Installation manualMori HR
PRECAUTIONS FOR INSTALLATION, USE AND MAINTENANCE
G
G
Read this manual carefully before using the product and keep it in a safe place for reference. This product was constructed up to standard and in compliance with regulations relating to electrical equipment and must be installed by technically qualified personnel. The manufacturer assumes no responsibility for damage to persons or property resulting from failure to observe the regulations contained in this booklet.
•Thedeviceshouldnotbeusedforapplicationsotherthanthosespecifiedinthismanual.•Afterremovingtheproductfromitspackaging,verify itscondition. Incaseofdoubt,contactaqualifiedtechnician.Donotleavepackagingwithinthereachofsmallchildrenor people with disabilities.
•Donottouchtheappliancewithwetordamphands/feet.•Thisappliancecanbeusedbychildrenagedfrom8yearsandaboveandpersonswithreducedphysical,sensoryormentalcapabilitiesorlackofexperienceandknowledgeif they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
•Do not use the product in the presence of inflammable vapours, such as alcohol,insecticides,gasoline,etc...
•Ifanyabnormalitiesinoperationaredetected,disconnectthedevicefromthemainssupplyandcontactaqualifiedtechnicianimmediately.Useoriginalsparepartsonlyforrepairs.
•Theelectricalsystemtowhichthedeviceisconnectedmustcomplywithregulations.•Beforeconnectingtheproducttothepowersupplyorthepoweroutlet,ensurethat: - the data plate (voltage and frequency) correspond to those of the electrical mains - theelectricalpowersupply/socket isadequate formaximumdevicepower. Ifnot,contactaqualifiedtechnician.
•The device should not be used as an activator forwater heaters, stoves, etc., norshoulditdischargeintohotair/fumeventductsderivingfromanytypeofcombustionunit.Itmustexpelairoutsideviaitsownspecialduct.
•Operatingtemperature:-20°Cupto+50°C.•Thedeviceisdesignedtoextractcleanaironly,i.e.withoutgrease,soot,chemicalorcorrosiveagents,orflammableorexplosivemixtures.
•Donotleavethedeviceexposedtoatmosphericagents(rain,sun,snow,etc.).•Donotimmersethedeviceoritspartsinwaterorotherliquids.•Turnoffthemainswitchwheneveramalfunctionisdetectedorwhencleaning.•For installation an omnipolar switch should be incorporated in the fixed wiring, inaccordancewiththewiringregulations,toprovideafulldisconnectionunderovervoltage
2
VERSIONSSTANDARDExternalgrilleinhighquality,impactandUV-resistantABScolourRAL9010.
categoryIIIconditions(contactopeningdistanceequaltoorgreaterthan3mm).•If thesupplycord isdamaged, itmustbe replacedby themanufacturer, itsserviceagentorsimilarlyqualifiedpersonsinordertoavoidahazard.
•Donotobstructthefanorexhaustgrilletoensureoptimumairpassage.•Ensureadequateairreturn/dischargeinto/fromtheroomincompliancewithexisting
regulations in order to ensure proper device operation.•Iftheenvironmentinwhichtheproductisinstalledalsohousesafuel-operatingdevice(waterheater,methanestoveetc.,thatisnota“sealedchamber”type),itisessentialto ensure adequate air intake, to ensure good combustion and proper equipmentoperation.
INTRODUCTIONMORI HR is a continuously running, alternate flow supply and extract fan with heatretention for use in habitable rooms such as; living rooms, bedrooms, dining roomsbasements and hallways. It is designed to ensure adequate ventilation in enclosedenvironments.Itisrecommendedthattwounitsareinstalledinapair:whenoneunitispulling,theotherispushing.Apairofunitscanbeinstalledinthesameroomorindifferentrooms(i.e.livingroomand bedroom). The unit is suitable for installation on an outside wall.
To achieve the best possible ventilation the unit should operate continuously, and only stopped for maintenance or service.
When heat exchange is not useful (for example in mid-seasons when indoor and outdoor temperatures are similar) it is recommended to set the
unit in “extract-only” or “intake-only” mode and not switch the fan off.
•Innerventilationunitmaterial:highquality,impactandUV-resistantABScolourRAL9010.•Designfrontcoverremovableforcleaningwithouttheuseoftools.•Easymaintenanceinstallationplate,foreasyaccesstotheheatexchangerfrominside
the room.•Anti-dustfilter,easilyremovableforwashingbytheuserwithouttools.•Regenerativehoneycombsceramicheatexchanger.•Externalgrilleinhighquality,impactandUV-resistantABScolourRAL9010.•High efficiency aerodynamic fan with “winglet” blades to optimise quietness andefficiency.
•SinglephaseECreversibleBrushlessmotorwithintegralthermalprotection.•Motormountedonhighqualityballbearings.•Theunitisdoubleinsulated:noearthconnectionisrequired.•Tricklespeedselectable.•Boostmode.•Free-cooling(Bypass)mode.•IPX4degreeofprotection.•Powersupply220Vto240V~50Hz.
TECHNICAL SPECIFICATIONS
Model Airflowl/s
PowerW
WeightKg
MoriHR100 2,8/4,2/7 1,2/1,7/2,6 2
MoriHR150 5,6/11,1/16,7 1,4/2,3/3,8 4,2
3
Every70secondstheunitalternatesbetweenbeingasupply fanandanextract fan.Duringtheextractmodetheunitshighefficiencyheatexchangercollectsandretainsheatfromtheextractedair,itthentransfersthemajorityofthisheattotheincomingairduringsupplymode,recoveringmostofthermalenergywhichwouldbeotherwiselostin the ventilation process.Theunitcanberuncontinuouslyatasetspeedbyaddinganinternallink,orcontrolledviathededicatedcontroller,149-SEN-CTRLSwhichallowsspeedselectionandtriggeringof free cooling mode.
S3switchactivatesthe“Freecooling“(Bypass)mode,whichstopsalternateflowandkeepsthefanin“extract-only”or“intake-only”mode,toavoidtheheatexchangewhennecessary.Tosettheextract-only”modeor“intake-only”,placetheintegraljumpersasperFig.20AorFig.20B).ThefrontcoverLEDindicateswhentheFreecoolingmodeison. Anautomatic“Boost”modecanbeachievedthroughadedicatedswitchorroomsensorslike149-SEN-HY,149-SEN-PIRor149-SEN-CO2.Wiringconfigurations:1.ConstantrunwithalternateflowandheatretentiononSpeed1only(Fig.18A).2.ConstantrunwithalternateflowandheatretentiononSpeed2only(Fig.18B).3.ConstantrunwithalternateflowandheatretentiononSpeed3only(Fig.18C).4.ConstantrunwithalternateflowandheatretentiononSpeed1withboosttoSpeed3triggeredbyexternalswitchingdevice(orderedseparatelyifrequired)(Fig.18D).5.ConstantrunwithalternateflowandheatretentiononSpeed2withboosttoSpeed3triggeredbyexternalswitchingdevice(orderedseparatelyifrequired)(Fig.18E).6.Operationusingcontroller149-SEN-CTRLS(orderedseparatelyifrequired)(Fig.18F).(a)Off.(b)ConstantrunwithalternateflowandheatretentiononSpeed1.(c)ConstantrunwithalternateflowandheatretentiononSpeed2.(c)ConstantrunwithalternateflowandheatretentiononSpeed3.(d)Constant runonselectedspeed inextractorsupplymodeonly (supplyorextractselectable at installation stage).Pleasenotethatthisswitchcancontroloneortwounitstoworkinharmonyi.e.whenoneunitisextractingtheotherissupplyingwhichcanimprovefurthertheventilationinaroomorhome.Wiringdiagramfor2units,Fig.18G.
“S1” “S2” OperationO O OFF
I O Speed1
O II Speed2
I II Speed3
S1 S2 S3
III
“S3” Operation
Heatrecovery(Alternateflow)
Freecooling
OPERATION
WARNING: Ensure that the electric wiring to L and N is done correctly; an incorrect connection will lead to malfunction or permanent damage of the fan.
Twoormoreunitscanoperateatafixedspeedinasynchronisedway(oneunitextracts,theothersupplies,andviceversa).Wiringdiagrams:Fig.18A-18B-18C.Theinitialstartingairdirectionisachievedbysettingthededicatedjumper(Fig.20A-20B).RESET OF THE SYNCHRONISATIONOPTION 1:Iftwoormoreunitsareconnectedunderthesamemainswitchorunderadedicatedswitch,toresetthesynchronisation,theswitchmustbeswitchedfirstOFFandthenONtoreactivate(Fig.31).
SYNCHRONISATION IN CASE OF INSTALLATION WITHOUT CONTROLLER
4
Maintenance can be carried out by the user as indicated at page 11.Servicemustbeperfmormedonlybytechnicallyqualifiedpersonnelinaccordancewithlocal rules and regulations. Make sure that the mains supply to the unit is disconnected (page12).Cleaningoftheheatexchangercanbeperformedfromoutsideaswell.
MAINTENANCE AND SERVICE
IntegraljumpersetinpositionA(Fig.20A)means“extract”mode.IntergaljumpersetinpositionB(Fig.20B)means“intake”mode.Thejumperpositiondefinesboththeair-flowdirectionwhentheunitisactivatedforthefirsttime(forthesynchronisation)andtheair-flowdirectionofthefree-coolingmode.
JUMPER POSITION
Iftwoormoreunitsarecontrolledbymeansofthesamecontroller(149-SEN-CTRLSorsimilar),theyalwaysoperateinasynchronisedway.WiringdiagramasperFig.18.
SYNCHRONISATION IN CASE OF INSTALLATION WITH CONTROLLER
DIMENSIONS
270÷510164q 164q
108
Omm
A 270÷510164q 164q
108
Omm
270÷510164q 164q
108
Omm
C
D
ØE
Externalgrille
270÷510164q 164q
108
Omm
B
MoriHR100 MoriHR150
A 164 218B 46 51
C 164 218D 270÷510 300÷560Ø E 108 158
OPTION 2:Iftwoormoreunitsarenotconnectedunderthesamemainswitch,toresetthesynchronisation,pressatthesametimetheblackpinofeachunit(Fig.32-33)atleast3seconds.
Year1 Inspectionoffiltercleanliness,ifrequiredwashunderatap(page11)
Year2 Inspectionoffiltercleanliness,ifrequiredwashunderatap(page11)Inspectionofheatexchangercore,ifrequiredwashunderatap(page12)
Year3 Inspectionoffiltercleanliness,ifrequiredwashunderatap(page11)
Year4 Inspectionoffiltercleanliness,ifrequiredwashunderatap(page11)Inspectionofheatexchangercore,ifrequiredwashunderatap(page12)
Year5 Inspectionoffiltercleanliness,ifrequiredwashunderatap(page11)
5
INSTALLATION
1
CONTENUTO IMBALLO MODELLO MORI HRMoriHR100-MoriHR150
4
3
5
min. 108mm HR100min. 158mm HR150 INDOOR OUTDOOR
1°÷2°
2
insulation foam
6 7
=Ø 5x40mm=Ø 8x10mm
6
8 9
10 11
100mm HR100115mm HR150
12 13
14 15
7
16 17
18C
S3
S2
S1
GN
DN
L
S3
S2
S1
GN
DN
L
S3
S2
S1
GN
DN
L
SPEED 1 (FIXED) SPEED 2 (FIXED)
SPEED 3 (FIXED)
S3
S2
S1
GN
DN
L
CTRL-SS1 S2 S3
III
N
LOK
1 1 1
S 3 S 2 S 1
18F
18A 18B
S3
S2
S1
GN
DN
L
S3
S2
S1
GN
DN
L
SPEED 1 to 3
SPEED 2 to 3
18D
18E
8
19
S3
S2
S1
GN
DN
LS1 S2 S3
III
N
LOK
S3
S2
S1
GN
DN
LCTRL-S
1 1 1
S 3 S 2 S 1
18G
UN
IT 1
UN
IT 2
S3
S2
S1
GN
DN
L
CTRL-SS1 S2 S3
III
N
LOK
1 1 1
S 3 S 2 S 1
18FAGGIUNTA FOGLIO ISTRUZIONI -
JUMPER POSITION A
20A
EXTRACT
21
AGGIUNTA FOGLIO ISTRUZIONI -
JUMPER POSITION B
20B
INTAKE
22
9
23CLICK
24
25
27
26
10
Ø 5x40mm3-5mm
EXTERNAL GRILLE
2928
30
31
32
TO RESET OF THE SYNCHRONIZATION OF THE UNITS (OPTION 2)
33
TO RESET OF THE SYNCHRONIZATION OF THE UNITS (OPTION 1)
11
34 35
36 37
38
I
39
40 41
I
FILTER CLEANING (MAINTENANCE)Can be carried out by the user
12
71
48 49
44 45
46
42 43
47
HEAT EXCHANGER CLEANING (SERVICE)Mustbecarriedoutonlybytechnicallyqualifiedpersonnel
13
7152
56
50
53
51
100mm HR100115mm HR150
54 55
Fig. 57149-SEN-CTRLS
I I I
REMOTE CONTROLLER (on request) HIGHLY RECOMMENDED
14
a) Mark - ELTA FANS
b) Model - MORI HR 100 MORI HR 150
c) SEC class - A
c1) SEC warm climates kWh/m2.a -15,6 -16,2
c2) SEC average climates kWh/m2.a -37,5 -38,2
c3) SEC cold climates kWh/m2.a -75,6 -76,4
Energy label - Yes
d) Unit typology - Residential - bidirectional
e) Type of drive - Multi-speed drive
f) Type of Heat Recovery System - Heat recovery
g) Thermal efficiency of heat recovery % 74
h) Maximum flow rate m3/h 25 60
i) Electric power input at maximum flow rate W 2,6 3,8
j) Sound power level (LWA) dBA 35 38
k) Reference flow rate m3/h 17 41
l) Reference pressure difference Pa 10
m) Specific power input (SPI) W/m3/h 0,071 0,054
n1) Control factor - 1
n2) Control typology - Manual control (no DCV)
o1) Maximum internal leakage rate % N/A
o2) Maximum external leakage rate % 1
p1) Internal mixing rate % N/A
p2) External mixing rate % N/A
q) Visual filter warning - N/A
r) Instructions to install regulated grilles - N/A
s) Internet address for preassembly/disassembly instructions - www.eltafans.com
t) Airflow sensitivity to pressure variations % N/A
u) Indoor/outdoor air tightness m3/h 21 60
v1) AEC - Annual electricity consumption - warm climates kWh 1 0,7
v2) AEC - Annual electricity consumption - average climates kWh 1 0,7
v3) AEC - Annual electricity consumption - cold climates kWh 1 0,7
w1) AHS - Annual heating saved - warm climates kWh 18 18,1
w2) AHS - Annual heating saved - average climates kWh 39,9 40
w3) AHS - Annual heating saved - cold climates kWh 78 78,2
ErP Directive - Regulations 1253/2014 1254/2014
15
Informationondisposalofunitsattheendoflife.ThisproductcomplieswithEUDirective2002/96/EC.The symbol of the crossed-out dustbin indicates that this product must be collected separately from other waste at the end of its life. The user must,therefore,disposeoftheproductinquestionatsuitableelectronicandelectro-technicalwastedisposalcollectioncentres,orelsesendtheproduct back to the retailerwhenpurchasinganew, equivalent typedevice.Separate collection of decommissioned equipment for recycling,treatment and environmentally compatible disposal helps to prevent negative effects on the environment and on health and promotes the recycling of the materials that make up the equipment. Improperdisposaloftheproductbytheusermayresultinadministrativesanctions as provided by law.
DISPOSAL AND RECYCLING
GUARANTEETheproductisofferedwithafiveyearwarranty.
Firstyearofwarrantycoverspartsandlabour,followingthisperiodthewarrantycoversreplacement parts only based on maintenance having being carried out in accordance with our literature and terms and conditions of sale.ProofofPurchase,Periodicinspectionandmaintenancewillberequiredintheeventofany warranty claim.
STANDARD CONFORMITY2014/35/EULowVoltageDirective(LVD)2014/30/EUElectromagneticCompatibility(EMC),inconformitywiththefollowingstandards:ElectricalSafety:EN60335-1(2012)+A11+A13;EN60335-2-80(2003)+A1+A2ElectromagneticCompatibility:EN55014-1(2017);EN55014-2(2015);EN61000-3-2(2014);EN61000-3-3(2013).
EltaFansLimitedBuildingServices46ThirdAvenuePensnettTradingEstateKingswinfordWest MidlandsDY67USUnitedKingdomT:+44(0)1384275800F:+44(0)1384275810E:[email protected] 000830-07-0718