fsss control

Upload: mukesh

Post on 01-Jun-2018

233 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/9/2019 FSSS Control

    1/25

    FSSS DESIGN DESCRIPTION

    1OF26 SPERI

    HARYANA POWER

    GENERATION CORPORATION

    PANCHKULA, HARYANA

    DESEIN PRIVATE LIMITED

    CONSULTING ENGINEER,

    NEW DELHI

    CENTRAL ELECTRICITY

    AUTHORITY, SEWA BHAWAN

    DCR THERMAL POWER PROJECT

    (2X300MW), YAMUNANAGAR

    FSSS DESIGN DESCRIPTION

    RELIANCE ENERGY LIMITED

    REL TOWER, A-2, SECTOR-24

    NOIDA (U.P) – 201301 

    SHANGHAI ELECTRIC (GROUP)

    CORPORATION (SEC)

    3669 Jindu Road, Shanghai, China 

    HONEYWELL Honeywell(Tianjin) Ltd

    Shanghai Power Equipment

    Research Institute

  • 8/9/2019 FSSS Control

    2/25

    FSSS DESIGN DESCRIPTION

    2OF26 SPERI

    HONEYWELL  

    Honeywell(Tianjin) Ltd  

    Shanghai Power Equipment Research Institute 

    Project: DCR THERAMAL POWER PROJECT (2X300MW), YAMUNANAGAR

    Document title: FSSS DESIGN DESCRIPTION

    Document no: 93601179-FSSS-1PSC-01-01

    Endorsement

    Guo

    Rong 2007.1 KangLei 2007.1 Yangjingqi 2007.1

    REV DRAWN DATE CHECKED DATE REVIEWED DATE APPROVED DATE REM.

     

  • 8/9/2019 FSSS Control

    3/25

    FSSS DESIGN DESCRIPTION

    3OF26 SPERI

    YANMUNA POWER PLANT FSSS DESIGN

    TABLE OF CONTENTS

    1,  Logic design of MFT--------------------------------------------- ----------------------------4

    2,  Logic design of furnace purging-------------------------------------------------------------7

    3,  Logic design of leakage test ------------------------------------------------------------------8

    4,  Logic design of oil trip-valve-----------------------------------------------------------------11

    5,  Logic of oil back-valve------------------------------------------------------------------------11

    6,  Logic design of OFT--------------------------------------------------------------------------12

    7,  Logic design of oil burner--------------------------------------------------------------------13

    8,  Programme of pulverizer logic design-----------------------------------------------------18

    9,  Pulverizer seal air damper logic-------------------------------------------------------------21

    10,Burner inlet cut off valve logic---------------------------------------------------------------212

    11,Pulverizer outlet cut off valve logic---------------------------------------------------------22

    12, Pulverizer inlet cooling valve logic---------------------------------------------------------22

    13, Pulverizer inlet hot valve logic--------------------------------------------------------------22

    14,  Pulverizer logic---------------------------------------------------------------------------------23

    15,Coal feeder logic--------------------------------------------------------------------------------23

    16, Coal feeder outlet valve logic----------------------------------------------------------------23

    17,Coal feeder inlet valve logic-------------------------------------------------------------------25

    18,Pulverizer fire steam valve logic--------------------------------------------------------------2519,Cooling fan logic---------------------------------------------------------------------------------25

    20, Runback Logic design--------------------------------------------------------------------------26

  • 8/9/2019 FSSS Control

    4/25

    FSSS DESIGN DESCRIPTION

    4OF26 SPERI

    一、LOGIC DESIGN OF MFT

    The Conditions Of MFT Action:

    Condition OR)

    MFT action by any condition coming

    Remark

    1.  Turbine trip 10OTRIP

    2.  All of the P.D.F stopped 10HLB10AN001XB02A,10HLB20AN001XB02A

    3.  All of the I.D.F stopped 10HNC31AN001XB02A,

    10HNC32AN001XB02A,10HNC33AN001XB02A

    4.  All of the P.A.F stopped(any

    Pulverizer is Running)

    10HFE10AN001XB02A,10HFE20AN001XB02A

    5.  All of the cooling air fan stopped 10HLSGC001DI03,10HLSGC002DI03

    6.  (XXXPa)Pressure of cooling air low(two

    of three) Delay 10s

    10HLS10CP304,10HLS10CP305,

    10HLS10CP306

    7.  (XXXPa)Pressure of furnace high(two of

    three)

    10HCP302B,10HCP303A,10HCP304A

    8.  (-XXXPa)Pressure of furnace low(two of

    three)

    10HCP302A,10HCP303B,10HCP304B 

    9.  (XXXmm)Level of drum high(two of

    three)

    10ADRUMLVL,10BDRUMLVL,10CDRUMLVL

    10. (-XXXmm)Level of drum low(two of

    three)

    10ADRUMLVL,10BDRUMLVL,10CDRUMLVL 

    11. All of the air preheaters stopped 10HLD11AC001XB02A,

    10HLD11AC002XB02A,

    10HLD12AC001XB02A,

    10HLD12AC002XB02A,

    12. Air flow less than 30% Delay 60s 10AIR30L

    13. Manual trip by operator

    14. (545℃)Reheater lose protection Furnace outlet air temperature high,

    high temperature drain tap and

    bypass valve closed

    15. Fuel lose All of the pulverizers stopped and

    oil trip valve closed, Or all of the

    pulverizers stopped and burner oil

    valve tripped(any three have been

    opened)

    16. Flame lose of any corner more than half pulverizers are

    running, but any corner loses flame

  • 8/9/2019 FSSS Control

    5/25

    FSSS DESIGN DESCRIPTION

    5OF26 SPERI

    and the running pulverizers number

    >= 3

    17. Flame lose of furnace At least 3 flames can’t be detected

    by flame detector in every layer and

    pulverizers have been started

    MFT logic is of the function of the first out memory, record the

    reset of MFT .

    The actions of FSSS will come after MFT action:

    1.  Close oil trip valve FSSS

    2.  All of the ignitors canceled, retracted and forbidden FSSS

    3. 

    All of the burner oil valves closed FSSS

    4.  All of the pulverizers and coal feeders trip FSSS

    5.  The pulverizer outlet valves close FSSS

    6.  The coal feeder inlet & outlet valves close,

    pulverizers hot air valve & cool air valve closeFSSS

    MFT relay action 

    MFT relays act by getting power when any condition of MFT action is coming 

    MFT relay reset 

    Condition AND) remark

    1.  No condition of MFT action is coming

    2.  The purge of furnace is completed

    3.  MFT is reset by the operator

    MFT relay is reset by all of the three conditions coming

    Fig.(1)

  • 8/9/2019 FSSS Control

    6/25

    FSSS DESIGN DESCRIPTION

    6OF26 SPERI

    As shown in Fig.(1),the first out of MFT will be displayed when MFT is coming.

    We can select the button as shown in Fig.(1) to reset MFT after no MFT

    condition coming and completing the purge of furnace, and a red frame appears

    around the operating faceplate which indicates that we can reset the MFT by

    left mouse clicking on the “MFT RESET” button.

    二、LOGIC DESIGN OF FURNACE PURGING

    Explanation of furnace purging:

    We must purge furnace before every time of starting boiler or after MFT

    tripped(no burner is running), which means that purging the combustible in

    the furnace and flue in valid time by prescriptive air flow to confirm the

    cleanness of the flue. We can reset the MFT relay only after furnace purging

    completed.

    Preconditions of furnace purging:

    Condition AND) Remark

  • 8/9/2019 FSSS Control

    7/25

    FSSS DESIGN DESCRIPTION

    7OF26 SPERI

    1.  No condition of purging completed 

    2.  No condition of MFT 

    3.  Any P.D.F is running and outlet valve is opened 

    4. 

    The chimney and end of flue is expedite(at least

    one of the flue is expedite, means that the inlet

    valve of the air preheater, I.D.F , electric dust

    catcher are opened), and the I.D.F is running

    5.  All of P.A.F stopped 

    6.  The motor and rotor of air preheater A(or B) are

    running normally 

    I. 

    7.  All of the electric dust catchers stopped 

    8.  No flame in the furnace 

    9.

      All of the burner oil valves closed 10. All of the coal feeders stopped 

    11. All of the pulverizers stopped 

    12. All of the pulverizer outlet valves closed 

    The process of purging

    We must purge furnace before every time of starting boiler or after

    MFT tripped(no burner is running), “purge is ready” will be displayed

    in the picture when all of purge conditions are coming, then operator

    can start purge after clicking the “start to purge” button.

    一,Send out the signal to open the secondary air baffle (Long signal, willbe reset after purge completed)

    二, Start to count down after all of the conditions are ready:

    Condition AND) Remark

    1.  Air flow more than 30% From MCS 

    2.  All of the secondary air baffle

    position more than 80%From MCS

    3.  The level of drum normal From MCS

    4. 

    The minus pressure of furnacenormal

    “Purge is running” signal will be sent out after all of the above

    conditions are ready, and last 300s. “Purge is completed” signal will

    be sent out after the leakage test completed successfully.

    We should wait one minute at least to start the purging if the MFT is

    caused by P.D.F or I.D.F tripped.

    三,If any purging condition is not satisfied during the 300s, the “purging

    is interrupted” signal and cause will be sent out , the boiler need to

    be purged again. We can purge again after all of the conditions are ready

  • 8/9/2019 FSSS Control

    8/25

    FSSS DESIGN DESCRIPTION

    8OF26 SPERI

    until purging completed.

    三、LOGIC DESIGN OF LEAKAGE TEST

    Preconditions of leakage test:

    Condition AND) Remark

    1. Oil pressure normal

    2. Oil trip-valve closed

    3. Oil back-valve closed

    4. All of the burner oil valves closed

    5. OFT is coming or No MFT & pulverizers are

    running

    Start leakage test:

    Start leakage test manually

    Stop leakage test OR):

    1.  Operator stops leakage test manually

    2.  MFT is coming ( MFT occurs during the leakage test on the boiler running

    normally)

    3.  Leakage test failure

    4.  Leakage test completed successfully

    Step design of leakage test:

    一, Open oil supply-valve

    二, Oil supply-valve opened, open oil trip-valve

    三, Oil trip-valve opened & oil back-valve closed, delay 15s , send out

    signal to detect oil pressure .

    1. “Leakage test failure” will be sent out when the oil pressure is not

    normal, then stopping the leakage test(close the oil trip-valve).

    2. “Close oil trip-valve” signal will be sent out if oil pressure is

    normal after 45s delay.

    四, Oil back-valve & oil trip-valve closed, “detect oil pressure” will besent out after 180s delay.

    1.  Oil pressure is higher or not(leakage may be caused by oil trip-valve)

    2.  Oil pressure is lower or not(leakage may be caused by oil back-valve

    or burner oil valve)

    3. “Leakage test failure” will be sent out to stop test if oil pressure

    is higher or lower ,then oil supply-valve and oil back-valve will be

    closed automatically.

    4.  Oil back-valve will be opened after 20s delay if the oil pressure is

    normal

  • 8/9/2019 FSSS Control

    9/25

    FSSS DESIGN DESCRIPTION

    9OF26 SPERI

    五, After oil back-valve opened and oil trip-valve closed , oil pressure will

    be detected after 10s delay

    1. “Leakage test failure” will be sent out to stop test if oil pressure

    is not low (leakage pressure high)

    2.  Oil back-valve will be closed after 25s delay if there is no failure

    六, Alarm will be sent out if there is any failure in the test of oil trip-

    valve or back-valve, then “Leakage test failure” will be sent out to

    stop test

    七, “Leakage test completed successfully” will be sent out after clicking

    the “test bypass” button

    八, If the leakage test is failed , we should check the cause , then start

    test again by clicking the “start leakage test” button after reset the

    test.九, The test will be stopped by clicking the “stop” button during the test,

    and oil supply-valve and back-valve will be closed

    Leakage test is of function to indicate the information and alarm about

    process 、end of test

    Fig. 3)

  • 8/9/2019 FSSS Control

    10/25

  • 8/9/2019 FSSS Control

    11/25

    FSSS DESIGN DESCRIPTION

    11OF26 SPERI

    1. MFT or OFT is coming ( leakage test is not running) Long

    signal

    2. Leakage test failure

    Oil trip-valve will be controlled automatically during the leakage test

    五、LOGIC DESIGN OF OIL BACK-VALVE

    1.  Oil back-valve will be controlled automatically during the leakage test

    2.  If the condition of OFT reset is ready, operator can reset OFT ,then oil

    back-valve will be opened automatically

    六、LOGIC DESIGN OF OFT

    Conditions of OFT action

    Condition OR) Remark

    1.  MFT(Long signal) 

    2.  OFT manually 

    3.

     Oil trip-valve or supply-valveis closed and burner valve is

    not closed 

    4.  Oil pressure is low during the

    burner is running

    Oil pressure is low after any burner

    valve is opened

    5.  Any burner valve failure No opened or closed signal during 15s

     

    After OFT is coming:

    1.  Close the oil trip-valve

    2.  Retract the oil gun and igniter

    3. 

    Close all of the burner oil valves

    Reset of OFT (AND): 

    1.  All of the oil guns and burner oil valves are closed

    2.  Leakage test completed

    3.  No condition of OFT

    4.  Click “Reset OFT” button

    As shown in Fig. (1) , the operation of OFT reset is same as the MFT reset.

    七、LOGIC DESIGN OF OIL BURNER

  • 8/9/2019 FSSS Control

    12/25

    FSSS DESIGN DESCRIPTION

    12OF26 SPERI

    Function of system:

    1, The system is of the function to control single oil gun, diagonal oil gun

    or group oil gun automatically(there is no stop command and OFT during the

    starting process)

    2, Every oil gun can be ignited and stopped automatically after receiving the

    signal

    3, Starting of group oil gun:

    a)  Oil gun 1、2、3、4 are ready, then click the start button manually

    b)  First of all , No.1 oil gun will be started(3s pulse), No.3 oil gun

    will be started after No.1 completed, then start No.2,No.4 as the same.

    c) 

    “Stop” command will be sent out if there is any under condition:d)  OFT, stop manually , any oil gun started failure, after sending out the

    command to start the No.4 oil gun.

    4, Starting of diagonal oil gun, such as oil gun No.1 & No.3

    a)  No.1 & No.3 oil gun are ready, then start diagonal oil gun signal

    manually

    b)  No.1 oil gun will be started(3s pulse), No.3 oil gun will be

    started(3s pulse) after No.1 completed

    c)  “Stop” command will be sent out if there is any under condition:

    d) 

    OFT, stop manually , after sending out the command to start the No.4

    oil gun.

    5, Stopping of group oil gun:

    a)  Click the stop button manually

    b)  First of all , No.1 oil gun will be stopped, No.3 oil gun will be

    started after 15s, then stop No.2,No.4 as the same.

    c) “Stop” command will be sent out if there is any under condition:

    d)  OFT, after sending out the command to stop the No.4 oil gun.

    6, Stopping of diagonal oil gun, such as oil gun No.1 & No.3

    a)  Click the stop button manually

    b)  First, send out command to stop No.1 oil gun, send out command to stop

    No.3 oil gun after 15s

    c) “Stop” command will be sent out if there is any under condition:

    OFT, after sending out the command to stop the No.3 oil gun

    Permissions of burner oil ignition: 

  • 8/9/2019 FSSS Control

    13/25

    FSSS DESIGN DESCRIPTION

    13OF26 SPERI

    Condition AND) remark

    1. Oil pressure is normal

    2. Oil temperature is normal

    3. 

    Oil trip-valve opened

    4. MFT relay is reset

    5. OFT relay is reset

    6. Cooling air pressure is

    normal

    7. Air Flow > 30MCR

    8. All of the burner nozzles are

    horizontal or there is flame

    in furnace

    9. 

    Furnace purging completed0. aFurnace differ pressure is

    norml

    Logic design of Starting oil gun:

    Permissions of starting oil gun automatically:Condition AND) Remark

    1.  Permission of burner oil ignition

    2. 

    Burner oil valve closed3.  Burner purge valve closed

    4.  Oil layer is remote

    5.  No forbidden command of burner oil

    ignition

    It is not allowed to ignite

    again in 60s after it failed

    Process of starting oil gun automatically:1.  Oil gun is in the automatic mode, then send out signal “Oil gun is in

    ignition mode”

    2.  Extend oil gun (no extended signal in ignition mode)

    3. 

    Oil gun purging (oil gun extended in ignition mode) 20s4.  Extend igniter (oil gun extended, purging completed) 15s

    5.  Open vapour steam valve ( igniter extended)

    6.  Open burner oil valve (vapour steam valve opened)

    7.  Ignition (burner oil valve opened, igniter extended, oil gun extended) 15s

    8.  Oil gun is in service (flame is detected, burner oil valve opened)

    9.  Delay Xs when oil gun is in ignition mode, program will be stopped when

    burner oil valve is not opened , then oil gun will be retracted.

  • 8/9/2019 FSSS Control

    14/25

    FSSS DESIGN DESCRIPTION

    14OF26 SPERI

    10. If there is any under condition after oil gun and valve opened, program

    will be stopped ,oil gun and valve will be closed automatically and

    purging will be started:

    Ignition failure Burner oil valve is not closed , there is no

    flame can be detected after 15s

    Burner oil valve failure Burner oil valve is not closed , there is no

    opened signal after 5s

    Oil gun is not extended Burner oil valve is not closed and oil gun

    is not extended

    Atomizing steam valve

    failure

    Atomizing steam valve not closed

    Fuel trip OFT is coming

    The logic of starting oil gun is of the function to alarm the first out MFT

    memory

    Logic design of stopping oil gun: After clicking the “stop” button to stop oil gun when oil gun is in service

    and remote:

    1.  Send out command to extend igniter and close burner oil valve

    2.  Ignite after igniter extended (15s)

    3. 

    Send out command to purge after burner oil valve is closed(20s)4.  Retract oil gun after purging completed

    5.  Reset “stop oil gun” command after oil gun retracted

    6.  Program will be stopped if there is any device failure in the process, and

    alarm

    Purging logic design of oil gun:

    1.  Requirement of purging (Purging command will be sent out if there is any

    under condition until purging completed)

    Burner oil valve closed (when this oil layer is in remote and power is

    normal , valve closes abruptly after normal opening)

    Purge before when starting oil gun

    Purge before when stopping oil gun

    2.  Open vapour steam valve : condition(AND)

    a)  Requirement of purging

    b)  Oil gun extended

    c)  No MFT signal

    3.  Oil gun purging completed

  • 8/9/2019 FSSS Control

    15/25

    FSSS DESIGN DESCRIPTION

    15OF26 SPERI

    The purging time will last 20s after vapour steam valve is opened , then

    send out “purging completed” signal

    4.  If there is any under condition to send out purging stop signal, “Purging

    stopped” signal will be sent out and vapurt steam valve will be closed:

    1.  Oil gun is not extended

    2.  MFT Long signal

    3.  OFT Long signal

    4.  Vapour steam valve open failure

    If MFT or OFT is coming , burner oil valve will be closed , ignition will be

    stopped , igniter and oil gun will be retracted.

    As shown in Fig. (5) ,the burning status of oil gun and the first out of

    tripping will be displayed in the picture , we can operate single oil gun tostart , stop , make it locally or remotely , and the same as diagonal oil gun

    and group oil gun.

  • 8/9/2019 FSSS Control

    16/25

    FSSS DESIGN DESCRIPTION

    16OF26 SPERI

    Fig. (5)

    八、PROGRAMME OF PULVERIZER LOGIC DESIGN

     

    The condition of burn coal

    condition AND) Remark

    1.  Hot air temperature more

    than 160℃ 

    2.  Air flow more than 30% 

    3.  MFT Reset 

    PROGRAM START CONDITION AND) REMARK

    1.  Pulverizer ignition

    energy OK

    border upon oil running

    Or load more than 60% and any two

    coal feeder running

    2.  Burn coal permission

    3.  No other program start

    4.  Pulverizer is not

  • 8/9/2019 FSSS Control

    17/25

    FSSS DESIGN DESCRIPTION

    17OF26 SPERI

    running

    5.  Any one seal fan running

    6.  P.A hand pressure>10KPa

    Start description

    Step of pulverizer group start

    1,Start lube oil pump ,and require open border upon S.A damper.

    After satisfied the condition as below go alone next operation

    CONDITION (AND) REMARK

    1.  Lube oil station started

    2.  Pulverizer is not running

    2, Open pulverizer seal air valve

    CONDITION (AND) REMARK

    1.  Pulverizer seal air valve opened

    2.  Pulverizer seal air outlet valve

    opened

    3.  Seal air and P.A differ pressure

    not low

    3, Open pulverizer outlet valve

    CONDITION (AND) REMARK1,All pulverizer outlet valve

    opened

    4, Open pulverizer inlet cooling valve

    CONDITION (AND) REMARK

    1.  Pulverizer inlet cooling valve

    opened

    2.  All burner inlet valve opened

    3. 

    Pulverizer seal air outlet valveopened

    4.  Seal air and P.A differ pressure not

    low

    5.  Coal feeder seal air valve opened

    6.  Pulverizer oil station OK

    7.  Pulverizer ignition energy OK and

    burn coal permission

  • 8/9/2019 FSSS Control

    18/25

    FSSS DESIGN DESCRIPTION

    18OF26 SPERI

    5, START PULVERIZER

    CONDITION (AND) REMARK

    1.  Pulverizer inlet cool valve opened

    2.  All burner inlet valve opened

    3.  Pulverizer seal air outlet valve

    opened

    4.  Seal air and P.A differ pressure not

    low

    5.  Pulverizer oil station OK

    6.  Pulverizer ignition energy OK and

    burn coal permission

    7.  No other group is running

    8. 

    No flame

    9.  P.A pressure normal

    6,OPEN PULVERIZER INLET HOT VALVE ,AND REGULATE PULVERIZER OUTLET

    TEMPERATURE

    CONDITION (AND) REMARK

    1.  Pulverizer cooling valve opened

    2.  pulverizer hot valve opened

    3. 

    55℃

  • 8/9/2019 FSSS Control

    19/25

    FSSS DESIGN DESCRIPTION

    19OF26 SPERI

    9, Open coal feeder inlet valve

    CONDITION (AND) REMARK

    1,Coal feeder inlet valve opened

    Pulverizer trip

    CONDITION (AND) REMARK

    1.  MFT Emergency

    trip

    2.  Operator trip Emergency

    trip

    3.  Pulverizer outlet temperature

    more than 100℃

    Emergency

    trip

    4.  Runbak Emergency

    trip

    5.  P.A flow less than xxx delay 15s Emergency

    trip

    6.  Pulverizer lube oil station

    trouble

    Emergency

    trip

    7. 

    Seal air and P.A differ pressurelow delay 15s

    (1000Pa) Emergencytrip

    8.  Any one pulverizer outlet valve

    not opened or any burner inlet

    valve closed yet pulverizer

    running

    Emergency

    trip

    9.  Ignition energy lost delay 5s Emergency

    trip

    10. Pulverizer outlet temperature >

    90℃ delay 2s

    Emergency

    trip

    11. Ignition failure Emergency

    trip

    Action after pulverize emergency trip Execute the step as below at the same time

  • 8/9/2019 FSSS Control

    20/25

    FSSS DESIGN DESCRIPTION

    20OF26 SPERI

    1.  Stop coal feeder, close coal feeder inlet valve and outlet valve

    2.  Stop pulverizer, close pulverizer outlet valve

    3. 

    Close pulverizer inlet cooling and hot valve

    4.  To MCS close cooling and hot regulate valve

    Action after pulverize fast stop Execute the step as below

    1.  Close hot and cooling regulate valve to xx position

    2.  Stop coal feeder , close coal feeder inlet and outlet valve

    3.  Stop pulverizer

    4.  Close cooling and hot valve

    5. 

    Close pulverizer outlet valve

    Pulverizer trip reset : AND)

    1.  No pulverizer trip condition

    2.  Pulverizer ignition energy satisfied

    3.  Burn coal permission

    4.  Pulverizer hot valve closed

    Stop pulverizer design

    Program start permission

    CONDITION (AND) REMARK

    1, No pulverizer trip condition

    1, Set coal feeder command at minimal value , Delay 60s

    CONDITION (AND) REMARK

    1.  Coal feeder command at minimal value

    delay 60s

    2, Close coal feeder inlet valve

    CONDITION (AND) REMARK

  • 8/9/2019 FSSS Control

    21/25

    FSSS DESIGN DESCRIPTION

    21OF26 SPERI

    2.  Coal feeder inlet valve closed

    3, Close hot valve and set cooling regulate valve to xx position

    CONDITION (AND) REMARK

    1.  Pulverizer inlet hot valve closed,

    2.  Pulverizer outlet temperature < 65℃

    4,Stop coal feeder

    CONDITION (AND) REMARK

    5, Close coal feeder outlet valve

    CONDITION (AND) REMARK

    1.  Coal feeder outlet valve closed

    6, Stop pulverizer

    CONDITION (AND) REMARK

    九、PULVERIZER SEAL AIR DAMPER LOGIC

    Open permission

    Any seal fan running

    Close permission

    Pulverizer stoped

    Close interlock

    Pulverizer outlet temperature > 100℃

    十、BURNER INLET CUT OFF VALVE LOGICManual operation , the four valve can be operate at the same time by manual ,

    each valve also can be operate singly ,when program start pulverizer

    interlock burner inlet cut off valve.

    十一、PULVERIZER OUTLET CUT OFF VALVE LOGIC

  • 8/9/2019 FSSS Control

    22/25

    FSSS DESIGN DESCRIPTION

    22OF26 SPERI

    The condition of open permission

    No MFT

    Close permission

    1.  Pulverizer not running

    Inlet cut off valve of the burner can be operate by manual

    十二、PULVERIZER INLET COOLING VALVE LOGIC

    The condition of open permission

    1.  Pulverizer outlet valve opened

    2. 

    No MFT3.  Pulverizer seal air valve opened and seal air differ pressure not low

    The condition of close permission 

    1, Pulverizer not running

    十三、PULVERIZER INLET HOT VALVE LOGIC

    The condition of open permission

    1.  Pulverizer outlet temperature less than 80℃

    2.  Pulverizer outlet valve opened

    3.  No MFT

    4.  Coal feeder seal air valve opened

    十四、PULVERIZER LOGIC

    The condition of start permission1.  Pulverizer inlet cooling valve opened

    2.  All burner inlet cooling valve opened

    3.  Pulverizer seal air valve opened

    4.  Seal air and P.A differ pressure not low

    5.  Pulverizer oil station OK

    6.  Ignition energy satisfied and burn coal permission

    7.  No other program is running

    8.  No flame

    9.  P.A pressure normal

  • 8/9/2019 FSSS Control

    23/25

    FSSS DESIGN DESCRIPTION

    23OF26 SPERI

    The condition of stop permission 

    Pulverizer not running

    十五、COAL FEEDER LOGIC

    The condition of start permission

    1.  Coal feeder outlet valve opened

    2.  Coal feeder speed command at minimal value

    3.  P.A flow more than XXX

    4.  Pulverizer running

    The condition of stop permission1,Coal feeder speed at minimal value

    Coal feeder trip

    1.  Coal feeder trouble

    2.  Pulverizer trip

    3.  Coal feeder outlet valve not open

    4.  Manual stop

    INTERLOCK AFTER COAL FEEDER TRIP

    1.  Close coal feeder inlet valve

    2.  Close coal feeder outlet valve

    十六、COAL FEEDER OUTLET VALVE LOGIC

    The condition of open permission

    1, Pulverizer outlet temperature

  • 8/9/2019 FSSS Control

    24/25

    FSSS DESIGN DESCRIPTION

    24OF26 SPERI

    十九、COOLING FAN LOGIC Cooling air pressure low interlock start standby fan

    Cooling fan A logic

    Interlock stop

    Cooling fan motor bearing temperature > x

    Interlock start

    Cooling fan B trip

    Cooling fan A running and cooling air hand pressure low

    Cooling fan B logic

    Interlock stop

    Cooling fan motor bearing temperature > x

    Interlock start

    Cooling fan A trip

    Cooling fan B running and cooling air hand pressure low

    二十、RUNBACK LOGIC (AS DISCUSS)

    More than three pulverizer are running , when any two feeder water pumps or

    air heater or air fan or two I.D fans or P.A fan trip ,then RUNBACK happen,

    action as below.

    (FSSS) RUNBACK ACTION

    1.  If there are six pulverizers are running , then stop F 、 E and A

    pulverizer and start BC oil gun combustion-supporting.

    2.  If there are five pulverizers are running:

    a)  If A、B、C、D、E pulverizers are running ,then stop A 、E pulverizer

    and start BC oil gun combustion-supporting.

    b)  If A、B、C、D、F pulverizers are running ,then stop F 、A pulverizer

    and start BC oil gun combustion-supporting.

    c) 

    If A、B、C、E、F pulverizers are running ,then stop F 、E pulverizerand start AB oil gun combustion-supporting.

    d)  If A、B、D、E、F pulverizers are running ,then stop A 、B pulverizer

    and start EF oil gun combustion-supporting.

    e)  If A、C、D、E、F pulverizers are running ,then stop A 、F pulverizer

    and start CD oil gun combustion-supporting.

    f)  If B、C、D、E、F pulverizers are running ,then stop B 、F pulverizer

    and start CD oil gun combustion-supporting.

    3.  If there are four pulverizers are running:

  • 8/9/2019 FSSS Control

    25/25

    FSSS DESIGN DESCRIPTION

    25OF26 SPERI

    a)  If A、B、C、D pulverizers are running ,then stop A pulverizer and

    start BC oil gun combustion-supporting.

    b)  If A、B、C、E pulverizers are running ,then stop E pulverizer and

    start BC oil gun combustion-supporting.

    c)  If A、B、C、F pulverizers are running ,then stop F pulverizer and

    start BC oil gun combustion-supporting.

    d)  If A、B、D、E pulverizers are running ,then stop E pulverizer and

    start AB oil gun combustion-supporting.

    e)  If A、B、D、F pulverizers are running ,then stop F pulverizer and

    start AB oil gun combustion-supporting.

    f)  If A、B、E、F pulverizers are running ,then stop F pulverizer and

    start AB oil gun combustion-supporting.

    g) 

    If A、C、D、E pulverizers are running ,then stop A pulverizer andstart CD oil gun combustion-supporting.

    h)  If A、C、D、F pulverizers are running ,then stop F pulverizer and

    start CD oil gun combustion-supporting.

    i)  If A、D、E、F pulverizers are running ,then stop A pulverizer and

    start EF oil gun combustion-supporting.

    j)  If B、C、D、E pulverizers are running ,then stop B pulverizer and

    start CD oil gun combustion-supporting.

    k)  If B、C、D、F pulverizers are running ,then stop B pulverizer and

    start CD oil gun combustion-supporting.

    l) 

    If B、C、E、F pulverizers are running ,then stop B pulverizer and

    start CD oil gun combustion-supporting.

    m)  If B、D、E、F pulverizers are running ,then stop B pulverizer and

    start EF oil gun combustion-supporting.

    n)  If C、D、E、F pulverizers are running ,then stop F pulverizer and

    start CD oil gun combustion-supporting.

    o)  If A、C、E、F pulverizers are running ,then stop A pulverizer and

    start EF oil gun combustion-supporting.