fx-pcg16 general purpose programmable controller...

25
FX-PCG16 General Purpose Programmable Controller Installation Instructions FX-PCG1611-x, FX-PCG1621-x Part No. 24-10143-152, Rev. G Issued April 2016 Refer to the QuickLIT website for the most up-to-date version of this document. Application The FX-PCG16 controller is part of the Facility Explorer Controller FX-PCG family. The FX-PCG16 controller runs pre-engineered and user-programmed applications and provides the inputs and outputs required to monitor and control a wide variety of HVAC equipment. The FX-PCG controllers operate on an RS-485 BACnet® Master-Slave/Token-Passing (MS/TP) Bus as BACnet Application Specific Controllers (B-ASC) and integrate into Johnson Controls® and third-party BACnet systems. With Release 10.1, you can use the FX-PCT software to switch the FX-PCG to use the N2 protocol. The FX-PCG16 controller is available with or without an integral LCD and push button user interface. Switchable Communications Protocols By default, the FX-PC family controllers and network sensors communicate using the standard BACnet protocol, based on the ANSI/ASHRAE 135-2004. The BACnet protocol is a standard for ANSI, ASHRAE, and the International Standards Organization (ISO) for building controls. FX-PCG, FX-PCX, and FX-PCV controllers are BTL- tested and listed as BACnet Application Specific Controllers (B-ASCs). FX-PCA field controllers are BTL-listed as BACnet Advanced Application Controllers (B-AACs). The NS Series Sensors are BTL-listed as BACnet Smart Sensors (B-SSs). Release 10.1 of FX-PCT and later can be used to switch the Field Bus communications protocol in FX-PC Controllers to be either the standard BACnet Master-Slave/Token-Passing (MS/TP) or the N2 protocol. BACnet MS/TP is the default communications protocol for all new controllers. Switchable communications protocols provide a cost-effective upgrade and modernization path for customers with existing N2 controllers. The Modernization Guide for Legacy N2 Controllers (LIT-12012045) and the controller-specific documentation provide installation and commissioning support and include tips for efficient and safe replacement. Refer to the N2 Compatibility Options chapter of the Controller Tool Help (LIT-12011147) for information about mapping N2 Objects in controllers with switchable communications protocols. The N2-capable FX-PC controllers can be used as functional replacements for legacy N2 controllers. The N2-capable FX-PC controllers: have the I/O quantities and characteristics of the FX-PC family controllers must be programmed with FX-PCT, which has programming capabilities that are similar (but not identical) to HVACPro, GX9100, GPL, and other legacy tools support SA Bus devices support FX-WRZ wireless sensors from the controller using the FX-WRZ7860 receiver when configured for BACnet MS/TP communication The N2-capable FX-PC controllers: do not support Zone Bus (for example, TMZ sensors and M100 actuators) do not support pass through in the commissioning mode do not support remote downloading or commissioning using BACnet routing do not support wireless connection to the N2 bus 1 FX-PCG16 General Purpose Programmable Controller Installation Instructions

Upload: ngoxuyen

Post on 05-Feb-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

FX-PCG16 General Purpose Programmable ControllerInstallation InstructionsFX-PCG1611-x, FX-PCG1621-x Part No. 24-10143-152, Rev. G

Issued April 2016Refer to the QuickLIT website for the most up-to-date version of this document.

ApplicationThe FX-PCG16 controller is part of the Facility ExplorerController FX-PCG family. The FX-PCG16 controller runspre-engineered and user-programmed applications andprovides the inputs and outputs required to monitor andcontrol a wide variety of HVAC equipment.

The FX-PCG controllers operate on an RS-485 BACnet®Master-Slave/Token-Passing (MS/TP) Bus as BACnetApplication Specific Controllers (B-ASC) and integrateinto Johnson Controls® and third-party BACnet systems.With Release 10.1, you can use the FX-PCT softwareto switch the FX-PCG to use the N2 protocol.

The FX-PCG16 controller is available with or without anintegral LCD and push button user interface.

Switchable CommunicationsProtocolsBy default, the FX-PC family controllers and networksensors communicate using the standard BACnetprotocol, based on the ANSI/ASHRAE 135-2004.

The BACnet protocol is a standard for ANSI, ASHRAE,and the International Standards Organization (ISO) forbuilding controls.

FX-PCG, FX-PCX, and FX-PCV controllers are BTL-tested and listed as BACnet Application SpecificControllers (B-ASCs). FX-PCA field controllers areBTL-listed as BACnet Advanced Application Controllers(B-AACs). The NS Series Sensors are BTL-listed asBACnet Smart Sensors (B-SSs).

Release 10.1 of FX-PCT and later can be used to switchthe Field Bus communications protocol in FX-PCControllers to be either the standard BACnetMaster-Slave/Token-Passing (MS/TP) or the N2 protocol.BACnet MS/TP is the default communications protocolfor all new controllers. Switchable communicationsprotocols provide a cost-effective upgrade andmodernization path for customers with existing N2controllers. The Modernization Guide for Legacy N2Controllers (LIT-12012045) and the controller-specificdocumentation provide installation and commissioningsupport and include tips for efficient and safereplacement. Refer to the N2 Compatibility Optionschapter of the Controller Tool Help (LIT-12011147) forinformation about mapping N2 Objects in controllers withswitchable communications protocols.

The N2-capable FX-PC controllers can be used asfunctional replacements for legacy N2 controllers. TheN2-capable FX-PC controllers:

• have the I/O quantities and characteristics of theFX-PC family controllers

• must be programmed with FX-PCT, which hasprogramming capabilities that are similar (but notidentical) to HVACPro, GX9100, GPL, and otherlegacy tools

• support SA Bus devices• support FX-WRZ wireless sensors from the controller

using the FX-WRZ7860 receiver when configured forBACnet MS/TP communication

The N2-capable FX-PC controllers:• do not support Zone Bus (for example, TMZ sensors

and M100 actuators)• do not support pass through in the commissioning

mode• do not support remote downloading or commissioning

using BACnet routing• do not support wireless connection to the N2 bus

1FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 2: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

North American EmissionsCompliance

CanadaThis Class (A) digital apparatus meets all therequirements of the Canadian Interference-CausingEquipment Regulations.

Cet appareil numérique de la Classe (A) respecte toutesles exigences du Règlement sur le matériel brouilleurdu Canada.

United StatesThis equipment has been tested and found to complywith the limits for a Class A digital device pursuant toPart 15 of the FCC Rules. These limits are designed toprovide reasonable protection against harmfulinterference when this equipment is operated in acommercial environment. This equipment generates,uses, and can radiate radio frequency energy and, if notinstalled and used in accordance with the instructionmanual, may cause harmful interference to radiocommunications. Operation of this equipment in aresidential areamay cause harmful interference, in whichcase the users will be required to correct the interferenceat their own expense.

InstallationObserve these guidelines when installing an FX-PCG:

• Transport the controller in the original container tominimize vibration and shock damage.

• Verify that all parts shipped with the controller.• Do not drop the controller or subject it to physical

shock.

Parts Included• one FX-PCG16 with removable terminal blocks• one installation instructions sheet

Materials and Special Tools Needed• three fasteners appropriate for the mounting surface

(M4 screws or #8 screws)• one 20 cm (8 in.) or longer piece of 35 mm DIN rail

and appropriate hardware for DIN rail mount (only)• small straight-blade screwdriver for securing wires in

the terminal blocks

MountingObserve these guidelines when mounting an FX-PCG:

• Ensure the mounting surface can support thecontroller, DIN rail, and any user-supplied enclosure.

• Mount the controller horizontally on 35 mm DIN railwhenever possible.

• Mount the controller in the proper mounting position(Figure 1).

• Mount the controller on a hard, even surfacewhenever possible in wall-mount applications.

• Use shims or washers to mount the controller securelyand evenly on the mounting surface.

• Mount the controller in an area free of corrosivevapors and observe the Ambient Conditionsrequirements in Table 10.

• Provide for sufficient space around the controller forcable and wire connections for easy cover removaland good ventilation through the controller (50 mm[2 in.] minimum on the top, bottom, and front of thecontroller).

• Do not mount the controller on surfaces prone tovibration, such as duct work.

• Do not mount the controller in areas whereelectromagnetic emissions from other devices orwiring can interfere with controller communication.

Observe these additional guidelines when mounting acontroller in a panel or enclosure:

• Mount the controller so that the enclosure walls donot obstruct cover removal or ventilation through thecontroller.

• Mount the controller so that the power transformerand other devices do not radiate excessive heat tothe controller.

• Do not install the controller in an airtight enclosure.

Figure 1: FX-PCG Mounting Positions

2FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 3: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

DIN Rail Mount ApplicationsMounting the controller horizontal on 35 mm DIN rail isthe preferred mounting method.

To mount an FX-PCG on 35 mm DIN rail:

1. Securely mount a 20 cm (8 in.) or longer section of35 mmDIN rail horizontal and centered in the desiredspace so that the controller mounts in the horizontalposition shown in Figure 1.

2. Pull the two bottom mounting clips outward from thecontroller to the extended position (Figure 2).

3. Hang the controller on the DIN rail by the hooks atthe top of the (DIN rail) channel on the back of thecontroller (Figure 2), and position the controller snuglyagainst the DIN rail.

4. Push the bottommounting clips inward (up) to securethe controller on the DIN rail.

To remove the controller from the DIN rail, pull thebottom mounting clips out to the extended positionand carefully lift the controller off the DIN rail.

Wall Mount ApplicationsTo mount an FX-PCG directly on a wall or other flatvertical surface:

1. Pull the two bottom mounting clips outward andensure they are locked in the extended position asshown in Figure 2.

2. Mark the three mounting hole locations on the wallusing the dimensions in Figure 2 and one of themountpositions shown in Figure 1. Or hold the controller upto the wall or surface in a proper mount position andmark the hole locations through the mounting clips.

3. Drill holes in the wall or surface at the locationsmarked in Figure 2, and insert appropriate wallanchors in all of the mounting holes (if necessary).

4. Hold the controller in place, and insert the screwsthrough the mounting clips and into the holes (oranchors). Carefully tighten all of the screws.

Important: Do not overtighten themounting screws.Overtightening the screwsmay damagethe mounting clips.

Figure 2: Back of Controller Showing ExtendedMounting Clips, DIN Rail Channel, and Mounting

Dimensions, mm (in.)

3FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 4: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Figure 3: FX-PCG16 Physical Features

Table 1: FX-PCG Physical Features Callouts and DescriptionsPhysical Feature: Description and ReferencesCalloutBinary Output (BO) Source Power Selection Jumpers (See Binary Output (BO) Source Power Selection Jumpers)1

Device Address DIP Switch Block (See Figure 9)2

Mounting Clip3

Configurable Output (CO) Terminal Blocks (See Table 3)4

24 VAC, Class 2 Supply Power Terminal Block (See Supply Power Terminal Block)5

Cover Lift Tab (One of Two) (See Figure 3)6

Display Navigation Buttons (See Setting Up an Integral or Local Display)

Note: Not available on all FX-PCG models.

7

LCD Display Area (See Setting Up an Integral or Local Display)

Note: Not available on all FX-PCG models.

8

FC Bus Terminal Block (See FC Bus Terminal Block)9

4FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 5: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Table 1: FX-PCG Physical Features Callouts and DescriptionsPhysical Feature: Description and ReferencesCalloutSensor Actuator (SA) Bus Terminal Block (See SA Bus Terminal Block)10

Sensor Port (Sensor Actuator [SA] Bus, RJ-12 6-pin Modular Jack) (See Figure 6)11

Binary Inputs (BIs) Terminal Block (See Table 3)12

Universal Inputs (UIs) Terminal Blocks (See Table 3)13

LED Status Indicators (See Table 8)14

Field Controller (FC) Bus Port (RJ-12 6-pin Modular Jack) (See Figure 6)15

Binary Output (BO) Terminal Block (See Table 3)16

Terminal Wiring Guidelines,Functions, Ratings, andRequirements

WiringObserve the following guidelines when wiring a controller:

Risk of Electric Shock: Disconnect the power supplybefore making electrical connections to avoid electricshock.

Mise En Garde: Risque de décharge électrique:Débrancher l'alimentation avant de réaliser toutraccordement électrique afin d'éviter tout risque dedécharge électrique.

Risk of Property Damage: Do not apply power to thesystem before checking all wiring connections. Shortcircuited or improperly connected wires may result inpermanent damage to the equipment.

Mise En Garde: Risque de dégâts matériels: Ne pasmettre le système sous tension avant d'avoir vérifié tousles raccords de câblage. Des fils formant un court-circuitou connectés de façon incorrecte risquentd'endommager irrémédiablement l'équipement.

Important: Do not exceed the controller electricalratings. Exceeding controller electricalratings can result in permanent damage tothe controller and void any warranty.

Important: Use copper conductors only. Make all wiringin accordance with local, national, andregional regulations.

Important: Electrostatic discharge can damagecontroller components. Use properelectrostatic discharge precautions duringinstallation, setup, and servicing to avoiddamaging the controller.

For detailed information on configuring and wiring anMS/TP Bus, FC bus, and SA bus, refer to the FX-PCSeries Controllers MS/TPCommunications Bus TechnicalBulletin (LIT-12011670) or to the MS/TP CommunicationsBus for BCM System Technical Bulletin (LIT-12011908).For detailed information on wiring an N2 bus, refer to theN2Communications Bus Technical Bulletin (LIT-636018).

FX-PCG Terminal Blocks and Bus PortsSee Figure 3 for terminal block and bus port locations onthe FX-PCG controller. Observe the following guidelineswhen wiring a controller.

Input and Output Terminal BlocksAll of the fixed input terminal blocks are mounted on thebottom of the controller and the output terminal blocksare mounted on the top of the controller. See Table 3 formore information about I/O terminal functions,requirements, and ratings.

FC Bus Terminal BlockThe FC Bus terminal block is a blue, removable,4-terminal plug that fits into a board-mounted jack.

Wire the removable FC bus terminal block plugs on thecontroller, and other controllers in a daisy-chainconfiguration using 3-wire twisted, shielded cable asshown in Figure 4. See Table 5 for more information.

5FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 6: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Figure 4: FC Bus Terminal Block Wiring

Note: The FC bus Shield (SHLD) terminal is isolatedand can be used to connect (daisy chain) theshields for FC bus wiring.

SA Bus Terminal BlockThe SA Bus terminal block is a brown, removable,4-terminal plug that fits into a board-mounted jack.

Wire the removable SA Bus terminal block plugs on thecontroller and other SA Bus devices in a daisy-chainconfiguration using 4-wire twisted, shielded cable asshown in Figure 5. See Table 5 for more information.

Figure 5: SA Bus Terminal Block Wiring

Note: The SA PWR terminal supplies 15 VDC. The SAPWR terminal can be used to connect (daisychain) the 15 VDC power leads on the SA bus.

FC Bus PortThe FC bus port on the front of the controller is an RJ-12,6-position modular jack that provides a connection forthe FX-BTCVT Bluetooth® Commissioning Converter,ZFR-USBHA-0 ZigBee®wireless dongle, or FX-ZFR1811Wireless Field Bus Router.

The FC bus port is connected internally to the FC busterminal block. See Table 5 for more information. The FCbus Port pin assignment is shown in Figure 6.Note: When an FX-PCG is configured for N2 network

communication, the FC bus port is not used.

Figure 6: Pin Number Assignments for Sensor, SABus, and FC Bus Ports on Controllers

Sensor Port

The Sensor (SA Bus) port on the bottom of the controller(Figure 3) is an RJ-12, 6-position modular jack thatprovides a connection for the Bluetooth CommissioningConverter, the VAV box Balancing Tool, specified networksensors, or other SA Bus devices with RJ-12 plugs.

When the FX-PCG is configured for N2 communication,the SA Bus port must be used to download andcommission the controller.

An FX-DIS1710 Local Controller Display also can beconnected to the SA Bus port (but only on FX-PCGmodels without integral display and push buttons).

The Sensor port is connected internally to the SA busterminal block. See Table 5 for more information. TheSensor Port pin assignment is shown in Figure 6.

6FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 7: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Supply Power Terminal BlockThe 24 VAC supply power terminal block is a gray,removable, 3-terminal plug that fits into a board-mountedjack on the top right of the controller.

Wire the 24 VAC supply power wires from the transformerto the HOT and COM terminals on the terminal plug asshown in Figure 7. The middle terminal on the supplypower terminal block is not used. See Table 5 for moreinformation about the Supply Terminal Block.

Figure 7: 24 VACSupply Power Terminal BlockWiring

Note: The supply power wire colors may be different ontransformers from other manufacturers. Refer tothe transformer manufacturer’s instructions andthe project installation drawings for wiring details.

Important: Connect 24 VAC supply power to thecontroller and all other network devices sothat transformer phasing is uniform acrossthe network devices. Powering networkdevices with uniform 24 VAC supply powerphasing reduces noise, interference, andground loop problems. The controller doesnot require an earth ground connection.

Wireless Network ApplicationsWhen configured for BACnet MS/TP communication, thecontroller can also be installed in a wireless applicationusing an FX-ZFR1811 Series Wireless Field Bus Router.

To configure a controller for use with the FX-ZFR1811Series Wireless Field Bus system:

1. Wire the input/output terminals and SA bus.

Note: In wireless network applications, do notconnect any wires to the FC Bus terminalblock. (Connect the SA/FC terminal block onan FX-PCX to an SA bus only.)

2. Connect the FX-ZFR1811 Wireless Field Bus Routerto the FC bus port (RJ-12 modular jack) on the frontof the controller.

3. Ensure that the controller's device address DIPswitches are set to the correct device address. SeeSetting the Device Addresses.

4. Set DIP switch 128 to ON, which enables wirelessoperation on the controller.

For more information on installing a controller in awireless configuration, refer to the FX-ZFR1811Wireless Field Bus Router Installation Instructions(Part No. 24-10325-29).

7FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 8: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Termination DiagramsA set of termination diagrams provides details for wiring inputs and outputs to the controllers. See the figures in thissection for the applicable termination diagrams.

Table 2: Termination DetailsTermination DiagramsType of

Input/OutputType of Field Device

UITemperature Sensor

UIVoltage Input - ExternalSource

UIVoltage Input - InternalSource

UIVoltage Input(Self-Powered)

UICurrent Input - ExternalSource (Isolated)

UICurrent Input - InternalSource (2 wire)

8FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 9: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Table 2: Termination DetailsTermination DiagramsType of

Input/OutputType of Field Device

UICurrent Input - InternalSource (3 wire)

UICurrent Input - ExternalSource (in Loop)

UIFeedback from EPP-1000

UI or BIDry Contact (Binary Input)

CO0–20 VDC Output toActuator (External Source)

CO0–10 VDC Output toActuator (Internal Source)

9FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 10: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Table 2: Termination DetailsTermination DiagramsType of

Input/OutputType of Field Device

CO24 VAC Triac Output(Switch Low, ExternalSource)

COIncremental Control toActuator (Switch Low,Externally Sourced)

CO

COIncremental Control toActuator (Switch High,Externally Sourced)

BO24 VAC Binary Output(Switch Low, ExternallySourced)

BO24 VAC Binary Output(Switch High, ExternallySourced)

10FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 11: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Table 2: Termination DetailsTermination DiagramsType of

Input/OutputType of Field Device

BOIncremental Control toActuator (Switch Low,Externally Sourced)

BO

SA BusNetwork Stat with PhoneJack (Fixed Address = 199)

11FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 12: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Table 2: Termination DetailsTermination DiagramsType of

Input/OutputType of Field Device

SA BusNetwork Stat withTerminals Addressable

SA BusNetwork Stat withTerminals (Fixed Address= 199)

12FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 13: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Input and Output WiringGuidelinesTable 3 provides information and guidelines about thefunctions, ratings, and requirements for the controllerinput and output terminals; and references guidelines fordetermining proper wire sizes and cable lengths.

In addition to the wiring guidelines in Table 3, observethese guidelines when wiring controller inputs andoutputs:

• Run all low-voltage wiring and cables separate fromhigh-voltage wiring.

• All input and output cables, regardless of wire size ornumber of wires, should consist of stranded, insulated,and twisted copper wires.

• Shielded cable is not required for input or outputcables.

• Shielded cable is recommended for input and outputcables that are exposed to high electromagnetic orradio frequency noise.

• Inputs/outputs with cables less than 30 m (100 ft)typically do not require an offset in the software setup.Cable runs over 30 m (100 ft) may require an offsetin the input/output software setup.

Table 3: FX-PCG Terminal Blocks, Functions, Ratings, Requirements, and CablesDetermine Wire Size andMaximum Cable Length

Function, Ratings, RequirementsTerminalLabel

Terminal BlockLabel

Same as (Universal) INn

Note: Use 3-wire cable fordevices that source power fromthe +15V terminal.

15 VDC Power Source for active (3-wire) input devicesconnected to the Universal INn terminals.

Provides 100 mA total current

+15 VUNIVERSAL

(Inputs)

See Guideline A in Table 4.Analog Input - Voltage Mode (0–10 VDC)

10 VDC maximum input voltage

Internal 75k ohm Pull-down

INn

See Guideline B in Table 4.Analog Input - Current Mode (4–20 mA)

Internal 100 ohm load impedance

Note: Current loop jumpers are fail-safe to maintain aclosed 4 to 20 mA current loop, even when the power tothe controller is interrupted or off. See Universal InputCurrent Loop Jumpers.

See Guideline A in Table 4.Analog Input - Resistive Mode (0–600k ohm)

Internal 12 V. 15k ohm pull up

Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel[Johnson Controls® sensor], 1k Platinum, and A99B SiliconTemperature Sensor) Negative Temperature Coefficient(NTC) Sensor (10k Type L, 10k JCI Type II, 2.252k TypeII)

See Guideline A in Table 4.Binary Input - Dry Contact Maintained Mode

1 second minimum pulse width

Internal 12 V. 15k ohm pull up

Same as (Universal) INnUniversal Input Common for all Universal Input terminals

Note: All Universal ICOMn terminals share a common,which is isolated from all other commons.

ICOMn

13FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 14: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Table 3: FX-PCG Terminal Blocks, Functions, Ratings, Requirements, and CablesDetermine Wire Size andMaximum Cable Length

Function, Ratings, RequirementsTerminalLabel

Terminal BlockLabel

See Guideline A in Table 4.Binary Input - Dry Contact Maintained Mode

0.01 second minimum pulse width

Internal 18 V. 3k ohm pull up

INnBINARY

(Inputs)

Binary Input - Pulse Counter/Accumulator Mode

0.01 second minimum pulse width

(50 Hz at 50% duty cycle)

Internal 18 V. 3k ohm pull up

Binary Input Common for all Binary Input (IN) terminals

Note: All Binary ICOMn terminals share a common, whichis isolated from all other commons, except the ConfigurableOutput (CO) common (OCOMn) when the CO is definedas an Analog Output.

ICOMn

See Guideline C in Table 4.Binary Output - 24 VAC Triac (External Power Source)

Connects OUTn to OCOMn when activated.

External Power Source Requirements:

30 VAC maximum output voltage

0.5 A maximum output current

1.3 A at 25% duty cycle

40 mA minimum load current

OUTnBINARY

(Output)

Power SelectionJumper positioned toExternal (EXT) power.

Binary Output Common (for OUTn terminal)

Note: Each Binary Output Common terminal (OCOMn) isisolated from all other commons, including other BinaryOutput Common terminals.

OCOMn

See Guideline C in Table 4.Binary Output - 24 VAC Triac (Internal Power Source)

Model FX-PCG1611-0: Sources internal 24 VAC power(24~ COM).

Model FX-PCG1611-1: Sources internal 24 VAC power(24~ HOT).

OUTnBINARY

(Output)

Power SelectionJumper positioned toInternal (INT) power.

Binary Output - 24 VAC Triac (Internal Power Source)

Model FX-PCG1611-0: Connects OCOMn to 24~ HOTwhen activated.

Model FX-PCG1611-1: Connects OCOMn to 24~ COMwhen activated.

Internal Power Source:

30 VAC maximum output voltage

0.5 A maximum output current

1.3 A at 25% duty cycle

40 mA minimum load current

OCOMn

14FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 15: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Table 3: FX-PCG Terminal Blocks, Functions, Ratings, Requirements, and CablesDetermine Wire Size andMaximum Cable Length

Function, Ratings, RequirementsTerminalLabel

Terminal BlockLabel

See Guideline A in Table 4.Analog Output - Voltage Mode (0–10 VDC)

10 VDC maximum output voltage

10 mA maximum output current

Required an external load of 1,000 ohm or more.

OUTnCONFIGURABLE

(Outputs)

See Guideline C in Table 4.Binary Output - 24 VAC Triac (External Power Sourceonly)

Connects OUTn to OCOMn when activated.

External Power Source Requirements:

30 VAC maximum output voltage

0.5 A maximum output current

1.3 A at 25% duty cycle

40 mA minimum load current

Same as (Configurable)OUTn.AnalogOutput Signal CommonAll Configurable Outputs(COs) defined as Analog Outputs (AOs) share a common,which is isolated from all other commons except the BinaryInput common.

Binary Output Signal Common All Configurable Outputs(COs) defined as Binary Outputs are isolated from all othercommons, including other CO commons.

OCOMn

Cable and Wire LengthGuidelinesTable 4 defines cable length guidelines for the variouswire sizes that may be used for wiring low-voltage (<30V)input and outputs.Table 4: Cable Length Guidelines for Recommended Wire Sizes for Low-Voltage (<30V) Inputs and Outputs

AssumptionsMaximum CableLength and Type

Wire Size/Gauge and TypeGuideline

100 mV maximum voltage drop

Depending on cable and the connected inputor output device, you may have to define anoffset in the setup software for the input oroutput point.

457 m (1,500 ft) twistedwire

1.5 mm2 (18 AWG) stranded copperA

297 m (975 ft) twisted wire0.8 mm (20 AWG) stranded copper

183 m (600 ft) twisted wire0.6 mm (22 AWG) stranded copper

107 m (350 ft) twisted wireN/A (24 AWG) stranded copper

100 mV maximum voltage drop

Depending on cable and the connected inputor output device, you may have to define anoffset in the setup software for the input oroutput point.

229 m (750 ft) twisted wire1.5 mm2 (18 AWG) stranded copperB

137 m (450 ft) twisted wire0.8 mm (20 AWG) stranded copper

91 m (300 ft) twisted wire0.6 mm (22 AWG) stranded copper

61 m (200 ft) twisted wireN/A (24 AWG) stranded copper

N/ASee Figure 8 to determinecable length. Use twistedwire cable.

See Figure 8 to select wire size/gauge.Use stranded copper wire

C

15FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 16: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Maximum Cable Length versusLoad Current

Use Figure 8 to estimate the maximum cable lengthrelative to the wire size and the load current (in mA) whenwiring inputs and outputs.

Note: Figure 8 applies to low-voltage (<30V) inputs andoutputs only.

Figure 8: Maximum Wire Length for Low-Voltage (<30V) Inputs and Outputs by Current and Wire Size

SA/FC Bus and Supply PowerWiring GuidelinesTable 5 provides information about the functions, ratings,and requirements for the communication bus and supplypower terminals; and guidelines for wire sizes, cabletypes, and cable lengths when wiring the controller'scommunication buses and supply power.

In addition to the guidelines in Table 5, observe theseguidelines when wiring an SA or FC bus and the 24 VACsupply power:

• Run all low-voltage wiring and cables separate fromhigh-voltage wiring.

• All SA and FC bus cables, regardless of wire size,should be twisted, insulated, stranded copper wire.

• Shielded cable is strongly recommended for all SAand FC bus cables.

• Refer to the FX-PC Series Controllers MS/TPCommunications Bus Technical Bulletin(LIT-12011670) or to the MS/TP CommunicationsBus for BCM System Technical Bulletin(LIT-12011908) for detailed information about wiresize and cable length requirements for the SA andFC buses.

16FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 17: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Table 5: Communications Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, andCables

Recommended Cable TypeFunction, Electrical Ratings/RequirementsTerminalLabels

TerminalBlock/PortLabel

0.6 mm (22 AWG) stranded, 3-wiretwisted, shielded cablerecommended

FC Bus Communications+

-FC BUS1

Signal Reference (Common) for Bus communicationsCOM

Isolated terminal (optional shield drain connection)SHLD

or

Bluetooth Commissioning Converterretractable cable or 24 AWG 3-pairCAT 3 Cable <30.5 m (100 ft)

RJ-12 6-Position Modular Connector provides:

FC Bus Communications

FC Bus Signal Reference and 15 VDC Common

15 VDC, 180 mA, Power for Bluetooth CommissioningConverter or ZFR1811 Wireless Router

FC BUS1

(Port)

0.6 mm (22 AWG) stranded, 4-wire(2 twisted-pairs), shielded cablerecommended.

Note: The + and - wire are onetwisted pair, and the COM and SAPWR are the second twisted pair ofwires.

SA Bus Communications+

-SA BUS1

SA Bus Signal Reference and 15 VDC CommonCOM

15 VDC Supply Power for Devices on the SA Bus

(Maximum total current draw for SA Bus is 240 mA.)

SA PWR

24 AWG 3-pair CAT3 cable <30.5m (100 ft)

RJ-12 6-Position Modular Connector provides:

SA Bus Communications

SA Bus Signal Reference and 15 VDC Common

15 VDC Power for devices on the SA bus and WirelessCommissioning Converter

SensorSensor1

0.8 mm to 1.5 mm2

(18 AWG) 2-wire

24 VAC Power Supply - Hot

Supplies 20–30 VAC (Nominal 24 VAC)

HOT24~

24 VAC Power Supply Common (Isolated from all otherCommon terminals on controller)

35 VA

COM

1 The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38.4k baud. For moreinformation, refer to the FX-PC Series Controllers MS/TP Communications Bus Technical Bulletin (LIT-12011670) or to theMS/TP Communications Bus for BCM System Technical Bulletin (LIT-12011908). For more information about N2 buscommunications, refer to the N2 Communications Bus Technical Bulletin (LIT-636018).

17FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 18: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Setup and Adjustments

Setting the Device AddressesFX-PCG controllers are master devices on MS/TP (SAor FC) buses. Before operating FX-PCG controllers ona bus, you must set a valid and unique device addressfor each controller on the bus. You set a controller'sdevice address by setting the positions of the switcheson the DIP switch block at the top of the controller (Figure3). Consult the appropriate Communication TechnicalBulletin to find valid addresses for these controllers.

Figure 9: Device Address DIP Switch Block Set toAddress 21

Note: FX-PCG ship with switch 128 ON and theremaining address switches off rendering thecontrollers wired slave devices, which do notoperate on MS/TP buses, but will not interferewith bus operation. Set a valid and unique deviceaddress on the controller before applying powerto the controller on the bus.

1. Set all of the switches on the address DIP switchblock (128 through 1) to off.

2. Set one or more of the seven address switches (64though 1) to ON, so that the sum of the switchnumbers set to ON equals the intended deviceaddress. See Table 6 for valid device addresses.

Set the highest number switch that is less than orequal to the intended device address to ON. Thencontinue setting lower numbered switches until thetotal equals the intended address. For example, if theintended device address is 21, set switch 16 to ONfirst, then set switch 4 ON, followed by switch 1(16+4+1= 21). See Figure 9.

3. Set switch 128 to ON only for controllers on anFX-ZFR Series Wireless Field Bus application. Forall hard-wired SA and FC bus applications, ensurethat switch 128 is set to Off.

Note: Do not connect a controller with switch 128set to ON to an active (hard-wired) SA or FCbus. When a controller with switch 128 set toON and a device address from 4 to 127 isconnected to a wired field bus, the entire fieldbus is rendered inoperable until the controlleris disconnected or switch 128 is set to Off.

Refer to the FX-ZFR Series Wireless Field BusSystem Technical Bulletin (LIT-12011660) for moreinformation on device addresses in wirelessapplications.

4. Set a unique and sequential device address for eachof the controllers connected on the SA or FC busstarting with device address 4.

To ensure the best bus performance, set sequentialdevice addresses with no gaps in the device addressrange (4, 5, 6, 7, 8, 9, and so on). The controllers donot need to be physically connected on the bus intheir numerical device address order.

5. Write each FX-PCG's device address on the whitelabel below the DIP switch block on the controller'scover.

Table 6 describes the FC bus and SA bus devicesaddresses for Johnson Controls® MS/TPcommunications bus applications.

Refer to the FX-PC Series Controllers MS/TPCommunications Bus Technical Bulletin(LIT-12011670) or MS/TP Communications Bus forBCM System Technical Bulletin (LIT-12011908) formore information on controller device addresses andhow to set them on MS/TP buses.

Refer to the Modernization Guide for Legacy N2Controllers (LIT-12012005) for more information oncontroller device addresses and how to set them onN2 buses.

Table 6: SA/FC Bus Device Address Descriptionsfor MS/TP Controllers

Use on DescriptionDeviceAddress

Reserved for FC Bus Supervisory Controller(not for use on FX-PC controllers).

0

(Switch128 Off)

Reserved for peripheral devices (not for useon FX-PC controllers).

1 to 3

(Switch128 Off)

18FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 19: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Table 6: SA/FC Bus Device Address Descriptionsfor MS/TP Controllers

Use on DescriptionDeviceAddress

Used for MS/TP master devices (FX-PCcontrollers) that are hardwired to an SA Busor FC Bus.

4 to 127

(Switch128 Off)

Reserved addresses for wired slave devices(not for use on FX-PC controllers).

Note: FX-PCG controllers ship with switch 128ON and the remaining address switches offrendering the controllers wired slave devices,which do not operate on MS/TP buses.

0 to 3

(Switch128 ON)

Valid for MS/TPMaster controllers onwirelessFC Buses only.

Note: Do not connect a controller with switch128 ON to an active (hard-wired) SA or FCbus. When a controller with switch 128 ONand a device address from 4 to 127 isconnected to a wired field bus, the entire fieldbus is rendered inoperable until the controlleris disconnected or switch 128 is set to Off.

4 to 127

(Switch128 ON)

19FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 20: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Removing the Controller CoverImportant: Electrostatic discharge can damage

controller components. Use properelectrostatic discharge precautions duringinstallation, setup, and servicing to avoiddamaging the controller.

Important: Disconnect all power sources to thecontroller before removing the cover andchanging the position of any jumper or theEOL switch on the controller. Failure todisconnect power before changing a jumperor EOL switch position can result in damageto the controller and void any warranties.

The controller cover is held in place by four plastic latchesthat extend from the base and snap into slots on theinside of the housing cover.

To remove the controller cover:

1. Place your fingernails under the two cover lift tabs(Figure 3) on the sides of the housing cover andgently pry the top of the cover away from the base torelease the cover from the two upper latches.

2. Pivot the top of the cover further to release it from thelower two latches.

3. Replace the cover by placing it squarely over thebase, and then gently and evenly push the cover onto the latches until they snap into the latched position.

Figure 10: FX-PCG with Cover Removed ShowingEOL Switch and Jumper Positions

Setting the End-of-Line (EOL) SwitchEach controller has an EOL switch, which, when set toON, sets the controller as a terminating device on thebus. See Figure 10 for the EOL switch location. Thedefault EOL switch position is Off.

Figure 11: End-of-Line Switch Positions

To set the EOL switch on a controller:

1. Determine the physical location of the controller onthe FC bus.

2. Determine if the controller must be set as aterminating device on the bus.

Note: Refer to the FX-PC Series Controllers MS/TPCommunications Bus Technical Bulletin(LIT-12011670) or to the MS/TPCommunications Bus for BCM SystemTechnical Bulletin (LIT-12011908) for detailedinformation about EOL termination rules andEOL switch settings on FC buses.

Refer to the N2 Communications Bus TechnicalBulletin (LIT-636018) for detailed information aboutEOL termination rules and EOL switch settings on N2buses.

3. If the controller is a terminating device on the bus, setthe EOL switch to ON. If the controller is not aterminating device on the bus, set the EOL switch toOff.

When an FX-PC controller is connected to power withits EOL switch set to ON, the amber EOL LED on thecontroller cover is lit.

20FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 21: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Setting the Input and OutputJumpers

Binary Output (BO) Source PowerSelection Jumpers

Risk of Electric Shock: Disconnect supply power tothe controller before attempting to adjust the BinaryOutput Source Power Selection Jumpers. Failure todisconnect the supply power may result in electric shock.

Mise En Garde: Risque de décharge électrique:Débrancher l'alimentation de l'controller avant toutréglage du Binary Output Source Power SelectionJumpers. Le non-respect de cette précaution risque deprovoquer une décharge électrique.

Important: Do not connect an external power sourceto a BO when the BO power source jumperis in the internal power (INT) position.Connecting external power to a BO thatsources internal power can damage thecontroller and void any warranties.

The BO source power selection jumpers determinewhether a BO provides internal power (sourced from thecontroller) to the output load (INT position) or requiresan external power source (EXT position) for the outputload. Figure 12 shows an example of a controller BOsand the associated power selection jumpers to the rightof the BOs terminal block.

Figure 12: Example Binary Outputs and theAssociated Source Power Jumper Positions

Universal Input Current Loop JumpersThe Universal Input (UI) current loop fail-safe jumpersare on the circuit board under the controller cover nearthe UI terminals (Figure 10). When a UI is defined (in thesystem software) as a 4-20 mA Analog Input and the UI’scurrent loop jumper is in the Disabled (default) position(Figure 13), the 4-20 mA current loop circuit openswhenever power to the controller is interrupted or off.

Figure 13: Current Loop Jumper Positions

Setting the current loop jumper to the Enabled position(Figure 13) connects an internal 100 ohm resistor acrossthe UI terminals, which maintains the 4-20 mA currentloop circuit even when power to the controller isinterrupted or off.

Important: Current Loop jumpers must be in theDisabled (default) position for all UIs thatare not set up to operate as 4-20 mA analoginputs.

Table 7 identifies the current loop jumpers associatedwith each UI on the FX-PCG16 controller.

Table 7: FX-PCG16 UI Inputs and Jumper LabelsJumper Label on Circuit BoardUniversal Input

LabelJ74IN1

J73IN2

Setting Up an Integral or LocalDisplayFX-PCG1621 models have an integral LCD and pushbutton user interface that allows you to set up andmonitorthe FX-PCG, the FX-PCG I/O points, and the modulesand I/O points connected on the SA bus. FX-PCG1611models do not have an integral display, but can beconnected to an FX-DIS1710 Local Controller Display.For detailed information on setting up and operating eitheran integral user interface or a remotely connectedFX-DIS1710 display, refer to the FX-DIS1710 LocalController Display Technical Bulletin (LIT-12011666).

21FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 22: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Commissioning ControllersYou commission FX-PCG controllers with the FX-PCTsoftware, either via a Bluetooth®Wireless CommissioningConverter, a ZigBee® wireless dongle, or in BACnetRouter mode when connected to a Facility ExplorerSupervisory Controller. Refer to the Controller Tool Help(LIT-12011147) for detailed information on commissioningcontrollers.

Troubleshooting ControllersObserve the Status LEDs on the front of the controllerand see Table 8 to troubleshoot the controller. Totroubleshoot an integral or local controller display, referto the FX-DIS1710 Local Controller Display TechnicalBulletin (LIT-12011666).

Table 8: Status LEDs and Descriptions of LED StatesDescription of LED StatesNormal LED

StateLED ColorLED Label

Off Steady = No Supply Power or the controller’s polyswitch/resettable fuseis open. Check Output wiring for short circuits and cycle power to controller.

On Steady = Power Connected

On SteadyGreenPOWER

Off Steady = No Faults

On Steady = Device Fault; no application loaded; Main Code downloadrequired, if controller is in Boot mode, or a firmware mismatch exists betweenthe FX-PCG and the FX-ZFR1811 Wireless Field Bus Router.

Blink - 2 Hz = Download or Startup in progress, not ready for normal operation

Off SteadyRedFAULT

Blink - 2 Hz = Data Transmission (normal communication)

Off Steady = No Data Transmission (N/A - auto baud not supported)

On Steady = Communication lost, waiting to join communication ring

Blink - 2 HzGreenSA BUS

Blink - 2 Hz = Data Transmission (normal communication)

Off Steady = No Data Transmission (auto baud in progress)

On Steady = Communication lost, waiting to join communication ring

Blink - 2 HzGreenFC BUS

On Steady = EOL switch in ON position

Off Steady = EOL switch in Off position

Off (Except onterminatingdevices)

AmberEOL

Repair InformationIf a controller fails to operate within its specifications,replace the controller. For a replacement controller,contact your Johnson Controls® representative.

22FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 23: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Accessories See Table 9 for controller accessories orderinginformation.

Table 9: Accessories Ordering InformationDescriptionProduct Code NumberBluetooth Commissioning Converter, with Bluetooth® TechnologyFX-BTCVT-1

Local Controller Display (for use with FX-PCG1611 model only)FX-DIS1710-0

Wireless Field Bus RouterFX-ZFR1811-0

Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall PlugTP-2420

Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount,8 in. Primary Leads and Secondary Screw Terminals, Class 2

Note: Additional Y6x-x Series transformers are also available. Refer to the SeriesY63, Y64, Y65, Y66, and Y69 Transformers Product Bulletin (LIT-125755) for moreinformation.

Y65T31-0

Power transformer (Class 2, 24 VAC, 50 VA maximum output), no enclosureAS-XFR050-0

Replacement SA Bus Terminal Blocks, 4-Position, Brown, Bulk PackAP-TBK4SA-0

Replacement FC Bus Terminal Blocks, 4-Position, Blue, Bulk PackAP-TBK4FC-0

Replacement Power Terminal Blocks, 3-Position, Gray, Bulk PackAP-TBK3PW-0

USB Dongle with ZigBee® Driver provides a wireless connection through FX-PCTto allow wireless commissioning of the wirelessly enabled FX-PCG, FX-PCA,FX-PCX, and FX-PCV field controllers. Also allows use of the FX-ZFR CheckoutTool (FX-ZCT) in FX-PCT.Note: The ZFR-USBHA-0 replaces the IA OEM DAUBI_2400 ZigBee USB dongle.For additional information on the ZFR-USBHA-0 ZigBee dongle, refer to the FX-ZFRSeries Wireless Field Bus System Technical Bulletin (LIT-12011660) or FX-ZFRSeries Wireless Field Bus System Quick Reference Guide (LIT-12011696).

ZFR-USBHA-0

Technical SpecificationsTable 10: FX-PCG Technical Specifications

FX-PCG16x1-x General Purpose Programmable Controller

Controller

FX-PCG1621-0-x Controller with Display and Push-button User Interface

Product Code Numbers

24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supplyClass 2 (North America), Safety Extra-Low Voltage (SELV) (Europe)

Supply Voltage

14 VA maximum for FX-PCG1611 only

20 VA maximum for FX-PCG1621 (with integral display) only

Note: VA rating does not include any power supplied to the peripheral devicesconnected to Binary Outputs (BOs) or Configurable Outputs (COs), which canconsume up to 12 VA for each BO or CO; for a possible total consumption of anadditional 84 VA (maximum).

Power Consumption

Operating: 0 to 50°C (32 to 122°F); 10 to 90% RH noncondensing

Storage: -40 to 80°C (-40 to 176°F); 5 to 95% RH noncondensing

Ambient Conditions

DIP switch set; valid controller device addresses 4–127 (Device addresses 0–3 and128–255 are reserved and not valid controller addresses.)

Controller Addressing for BACnetMS/TP

DIP switch set; valid control device addresses 1-255Controller Addressing for N2

23FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 24: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

Table 10: FX-PCG Technical SpecificationsRS-485: selectable BACnet MS/TP or N2

3-wire FC bus between the supervisory controller and other controllers

4-wire SA bus between controller, network sensors and other sensor/actuator devices,includes a lead to source 15 VDC supply power (from controller) to bus devices.

N2 Open Protocol:

N2/FC Bus: 1.5 mm (18 AWG) standard 3-wire, twisted, shielded cable recommendedbetween the supervisory controller and field controllers

Communications Bus

H8SX/166xR Renesas® 32-bit microcontrollerProcessor

640 KB flash memory and 128 KB RAMMemory

2 - Universal Inputs: Defined as 0-10 VDC, 4-20 mA, 0-600k ohm, or Binary DryContact

2 - Binary Input: Defined as Dry Contact Maintained or Pulse Counter/AccumulatorMode

3 - Binary Outputs: Defined as 24 VAC Triac (selectable internal or external sourcepower)

4 - Configurable Outputs: Defined as 0-10 VDC or 24 VAC/DC Field-EffectTransistor (FET) BO

Input and Output Capabilities

Input: 16-bit resolution

Output: 16-bit resolution, +/- 200 mV accuracy in 0-10 VDC applications

Analog Input/AnalogOutput Resolutionand Accuracy

Input/Output: Fixed Screw Terminal Blocks

SA/FC Bus and Supply Power: 4-Wire and 3-Wire Pluggable Screw TerminalBlocks

SA/FC Bus Port: RJ-12 6-Pin Modular Jacks

Terminations

Horizontal on single 35 mmDIN rail mount (preferred), or screwmount on flat surfacewith three integral mounting clips on controller

Mounting

Enclosurematerial: ABS and polycarbonate UL94 5VB; Self-extinguishing, PlenumRated

Protection Class: IP20 (IEC529)

Housing

150 x 164 x 53 mm (5-7/8 x 6-1/2 x 2-1/8 in.) including terminals and mounting clipsNote: Mounting space requires an additional 50 mm (2 in.) space on top, bottomand front face of controller for easy cover removal, ventilation and wire terminations.

Dimensions(Height x Width x Depth)

0.4 kg (0.9 lb)Weight

United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy ManagementEquipment

FCC Compliant to CFR47, Part 15, Subpart B, Class A

Compliance

Canada: UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No.205, SignalEquipment

Industry Canada Compliant, ICES-003

Europe: Johnson Controls, Inc. declares that this product is in compliance with theessential requirements and other relevant provisions of the EMC Directive.

Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant

BACnet International: BACnet Testing Laboratories (BTL) Protocol Revision 4Listed BACnet Application Specific Controller (B-ASC)

24FX-PCG16 General Purpose Programmable Controller Installation Instructions

Page 25: FX-PCG16 General Purpose Programmable Controller ...cgproducts.johnsoncontrols.com/MET_PDF/2410143152.pdf · ObservetheseguidelineswhenmountinganFX-PCG: • Ensurethemountingsurfacecansupportthe

The performance specifications are nominal and conform to acceptable industry standard. For application at conditionsbeyond these specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liablefor damages resulting from misapplication or misuse of its products.

APAC Single Point of Contact:NA/SA Single Point of Contact:European Single Point of Contact:JOHNSON CONTROLS

C/OCONTROLSPRODUCTMANAGEMENT

NO. 22 BLOCK D NEW DISTRICT

WUXI JIANGSU PROVINCE 214142

CHINA

JOHNSON CONTROLS

507 E MICHIGAN ST

MILWAUKEE WI 53202

USA

JOHNSON CONTROLS

WESTENDHOF 3

45143 ESSEN

GERMANY

Building Efficiency507 E. Michigan Street, Milwaukee, WI 53202

Johnson Controls® is a registered trademark of Johnson Controls, Inc.All other marks herein are the marks of their respective owners.© 2016 Johnson Controls, Inc.

www.johnsoncontrols.comPublished in U.S.A.

25FX-PCG16 General Purpose Programmable Controller Installation Instructions