fortress

Upload: sitiodistinto

Post on 09-Jan-2016

215 views

Category:

Documents


0 download

DESCRIPTION

SAI Fortress

TRANSCRIPT

  • Best answers in power protection products

    Fortress9910 Uninterruptible Power Systems660VA to 1.3kVA

    Advanced Power Integrity and Management forAS/400 Midrange Computing

    A True UPS

    Reliable, on-line, no-break power to AS/400applications can be user programmed to protect againstdisturbances as low as 27 percent below nominalvoltage. Fortress for AS/400 is the newest member ofthe Fortress family, which recently scored over 300,000hours Mean Time Between Failure (MTBF) in anindependent field research study.

    Expandable and Upgradeable

    Adding modular battery packs allows extendedruntimes. Fortress B63 and B64 are upgradeable to B67or B68 (respectively).

    Intelligent Communications

    An AS/400 interface port, an interface cable, alongwith a keypad and front display panel offer convenientlocal unit communication and monitoring of 14 systemparameters. Fortress also has RS-232 external commu-nications through optional Best Power CheckUPSpower monitoring, management and control software. ABest Power SNMP Adapter enables remote networkoperations.

    Order with New or Installed AS/400s

    You can order Fortress classic black UPS models withAS/400 9402/04 models: 200 Series or 400 Series.Order for installed AS/400 models through the MESupgrade path in the AS/400 configurator.

    A Perfect Match for AS/400s

    Fortress matches the raven black color of the AS/400. Itis extremely compact and designed for office environ-ments.

    U N I N T E R R U P T I B L EP O W E R S Y S T E M S

    P.O.

    Box

    28

    0,

    N9

    24

    6 H

    ighw

    ay 8

    0 S

    ., N

    eced

    ah,

    WI 5

    46

    46

    U.S

    .A.

    1-6

    08

    -56

    5-7

    20

    0/

    1-8

    00

    -35

    6-5

    79

    4(U

    .S.A

    . an

    d Can

    ada)

    Fax:

    1-6

    08

    -56

    5-2

    22

    1

    Fax-

    On-

    Dem

    and:

    1-8

    00

    -48

    7-6

    81

    3

    Web

    Site

    : w

    ww.b

    estp

    ower

    .com

    Support for

    AS/400Advanc

    ed Series

    Models 200

    and 400

  • MLP-0236A 9/971997, Best PowerAll rights reserved.

    Fortress9910 Uninterruptible Power Systems660VA to 1.3kVA

    Optional Battery Packs

    IBM Model Number (9910) B24 B63 B67 B69 B64 B68 B70 6610 6611

    Best Model LI660BW5 LI675BWM LI750BWM LI1.3KBWN LI675DWM LI750DWM LI1.3KDWN LIEBP2W LIEBPW

    Capacity (VA/Watts) 660/400 675/400 750/750 1100/940 675/400 750/750 1300/940

    Dimensions H x W x D (inches) 6.5/5.25/15.5 10.75/5.25/17.25 17.25/8/20 Same as Same as Same as 10/8/19.5

    (mm) 165/135/395 275/135/440 440/205/510 B63/B67 B69 B63 260/205/495

    Weight (lbs) 28 47 122* Same as Same as Same as 68

    (kg) 12.7 21.3 55.3* B63/B67 B69 B63 30.8

    Output (AC) Receptacles Quantity/Type 4 ea 5-15R 6 ea 5-15R 4 ea C13 None

    Output Connector (DC) None 1 ea. Anderson

    Input Connector C14 Anderson

    Equipment cords Quantity/Type 1 ea. C13 to 5-15P 1 ea. C13 to C14

    each 6/1.8 m long N/A

    Runtimes (Full Load) 6.5m 13m 5m *18m 13m 5m *18m N/A

    (Half Load) 18m 35m 15m 42m 35m 15m 42m

    Operation

    Nominal Input Voltage 110/115/120 VAC 220/230/240 VAC N/A

    Input Range of On-line Operation For input range voltage of 92-136 VAC, output For input voltage of 176-254 VAC,

    voltage will be 105-136 VAC output voltage will be 196-254 VAC

    On-Battery Voltage 105-136 VAC 200-254 VAC

    On-Battery Frequency 50/60 Hz 1 Hz, autosensing

    On-Battery Waveform Sine-wave

    On-line Voltage Same as input on line

    Output Protection Automatic current and overvoltage protection

    Lightning and Surge Protection Passed ANSI/IEEE C62.41 Categories A and B. IEC - 801/5

    Normal Mode Surge Let-Through Voltage 0.7% of peak 0.3% of peak (max) 0.6% of peak (max)

    When Subjected to IEEE 587 Cat A 6kV Test

    Noise (RF) Isolation 5-45 dB common-mode, 28-80db normal mode 5-60 dB common-mode, 28-80 db normal mode

    Input Protection Fuse

    Transfer Time 0 ms

    Recharge Time to 85% Capacity Temperature compensated charger provides typical recharge time of 3-12 hours

    Battery Type Sealed, maintenance-free UL 924 recognized

    Battery 24 volts

    Efficiency 95% on line

    User-Selectable Functions Silence Alarm 1; Silence Alarm 2; Low Battery Time Warning Set Point; Auto Restart; Startup

    Test; Communications Mode; Low Voltage Set Point; High Voltage Set Point

    Alarms Overload; High Ambient Temperature; Overcurrent Shutdown; Replace Battery; Inverter

    Failure; High Battery Low Battery; Fan Alarm (some alarms are model-dependent)

    Safety Compliance UL, cUL or CSA-Certified TUV/GS Same as UPS

    EMI Compliance FCC Class B FCC Class A VDE 0871 or VFG 243/46 1992 Level B Same as UPS

    Environmental

    Operating Temperature 0 to 40 C (32 to 104 F)

    Storage Temperature 0 to 40 C (32 to 104 F)

    Humidity 0 to 95%, RH

    Audible Noise On-line at One Meter 38 - 44 db depending on model

    Extended Runtimes with optional External Battery Packs (Full Load)

    UPS One (1) 9910-6610 Two (2) 9910-6610 Three (3) 9910-6610 One (1) 9910-6611 Two (2) 9910-6611 Three (3) 9910-6611

    (LIEBP2W) (LIEBP2W) (LIEBP2W) LIEBPW) (LIEBPW) (LIEBPW)

    B63, B64 1 hour 2 hours 3 hours N/A N/A N/A

    B67, B68 25 minutes 55 minutes 80 minutes N/A N/A N/A

    B69, B70 N/A N/A N/A 50 minutes 75 minutes 100 minutes