fundamentals of grounding - erico seminar
TRANSCRIPT
![Page 1: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/1.jpg)
Fundamentals of Grounding and Bonding
Terry Klimchak
Revised 11/19/13
![Page 2: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/2.jpg)
ERICO has met the standards and requirements of the Registered Continuing Education Providers
Program. Credit earned on completion of this program will be reported to RCEPP. A certificate of
completion will be issued to each participant. As such, it does not include content that may be
deemed or construed to be an approval or endorsement by NCEES or RCEPP.”
![Page 3: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/3.jpg)
Copyrighted Materials
This educational activity is protected by copyright laws. Reproduction, distribution, display and use of the educational activity without written permission of the
presenting sponsor is prohibited.
Copyright ERICO International Corporation, 2013
![Page 4: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/4.jpg)
Learning Objectives
At the end of this presentation you will be able to:
• Discuss the basics of electrical grounding and bonding.• Discuss electrical engineering principles and relevant
specifications.• Discuss the basic design criteria for grounding systems.• Understand and learn how to limit STEP AND TOUCH
potentials• Observe and describe exothermic welded grounding
connections
4
![Page 5: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/5.jpg)
Outline
• Basic Electricity and Materials• Utility Grounding • C & I – Residential Grounding• Telecommunications Systems
Considerations
5
![Page 6: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/6.jpg)
Relevant Standards for Utility Grounding• IEEE Std 80: Guide for Safety in AC Substation Grounding• IEEE Std 837: Standard for Qualifying Permanent Connections
Used on Substation Grounding• IEEE Std 142: Grounding of Industrial and Commercial Power
Systems• IEEE Std 81: Guide for Measuring Earth Resistivity, Ground
Impedance, and Earth Surface Potentials of a Ground System
• IEEE 1246: Guide for Temporary Protective Grounding Systems used in Substations
• IEEE 1268: Guide for Safe Installation of Mobile Substation Equipment
• IEEE C2: National Electrical Safety Code (NESC)6•IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc.
![Page 7: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/7.jpg)
Purpose of System Grounding
7
IEEE 142 - 20071.3 Purposes of system grounding:System grounding is the intentional connection to ground of a phase or neutral conductor for the purpose of:
a) Controlling the voltage with respect to earth, or ground, within predictable limits, and
b) Providing for a flow of current that will allowdetection of an unwanted connection between systemconductors and ground. Such detection may then initiate operation of automatic devices to remove the source of voltage from these conductors.
•IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc.
![Page 8: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/8.jpg)
Purpose of Grounding
• Limit potential difference of neutralfor system stability
• Allow for operation of relays and system protections devices
• Personnel safety
This is different from most grounding presentations; if you do the first two, you will get safety for free.
8
![Page 9: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/9.jpg)
Grounding (IEEE 100)
• Definition:“A conducting connection, whether intentional or accidental, by which an electric circuit or equipment is connected to the Earth, or to some conducting body of relatively large extent that serves in place of the Earth.”
• Purpose:Used for establishing and maintaining the potential of the Earth (or other conducting body) or approximately that potential, on conductors connected to it, and for conducting ground current to and from the Earth (or other conducting body).
9•IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc.
![Page 10: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/10.jpg)
Bonding (IEEE 100)
• Definition:“The permanent joining of metallic parts to form an electrically conductive path that ensures electrical continuity and the capacity to conduct safely any current likely to be imposed.”
• Conclusion:A Grounding System Is Made up of Both Grounding and Bonding Elements.
10•IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc.
![Page 11: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/11.jpg)
First: Some Basic Electrical Theory
Resistivity is the intrinsic property of a material to impede the flow of electrical current. It is the resistance factored by the length and cross sectional area. It is also referred to as volume resistivity.
11
l
RA
mm
m
2
A
l
R
![Page 12: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/12.jpg)
Volume Resistivity of Materials
12
10-8 10-2 104 1012102
All in m
Metals Soils Wood Insulators
![Page 13: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/13.jpg)
Soil Resistivity
LoamClaySand & GravelSurface LimestoneShaleSandstoneGranites, BasaltSlates
1 to 50 ohm-m20 to 100 ohm-m50 to 1000 ohm-m100 to 10,000 ohm-m5 to 100 ohm-m20 to 2000 ohm-m10,000 ohm-m10 to 100 ohm-m
13
![Page 14: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/14.jpg)
Impedance
Impedance is the sum (and much more complex mathematical operations) of a circuit resistance elements and the REACTANCE which is caused by inductors and capacitive elements in the circuit. IT IS AFFECTED BY FREQUENCY f in Hz. Transients or faults in electrical systems look like very high frequency events, not 60 hz.
LX L
CXC
1
f 2Inductive Reactance
Capacitive Reactance
14
![Page 15: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/15.jpg)
Electrical Systems – Transients • CLOSED ELECTRICAL SYSTEM:
• Generators, Transformers, and Utilization devices• Use the earth as a reference for system stability• The EARTH IS NOT a destination of currents• The System Neutral is the destination for currents• Earth is sometimes a conductor during transients
• NON SYSTEM TRANSIENTS:• Lightning is a Non System Transient• The EARTH IS a destination for currents and they are large
magnitude currents.15
![Page 16: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/16.jpg)
Utility Electrical Systems• GENERATION
– Transforms mechanical energy to electricity P = 1,300MW @ 30 kV
• TRANSMISSION– P = V x I – Losses are proportional to I so V is increased, I is
decreased for efficient transmission. V >130kV• DISTRIBUTION
– Requires lower voltage for practical handling of components. Substations transform voltage to 15-25kV and then to 480 or 240/120V
16
![Page 17: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/17.jpg)
17
1,000 MW 30 kVXFMR 500 kV
GENERATIONTRANSMISSION
DISTRIBUTION
500 kVXFMR 15-25 kV
SUBSTATION
15-25 kV
25 kV XFMR 480V 3Φ
25 kV XFMR 240/120V 1Φ
![Page 18: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/18.jpg)
Typical Utility System
18
![Page 19: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/19.jpg)
Utility Grounding Summary
• Establish Reference to Earth– Allows for Protection devices to operate– Keeps metallic and structures at the potential of the earth
• Creates Equipotential Plane– Significantly reduces risk of step and touch potential
• Provides Low Impedance Path– Especially for SYSTEM and NON SYSTEM transients
19
![Page 20: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/20.jpg)
Purpose of Grounding
• Establish a reference for the system by intentionally connecting the neutral to the earth
• Limit potential difference of neutral for system stability
• Allow for operation of relays and system protections devices
• Personnel safety – Establish an equipotential plane
20
![Page 21: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/21.jpg)
AC Three Phase
21
3 PHASE VOLTAGE
-1.5
-1
-0.5
0
0.5
1
1.5
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
Angle (/10)
Phase A
Phase B
Phase C
Ground SystemReference
![Page 22: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/22.jpg)
Utility Substation Grounding
Substations have high fault currents and potential for voltages caused by that current. Fault Currents > 50kA
22
RIV
SAFETY: At 50-60 Hz 60-100mA can cause ventricular fibrillation. Threshold voltage can be as low as 50 V.
![Page 23: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/23.jpg)
Typical Substation Grounding
• 4/0 Cu buried at 18” • 10-20’ grid, welded• Ground Rods every 20’
typical.• Extremely low R• Meets the requirements of
IEEE Standard 80
23
Typ
![Page 24: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/24.jpg)
• Provides a Molecular Bond Between Conductors– Current Carrying Capacity Equal to that
of the Conductor– Permanent - Cannot Loosen or Corrode
to Cause a High-Resistance Connection– Requires No External Source of Power
or Heat– Can be Visually Checked for Quality
24
Exothermic Welding for Connections
![Page 25: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/25.jpg)
C & I Grounding
• Generally C & I and Residential grounding methods establish a good earth reference
• Also grounding elements provide a path for fault currents
• All metal parts associated with the electrical system shall be connected to the ground reference for safety (equipotental plane).
25
![Page 26: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/26.jpg)
NEC 250 Definition of Grounding
• Intentional permanent low impedancepath to carry fault current
• Capacity to carry ground fault current• Returns fault current to source, not earth• Is connected to earth for system reference • Used to allow operation of protection devices
26
![Page 27: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/27.jpg)
C & I and Residential System Grounding Elements
• Grounded Conductor - Neutral• Grounded Electrode – Several • Grounding Electrode Conductor (GEC)• Service Bonding Jumper• Equipment Grounding Conductor
27
![Page 28: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/28.jpg)
Solidly Grounded 3 Phase Electrical System
Other GroundingElectrodes& Bonds 28
![Page 29: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/29.jpg)
NEW – MUST Be Bonded into GEC System
29
![Page 30: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/30.jpg)
Grounding Electrode Sizing
• Most Grounding Electrode Conductors are sized to 250.66 as they exist downstream of the service disconnection device.
• Ground Rods only require a #6 - this GEC ISN’T intended to carry fault current!
![Page 31: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/31.jpg)
Main Bonding Jumper
Neutral – GroundedConductor
Equipment Grounding Conductors
Typical Grounding Connections in Small Main Service Panel
31
![Page 32: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/32.jpg)
Difference between Neutral (Grounded) and Grounding Conductor
32
![Page 33: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/33.jpg)
NEC 250 Resistance Requirement• Section 250.53 requires < 25 Ω resistance for pipe, rod or
plate electrodes OR• Add another electrode > 6’ away from the first, WITHOUT
FURTHER MEASUREMENT
d
l
lRO
4ln
2 rod of Resistance OR
33
Using this formula for resistance (from MIL Handbook 419)
diameter Rod dlength rod l
yResistivit Volume Soil
Source : http://www.mikeholt.com/newsletters.php?action=display&letterID=407
A ¾” by 10’ in 500 Ω M soil would have a resistance of over 160 Ω
![Page 34: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/34.jpg)
Practical Ground Resistance• Most rods have much less than 160 Ω • Typical rod resistances will be less than 25 Ω in most soils
because of the existence of proximate utility ground references.
Low ground resistance (< 10 Ω ) can be achieved with– Multiple Rods bonded together– Counterpoise system– Coupled rods– Conductive Enhancement Materials – Chemical Rods
34
![Page 35: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/35.jpg)
Beware of False Claims
35UL 467 Bend Test Results Galvanized Rod
![Page 36: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/36.jpg)
Copper Electroplated Rod
36
UL 467 Bend Test Results - Cu Electroplated Rod
![Page 37: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/37.jpg)
Bonding
• 2011 NEC® Article 250.94– Intersystem Bonding Termination
• Interconnecting of all Ground Electrode Systems– Electrical Power Grounding System– Lightning Grounding System– Telecommunications Grounding System– Cable TV Grounding System
• Connect all conductive objects together both internal and external to the facility
• Provides near zero voltage difference during ground potential rise
37
![Page 38: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/38.jpg)
Intersystem Bonding Termination
38
![Page 39: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/39.jpg)
Other Grounding and Bonding Applications
• Signal Reference Grids• Grounding Bus Bars• Equipotential Mesh• Rebar Clamps• Swimming Pool Grounding• Wind Turbine Grounding
39
![Page 40: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/40.jpg)
SRG for Low Impedance Ground
• Stops noise from interfering with low voltage digital signals.
• Provides a lower impedance ground reference than signal conductors and shields.
• Minimizes voltage potential difference between interconnected equipment.
40
![Page 41: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/41.jpg)
SRG Impedance vs. Freq
41
![Page 42: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/42.jpg)
Signal Reference Grids &Sensitive Electronics Grounding
42
![Page 43: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/43.jpg)
• Applications:– Reduce step & touch potential– Signal Reference Grid– Antenna ground screen– Electronic shielding
• Configuration:– Wire: #6 to #12 - 30 %CW, 40% CW, Cu– Mesh size: 2” x 2” up to 48” x 24”– 20’ maximum width - 500 lb maximum weight– Wire overhang for field splicing using PG style connection.
43
Prefabricated Wire Mesh
![Page 44: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/44.jpg)
EIA/TIA Ground Bars and Ground Plates
44
![Page 45: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/45.jpg)
TGB and TMGB Grounding Bus Bars
45
![Page 46: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/46.jpg)
Main Elements of Telecom Grounding and Bonding Equipment
• Bonding Conductor for Telecommunications• Telecom Main Grounding Busbar (TMGB)
-----------------------------------------------------• Telecomm Bonding Backbone (TBB)• Telecomm Grounding Busbar (TGB)• Telecomm Bonding Backbone Interconnecting
46
![Page 47: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/47.jpg)
Bonding Conductor for Telecommunications
47
Bonding conductor for telecommunications
Equipment
TelecommunicationsEntrance Facility
Electrical Entrance Facility
TMGB
Grounding Electrode Conductor
Service Equipment
N
G
TBB
Outside the scope of this Standard
Within the scope of this Standard
![Page 48: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/48.jpg)
48
![Page 49: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/49.jpg)
Grounding and Bonding Summary
• Discussed basic electricity• Understand resistivity• Should know why utilities ground their systems• Should know elements of commercial, industrial, &
residential grounding• Should know elements of telecom bonding and
grounding
49
![Page 50: Fundamentals of Grounding - Erico Seminar](https://reader033.vdocuments.net/reader033/viewer/2022061511/555bc01ad8b42a96108b526f/html5/thumbnails/50.jpg)
Thank you for your time!
This concludes the educational content of this activity
www.erico.com