Forest Grove, OR Non-‐Compliance
Facts: • Elevated using FEMA Funds • Not NFIP compliant • County in viola;on poten;ally • Home owner paying the price
Gales Creek
![Page 2: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/2.jpg)
“A8 & A9” Iden@fying Non-‐Compliance
• EC shows that the enclosed space is short 439 sq.in of flood ven;ng coverage • Air vents were miss-‐rated as well, but Surveyor was accurate • NFIP Lowest rated floor becomes the enclosure floor below the BFE
Surveyor omi+ed diagram
![Page 3: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/3.jpg)
Miss-‐Rated Air Vents
Flaps must be broken off Inserts are not allowed
• Original Thinking 18 x 128 sq.in = 2,304 sq.in • 73 sq.in NET not 128 sq.in GROSS • Actual Flood VenGng coverage 1,314 sq.in • Flood Vents must be passive
![Page 4: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/4.jpg)
Sec@on “B” FIRM Info
“A5” Flood Zone. Any Flood Zone with a “A” in front of it will require flood vents BFE: 204.5
![Page 5: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/5.jpg)
Sec@on “C” Eleva@ons Iden@fying Non-‐Compliance
• Because the LAG (f) is 10.8” lower then the Top of BoYom Floor (e) this space is sub-‐grade
• f) Cannot be greater then e) • Lowest rated floor is 200.3 which equals a -‐4
(BFE 204.5 – 200.3)
![Page 6: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/6.jpg)
Summary of Issues
• Not Enough Flood Ven;ng • Subgrade enclosed space below the BFE • Lowest rated floor a -‐4
![Page 7: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/7.jpg)
Non-‐Compliance -‐ Before Premium
$150,000 Building Coverage Annual Premium: $2,567
![Page 8: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/8.jpg)
Fixing The Issues
1. Must Eliminate Sub-‐Grade Space
![Page 9: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/9.jpg)
Diagram 2 Current
LAG: 201.2’
Top of BoYom Floor: 200.3’ NFIP Lowest Rated Floor -‐4
BFE: 204.5
![Page 10: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/10.jpg)
Now Diagram 7
LAG: 200’ Top of BoYom Floor: 200.3’
![Page 11: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/11.jpg)
Compliant Flood Vent Retro-‐Fit
• ICC-‐ES Cer;fied for 200 sq.a each • 1908 sq.a / 200 = 9.54 Rounded to 10 Vents • Louvers open and close with temperature change
![Page 12: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/12.jpg)
Summary of Fixes • Excavated 10.8” of soil to lower the LAG below the Top of BoYom floor
Changed Building Diagram to a 7 • RetrofiYed in (10) ICC-‐ES Cer;fied Engineered Openings
Now fully compliant with FEMA & Building Codes
• Enclosed Area Below BFE Now NFIP Exempt From Ra;ng Lowest Rated Floor 207.5’ +3!
![Page 13: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/13.jpg)
Results
BFE: 204.5
LAG: 200’
Next Higher Floor: 207.5 New Lowest Rated Floor +3!
![Page 14: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/14.jpg)
Compliance -‐ ARer Premium $150,000 Building Coverage Annual Premium: $279
89% Reduc;on!
![Page 15: Forest’Grove,’ORNon/Compliance’...MissRated’Air’Vents Flaps must be broken off Inserts are not allowed • Original(Thinking(18(x(128(sq.in(=2,304( sq.in( • 73 sq.inNETnot128](https://reader033.vdocuments.net/reader033/viewer/2022051913/600453a0e86aa10e5238fbee/html5/thumbnails/15.jpg)
Recap
• Es;mated Cost For Retrofit: $5,000 • Owner Saves $2,288 a year • ROI a liYle over 2 years • 30 year savings $68,640 • Could have been avoided