Burners
Free flame burners
EMB (E3004 rev. 09 - 18/01/2018)
![Page 2: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/2.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 2
GENERAL WARNINGS:
¾¾ All installation, maintenance, ignition and setting mustbe performed by qualified staff, respecting the norms
present at the time and place of the installation.
¾¾ To avoid damage to people and things, it is essentialto observe all the points indicated in this handbook. The
reported indications do not exonerate the Client/User
from observing general or specific laws concerning acci-
dents and environmental safeguarding.
¾¾ The operator must wear proper DPI clothing (shoes,helmets...) and respect the general safety, prevention
and precaution norms.
¾¾ To avoid the risks of burns or high voltage electrocu-tion, the operator must avoid all contact with the burner
and its control devices during the ignition phase and
while it is running at high temperatures.
¾¾ All ordinary and extraordinary maintenance must beperformed when the system is stopped.
¾¾ To assure correct and safe use of the combustionplant, it is of extreme importance that the contents of this
document be brought to the attention of and be meticu-
lously observed by all personnel in charge of controlling
and working the devices.
¾¾ The functioning of a combustion plant can be dange-rous and cause injuries to persons or damage to equip-
ment. Every burner must be provided with certified com-
bustion safety and supervision devices.
¾¾ The burner must be installed correctly to prevent anytype of accidental/undesired heat transmission from the
flame to the operator or the equipment.
¾¾ The performances indicated in this technical docu-ment regarding the range of products are a result of
experimental tests carried out at ESA-PYRONICS. The
tests have been performed using ignition systems, flame
detectors and supervisors developed by ESA-PYRO-
NICS. The respect of the above mentioned functioning
conditions cannot be guaranteed if equipment, which is
not present in the ESA-PYRONICS catalogue, is used.
CONTACTS / SERVICE:
To dispose of the product, abide by the local legislations
regarding it.
DISPOSAL:
Esa S.p.A.
Via Enrico Fermi 40
24035 Curno (BG) - Italy
Tel +39.035.6227411
Fax +39.035.6227499
ESA Belgium
Zoning Industriel, 4ème rue
B-6040 Jumet - Belgium
Tel +32.71.256970
Fax +32.71.256979
www.esapyronics.com
GENERAL NOTES:
¾¾ In accordance to the internal policy of constant quali-ty improvement, ESA-PYRONICS reserves the right tomodify the technical characteristics of the present docu-ment at any time and without warning.
¾¾ It is possible to download technical sheets whichhave been updated to the latest revision from the www.esapyronics.com website.
¾¾ The EMB products have been designed, manufactu-red and tested according to the most correct construc-tion practices and following the applicable requirementsdescribed in UNI EN 746-2-2010 “Industrial heating pro-cess equipment - Part 2: Safety requirements for com-bustion and for the handling and processing of fuels’.We emphasize that the burners described in this datasheet are provided as independent units and areexcluded from the scope of the Machine Directive2006/42/EC not having any mobile items that are notexclusively manual.
¾¾ Certified in conformity with the UNI EN ISO 9001Norm by DNV GL.
CERTIFICATIONS:
The products conform to the requests for the Euroasia market
(Russia, Belarus and Kazakhstan).
![Page 3: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/3.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 3
APPLICATIONS
The EMB are metallic gas burners are used for direct
heating. These burners allow excess air, stoichiomentric
and excess gas regulation. Depending on the size and
use, this type of burner can be used for natural gas and
LPG combustion (in the standard version) and other
types of gaseous combustive agents with heating diffe-
rent properties (special versions on request).
¾¾Ceramic furnaces or fibre cover treatment furnaces.
¾¾Tunnel or chariot furnaces.
¾¾Dryers.
¾¾Textile and dry cleaning machines (Rameause).
¾¾Stretching furnaces.
CHARACTERISTICS
GENERAL:
¾¾Capacity: From 20 to 2.500 kW
¾¾Temperature limit: 1.000°C
¾¾Air and gas pressure to burner: 45mbar
¾¾Flow ratio: 8 : 1
¾¾Flame speed: 50-60 m/s
¾¾Low CO2 content: <10PPM (@ 3% O2 )
¾¾Excess air: up to 400%
MATERIAL COMPOSITION:
¾¾Mixer body: Cast iron G25
¾¾Gas collector: Cast iron G25
¾¾Flameproof tube: AISI304 / AISI310
¾¾Combustion head: AISI310
¾¾Fixing flange: Fe 360
F3004I03
F3004I04
![Page 4: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/4.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 4
BLOCK HOLDER BURNER VERSION (EMB-BH)
The EMB-BH are gas burners used for direct heating.
These burners allow excess air, stoichiomentric and
excess gas regulation. Depending on the size and use,
this type of burner can be used for natural gas and LPG
combustion (in the standard version) and other types of
gaseous combustive agents with heating different proper-
ties (special versions on request). The burner is pronded
with concrete block holder for special high temperature
application such as:
¾¾NOx galvanizing lines.
¾¾Ceramic furnaces or fibre cover treatment furnaces.
¾¾Tunnel or car bottom furnaces.
¾¾Dryers.
¾¾Stretching furnaces.
¾¾Treatment furnaces.
F3400I05
F3004I06
CHARACTERISTICS
GENERAL:
¾¾Temperature limit: 1.300°C
¾¾Air and gas pressure to burner: 45mbar
¾¾Flow ratio: 8 : 1
¾¾Flame speed: 50-60 m/s
¾¾Excess air: up to 400%
¾¾Excess gas: up to 20%
¾¾Preheated air up to: 550°C
MATERIAL COMPOSITION:
¾¾Mixer body: Cast iron G25
¾¾Gas collector: Cast iron G25
¾¾Flameproof tube: AISI304 / AISI310
¾¾Combustion head: AISI310
¾¾Fixing flange: Fe
¾¾Refractory block: T.max 1750°C
![Page 5: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/5.jpg)
The EMB burners develop the maximum capacity in stoi-
chiometric ratio with 45mbar of air pressure. This implies
the use of low prevalence blowers which are also inex-
pensive; the setting is simplified due the special differen-
tial pressure plugs that allow the measurement of air and
gas flow.
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 5
PARAMETER CAPACITY AND FLAME LENGTH
DESCRPTION
The EMB burner ignition takes place through a high ten-
sion discharge obtained via an electrode and the detec-
tion is performed by another electrode, or by UV scanner
(in block holder version).
ModelCapacity
[kW]
Flame length
[mm]
Flame tube outlet diameter
[mm]
Flame speed[m/s]
Flame ignition and detection
EMB-0 20 150 ÷ 200 37 40 N.1 WAND electrode
EMB-1 30 300 ÷ 400 43 42 N.2 WAND electrodes
EMB-2 80 500 ÷ 700 64 51 N.2 WAND electrodes
EMB-3 150 700 ÷ 1000 94 44 N.2 EN electrodes
EMB-4 300 1000 ÷ 1250 122 52 N.2 EN electrodes
EMB-5 400 1200 ÷1500 122 69 N.2 EN electrodes
EMB-6 600 1500 ÷ 2000 160 56 N.2 EN electrodes
EMB-7 900 1800 ÷ 2400 187 67 N.2 EN electrodes
EMB-8 1.500 2200 ÷ 3000 211 88 N.2 EN electrodes
EMB-9 2000 2800 ÷ 3500 250 75 N.2 EN electrodes
EMB-10 2500 3000 ÷ 3800 250 80 N.2 EN electrodes
The adoption of flame control systems is highly recom-
mended in all plants operating at temperatures lower
than 750°C (UNI EN746/2 Regulation).
The flame lengths and velocities are approximate, they
refer to burners fed by natural gas that are placed in open
air and function in stoichiometric ratio at nominal capaci-
ty.
In special applications, mono-electrodes for the ignition
and flame detection are used or else an electrode for
flame ignition and a UV photocell for the flame detection
is used.
The EMB burners are "nozzle mix" type burners. The fuel
and combustive agents are mixed at the combustion head
to avoid dangerous flame flashbacks. Furthermore, the
special shape of the combustion head allows regulation in
stoichiometric ratio as well as in air excess or gas excess.
The burners can work also with preheated combustion air
up to 550°C.
![Page 6: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/6.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 6
BURNER PERFOMANCE
¾¾Chamber temperature 1000°C
¾¾NOx < 200 mg/Nm3 [O2 = 3% ref.]
¾¾Room air temperature
MAXIMUM CAPACITY
MINIMUM CAPACITY
The flame capacity, length and speed refer to a natu-
ral gas fed burner (8600 Kcal/Nm³) placed in a com-bustion chamber at zero pressure above sea level,
functioning with 10% of excess air.
Free flame applicationBurner model
EMB-0 EMB-1 EMB-2 EMB-3 EMB-4 EMB-5 EMB-6 EMB-7 EMB-8 EMB-9 EMB-10
Burner capacity (2% O2) [kW] 20 30 80 150 300 400 600 900 1500 2000 2500
Combustion air flow [Nm3/h] 22 33 88 165 330 440 660 990 1650 2200 2750
Gas flow [Nm3/h] 2 3 8 15 30 40 60 90 150 200 250
Burner air inlet pressure [mbar] 45
∆p flange gas measurement [mbar] 10
Max capacity
Free flame applicationBurner model
EMB-0 EMB-1 EMB-2 EMB-3 EMB-4 EMB-5 EMB-6 EMB-7 EMB-8 EMB-9 EMB-10
Burner capacity(2% O2) [kW] 2 3 8 15 30 40 60 90 150 200 250
Combustion air flow [Nm3/h] 2,2 3,3 8,8 16,5 33 44 66 99 165,5 220 275
Gas flow [Nm3/h] 0,2 0,3 0,8 1,5 3,0 4,0 6,0 9,0 15,0 20 25
Burner air inlet pressure [mbar] 0,5
∆p flange gas measurement [mbar] 0,1
Min capacity
![Page 7: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/7.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 7
AIR CAPACITY TABLE
G3004I02
0,1
1
10
100
1 10 100 1.000 10.000
EM
B-0
EM
B-1
EM
B-2
EM
B-3
EM
B-4
EM
B-5
EM
B-6
EM
B-7
EM
B-8
EM
B-9
EM
B-1
0
Total air flow (burner + ejector) @ 30 °C P.S.= 1 [Nm3/h]
Burn
er
feedin
g p
ressure
[m
bar]
NATURAL GAS CAPACITY TABLE
EM
B-0
EM
B-1
EM
B-2
EM
B-3
EM
B-4
EM
B-5
EM
B-6
EM
B-7
EM
B-8
1,5
0,1
1
10
0,1 1 10 100
EM
B-9
EM
B-1
0
G3004I01
Natural gas flow @ 20 °C P.S.=0,6 [Nm3/h]
Diffe
ren
tia
l p
ressu
re a
t o
rifice
flo
w m
ete
r [m
ba
r]
![Page 8: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/8.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 8
AIR INLET
1 2
3
5
6
7
13
1410
9
12
11
TO
OT
HE
R B
UR
NE
RS
IGN
DET
4
15
8
GAS INLET
SINGLE ZONE REGULATION
SLOW OPENING
FLOW SCHEME -FREE FLAME METALLIC BURNER
Pos. Description Included Not included
1 Main gas interception ball valve X
2 Balanced modulator X
3 Impulse line X
4 Servo-controlled air regulation butterfly valve X
5 Electric servo-control X
6 Single burner gas interception ball valve X
7 Main burner safety gas solenoid valve X
8 DP gas measurement calibrated flange X
9 Gas passage limiting device X
10 Manual air regulation butterfly valve X
11 DP inlet air pressure measurement calibrated orifice X
12 Free flame burner X
13 Ignition transformer X
14 Flame control X
15 Premix air regulation kit (only LPG versions) X
D3004I01
![Page 9: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/9.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 9
FLOW SCHEME -FREE FLAME METALLIC BURNER
Pos. Description Included Not included
1 Main gas interception ball valve X
2 Balanced modulator X
3 Impulse line X
4 Servo-controlled air regulation butterfly valve X
5 Electric servo-control X
6 Single burner gas interception ball valve X
7 Main burner safety gas solenoid valve X
8 DP gas measurement calibrated flange X
9 Gas passage limiting device X
10 Manual air regulation butterfly valve X
11 DP inlet air pressure measurement calibrated orifice X
12 Free flame burner X
13 Ignition transformer X
14 Flame control X
15 Premix air regulation kit (only LPG versions) X
AIR INLET
1 2
5
13
14
9
12
11
IGN
DET
15
GAS INLET
83
SINGLE BURNER REGULATION
D3004I02
![Page 10: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/10.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 10
WARNINGS
¾¾ The EMB burner ignition must always be carried outat minimum power, modulating towards the maximum,
facilitating the ignition and reducing the outlet overpres-
sures. Thus it is opportune to use slow opening solenoid
valves on the fuel line.
¾¾ The passing from minimum to maximum power andvice-versa, must be gradual and not instantaneous. In
double stage regulations, the use of MRBV regulation
valves (data sheet E1302) is suggested.
¾¾ For all low temperature applications (up to 750°C),the burner ignition and the fuel gas solenoid valve com-
mands must be performed via a certified burner control
device.
¾¾ To avoid possible damage to burners, make sure thatthe blower does not send them air that may be fouled by
combustion products, oils, solvents or other. To avoid
these phenomena from taking place, possibly install the
blower or the suction duct outside the establishment and
far from the exhaust pipes.
¾¾ Check the correct connection of the feeding lines afterinstallation. Before switching the burner on, check that
the combustive air and fuel gas pressure values are cor-
rect (Pag.05).
¾¾ The burner can only function within the indicatedpower range. Functioning at lower or higher powers
could compromise the burner performance as well as its
life span. In which case, the general warrantee condi-
tions will automatically expire and ESA will not be held
responsible for any damage to persons or things.
¾¾ If there is trouble with other devices during the burnerstart up phase, use the connector with anti disturbance
filter for the high-tension (HT) cable connection of the
ignition electrode.
¾¾ Avoid burner ignition close to each other so as not toheat the ignition command system devices (solenoid val-
ves and transformers). Prewash time lapse + first safety
time lapse + min. of 5 sec. = time lapse between one igni-
tion and another. (however, do not attempt more than 2
ignitions during a 30sec. time lapse).
¾¾ Make sure the power supply is TURNED OFF whenintervening on the burner and its devices. In case of bur-
ner malfunctioning, follow the indications in the
'Maintenance' chapter of the present manual or contact
ESA-PYRONICS assistance.
¾¾ Any modification or repair done by third parties cancompromise the application safety and automatically
cause the general warrantee conditions to expire.
![Page 11: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/11.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 11
INSTALLATION
The EMB series burners are supplied with a special fur-nace wall fixing flange. The light obtained for the burnerhousing must leave open space around the burner. Thisspace has then to be filled with ceramic-fibre.
For the installation carefully follow the instructions below:
1 - Place the EMB burners far from heat sources and pro-ducts such as: liquids, solvents or corrosive gases.
2 - Make sure that the housing dimensions and thedistance between the centers of the feeding pipes corre-spond to what is specified in the "Overall dimensions"chapter.
3 - Assemble the burner on the furnace wall (pos. 01)interposing a ceramic fibre gasket between the atta-chment flange and the furnace wall (pos.02) *. During theburner insertion phase check that the insulation previou-sly wrapped around the outside is not altered nor dama-ged. Once the spacer has been fixed onto the furnace,from the inside of the combustion chamber, seal any pos-sible cracks that may be left between the wall and thespacer with ceramic fibre.
4 - Connect the combustion air and fuel gas inlet piping,interposing, if possible, dilation joints in AISI.
5 - Connect electricity to the ignition electrode and to theuv-scan detector making sure not to pass the conductorsnear heat sources.
6 - Check that the burner body and all its metallic ele-ments are earthed with appropriate conductors.
7 - The connecting cable from the ignition transformer tothe electrode must be specific for high tension and notscreened. It must not be more than 1 metre long; other-wise the ignition transformer must be positioned near theburner. The high tension cable must be placed far fromthe power cables and not in metallic ducts. Ideally itshould be left in open air.
8 - For further information please consult the technicaldata sheet concerning the ignition transformers.
9 - Connect electricity to the ignition electrode and to theuv-scan detector making sure not to pass the conductorsnear heat sources.
NOTE: * The furnace wall seal, unless specifically reque-sted by the customer, is not included in the burner supply.
01
02
D3004I03
FIBER CERAMICBY CUSTOMER
80
WALL THICKNESS
D3004I04
![Page 12: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/12.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 12
START-UP - SETTING
PREMIX AIR FLOW SETTING WHERE SCHEDULED (LPG BURNERS)
The procedures indicated in the following chapter must
be carried out by expert technicians. The non-observan-
ce of the instructions given can provoke dangerous con-
ditions.
1 - Check that the combustion air pressure exiting the
blower and the combustive fuel feeding pressure are both
within the allowed range.
2 - Adjust the working pressure and the safety device
pressure of the combustion plant, whether there is one
per burner or one for the whole plant i.e. gas pressure
reduction gear, block valve, relief valve, pressure swit-
ches etc. Simulate the intervention of all the safety devi-
ces including the intervention of the safety over tempera-
ture, checking that the fuel safety block devices act pro-
perly.
3 - Place the motorized air regulation valve in its maxi-
mum opening position and, via the gate valve, regulate
the inlet air pressures to the burner, referring to the
values indicated in the "burner performance" chapter for
the maximum capacities (pag.05).
4 - Place the motorized air regulation valve in its mini-
mum opening position and regulate its opening to obtain
(in burner and ejector inlet) the relative minimum power
pressure.
5 -Activate the burner control device and attempt the igni-
tion until the burner switches on. While attempting to igni-
te the burner, act on the gas adjustment valve and, star-
ting from the totally closed position, open it gradually until
the burner ignites.
6 - Fully open the air regulation valve and adjust the maxi-
mum fuel capacity via the gas adjustment valve, checking
the differential pressure created on the calibrated gas
flange.
7 - Double check that, at minimum and maximum power,
the burner inlet pressure corresponds to the values in the
in the 'Parameter capacity" chapter. These values may be
different depending on whether the burner is on or off.
8 - If necessary, with all burners turned onto the same
power, analyse the combustion products in the chamber
(where possible).
9 - Repeatedly attempt ignition at minimum burner power,
with maximum amplitude, to check the ignition reliability
and flame stability during the adjustment.
The premix line is supplied with the LPG burners. The
setting must be carried out with burner off and in mini-
mum flow conditions. The premix line must be fed by an
inlet necessarily placed upstream the air flow regulation
valve, whether it is in zone or interlocked by the main bur-
ner.
1. Place the burner in the minimum combustion air flow
conditions.
2. Open the premix air tap.
3. Regulate the micrometric pin valve according to the fol-
lowing conditions:
4. Check, however, that at minimum power, the burner
does not create black smoke on the combustion head
and on the electrodes. In case this should occur, increa-
se the premix air setting.
EMB-1: Gas body pressure = 2 mbar
EMB-2: Gas body pressure = 2 mbar
EMB-3: Gas body pressure = 2 mbar
EMB-4: Gas body pressure = 2 mbar
EMB-5: Gas body pressure = 2 mbar
EMB-6: ∆p = 6.5 mbar
EMB-7: ∆p = 2.5 mbar
EMB-8: ∆p = 5 mbar
EMB-9: ∆p=5 mbar
EMB-10: ∆p=5 mbar
![Page 13: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/13.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 13
GENERAL MAINTENANCE PLAN
Operation Type Advised time Notes
High tension electrode connection O annualcheck integrity of outer plastic and oxidi-
zation of internal electrode terminal.
Electrode ignition / detection O annual replace if the kantal terminal is worn.
Flanged tube combustion head O annual
during furnace stop, check that the two
elements do not show signs of oxidiza-
tion caused by high temperature.
Burner setting O annual
check the correctness of air and gas
pressures or oxygen content with a sui-
table analyzer.
Premix air setting (where scheduled) O annualcheck the correctness of the calibration
of the premix line with the burner off.
Replacement of gas side gaskets (**) S biennale
check that the gaskets are free of air
leaks and that there is no vulcanization
in the rubber.
NOTES:
Key: O=ordinary / E=extraordinary
(*) it is suggested that the gaskets on the gas side are replaced after every disassembly of the gas feeding line.
(**) use high temperature gaskets
![Page 14: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/14.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 14
ORDINARY MAINTENANCE
For correct dismantling and better maintenance of the
EMB burner, meticulously follow the instructions below
with the plant turned off.
IGNITION AND FLAME DETECTION ELECTRODE
REPLACEMENT
1 - Check that the burner control device is disconnected.
2 - Disconnect electrical supply to the electrodes
(pos.01).
3 - Unscrew the connector (pos.02) at the base of the gas
collector, removing the electrode (pos.03).
4 - Replace the faulty electrode (pos.03) paying attention
to the correct repositioning of the new electrode.
5 - Reconnect the electrical supply (pos.01).
6 - Check the electrode's correct flame ignition/detection.
01 02 03
D3004I05
![Page 15: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/15.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 15
For correct dismantling and better maintenance of the
EMB burner, meticulously follow the instructions below
with the plant turned off.
BURNER-SHUTDOWN
For correct dismantling and better maintenance of
the EMB burners, meticulously follow the instruc-
tions with the plant turned off. In shutdown condi-
tions of the burner refer to the burner control device
indications and to the relative manual to identify the
cause. The main cases are indicated here below:
¾¾ Illegal flame detection: the shutdown is due to an ille-
gal flame detection during the phases prior to ignition or
after the turning off. The causes are within the detection
system (broken or faulty sensor or presence of humidi-
ty), or in the gas draw from the solenoid safety valve,
which allows the burner to remain turned on.
EXTRAORDINARY MAINTENANCE
¾¾Failed ignition: shutdown is caused due to the fact
that no flame has been created during the starting pro-
cess. The causes can be found in the start-up system
(spark absence, faulty electrodes or incorrect position),
in the bad setting of the fuel and combustion flow or in
the detection system (faulty sensor or interrupted
cables). More precisely, in the first two cases the flame
is not ignited, while in the last case the flame is created
but the burner control device is unable to detect it.
¾¾Flame signal loss: shutdown due to the loss of flame
signal during the normal functioning of the burner. The
causes can be found in the combustion air flow adju-
stment (rapid flow variations, adjustment out of allowed
range). They can also be found in the detection system
(faulty, dirty or badly positioned sensors).
![Page 16: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/16.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 16
EMB-0 OVERALL DIMENSIONS
86
Ø26
9
Ø70
± 5
120 (
a)
Nr.4 Ø10 holes (a)
Air inletRp 1"
Gas inlet
Rp 3/8"
100 (
a)
Ø42.4
X=
Wall
thic
kness
73
8
159
Min
. 100 (
b)
Min
. 100 (
b)
Ø47.5
Gas inletR 3/8"
Rp 3/8"
Ø54
Gas orifice flowmeter (included)
Assembly by customer
75
NOTES:
(a) Suitable on
customer request
(b) by customer
D3004I06
![Page 17: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/17.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 17
EMB-1-CH4 OVERALL DIMENSIONS
RA
Ø 48.3
70
±5
Nr.4 holes Ø 13
83
R 1/2"
Air inlet
Ø 60
88
10
Rp 1.1/2"
Gas inlet Rp 1/2"
17
1
X=
Wa
ll th
ickn
ess
Min
.10
0 (
b)
Min
.10
0 (
b)
43
.5 Gas inlet
15
0 (
a)
28
1
Gas orifice flowmeter (included)
Assembly by customer
107
86
NOTES:
(a) Suitable on
customer request
(b) by customer
12
0 (
a)
D3004I07
![Page 18: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/18.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 18
EMB-1 LPG OVERALL DIMENSIONS
RA
Ø 48.3
70
±5
N°4 holes Ø 13 onD.B.C Ø120 (a)
83
R 1/2"
Air inlet
Ø 60
88
10
Rp 1.1/2"
Gas inlet Rp 1/2"
171
X=
Wall
thic
kness
Min
.100 (
b)
Min
.100 (
b)
43.5
Gas inlet
150 (
a)
142 ±
5
31
5
NOTES:
(a) Suitable oncustomer request
(b) by customer
Gas orifice
flowmeter (included)
Assembly by customer
107
90
Premixing air inlet Rp 1/4"
D3004I08
![Page 19: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/19.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 19
EMB-2-CH4 OVERALL DIMENSIONS
Ø70
RA
Rp 1.1/2"
10
88
8
19
6
14
0 (
a)
17
0 (
a)
AIR INLET
X =
Wa
ll th
ickn
ess
N°4 holes Ø13 (a)
10
Rp 1/2"GAS INLET
Ø82
R 1/2"Gas inlet
10
0 M
in.
(b)
44
10
0 M
in.
(b)
107
103
Gas orifice flowmeter (included)
Assembly by client
31
6
70
±5
NOTES:
(a) Suitable onclient request
(b) by client
D3004I09
![Page 20: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/20.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 20
EMB-2 LPG OVERALL DIMENSIONS
Ø70
RA
Rp 1.1/2"
10
88
8
19
6
140 (
a)
170 (
a)
AIR INLET
X =
Wall
tig
htn
ess
Nr.4 holes Ø13 (a)
10
Rp 1/2"GAS INLET
Ø82
106.5
103
31
6
70
±5
Premixing air inlet Rp 1/4"
142±5
Nr.4 holes Ø 13 onD.B.C Ø120 (a)
R 1/2"Gas inlet
10
0 M
in.
(b)
44
10
0 M
in. (b
)Gas orifice flowmeter (included)
Assembly by client
NOTES:
(a) Suitable onclient request
(b) by client
D3004I10
![Page 21: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/21.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 21
EMB-3-CH4 OVERALL DIMENSIONS
AIR INLET
GAS INLET Ø1"
DN65
GAS INLETRp 1"
Gas orifice flowmeter (included)Assembly by client
10
0 M
in.
(b)
44
10
0 M
in.
(b)
NOTES:
(a) Suitable onclient request
(b) by client
10
11
0
21
0
27
4
103,5
108
WA
LL T
HIC
KN
ES
S "
X"
Ø101,6
20
0 (a
)
24
0 (a
)
Nr.4 holes Ø14 (a)
Ø113
D3004I11
![Page 22: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/22.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 22
EMB-3 LPG OVERALL DIMENSIONS
GAS INLET Ø 3/4"
Ø113
Gas orifice flowmeter (included)
Assembly by client
10
0 M
in.
(b)
44
10
0 M
in.
(b)
NOTES:
(a) Suitable oncustomer request
(b) by client
Premixing air inlet Rp 1/4"
10
11
0
21
0
32
6
104
108
Ø101,6
WA
LL T
HIC
KN
ES
S "
X"
14
0±5
20
0
24
0
Nr.4 holes Ø14
2437
GAS INLETRp 3/4"
AIR INLETDN65
D3004I12
![Page 23: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/23.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 23
EMB-4-CH4 OVERALL DIMENSIONS
AIR INLETDN65
10
0 M
in (
b)
67
10
0 M
in.
(b)
Gas inlet Ø 1.1/2"
Gas orifice flowmeter (included)Assembly by client
NOTES:
(a) Suitable onclient request
(b) by client
10
11
0
21
8
27
9 W
AL
L T
HIC
KN
ES
S "
X"
20
0 (a
)
24
0 (a
)
104
119
Nr.4 holes Ø14 (a)
Ø129
Ø141
GAS INLETRp 1.1/2"
D3004I13
![Page 24: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/24.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 24
EMB-4 LPG OVERALL DIMENSIONS
AIR
INLETDN65
Gas inlet Ø 1"
Gas orifice flowmeter (included)Assembly by customer
10
0 M
in.
(b)
44
10
0 M
in.
(b)
NOTES:
(a) Suitable oncustomer request
(b) by customer
20
0 (
a)
24
0 (
a)
Nr.4 holes Ø 14 (a)
24
Ø129
WA
LL T
HIC
KN
ES
S "
X"
101
10
,02
21
8
33
9104
130
14
0±5
37
Ø141
Premixing air inlet Rp 1/4"
GAS
INLETRp 1"
D3004I14
![Page 25: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/25.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 25
EMB-5-CH4 OVERALL DIMENSIONS
X=
Wall
thic
kness
Ø129
Ø203
Nr.4 holes Ø14 on 235 D.B.C.
AR
Gas inletRp 1.1/2"
100 M
in (
a)
67
100 M
in.
(a)
Gas inlet Ø 1.1/2"
Gas orifice flowmeter (included)Assembly by customer
Air inletØ 4"
10
7
13
1137
26
8
126
135
Ø141 NOTES:
(a) by customer
D3004I15
![Page 26: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/26.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 26
EMB-5 LPG OVERALL DIMENSIONS
Ø129
110421 ± 10
12292 4850
Premix air inlet Rp 1/2"
126
Ø141
Gas orifice flowmeter (included)Assembly by customer
Gas inlet Ø 1"
10
0 M
in.
(a)
44
10
0 M
in.
(a)
Gas inletRp 1"
AR
Ø203
Nr.4 holes Ø14 on 235 D.B.C.
Air inletDN100
83
13
11
37
35
1X
= W
all
thic
kn
ess
NOTES:
(a) by customer
D3004I16
![Page 27: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/27.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 27
EMB-6-CH4 OVERALL DIMENSIONS
Gas inlet
RA
Ø 2
03
Rp 2"
Air inletDN150
Gas orifice flowmeter (included)
Assembly by customer
Gas inlet Ø 2"
10
0 M
in.
(a)
70
10
0 M
in.
(a)
Nr.4 holes Ø14 on 235 D.B.C.
Ø168
12
11
75
15
5
45
1X
= W
all
thic
kn
ess
156
186
NOTES:(a) by customer
Ø180
D3004I17
![Page 28: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/28.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 28
EMB-6 LPG OVERALL DIMENSIONS
Gas inlet
RA
Ø 2
03
Rp 1.1/2"
Air inletDN150
Gas orifice flowmeter (included)Assembly by customer
Gas inlet Ø 1.1/2"
Nr.4 holes Ø14 on 235 D.B.C.
Ø168
17
51
55
X=
Wa
ll th
ickn
ess
156
1861
00
Min
. (a
)7
21
00
Min
. (a
)
1221204812092
501± 5
Premix airInlet Rp 1.1/2"
94
33
0
62
4
NOTES:(a) by customer
Ø180
D3004I18
![Page 29: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/29.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 29
EMB-7-CH4 OVERALL DIMENSIONS
67 Min=100mm (b)
Gas orifice flowmeter (included)Assembly by client
NOTES:
(a) Suitable onclient request
(b) by client
Min=100mm (b)
WA
LL T
HIC
KN
ES
S "
X"
AIR INLETDN 150
GAS INLETDN50
Ø207
Rp
2"
Rp
2"
Nr. 4 holes Ø18
15
21
7
44
3
51
6
Ø195
Ø3
60
(a
)
Ø4
00
(a
)
D3004I19
![Page 30: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/30.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 30
EMB-7 LPG OVERALL DIMENSIONS
Gas orifice flowmeter (included)Assembly by client
PREMIX
AIR INLET
Rp 1/2"
67 Min=100mm (b)
Rp
2"
Rp
2"
Min=100mm (b)
NOTES:(a) Suitable on
client request(b) by client
LPG INLETDN50
Ø3
60
(a
)
Ø4
00
(a
)
Nr.4 holes Ø18 (a)
15
21
7
44
4
54
059
2W
AL
L T
HIC
KN
ES
S "
X"
n195
226
169
422
AIR INLETDN 150
n207
D3004I20
![Page 31: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/31.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 31
EMB-8-CH4 OVERALL DIMENSIONS
Gas orifice flowmeter (included)Assembly by client
AIR INLETDN 200
GAS INLETDN65
Ø7
6.1
Ø7
6.1
42 Min.=100mm (b)Min.=100mm (b)
NOTES:
(a) Suitable onclient request
(b) by client
Ø219,1
WA
LL T
HIC
KN
ES
S (
a)
15
21
7
44
351
6
169
226
Ø3
60
(a)
Nr.4 holes Ø18(a)
Ø231
Ø4
00
(a)
D3004I21
![Page 32: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/32.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 32
EMB-8 LPG OVERALL DIMENSIONS
Gas orifice flowmeter (included)Assembly by customer
PREMIX
AIR INLET
Rp 1/2"
Ø231
AIR INLETDN 200
GAS INLETDN65
NOTES:
(a) Suitable oncustomer request
(b) by customer
Nr.4 holes Ø18 (a)
Ø4
00
(a)
15
21
6,9
4
44
4
54
059
2 W
AL
L T
HIC
KN
ES
S "
X"
169
226
422
Ø219,1
Ø7
6.1
Ø7
6.1
42 Min.=100mm (b)Min.=100mm (b)
Ø3
60
(a)
D3004I22
![Page 33: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/33.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 33
EMB-9 CH4 OVERALL DIMENSIONS
Gas orifice flowmeter (included)Assembly by customer
Ø2
.1 2"
42Min.=100mmby customer
Min.=100mmby customer
NOTES:
(a) Suitable oncustomer request
(b) by customer
W
AL
L T
HIC
KN
ES
S =
"X
"
AIR
IN
LE
T
DN
25
0
201232
28
2
Ø256
Ø400
Ø370
53
961
6
45°
GA
S
INL
ET
DN
65
Ø270
Ø14x8
Ø2
.1 2"
D3004I24
![Page 34: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/34.jpg)
EMB-9 GPL OVERALL DIMENSIONS
W
ALL T
HIC
KN
ES
S =
"X
"
AIR
IN
LE
T
DN
250
201
232
282
Ø256
Ø400
Ø370
5396
16
45°
GA
S
INLE
T
DN
65
Ø270
Ø14x8
G 1/2"
PREMIX
AIR INLET
422
Gas orifice flowmeter (included)Assembly by customer
Ø2.1 2"
42Min.=100mmby customer
Min.=100mmby customer
NOTES:
(a) Suitable oncustomer request
(b) by customer
Ø2.1 2"
D3400I26
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 34
![Page 35: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/35.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 35
EMB-10 CH4 OVERALL DIMENSIONS
Gas orifice flowmeter (included)Assembly by customer
42MIN = 100mmBY CLIENT
MIN = 100mmBY CLIENT
NOTES:(a) Suitable on
customer request(b) by customer
Ø8
8.9
Ø8
8.9
WA
LL T
HIC
KN
ES
S =
"X
"
AIR
IN
LE
T
DN
25
0
201
262
28
2
Ø256
Ø460
Nr.8 holes Ø14Ø430
55
963
6
45°
GA
S
INL
ET
DN
80
Ø270
D3400I25
![Page 36: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/36.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 36
EMB-10 GPL OVERALL DIMENSIONS
Gas orifice flowmeter (included)Assembly by customer
Ø88.9
Ø88.9
NOTES:(a) Suitable on
customer request(b) by customer
WA
LL T
HIC
KN
ES
S =
"X
"
AIR
IN
LE
T
DN
250
201
262
282
Ø256
Ø460
Ø430
5596
36
GA
S
INLE
T
DN
80
Ø270
Ø14x8
PREMIX
AIR INLET
G 1/2"
422
655
45°
42Min.=100mmby customer
Min.=100mmby customer
D3400I27
![Page 37: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/37.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 37
EMB-6-BH OVERALL DIMENSIONS
184
358
15
50
350
UV-SCANNERG3/4" socket
Ø440
No.8 holes Ø18
425
Ø480
AIR INLETDN150
GAS INLETDN32/DN40
Ø3
80
FU
RN
AC
E H
OU
SIN
GH
OL
E Ø
39
2
CERAMIC FIBERBY ESA. DO NOTREMOVE!
D3004I23
![Page 38: Free flame burners - esapyronics.com · and precaution norms. ¾To avoid the risks of burns or high voltage electrocu- ... Belarus and Kazakhstan). EMB - E3004 rev. 09 - 18/01/18](https://reader034.vdocuments.net/reader034/viewer/2022051604/5ffdc032b6e523308109a7e5/html5/thumbnails/38.jpg)
EMB - E3004 rev. 09 - 18/01/18
www.esapyronics.com 38
ORDERING CODE FOR COMPLETE BURNER
- --EMB- --
The codes marked with an asterisk (*) indentify the standards.
Notes:
1 Particular performance according to gas characteristics2 Standard version for free flame applications3 Version for applications with burner placed in open tube. Available up to version 4.4 Available in the 3,4,5 and 6 models (see "ignition and detection"paragraph).5 In open radiant tube applications.
Model
EMB-0EMB-1EMB-2... (see capacity table)
0
1
2
.....
Fuel
Natural gas
LPG
Poor gas (1)
CH4
GPL
GP
Gas adjuster
With gas adjusterWithout gas adjuster
GA*F
Type of flanging
According to ESA drawingAccording to Client's drawing
E*C
Ignition and detection
Ign. + det. ElectrodeMono electrodePilot burner (4)
E*MP
01
01 02 03 04 05 06
02
03
07
"X" flanged tube length
Indicate the length in mm (see overall dime-nions)
...
06
05
Flame length
Short flame (2)Long flame (3)
FC*FL (5)
04
-07