    7.2 kV IEC Withdrawable Vacuum Contactor-Fuse Combination Truck

    W-SLC Medium Voltagefused contactor truckA safe, reliable and efficient motor starter

  • 8/12/2019 FUSED CONTACTOR

    2/122

    Hydraulics

    Powering

    business

    worldwide

    Next generation

    transportation

    Eaton is driving the

    development of new

    technologies from hybrid

    drivetrains and emission control

    systems to advanced engine

    components that reduce fuel

    consumption and emissions in

    trucks and cars.

    Higher expectations

    We continue to expand ouraerospace solutions and

    services to meet the needs

    of new aviation platforms,

    including the high-flying light jet

    and very light jet markets.

    Building on our strengths

    Our hydraulics business

    combines localized service

    and support with an innovative

    portfolio of fluid power

    solutions to answer the needs

    of global infrastructure projects,

    including locks, canals and

    dams.

    Powering Greener Buildings

    and Businesses

    Eatons Electrical Group is

    a leading provider of power

    quality, distribution and control

    solutions that increase energy

    efficiency and improve power

    quality, safety and reliability.

    Our solutions offer a growing

    portfolio of green products

    and services, such as energy

    audits and real-time energy

    consumption monitoring.

    Eatons Uninterruptible Power

    Supplies (UPS), variable-speed

    drives and lighting controls help

    conserve energy and increase

    efficiency.

    Eaton delivers the power inside hundreds of productsthat are answering the demands of todays fast changingworld.

    We help our customers worldwide manage the powerthey need for buildings, aircraft, trucks, cars, machineryand entire businesses. And we do it in a way thatconsumes fewer resources.

    Automotive

    Aerospace

    lectrical

    ruck

    Hydraulics

    Automotive

    Aerospace

    lectrical

    ruck

    ydraulics

  • 8/12/2019 FUSED CONTACTOR

    3/12

    MV Switchgear Technology

    is in our DNA

    Complete Global Medium Voltage Switchgear Solutions

    Eaton, a premier leader in designing and manufacturing powerdistribution and protection equipment in the electrical industry,offers a comprehensive range of medium voltage (MV) solutionsto meet the needs of virtually every application. From productsthat feature cutting-edge design that allow for easy access,maintenance and space savings, to arc-resistant products thatenhance safety, Eatons medium voltage solutions provide avariety of products for every need. Additionally, Eatons globalservice network provides maximum customer support in allregions of the world.

    As one of the few completely vertically integrated and diversifiedindustrial manufacturers in the world, Eaton designs not only MV

    assemblies, but also the key components that comprise the MVsolutions from steel housing and circuit breaker compartmentsto vacuum interrupters, circuit breakers, bus systems and fuses.

    Eatons MV heritage, strengthened by acquisitions such asWestinghouse DCBU, Cutler Hammer, MEM and Holec, hasresulted in breakthrough MV technologies and numerousinternational patents over the years.

    Integral to Eatons complete electrical PowerChain Solutions which help businesses increase reliability, efficiency andsafety Eatons medium voltage equipment meets all applicablestandards and certifications such as IEC, NEMA / ANSI, GB, UL,IEEE, KEMA and CSA.

    When it comes to medium voltage solutions, you can trust theone name with a long history of proven performance: Eaton.

    3

    Eaton Corporation is a worldwide leader in thedesign, manufacture, and sale of safe, reliableand high-performance medium voltage powerdistribution equipment in accordance with IEC,GB and ANSI standards.

  • 8/12/2019 FUSED CONTACTOR

    4/124

    Introduction

    Developed on cutting-edge technologies, Eatons W-SLC withdrawable typevacuum contactor-fuse combination units are world leading in terms of performance,safety and functionality. The W-SLC vacuum contactor-fuse combination units areapplicable in AC systems with voltages up to 7.2 kV and 50/60 Hz. They canbe used in frequently operated heavy loads and harsh environments.

  • 8/12/2019 FUSED CONTACTOR

    5/125

    Product safety featuresThe contactor is prevented from closing and a panelindication is provided when:

    Fuse blown and or Fuse not fitted

    Additional interlock options are available to interfacewith the panel if appropriate panel designs are incorporatedsuch that:

    The truck is prevented from being racked in if: - The front door is open - The earth switch is ON The earth switch cannot be switched ON if the truck is

    in the Service Position. The panel door cannot be opened if the truck is in

    the Service Position.

    ApplicationsW-SLC vacuum contactor-fuse combinationmotor starting applications:

    Squirrel-cage induction motors Synchronous motors Wound-rotor motors

    Suitable for: Full voltage starting Reduced voltage starting

    The perfect choicefor all applications HVAC Mining Automotive Petrochemical Pulp and Paper

    Pumps, Fans, Conveyors and Crushers

  • 8/12/2019 FUSED CONTACTOR

    6/126

    Utilization conditionsEatons vacuum contactor-fuse combination unitsare suitable for use in the following conditions:

    Ambient temperatue: -15 C to +40 C Relative humidity: max. 95% non-condensing Altitude: up to 1000 m

    Please contact Customer service for special requirements.

    Design and testing standardsEatons vacuum contactor-fuse combinationunits are fully in line with IEC standards.

    IEC 62271-200 IEC 60470

    Key technical features*

    The ratings for new vacuumcontactor-fuse combination units:

    Voltage: up to 7.2 kV Current: Contactor continuous current: 400 A Combination Continuous current: 200 A Breaking: up to 50 kA with fuse 8500 A interrupting rating without fuse

    Control voltages:

    110, 220 50 Hz Vac 120, 240 60 Hz Vac 110, 120 Vdc

    Service life: 300,000 electrical operations 1,000,000 mechanical operations* For detailed information, please refer to technical data table

  • 8/12/2019 FUSED CONTACTOR

    7/127

    DimensionsEatons mid-mounted type withdrawable vacuum contactor-fuse combination units

    Striker Pin length after fuse blown = 10 - 16mm

    Maximum dimensions for fuse

  • 8/12/2019 FUSED CONTACTOR

    8/128

    Electrical operationWiring Diagram

    Auxiliary contacts when the trolley is onTest Position or connected Position

    Note: The drawing is shown with the Contactor

    Truck in the withdrawn Test Position,

    de-energised, with fuses fitted and healthy.

    +Ve +Ve

    -Ve

    K1

    K1

    K1

    Y1

    -Ve

    Q1

    Fusestatus

    IndicationCircuit

    Closing Circuit HousingEarthing

    OpeningCircuit

    Auxiliary Contact Circuits

    Electrical operation wiring diagram of W-SLC-400 withdrawable vacuum contactor-fuse combination units

    64 Pin Secondary Disconnect

    K1: Closing / Holding relayPC: Operations counterQ1: Auxiliary contact (switching when the contactor closes or trips)SC: Closing buttonSO: Opening buttonS1: Auxiliary contact (switching when fuse is blown or not fitted)*S8: Auxiliary contact (switching when the trolley is on Test Position)S9: Auxiliary contact (switching when the trolley is on Connected Position)Ve: Control supplyV1: Bridge rectifier (not included for DC applications)Y1: Closing coil

    * When MV fuse is replaced by a link S1 only switches

    when Open push button is pressed.

  • 8/12/2019 FUSED CONTACTOR

    9/129

    Mechanical latching optionWiring Diagram

    Note: The drawing is shown with the Contactor

    Truck in the withdrawn Test Position,

    de-energised, with fuses fitted and healthy.

    K1: Closing relayK2: Trip relayPC: Operations counterQ1: Auxiliary contact (switching when the contactor closes or trips)SC: Closing buttonSO: Opening buttonS1: Auxiliary contact (switching when the fuse is blown or not fitted)*S8: Auxiliary contact (switching when the trolley is on Test Position)S9: Auxiliary contact (switching when the trolley is on Connected Position)Ve: Control supplyV1: Bridge rectifier (not included for DC applications)V2: Bridge rectifierY1: Closing coilY2: Trip coil

    * When MV fuse is replaced by a link S1 only switches

    when Open push button is pressed.

    +Ve +Ve +Ve +Ve +Ve

    Y1

    Q1

    Y2

    -Ve -Ve -Ve -Ve

    Q1

    Fusestatus

    IndicationCircuit

    Closing Circuit HousingEarthing

    Opening Circuit Auxiliary Contact Circuits

    Mechanical latching wiring diagram of W-SLC-400 withdrawable vacuum contactor-fuse combination units

    64 Pin Secondary Disconnect

  • 8/12/2019 FUSED CONTACTOR

    10/12

    Selection and ordering information

    Type W-SLC, 400 A, vacuum contactor ratingsRatedutilizationvoltage

    Interrupting rating (kA) Application table Transformer(kVA)

    Capacitor(A)*

    Maximuminsulationvoltage (V)Unfused Fused Induction

    motor (kW)Synchronous motor (kW)

    (0.8 PF) (1.0 PF)

    2200 - 25003000 - 36003800 - 48006000 - 6900

    8.58.58.58.5

    50505050

    1300167522503350

    1300167522503350

    1500185026004100

    1500200025004000

    295 7200

    *Ratings not applicable for back-to-back switching. Please contact Customer Service for back-to-back switching applications.

    Rated current.......................................................400 A enclosed Max fuse rating .................................................................. 355 A Fused combination ............................................................. 200 A

    IEC make-break capability-AC4 Make ................................................................................ 4000 A Break ................................................................................ 3200 A

    Maximum interrupting current (3 Operations) ................................................................... 8500 A

    Short time withstand current 30 Second ........................................................................ 2400 A 1 Second .......................................................................... 6000 A 8.7 ms (0.5 Cycle) ......................................................63 kA peak

    Fuse protected (based on fuse cut-off) .............................. 50 kA

    Normal service altitude.......................................... 1000 meters

    Mechanical life................................................................ 1 million

    Electrical lifeAC3 & AC4 ....................................................300,000 operations

    Impulse withstand..............................................................60 kV

    Dielectric strength......................................20 kV rms (1 minute)

    Closing time (Energization to contact touch) ....................................< 120 ms

    Opening times (field selectable).........................< 50 330 ms

    Arcing time.............................................................12 ms or less

    Control voltages ac/Hz..................... 110 / 50, 120 / 60, 220 / 50, 240 / 60 Vac/Hz dc........................................................................... 110 / 220 Vdc

    Pickup voltage..........................................80% rated coil voltage

    Dropout voltage.......................................60% rated coil voltage

    Control circuit burden Closing 100 125 V ........................................................... 1 kVA 200 240 V ........................................................1.8 kVA Holding 100 125 V ...........................................................40 VA 200 240 V ...........................................................50 VA

    Auxiliary contact rating

    Voltage (maximum) ............................................................ 600 V Continuous current ............................................................... 10 A Making capacity (ac) ...................................................7200 VA (dc) .....................................................125 VA Breaking capacity (ac) .....................................................720 VA (dc) .....................................................125 VA

    Latch (when specified) Mechanical life .............................................250,000 Operations Trip voltage (dc) ......................................................... 24 V (dc) ....................................................... 125 V (ac) ..............................................110 / 120 V Minimum trip voltage ....................................80% Rated Coil V Trip burden .......................................................................400 VA Trip time .............................................................................30 ms

    Weight (without fuses).......................................................96 kg

    Specifications

    Order instruction

    W-SLC 1 SLC014S 5 Y - 66 5

    IEC draw-out contactor IEC SLcontactor7.2 kV, 400 A1= with fuses

    0= fuses replacedby conductors

    Note: fuses are

    supplied by user

    Contactors auxiliary contact66= 6 NO, 6 NC

    Coil drop-out time5= 30 ms6= 50 ms7= 130 ms8= 250 ms9= 330 ms

    Coil voltageA= 120 Vac/60 HzB= 240 Vac/60 HzU= 110 Vac/50 HzW= 220 Vac/50 HzX= 110 VdcY= 220 Vdc

    Mechanical latch(Coil voltage)0= None4= 110/50, 120/60 Hz5= 220/50, 240/60 Hz

  • 8/12/2019 FUSED CONTACTOR

    11/12

    1874 1886 1911 19981893 19901962 19991983190819061899 1963

    The power of fusion.

    Theres a certain energy at Eaton. Its the power of uniting someof the worlds most respected names to build a brand you cantrust to meet every power management need. The energy createdsupports our commitment to powering business worldwide.

    From power distribution to power quality and control, Eaton allows

    you to proactively manage your complete power system byproviding electrical solutions that make your applications safer,more reliable, and highly efficient. Visit www.eaton.com/electrical.

    All of the above are trademarks of Eaton Corporation or its affiliates. Eaton has a licenseto use the Westinghouse brand name in Asia Pacific. 2009 Eaton Corporation.

  • 8/12/2019 FUSED CONTACTOR

    12/12

    Eatons electrical business is a global leader with expertisein power distribution and circuit protection; backup powerprotection; control and automation; lighting and security;structural solutions and wiring devices; solutions for harshand hazardous environments; and engineering services.Eaton is positioned through its global solutions to answertodays most critical electrical power management challenges.

    Eaton is a diversified power management company providingenergy-efficient solutions that help our customers effectivelymanage electrical, hydraulic and mechanical power. Thecompany is a global technology leader in electrical products,

    systems and services for power quality, distribution andcontrol, power transmission, lighting and wiring products;hydraulics components, systems and services for industrialand mobile equipment; aerospace fuel, hydraulics andpneumatic systems for commercial and military use; andtruck and automotive drivetrain and powertrain systemsfor performance, fuel economy and safety. Eaton acquiredCooper Industries plc in 2012. Eaton has approximately100,000 employees and sells products to customers in morethan 150 countries. For more information, visit www.eaton.eu.

    2012 Eaton CorporationAll rights reservedBR022002EN/ January 2013

    Europe, Middle East and AfricaEaton Industries (Netherlands) B.V.P.O. Box 237550 AA Hengelo

    The NetherlandsTel.: +31 74 246 4012Fax: +31 74 246 4601

    [email protected]

    Asia PacificEaton Electrical Sector Asia PacificHeadquartersNo.3 Lane 280 Linhong Road

    Changning DistrictShanghai 200335, P.R.ChinaTel.: +86 21 5200 0099Fax: +86 21 5200 0200www.eatonelectrical.com.cn

    South AmericaEaton Ltda.Av. Pierre Simon de Laplace, 751Cond. Techno Park Via Anhanguera,Km 104,5Campinas - SP - 13069-320 - BrasilTel.: +55 19 2117 [email protected]

    www.eaton.com.br

    North AmericaEaton CorporationElectrical Sector1000 Cherrington ParkwayMoon Township, PA 15108United States

    877-ETN-CARE (877-386-2273)www.eaton.com

    The information provided in this documentreflects the general characteristics of the

    referenced products at the time of issue andmay not reflect their future characteristics.Eaton Corporation reserves the right tomodify the contents of this documentand the characteristics of the referencedproducts without prior notification. EatonCorporation does not assume liability forpotential errors or omission of informationin this document.