ge critical power - abb group...ge critical power overhead distributed power busway for the...
TRANSCRIPT
GE Critical Power Overhead Distributed Power Busway for the Datacenter
GE Series DPB Gen 2
Series DPB Distributed Power Busway
ELECTRICAL SPECS • Bus Ratings (Amps):
160/225/250, 400, 800 • Voltage:
120 thru 600VAC, 3ph • 3w or 4w, 100% Neutral • Frequency: 60 or 50 Hz • Short Circuit Capacity: 22KAIC @ 600VAC 35KAIC @ 480VAC 42KAIC @ 208VAC • Copper bus bars • Class H (220) insulation
2
FEATURES • 20-30% less expensive than traditional cable/conduit installs • Finger-safe, indoor rated bus system • Multiple Rail lengths: 3, 5, 6, 10, 12 feet • 99% Recyclable • UL/ETL/CE/IEC approved & certified • Interchangeable Tap-Off Boxes, 160-400 Amp • End Feed/Bus Rail Monitoring, BCM Basic or Plus (optional) • Near-wall mounting okay, due to straight-up Tap-Box install • Flexible configuration via use of Elbows, Tees, & Cross units • Options: 150% Neutral ; 100% Rated Isol Ground
End Feed (monitoring optional)
Standard or IEC (monitoring – opt)
Monitored with whips
Standard or IEC w/ whips
Custom Load Distribution (Tap-Off Boxes)
Bus Rail Sections
Series DPB Bus System Main Components
Local Display Monitor (optional)
The Zenith Series DPB Bus System Busway assembly is comprised of three major elements
Anodized Aluminum Housing
• protects the assembly
• improves thermal properties,
• Incorporates TOUGHRAIL technology allowing optimized support methods, site specific labeling and system communication links
Bus Bars • vary in cross-sectional area depending on
ampacity
• nickel-plated to resist corrosion and minimize contact resistance
• 99% pure electrical grade copper.
Insulators • Class B 148° C material
• enhanced short circuit capability
• insulating capacity of up to 1000 volts
Series DPB Bus Rail Technology
Housing – common housing, 160 - 800 Amps
Top channel - bus rail hanger / mounting and grounding plate
Side channel – integrated custom labeling, side mount support
Integrated communication channel monitor all loads / devices
True IP2X-rated bus rail channel opening finger safe!
Isolated ground channel (optional) integrated channel design
Datacenter A/B Exterior Color Coding standard is black ; red & blue option
Series DPB Bus Rail Technology
Robust, Configurable, Multi-Purpose Housing Assembly
• Improved Bus Rail Coupler is 50% less size, and doubled the number of contact points. Minimizes resistance and voltage drop.
• Tested for 60degr C ambient (200-400A)
• Compact design minimizes “Keep Out Area”, so more TapOff Boxes can be installed on the rails
• No special tools required for installation
• Supports BCMS communication cable for secure use of installation & maintenance
Series DPB Bus Rail Coupler Technology
3.75” Industry Leading Keep Out Area
Two Step Process insures Safety and Electrical Integrity
STEP 1: Mechanical Connection • All grounding connections engage &
seat directly to the open bus channel.
• Top Mast connects mechanically to the bus rails. Set screws then insure alignment to rails. Rail design prevents backwards installation.
STEP 2: Electrical Connection • Once Top Mast is mechanically
secured, the cam action lever seats all electrical contacts against the phase bussing. Once energized, it locks down into position. At this point, the circuit breakers can be safely energized.
Series DPB Tap-Off Box Connection to Bus Rail
Series DPB Tap-Off Boxes
TAP-OFF BOXES • 160-400 Amp • GE Branch Circuit Breakers, 10 or 22 KAIC • Multiple Branch Cord Lengths available • Multiple single & duplex receptacles/connectors
available • IEC/CE version receptacles & connectors available • Branch Circuit Monitoring (optional)
8
BCMS-equipped Tap-Off Box
End Feed Box
Bus Rail
Tap -Off Box Tap Off Box
Communication Cable
IntelliBUS Board
Communication Connection
MODBUS BMS & DCIM
Local Display
Hub
Branch Circuit Monitoring
Source Monitoring
Series DPB Rail & Tap-Off Box Monitoring
Communication Options
Series DPB
10
Optional Local Display to show Voltage, Current, Current Demand, Crest factor, KVA, KW, PF, kWh, kVAR, % Load
Communications
Series DPB Busway GE Website Customer Resources
11
Available Documents • DPB Gen 2 Brochure • Template Guide Specifications • Drawings • O&M Manuals • Whitepapers • And much more…….
www.gecriticalpower.com