galaxy 3000 breaker cabinet - - apc usa · vigilohm tr5a ka1 1 l+ (1) b- b+ (1) : strap or one of...
TRANSCRIPT
51030764EN/AD - Page 1
MGE UPS SYSTEMS
Installation manual
Galaxy 300010 - 30 kVA
www.mgeups.com
Battery circuit-breaker cabinet
TH
EU
NI
NT
ER
RU
PT
IB
L
EP
OW
ER
P R O V I D E R
51030764EN/AD - Page 3
1. Installation of cabinet ............................................................................................................ 4
2. Characteristics of cabinet ..................................................................................................... 5
2.1 Mechanical characteristics of cabinet ............................................................................................................ 5
2.2 Electrical characteristics of QF1 circuit-breaker ........................................................................................... 5
3. Connection ............................................................................................................................. 6
3.1 Connection points ............................................................................................................................................ 6
3.2 Connection diagrams ....................................................................................................................................... 6
3.3 Auxiliary cabinet connections in the Galaxy cubicles .................................................................................. 8
contents
Page 4 - 51030764EN/AD
◗ The circuit-breaker cabinet must be located as close to the battery as possible.
◗ The cabinet is fixed to a vertical wall by means of 4 screws of diameter 8 using the fastening lugs placed in the vertical or
horizontal position.
◗ The cabinet door is closed by two lock knobs with a key (405 type) on one of the knobs.
◗ The cabinet version with insulation controller has the same characteristics as the standard version (except for
dimensions), with the insulation controller being located in the upper part of the cabinet door.
◗ Cables are fed through the bottom of the cabinet via a 315 x 90 mm opening for a 400 mm wide cabinet.
1. Installation of cabinet
I
MJH
L
K
P
24
opening for cable feed-throughfrom the bottom
location forinsulationmonitor
W
51030764EN/AD - Page 5
◗ The characteristics of the cabinets indicated in the tables below are valid for a linear load charge with power factor of 0.8.
◗ The recommended cable cross-sections are applicable to U1000R02V type copper conductors. They are calculated in
relation to permissible temperature rises and take into account a maximum line voltage drop of 1% for a maximum cable
length of 25 m. For greater cable lengths, cross-sections will be chosen to keep the voltage drop within 1%.
2. Characteristics of cabinet
2.1 Mechanical characteristics of cabinet
Dimensions of cabinet:
H = 600 mm
W = 400 mm
P =200 mm
M = 658 mm
I = 350 mm
K = 458 mm
J = 550 mm
Weight of cabinet:
Cabinet without insulation monitor: 15 kg
Cabinet with insulation monitor: 17 kg
Max. cable cross-section:
35 mm2
2.2 Electrical characteristics of QF1 circuit-breaker
Type:
NS100
Release:
TM100D
Magnetic setting:
800 A
Thermal setting:
Galaxy 3000 10/15 kVA: 0.8
Galaxy 3000 20/30 kVA: 1
Page 6 - 51030764EN/AD
3.1 Connection points
3. Connection
terre
QF1
L- L+
B+
XR1 XR2
A
A
B-
◗ Connection to the inverter on 25 x 5 mm copper terminals with 8.2 mm diameter holes.
◗ Connection to the battery on 25 x 5 mm copper terminals with 8.2 mm diameter holes.
◗ Earth connection on 8 mm diameter threaded rod, or on 50 x 5 mm copper terminal.
3.2 Connection diagrams
Connection for a type 1 cabinet without insulation monitor
to terminals 1 of the 1 connectorto terminals 2 of the 1 connector
to terminals 3 of the 1 connector
◗ The cross-section of the power cables is given in the tables in the section entitled "characteristics of cabinet".
◗ Recommended cross-section of auxiliary conductors: 1 mm2 (terminal acceptance capacity: 2.5 mm2).
◗ Make sure that the auxiliary conductors and power cables do not follow the same path.
◗ Power cables and auxiliary conductors are not supplied.
Important: leave the QF1 circuit-breaker in "off" position until the Galaxy 3000 unit has been commissioned.
(1) : Strap or one of the contacts of the emergency stop button, if any.
L- L+
1 2 3 4 5 6
11 14 D1 D4
(1)
B- B+
cabinet withdoor open
view AA
to invertercubicle
auxiliaries
earth
to battery
positioncontact ofQF1 circuit-breaker
QF1 tripping:48V under-voltage coil
to BATTERY
QF1 batterycircuit-breaker
battery circuit-breakercabinet to INVERTER
XR1terminal block
51030764EN/AD - Page 7
Connection for a type 1 cabinet with insulation monitor
QF1 tripping:48V under-voltage coil
positioncontact ofQF1 circuit-breakerQF1 battery
circuit-breaker
to BATTERY
to INVERTERpower supply unit
mains 1 interphase voltage (380V, 400V or 415V):
to QD1 circuit-breaker
3. Connection
L-
1 2 3 4 5 62MM10 8 9
876
2 1 9 3
3 4 5
1 2
2A gI
VigilohmTR5A
KA1
1
L+
(1)
B- B+
(1) : Strap or one of the contacts of the emergency stop button, if any.
batterycircuit-breakercabinet
XR1terminal block
earthinsulation fault
XR2 terminal block
to terminals 1 of the 1 connectorto terminals 2 of the 1 connector
to terminals 3 of the 1 connector