

e) 40%

50%

60%

70%

75%

77%

77%

75%

70%

50%60%

Page 36: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

1 + 1 = 2

0 100 200 300 400 500 600

Flow

05

101520253035404550

Tota

l Hea

d (P

ress

ure)

700 800 900 1000

0 100 200 300 400 500 600

Flow

05

101520253035404550

Tota

l Hea

d (P

ress

ure)

0 100 200 300 400 500 600

Flow

05

101520253035404550

Tota

l Hea

d (P

ress

ure)

+

=

Page 37: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

1 pump at full speed

0 100 200 300 400 500 600

Flow

05

101520253035404550To

tal H

ead

(Pre

ssur

e) 40%

50%

60%

70%

75%

77%

77%

75%

70%

50%60%

60% efficiency

Page 38: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

0 100 200 300 400 500 600

Flow

05

101520253035404550

Tota

l Hea

d (P

ress

ure) 40

%50

%

60%

70%

75%

77%

77%

75%

70%

50%60%

2 pumps at 50% speed

>77% efficiency

Page 39: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Significance

Page 40: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

0123456

30 40 50 60 70 80 90 100

Flow Percentage

kW c

onsu

med

Comparison Study

Page 41: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

19% less kWh consumed

1 Best Efficiency 2 Standard Master/Slave

Best Efficiency Staging

2068925596

01000020000

30000

1 2

System

kW c

onsu

med

12

Page 42: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Control Options

20689

3303725596

48492

0.0010000.0020000.0030000.00

40000.0050000.0060000.00

M/S V/S+C/S V/S C/S

kWh

cons

umed

Page 43: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Best Efficiency PC Tool

Input scheme with pump and system data

Page 44: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Best Efficiency PC Tool

Output scheme with staging and de-staging frequencies

Page 45: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Procedure

Input pump and system data

The PC Tool

Models the pump system

Executes efficiency algorithms

Determines best stage on/off frequencies

Program the frequencies in Parameter 739 and 740

Page 46: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

New Construction

Promote differentiating features. We can easily be out-specified by competitorsWe provide a capable system that gets the job done at a low price.

Usually requires commissioning assistancePrice the option to include expected support requirements. Option plus commissioning quoted together.

Page 47: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

OEM Customers:

A key market opportunity for this productWe will make our profit selling them our drive

We shouldn’t price the option too high or we lose our advantage

“price protection” will be perceivedThey will usually commission projectsWe will be including this cost on new construction

Page 48: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

Retrofit:The Cascade Controller is one of the important tools

We should be selling the system based on the total payback, not based on equipment costs.

This option will help us approach the pumping applications without the need for a BMS partner

Page 49: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

FAB

Best energy savings

Pumps operate at η max

Best Efficiency Control

Better energy savings

Less over –pressurization

Control curve approximation

1 system to be familiar with

1 common productCombined M/S & Cascade

FlexibilityVery capable system

5 pump controller

1 product1 computer, not 2Controller option

BenefitAdvantageFeature

Page 50: For VLT 6000 HVAC Only

Global Global Global HVACHVACHVAC Danfoss Taiwan

FAB

Averages wearEqual pump operating time

Pump cycling

Maintain controlRedundancyOperation with drive trip (cc)

Maintenance scheduling

Direct readout of running hrs.

Operation Hour counter

Energy savingsLow wear

best number of pumps running

De-stage timer

Lower system damage/wear

Less water hammer

Transition Frequency

BenefitAdvantageFeature