gea compressor hgx46 co 2 t assembly instructions documents/bock...d gb f e 3 96259-03.2016-dgb...

46
engineering for a better world GEA Compressor HGX46 CO 2 T Assembly instructions HGX46/250-4 ML CO 2 T HGX46/250-4 S CO 2 T HGX46/250-4 SH CO 2 T HGX46/280-4 ML CO 2 T HGX46/280-4 S CO 2 T HGX46/280-4 SH CO 2 T HGX46/310-4 ML CO 2 T HGX46/310-4 S CO 2 T HGX46/310-4 SH CO 2 T HGX46/345-4 ML CO 2 T HGX46/345-4 S CO 2 T HGX46/345-4 SH CO 2 T HGX46/440-4 ML CO 2 T

Upload: others

Post on 20-Jun-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

1

9625

9-03

.201

6-DG

b

engineering for a better world

GEA Compressor HGX46 CO2 T

Assembly instructions

HGX46/250-4 ML CO2 T HGX46/250-4 S CO2 T HGX46/250-4 SH CO2 THGX46/280-4 ML CO2 T HGX46/280-4 S CO2 T HGX46/280-4 SH CO2 THGX46/310-4 ML CO2 T HGX46/310-4 S CO2 T HGX46/310-4 SH CO2 THGX46/345-4 ML CO2 T HGX46/345-4 S CO2 T HGX46/345-4 SH CO2 THGX46/440-4 ML CO2 T

Page 2: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

2

D

GB

F

E

9625

9-03

.201

6-DG

b

About these instructionsRead these instructions before assembly and before using the compressor. This will avoid misunder-standings and prevent damage. Improper assembly and use of the compressor can result in serious or fatal injury. Observe the safety instructions contained in these instructions.These instructions must be passed onto the end customer along with the unit in which the compres-sor is installed.

GEA Bock GmbH

72636 Frickenhausen

GEA Bock GmbH

Benzstraße 7

72636 Frickenhausen

Germany

Telephone +49 7022 9454-0

Fax +49 7022 9454-137

[email protected]

www.gea.com

Manufacturer

Contact

1 Safety 4 1.1 Identificationofsafetyinstructions 1.2 Qualificationsrequiredofpersonnel 1.3 Safety instructions 1.4 Intended use 2 Product description 6 2.1 Short description 2.2 Name plate 2.3 Type key 3 Areas of application 8 3.1 Refrigerants 3.2 Oil charge 3.3 Limits of application

Contents Page

Page 3: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

3

9625

9-03

.201

6-DG

b

Contents Page

4 Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up 4.3 Connecting the pipelines - solder system 4.4 Connecting the pipelines - cutting ring system 4.5 Pipes 4.6 Flange shut-off valves (HP/LP) 4.7 Option: cutting ring screw joint (HP/LP) 4.8 Laying suction and pressure lines 4.9 Operating the shut-off valves 4.10 Operating mode of the lockable service connections 4.11 Oil return 5 Electrical connection 17 5.1 Information for contactor and motor contactor selection 5.2 Standard motor, designed for direct or part winding start 5.3 Basic circuit diagram for part winding start --> with MP10 5.4 Basic circuit diagram for part winding start --> with INT69 G 5.5 Special motor: design for direct or star-delta start 5.6 Basic circuit diagram for star-delta start with special motor --> with MP10 5.7 Electronic trigger unit MP10 5.8 Connection of the electronic trigger unit MP10 5.9 Functional test of the electronic trigger unit MP10 5.10 Basic circuit diagram for star-delta start with special motor --> with INT69 G 5.11 Electronic trigger unit INT69 G 5.12 Connection of the electronic trigger unit INT69 G 5.13 Functional test of the electronic trigger unit INT69 G 5.14 Oil sump heater 6 Commissioning 34 6.1 Preparations for start-up 6.2 Pressure strength test 6.3 Leak test 6.4 Evacuation 6.5 Refrigerant charge 6.6 Start-up 6.7 Pressure switch 6.8 Decompression valves 6.9 Avoiding slugging 6.10 Filter dryer 7 Maintenance 38 7.1 Preparation 7.2 Work to be carried out 7.3 Accessories 7.4 Spare parts recommendation 7.5 Lubricants 7.6 Decommissioning 8 Technical data 40 9 Dimensions and connections 42 10 Declaration of installation 44 11 Service 45

Page 4: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

4

D

GB

F

E

9625

9-03

.201

6-DG

b

1 | Safety

1.1 Identificationofsafetyinstructions:

1.2 Qualificationsrequiredofpersonnel

WARNING Inadequatelyqualifiedpersonnelposestheriskofaccidents, theconsequencebeingseriousor fatal injury.Workoncompressorsmust therefore only be performed by personnel with the qualificationslistedbelow:• For example, a refrigeration technician, refrigeration mechatronics

engineer. As well as professions with comparable training, which enable personnel to assemble, install, maintain and repair refrigeration and air-conditioning systems. Personnel must be capable of assessing the work to be carried out and recognising any potential dangers.

DANGER Indicatesadangeroussituationwhich,ifnotavoided,willcauseimmediatefatalorseriousinjury

WARNING Indicatesadangeroussituationwhich,ifnotavoided,maycausefatalorseriousinjury

CAUTION Indicatesadangeroussituationwhich,ifnotavoided,mayimmediatelycausefairlysevereorminorinjury.

ATTENTION Indicatesasituationwhich,ifnotavoided,maycauseproperty damage

INFO Importantinformationortipsonsimplifyingwork

Page 5: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

5

9625

9-03

.201

6-DG

b

1 | Safety

These assembly instructions describe the standard version of the compressors named in the title manufactured by GEA. GEA refrigerating compressors are intended for installing in a machine (within the EU according to the EU Directives 2006/42/EC Machinery Directive, 97/23/EC PressureEquipmentDirectiveand2006/95/EC–LowVoltageDirective).Commissioning is only permissible if the compressors have been installed in accordance with these assembly instructions and the entire system into which they are integrated has been inspected and approved in accordance with legal regulations.

The compressors are intended for use with CO2 in transcritical and/or subcritical systems in compliance with the limits of application.

Onlytherefrigerantspecifiedintheseinstructionsmaybeused.

Any other use of the compressor is prohibited!

1.4 Intended use

1.3 Safety instructions

WARNING Riskofaccident.Refrigerating compressors are pressurised machines and therefore requireparticularcautionandcareinhandling.

The maximum permissible overpressure must not be exceeded,even for testing purposes.

Riskofburns!-Dependingontheoperatingconditions,surfacetemperaturesof over 60 °C on the pressure side or below 0 °C on the suction side can be reached.- Avoid the contact with refrigerant under any circumstances. Thecontactwithrefrigerantcan leadtosevereburnsandskin irritations.

Danger of suffocation.CO2 is a nonflammable, acidic, colorless and odorless gas and heavier than air.NeverreleasesignificantvolumesofCO2 or the entire contents of the system into closed rooms!

Safety installationsaredesignedoradjusted inaccordancewithEN 378-2 or appropriate safety standards.

• Transcritical CO2 applications are still in the development phase.•Theyrequireacompletelynewkindofsystemandcontrol.• They are not a general solution for the substitution of F-gases.•Therefore, we expressly point out that all information in this assembly instruction has been provided according to our current levelofknowledgeandmaychangeduetofurtherdevelopment. Legal claims based on the correctness of the information cannot be made at any time and are hereby expressly excluded.

WARNING The compressor may not be used in potentially explosive environments!

Page 6: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

6

D

GB

F

E

9625

9-03

.201

6-DG

b

2 | Product description

• Semi-hemetic six-cylinder reciprocating compressor with suction gas cooled driving motor.• Theflowofrefrigerantsuckedinfromtheevaporatorisledovertheengineandprovidesfor

a particularly intensive cooling. Thus the engine can be kept special during high load on a relatively low temperature level.

• Oil pump independent of direction of rotation for reliable and safe oil supply.• One decompression valve each on the low and high pressure side, which vent into the

amosphere when these inadmissibly high printing pressures are reached.

Fig. 1

Fig. 2

Dimension and connection values can be found in Chapter 9

2.1 Short description

Oil sight glass

Valveplate

Cylinder cover

Motor section

Transport eyelet

Oil pump

Drive section

Discharge shut-off valve

Name plate

Suction shut-off valve

Terminal box

Page 7: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

7

9625

9-03

.201

6-DG

b

12345

6789

10111213

AV12345-001

91,7 A

289 A 374 A

30,2

36,2

CO2,C 85 E

HGX46/345-4 S CO2 T

100/150 bar

GEA Bock GmbH72636 Frickenhausen, Germany

1 Type designation2 Machine number3 maximum operating current4 Starting current (rotor blocked) Y: Part winding 1 YY: Part winding 1 and 25 ND (LP): max. permissible operating pressure (g) Low pressure side HD (HP): max. permissible operating pressure (g) High pressure side Observe the limits of

application diagrams!

50 Hz

60 Hz

6 Voltage,circuit,frequency7 Nominal rotation speed8 Displacement9 Voltage,circuit,frequency10 Nominal rotation speed11 Displacement12 Oiltypefilledatthefactory13 Terminal box protection type Electrical accessories can change the IP protection class!

2 | Product description

}

}

Fig. 3

2.2 Name plate (example)

/HG 4 6 345- 4 CO2X

2.3 Typekey (example)

¹) HG - Hermetic Gas-Cooled (suction gas-cooled) ²) X - Ester oil charge³) ML - Normal cooling and deep freezing at low and medium evaporation temperaturesS - Forfrequencyregulationandextendedlimitsofapplication SH - For high evaporating temperatures eg. heat pumps, different oil charge

transcritical

CO2 version

Compressor version ³)

Number of poles

Swept volume

Numbers of cylinders

Size

Oil charge ²)

Series ¹)

TS

Page 8: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

8

D

GB

F

E

9625

9-03

.201

6-DG

b

3 | Areas of application

Thecompressorsarefilledatthefactorywiththefollowingoiltype: Compressor version ML andS: GEAC85E Compressor versionSH: GEAC150E (only this oils may be used)

3.1 Refrigerants• CO2: R744(RecommendationCO2quality4.5(<5ppmH2O))

3.2 Oil charge

3.3 Limits of application

ATTENTION Property damage possible.

The oil level must be in the visible part of the sight glass; damage to the compressor is possible if overfilled or underfilled!

Fig. 4

max.

min.

1,5 Ltr. oil level ~~

ATTENTION Compressor operation is possible within the operating limits shown in the diagrams. Please note the significance of the shaded areas. Thresholds should not be selected as design or continuous operation points.

- Permissible ambient temperature (-20°C) - (+60°C).- Max. permissible discharge end temperature 160°C.- Min. oil temperature ≥ 30°C.- Min. pressure gas temperature ≥ 50°C.-Max.permissibleswitchingfrequency12x/h.- A minimum running time of 3 min. steady-state condition (continuous operation) must be achieved.

Avoid continuous operation in limit range.

Foroperationwithfrequencyconverter:-Frequencyrange20-70Hz- The maximum current and power consumption must not be exceeded.Inthecaseofoperationabovethemainsfrequency, the application limit can therefore be limited.

Page 9: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

9

9625

9-03

.201

6-DG

b

3 | Areas of application

to Evaporation temperature (°C)∆toh Suction gas superheat (K)po Suction pressure (bar)pv2 Discharge end pressure (bar)

Unlimited application range

Fig. 5

Max. permissible operating pressure (LP/HP)1):100/150bar

1) LP = Low pressure HP = High pressure

10 20 30 50

50

40

90

80

120

Einsatzgrenzen HGX34 CO 2 T

100

70

60

40 po (bar)

pV2 (bar)

110

130

140

60

0-10-20-30-40

10to (°C)

20

64,3 70

25

?t = 10 KOh

10 20 30 50

50

40

90

80

120

100

70

60

40 po (bar)

pV2 (bar)

110

130

140

60

0-10-20-30-40

10to (°C)

20

64,3 70

25

?t = 10 KOh

10 20 30 50

50

40

90

80

120

100

70

60

40 po (bar)

pV2 (bar)

110

130

140

60

0-10-20-30-40

10to (°C)

20

64,3 70

25

?t = 10 KOh

Compressor version ML

Page 10: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

10

D

GB

F

E

9625

9-03

.201

6-DG

b

to Evaporation temperature (°C)∆toh Suction gas superheat (K)po Suction pressure (bar)pv2 Discharge end pressure (bar)

Unlimited application range

Fig. 6

Max. permissible operating pressure (LP/HP)1):100/150bar

1) LP = Low pressure HP = High pressure

10 20 30 50

50

40

90

80

120

Einsatzgrenzen HGX34 CO 2 T

100

70

60

40 po (bar)

pV2 (bar)

110

130

140

60

0-10-20-30-40

10to (°C)

20

64,3 70

25

?t = 10 KOh

10 20 30 50

50

40

90

80

120

100

70

60

40 po (bar)

pV2 (bar)

110

130

140

60

0-10-20-30-40

10to (°C)

20

64,3 70

25

?t = 10 KOh

10 20 30 50

50

40

90

80

120

100

70

60

40 po (bar)

pV2 (bar)

110

130

140

60

0-10-20-30-40

10to (°C)

20

64,3 70

25

?t = 10 KOh

Compressor version S

3 | Areas of application

Page 11: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

11

9625

9-03

.201

6-DG

b

to Evaporation temperature (°C)∆toh Suction gas superheat (K)po Suction pressure (bar)pv2 Discharge end pressure (bar)

Unlimited application range

Fig. 7

Max. permissible operating pressure (LP/HP)1):100/150bar

1) LP = Low pressure HP = High pressure

10 20 30 50

50

40

90

80

120

Einsatzgrenzen HGX34 CO 2 T

100

70

60

40 po (bar)

pV2 (bar)

110

130

140

60

0-10-20-30-40

10to (°C)

20

64,3 70

25

?t = 10 KOh

10 20 30 50

50

40

90

80

120

100

70

60

40 po (bar)

pV2 (bar)

110

130

140

60

0-10-20-30-40

10to (°C)

20

64,3 70

25

?t = 10 KOh

10 20 30 50

50

40

90

80

120

100

70

60

40 po (bar)

pV2 (bar)

110

130

140

60

0-10-20-30-40

10to (°C)

20

64,3 70

25

?t = 10 KOh

Compressor version SH

3 | Areas of application

Evaporationtemperatures<5°C(40bar)onrequest!

Page 12: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

12

D

GB

F

E

9625

9-03

.201

6-DG

b

4| Compressor assembly

INFO Newcompressorsarefactory-filledwithinertgas(3barnitrogen). Leave this service charge in the compressor for as long as possible and prevent the ingress of air. Immediately after coolingtechnical connection of the compressor ofshutoffdevicesinsuction-,discharge-,oilreturnlineetc.closeand compressors evacuate.Check the compressor for transport damagebefore starting any work.

4.2 Setting up

Setuponanevensurfaceorframewithsufficientload-bearingcapacity.

Single compressor preferably on vibration damper. Compound connection basically rigid.

Provideadequateclearanceformaintenancework. Ensureadequatecompressorventilation.

Do not use in a corrosive, dusty, damp atmosphere or a com-bustible environment.

Fig. 10

Fig. 11

Fig. 12

F

E

D

C

B

A

1234

F

E

D

C

4 3 2 1

A

BTol.-Ang. DIN ISO 2768-mK

Ra Rz

Maß Passung Freigabe

Alternativbezug:Baumustergeprüft

Teil inaktiv

Lieferantenzeichnung

--

K.-Auftrag:PL:

Zeichnung ungültig

Entwicklungsstand

Teil keine Serie

120400

±0.5

über 0.5bis 6

Benzstraße 7 - 72636 Frickenhausen - Germany - www.bock.de

-

-Unbemaßte Radien:

-

Diese Zeichnung ist unser Eigentum!Sie darf ohne unsere Genehmigung weder nach-gebildet, vervielfältigt, oder Dritten Personen zu-gänglich gemacht werden. Der Nachbau nachdieser Zeichnung, oder an Hand der nach dieserZeichnung hergestellten Gegenstände durch denAbnehmer oder Dritte ist nicht gestattet.Wir behalten uns alle Rechte, gemäß DIN ISO 16016an dieser Zeichnung vor.

Bearb.DatumÄnderungs-Nr.

Werkstoff:

Ausgangsteil, bzw. Rohteil:-

-

Gepr.

NameDatum19.04.

WerkstückkantenDIN ISO 13715

Ersatz für:

Ersetzt durch:

Erstellt2010

Geprüft

-

Kurz

Zone

1/x

Oberflächenbehandlung / Härte:-

Blatt:Änderungsbeschreibung

400Benennung:

±0.8

1000 30 6

-

±0.3

12030

±0.2

Zeichn.-Nr. Teile-Nr.

Oberflächenangaben ISO 1302

x.xxxx-xxxxx.x

Zust.Gußtoleranzen:

Gewicht: (kg)

±0.1

Maßstab:

1:1

Wasserwaagefür Indesign

Der Lieferant muß sicherstellen, dass die Ware ineinwandfreiem Zustand angeliefert wird (Korrosions-schutz, Verpackung für sicheren Transport).

Rz 25Rz 160

s

25

zyxwut

0,05 Rz 1,60,30,71,62 Rz 166,3 Rz 63 Rz 6,3Rz 12,5

F:\u

ser\k

urz\

3D S

ache

n\3D

Tei

le\Z

eich

nung

en\W

asse

rwaa

ge

?4.1 Storage and transportation

Use transport eyelet. Donotliftmanually! Useliftinggear!

Storage at (-30°C) - (+70°C), maximum permissible relative humidity 10% -95 %, no condensation. Do not store in a corrosive, dusty, vaporous atmosphere or in a com-

bustible environment.

Fig. 9

Fig. 8

ATTENTION Attachments(e.g.pipeholders,additionalunits,fasteningparts,etc.) directly to the compressor are not permissible!

Page 13: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

13

9625

9-03

.201

6-DG

b

4| Compressor assembly

• On its high-pressure side, the compressor has a shut-off valve with multi-sided cutting ring for safe installation of the discharge line.

Cutting ring function before tightening the union nut

4.4 Connecting the pipelines - cutting ring system

Tubepreparation:

The tube has to be sawn in a right angle. An angular tolerance of ±1° is permissible. Slightly trim the pipe ends inside and outside. For thin walled steel pipes or soft pipes made of nonferrous metal, reinforcing sleeves have to be used.

Pipeassembly:

Push Union Nut (5) and Cut Ring (3) onto Pipe (2). Insert pipe into Socket (6) as far as it will go and firmly press against pipe stop, otherwise incorrect assembly. Hand tighten union nut until socket, cutting ring and union nut are locked. Tighten union nut 1 ½ turns using a spanner wrench. The cutting ring is noticeably locked to the socket face (for assembly inside pipe connection, hold up valve with a spanner wrench). This should cause the cutting ring with its cutting edges to cut into the pipe resulting in a visible collar. In order to stick to the turns we recommend using marking lines on union nut and pipe. After assembly, it is necessary to check the collar. The gasket must not be damaged. At least 80% of the cutting face has to be covered. After check-up, screw on and tighten again as described above.

Fig. 14Figure similar

. . . . .

Collar

Materialsoldering/weldingconnection:S235(JRG2C) The pipe connections have graduated inside diameters so that pipes with standart millimetre and inch dimensions can be used. The connection diameters of the shut-off valves are rated for maximum compressor output. Theactualrequiredpipecrosssectionmustbematched to the output. The same applies for non-return valves.Fig. 13: graduated

internal diameter

4.3 Connecting the pipelines - solder system

ATTENTION Damage possible.

Superheating can damage the valve.Remove the pipe supports therefore from the valve for soldering and accordingly cool the valve body during and after soldering.Only solder using inert gas to inhibit oxidation products (scale).

Page 14: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

14

D

GB

F

E

9625

9-03

.201

6-DG

b

4| Compressor assembly

4.5 Pipes

4.6 Flange shut-off valves (HP/LP)

4.7 Option:cuttingringscrewjoint(HP/LP)

RemoveSchraderconnection LP

Fig. 17 Fig. 18

CAUTION Riskofinjury.

The compressor must be depressurised through connections A andBbeforecommencinganyworkandpriortoconnectingtotherefrigerant system.

ATTENTION Property damage possible.

ThecompressorasdeliveredisequippedwithSchradervalveson the high and low pressure connections. These are used exclusively forchangingwithinertgasinthefactory,andundernocircum-stances may they be connected to the refrigeration circuit (the Schrader valves are approved for overpressure up to 28 bar only)!

INFO Optionally to theflangeshut-offvalves,cuttingringscrewjoints (Fig.17 and 18) (HP/LP) are also available.

Fig. 15 Fig. 16

Pipes and system components must be clean and dry inside and free of scale, swarf and layers of rust and phosphate. Only use hermetically sealed parts.

Lay pipes correctly. Suitable vibration compensators must be provided to prevent pipes being cracked and broken by severe vibrations.

Ensure a proper oil return. Keep pressure losses to an absolute minimum.

A B

Remove Schraderconnection HP

Page 15: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

15

9625

9-03

.201

6-DG

b

4| Compressor assembly

4.9 Operating the shut-off valves

Before opening or closing the shut-off valve, release the valve spindle seal by approx. ¼ of a turn counter-clockwise.

After activating the shut-off valve, re-tighten the adjustable valve spindle seal clockwise.

Fig. 20 Fig. 21

Valve spindle seal

release tighten

Fig. 19

Rigid fixed point

4.8 Laying suction and pressure lines

Aruleofthumb:Alwayslaythefirstpipesectionstartingfromtheshut-offvalvedownwards and parallel to the drive shaft.

As short as possible

ATTENTION Property damage possible.

Improperlyinstalledpipescancausecracksandtearswhichcanresult in a loss of refrigerant.

INFO Proper layout of the suction and pressure lines directly after the compressor is integral to the smooth running and vibration behaviour of the system.

Page 16: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

16

D

GB

F

E

9625

9-03

.201

6-DG

b

4| Compressor assembly

Toensuretheoilreturnfunctionwillworkreliablynomatterwhatkindofsystemconfigurationyouareusing,GEArecommendsincorporatingoilseparatorsoroillevelmonitoringequipment.The"O"connection is already available from the factory for the purpose of installing the additional oil level monitoringcomponent.Oilshouldbereturnedfromtheoilseparatortothecompressorviathe"D1"connection provided for this purpose on the compressor.

4.11 Oil return

Pipe connection

Pipe connection

4.10Operatingmodeofthelockableserviceconnections

Fig. 22Openingtheshut-offvalve:Spindle: turn to the left (counter-clockwise) as far as it will go. —> Shut-off valve completely opened / service connection closed.The connection which cannot be shut off is intended for safety devices.

Fig. 23Opening the service connectionSpindle: Turn ½ - 1 turn to the right clockwise. —> Service connection opened / shut-off valve opened.The connection which cannot be shut off is intended for safety devices.

Service connection closed

Connectionblocked

Spindle

Connection cannot be shut off

Connection cannot be shut off

Service connection opened

SpindleConnectionopen

Compressor

Compressor

Afteractivatingthespindle,generallyfitthespindleprotectioncapagainandtightenwith40-50Nm.This serves as a second sealing feature during operation.

Page 17: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

17

9625

9-03

.201

6-DG

b

5| Electrical connection

5 Electrical connection

INFO Connect the compressor motor in accordance with the circuit diagram (see inside of terminal box). Use suitable cable entry point of the correct protection type (see

name plate) for routing cables into the terminal box. Insert the strain reliefs and prevent chafe marks on the cables.Comparethevoltageandfrequencyvalueswiththedataforthe

mains power supply. Only connect the motor if these values are the same.

DANGER Riskofelectricshock!Highvoltage! Onlycarryoutworkwhentheelectricalsystemisdisconnectedfrom the power supply!

5.1 Information for contactor and motor contactor selection

All protection equipment, switching and monitoring devices must comply with the local safetyregulationsandestablishedspecifications(e.g.VDE)aswellasthemanufacturer’sspecifications. Motorprotectionswitchesarerequired! Motor contactors, feed lines, fuses and motor protection switches must be rated according to the maximum operating current (see name plate). For motor protection, use a current-independent, time-delayed overload protection device for monitoring all three phases. Adjust the overload protection device so that it must be actuated within 2 hours at 1.2 times the maximum working current.

ATTENTION Whenattachingaccessorieswithanelectricalcable,aminimumbending radius of 3 x the cable diameter must be maintained for laying the cable.

Page 18: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

18

D

GB

F

E

9625

9-03

.201

6-DG

b

5.2 Standardmotor,designedfordirectorpartwindingstart

Designation on the name plate Sticker on the terminal box

Y/YY

Compressors marked in this way are suitable for direct or part winding start. The motor winding is divided into two parts: part winding 1 = 66% and part winding 2 = 33%. This winding devision reduces the start-up current during a part winding start to approx. 65% of the value for a direct start.

5| Electrical connection

Page 19: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

19

9625

9-03

.201

6-DG

b

In the factory, the motor is switched for direct starting (YY). For part winding start (Y/YY), remove the bridges and connect the motor feed cable according to the circuit diagram:

400 V

Direct start YY Part winding start Y/YY

L1

L2

L3

L1

L2

L3

L1 L3L2

PTC

PW II

PW I

PTC

ATTENTION Property damage possible.

Failure to comply results in reversed fields of rotation and cancause motor damage. After the motor has started up with part win-ding1,partwinding2mustbeswitchedonaftermax.1seconddelay. Failure to comply can be detrimental to the service life of the motor.Ensure that power is supplied via K1 to winding 1 (66%) (1U1 / 1V1 / 1W1) and via K2 to winding 2 (33%) (2U1 / 2V1 / 2W1). The motor contactors (K1/K2) are each to be rated for approx. 70% of the max. operating current.

5| Electrical connection

Page 20: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

20

D

GB

F

E

9625

9-03

.201

6-DG

b

Οnderung

6.1

0

Datum Name

Datum

Bearb.

Gepr.

Norm

1

20.02.2009

Kelich

27.05.2015

Urspr.

2

Ers. f.

3

Ers. d.

4

PW INT69 HG44/56

5 6 7

BOCK COMPRESSORS

8

=

+

9

Bl.

6.2 Bl.

6.2

Anschlußkasten Verdichter

BT1

BP1

P-Öl

MP10

QA1

L1 L2 L3 N PE

FC1.1

I> I>I>

QA2

1U1

1V1

1W1

PE

EC1

MY/YY

2U1

2V1

2W1

FC1.2

I> I>I>

QA3FC1.1

FC1.2

FC2

SF1

BP2

P>

QA2

BP3

P

QA2

KF1

KF1

6.8

6.1.8

QA2

EB1

L1.1L2.1L3.1L1.2

NPE

QA3

BT3

T2 N L M S

QA2

PE

BT2Θ

BT2Θ

X1 L1 L1 N N 43 43 11 12 14L S M

X2 1 2 3 4 5 6

5.3 Basic circuit diagram for part winding start --> compressor with MP10

Fig. 24

5| Electrical connection

Compressor terminal box

BP1 Oil pressure safety switchBP2 High pressure safety monitorBP3 Safety chain (high/low pressure monitoring)BT1 Cold conductor (PTC sensor) motor windingBT2 Thermal protection thermostat*BT3 Release switch (thermostat)EB1 Oil sump heaterEC1 Compressor motor

* With several connect them in series

Page 21: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

21

9625

9-03

.201

6-DG

b

Οnderung

6.1

0

Datum Name

Datum

Bearb.

Gepr.

Norm

1

20.02.2009

Kelich

27.05.2015

Urspr.

2

Ers. f.

3

Ers. d.

4

PW INT69 HG44/56

5 6 7

BOCK COMPRESSORS

8

=

+

9

Bl.

6.2 Bl.

6.2

Anschlußkasten Verdichter

BT1

BP1

P-Öl

MP10

QA1

L1 L2 L3 N PE

FC1.1

I> I>I>

QA2

1U1

1V1

1W1

PE

EC1

MY/YY

2U1

2V1

2W1

FC1.2

I> I>I>

QA3FC1.1

FC1.2

FC2

SF1

BP2

P>

QA2

BP3

P

QA2

KF1

KF1

6.8

6.1.8

QA2

EB1

L1.1L2.1L3.1L1.2

NPE

QA3

BT3

T2 N L M S

QA2

PE

BT2Θ

BT2Θ

X1 L1 L1 N N 43 43 11 12 14L S M

X2 1 2 3 4 5 6

FC1.1 Motor protection switch (part winding 1)FC1.2 Motor protection switch (part winding 2)FC2 Control power circuit fuseKF1 Delay relay max. 1sQA1 Main switchQA2 Mains contactor (part winding 1)QA3 Mains contactor (part winding 2)SF1 Control voltage switch

Page 22: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

22

D

GB

F

E

9625

9-03

.201

6-DG

b

5.4 Basic circuit diagram for part winding start --> compressor with INT69 G

Οnderung

6

0

Datum Name

Datum

Bearb.

Gepr.

Norm

1

20.02.2009

Kelich

27.05.2015

Urspr.

2

Ers. f.

3

Ers. d.

4

PW INT69 HG44/56

5 6 7

BOCK COMPRESSORS

8

=

+

9

Bl.

6.2 Bl.

6.2

6.1

Anschlußkasten Verdichter

BT1INT69

BP1

P-Öl

QA1

L1 L2 L3 N PE

FC1.1

I> I>I>

QA2

1U1

1V1

1W1

PE

EC1

MY/YY

2U1

2V1

2W1

FC1.2

I> I>I>

QA3FC1.1

FC1.2

FC2

SF1

BP2

P>

QA2

BP3

P

QA2

KF1

KF1

6.8

6.2.8

QA2

EB1

L1.1L2.1L3.1L1.2

NPE

QA3

1112 14L N B1 B2

BT3

BT2Θ

T2 N L M S

QA2

PE

BT2Θ

Fig. 25

5| Electrical connection

Compressor terminal box

BP1 Oil pressure safety switchBP2 High pressure safety monitorBP3 Safety chain (high/low pressure monitoring)BT1 Cold conductor (PTC sensor) motor windingBT2 Thermal protection thermostat*BT3 Release switch (thermostat)EB1 Oil sump heaterEC1 Compressor motor

* With several connect them in series

Page 23: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

23

9625

9-03

.201

6-DG

b

Οnderung

6

0

Datum Name

Datum

Bearb.

Gepr.

Norm

1

20.02.2009

Kelich

27.05.2015

Urspr.

2

Ers. f.

3

Ers. d.

4

PW INT69 HG44/56

5 6 7

BOCK COMPRESSORS

8

=

+

9

Bl.

6.2 Bl.

6.2

6.1

Anschlußkasten Verdichter

BT1INT69

BP1

P-Öl

QA1

L1 L2 L3 N PE

FC1.1

I> I>I>

QA2

1U1

1V1

1W1

PE

EC1

MY/YY

2U1

2V1

2W1

FC1.2

I> I>I>

QA3FC1.1

FC1.2

FC2

SF1

BP2

P>

QA2

BP3

P

QA2

KF1

KF1

6.8

6.2.8

QA2

EB1

L1.1L2.1L3.1L1.2

NPE

QA3

1112 14L N B1 B2

BT3

BT2Θ

T2 N L M S

QA2

PE

BT2Θ

FC1.1 Motor protection switch (part winding 1)FC1.2 Motor protection switch (part winding 2)FC2 Control power circuit fuseKF1 Delay relay max. 1sQA1 Main switchQA2 Mains contactor (part winding 1)QA3 Mains contactor (part winding 2)SF1 Control voltage switch

Page 24: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

24

D

GB

F

E

9625

9-03

.201

6-DG

b

5| Electrical connection

5.5 Specialmotor:designfordirectorstar-deltastart

Designation on the name plate Sticker on the terminal box

∆ / Y

Page 25: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

25

9625

9-03

.201

6-DG

b

5| Electrical connection

Star-delta start-up is only possible for 230 V power supply. Example:

230 V ∆

Direct start Star-delta start

400 V Y

Direct start only

L1 L3L2

PTC

L1

L2

L3

L1

L2

L3

L1 L3L2

PTC PTC

W2

U2

V2

W1U1

V1

W2

U2

V2

W1U1

V1

Page 26: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

26

D

GB

F

E

9625

9-03

.201

6-DG

b

5.6 Stern-Dreieck-AnlaufmitSondermotor--> Verdichter mit MP10

Οnderung

2.1

0

Datum Name

Datum

Bearb.

Gepr.

Norm

1

20.02.2009

Kelich

28.05.2015

Urspr.

2

Ers. f.

3

Ers. d.

4

D/S

INT69 HG44/56

5 6 7

BOCK COMPRESSORS

8

=

+

9

Bl.

6.2 Bl.

6

2.2

Anschlußkasten Verdichter

BT1

BP1

P-Öl

MP10

QA1

L1 L2 L3 N PE

FC1.1

I> I>I>

QA2

FC1.2

I> I>I>

PE

U1

V1

W1

EC1

M3 ˜

QA4Y

W2

U2

V2

QA3D

FC1.1

FC1.2

FC2

SF1QA2

QA2

2.7

2.1.5

2.1.7

.513 14 2.5

QA4

BP2

P>

KF1

QA4

QA3

2.8

2.1.8

KF1

QA3

QA4

2.8

2.1.8

KF1

P

BP3

QA2

EB1

L1.1L2.1L3.1L1.2

NPE

BT2Θ

BT3

T2 N L M S

QA2

PE

BT2Θ

X1 L1 L1 N N 43 43 11 12 14L S M

X2 1 2 3 4 5 6

Fig. 26

* With several connect them in series

5.6 Basic circuit diagram for star-delta start with special motor --> compressor with MP10

5| Electrical connection

Compressor terminal box

BP1 Oil pressure safety switchBP2 High pressure safety monitorBP3 Safety chain (high/low pressure monitoring)BT1 Cold conductor (PTC sensor) motor windingBT2 Thermal protection thermostat*BT3 Release switch (thermostat)EB1 Oil sump heaterEC1 Compressor motor

Page 27: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

27

9625

9-03

.201

6-DG

b

Οnderung

2.1

0

Datum Name

Datum

Bearb.

Gepr.

Norm

1

20.02.2009

Kelich

28.05.2015

Urspr.

2

Ers. f.

3

Ers. d.

4

D/S

INT69 HG44/56

5 6 7

BOCK COMPRESSORS

8

=

+

9

Bl.

6.2 Bl.

6

2.2

Anschlußkasten Verdichter

BT1

BP1

P-Öl

MP10

QA1

L1 L2 L3 N PE

FC1.1

I> I>I>

QA2

FC1.2

I> I>I>

PE

U1

V1

W1

EC1

M3 ˜

QA4Y

W2

U2

V2

QA3D

FC1.1

FC1.2

FC2

SF1QA2

QA2

2.7

2.1.5

2.1.7

.513 14 2.5

QA4

BP2

P>

KF1

QA4

QA3

2.8

2.1.8

KF1

QA3

QA4

2.8

2.1.8

KF1

P

BP3

QA2

EB1

L1.1L2.1L3.1L1.2

NPE

BT2Θ

BT3

T2 N L M S

QA2

PE

BT2Θ

X1 L1 L1 N N 43 43 11 12 14L S M

X2 1 2 3 4 5 6

FC1.1/1.2 Motor protection switchFC2 Control power circuit fuseKF1 Delay relay for contactor changeoverQA1 Main switchQA2 Mains contactorQA3 Δ-contactorQA4 Y-contactorSF1 Control voltage switch

Page 28: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

28

D

GB

F

E

9625

9-03

.201

6-DG

b

5| Electrical connection

Fig. 27

Temperature monitoring connections: Motor winding: Terminals 1 - 2 Thermal protection thermostat: Terminals 3 - 4 Restart prevention: Terminals 5 - 6

ATTENTIONTerminals 1 - 6 on the trigger unit MP10 and terminals PTC 1 and PTC 2 on the compressor terminal board must not come into contact with mains voltage. This would destroy the trigger unit and PTC sensors.The supply voltage at L1-N (+/- for DC 24 V version) must be identical tothevoltageatterminals11,12,14 and 43.

5.7 Electronic trigger unit MP10

Thecompressormotorisfittedwithcoldconductortemperaturesensors(PTC)connectedtotheelec-tronic trigger unit MP10 in the terminal box. Readiness to operate is signalled by the H3 LED (green) after the power supply is applied. In the case of excess temperature in the motor winding, the unit switches off the compressor and the H1 LED lights red.

The hot gas side of the compressor can also be protected against overtemperature using a thermal protection thermostat. The H2 LED (red) is provided for the protection function.

The unit trips when an overload or inadmissible operating conditions occur. Find and remedy the cause.

5.8 Connection of the trigger unit MP10

INFO Theunithasarestartpreventiondevice.Afteryouhaverectifiedthefault,interruptthemainsvoltage.Thisunlockstherestartpreventiondevice and the LEDs H1 and H2 go out.

INFO Connect the trigger unit MP10 in accordance with the circuit dia-gram. Protect the trigger unit with a delayed-action fuse (FC2) of max.4A.Inordertoguaranteetheprotectionfunction,installthetriggerunitasthefirstelementinthecontrolpowercircuit.

Terminal box

Page 29: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

29

9625

9-03

.201

6-DG

b

5| Electrical connection

5.9 Function test of the trigger unit MP10

The compressor and the trigger unit MP10 are operational when the H3 LED (green) lights.

Pos ProcedureLED H1 LED H2 LED H3

red red green1 • Interrupt power supply (L1 or SF1) OFF OFF OFF

• Release the motor temperature sensor connection (1 or 2)• Release the hot gas temperature sensor (if installed) (3 or 4)

2 • Restore the power supply (L1 or SF1) ON• Function check of motor temperature sensor: operational ON• Function check of hot gas temperature sensor: operational ON

3 • Interrupt power supply again (L1 or SF1) OFF OFF OFF• Reconnect terminals 1 or 2 and/or 3 or 4

4 •Restorethepowersupply(L1orSF): OFF OFF ON• MP10 is operational again

Before start-up, troubleshooting or making changes to the control power circuit, check the functionality of the trigger unit:

Page 30: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

30

D

GB

F

E

9625

9-03

.201

6-DG

b

Οnderung

2

0

Datum Name

Datum

Bearb.

Gepr.

Norm

1

20.02.2009

Kelich

28.05.2015

Urspr.

2

Ers. f.

3

Ers. d.

4

D/S

INT69 HG44/56

5 6 7

BOCK COMPRESSORS

8

=

+

9

Bl.

6.2 Bl.

2.2

2.1

Anschlußkasten Verdichter

BT1INT69

BP1

P-Öl

QA1

L1 L2 L3 N PE

FC1.1

I> I>I>

QA2

FC1.2

I> I>I>

PE

U1

V1

W1

EC1

M3 ˜

QA4Y

W2

U2

V2

QA3D

FC1.1

FC1.2

FC2

SF1QA2

QA2

2.7

.5 2.2.5

2.2.7

13 14 2.5

QA4

BP2

P>

KF1

QA4

QA3

2.8

2.2.8

KF1

QA3

QA4

2.8

2.2.8

KF1

P

BP3

QA2

EB1

L1.1L2.1L3.1L1.2

NPE

OG OG

1112 14L N B1 B2

BT2Θ

BT3

T2 N L M S

QA2

PE

BT2Θ

5.10 Basic circuit diagram for star-delta start with special motor --> compressor with INT69 G

Fig. 28

* With several connect them in series

BP1 Oil pressure safety switchBP2 High pressure safety monitorBP3 Safety chain (high/low pressure monitoring)BT1 Cold conductor (PTC sensor) motor windingBT2 Thermal protection thermostat*BT3 Release switch (thermostat)EB1 Oil sump heaterEC1 Compressor motor

Compressor terminal box

5| Electrical connection

Page 31: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

31

9625

9-03

.201

6-DG

b

Οnderung

2

0

Datum Name

Datum

Bearb.

Gepr.

Norm

1

20.02.2009

Kelich

28.05.2015

Urspr.

2

Ers. f.

3

Ers. d.

4

D/S

INT69 HG44/56

5 6 7

BOCK COMPRESSORS

8

=

+

9

Bl.

6.2 Bl.

2.2

2.1

Anschlußkasten Verdichter

BT1INT69

BP1

P-Öl

QA1

L1 L2 L3 N PE

FC1.1

I> I>I>

QA2

FC1.2

I> I>I>

PE

U1

V1

W1

EC1

M3 ˜

QA4Y

W2

U2

V2

QA3D

FC1.1

FC1.2

FC2

SF1QA2

QA2

2.7

.5 2.2.5

2.2.7

13 14 2.5

QA4

BP2

P>

KF1

QA4

QA3

2.8

2.2.8

KF1

QA3

QA4

2.8

2.2.8

KF1

P

BP3

QA2

EB1

L1.1L2.1L3.1L1.2

NPE

OG OG

1112 14L N B1 B2

BT2Θ

BT3

T2 N L M S

QA2

PE

BT2Θ

FC1.1/1.2 Motor protection switchFC2 Control power circuit fuseKF1 Delay relay for contactor changeoverQA1 Main switchQA2 Mains contactorQA3 Δ-contactorQA4 Y-contactorSF1 Control voltage switch

Page 32: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

32

D

GB

F

E

9625

9-03

.201

6-DG

b

5.11 Electronic trigger unit INT69 G

5.12 Connection of the trigger unit INT69 G

The compressormotor is fittedwith cold conductor temperature sensors (PTC) connected to theelectronic trigger unit INT69 G in the terminal box. In case of excess temperature in the motor winding, the INT69 G deactivates the motor contactor. Once cooled, it can be restarted only if the electronic lock of the output relay (terminals B1+B2) is released by interrupting the supply voltage.

The hot gas side of the compressor can also be protected against overtemperature using thermal protection thermostats (accessory).

The unit trips when an overload or inadmissible operating conditions occur. Find and remedy the cause.

INFO The relayswitchingoutput isexecutedasafloatingchangeover contact.Thiselectricalcircuitoperatesaccordingtothequiescent currentprinciple, i.e. the relaydrops intoa the idlepositionand deactivatesthemotorcontactorevenincaseofasensorbreakor open circuit.

INFO Connect the trigger unit INT69 G in accordance with the circuit dia-gram. Protect the trigger unit with a delayed-action fuse (FC2) of max.4A.Inordertoguaranteetheprotectionfunction,installthetriggerunitasthefirstelementinthecontrolpowercircuit.

Οnderung

Klebeschilder

0

Datum Name

Datum

Bearb.

Gepr.

Norm

1

04.12.2009

Kelich

22.05.2015

Urspr.

2

Ers. f.

3

Ers. d.

4

Schaltplan

5 6 7

BOCK COMPRESSORS

8

=

+

9

Bl.

MP10 INt69 Bl.

MP10 INt69

INT69 G Motor Protection MP10

Steuerstrom-

kreis

LN

Steuerstrom-

kreis

L N1112 14

B1 B2OG OG

+

-BT1

Θ

X1 L1 L1 N N 43 43 11 12 14L S M

X2 1 2 3 4 5 6

R1 R2

+

-BT1

Θ

+

-BT2

Θ

+

-BT2

ΘLN

5| Electrical connection

Terminal boxFig. 29

ATTENTION Measure circuit BT1 and BT2 (PTC sensor) must not come into contact with external voltage. This would destroy the trigger unit INT69 G and PTC sensors.

Control circuit

Page 33: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

33

9625

9-03

.201

6-DG

b

Operation: The oil sump heater operates when the compressor is at a standstill. When the compressor starts up, the oil sump heating switches off.

Connexion:The oil sump heater must be connected via an auxiliary contact (or parallel wired auxiliary contact) of the compressor contactor to a seperate electric circuit.

Electricaldata:230V-1-50/60Hz,160W.

ATTENTION The oil sump heater must generally be connected and operated!

5.14 Oil sump heater

Inordertoavoiddamagetothecompressor,thecompressorisequippedwithanoilsumpheaterasa standart feature.

Relay position INT69 G

B2 12 14 11

Fig. 30

5.13 Function test of the trigger unit INT69 G

Before commissioning, after troubleshooting or making changes to the control power circuit, check the functionality of the trigger unit. Perform this check using a continuity tester or gauge.

5| Electrical connection

Gauge state Relay position

1. Deactivated state 11-12

2. INT69 G switch-on 11-14

3. Remove PTC connector 11-12

4. Insert PTC connector 11-12

5. Reset after mains on 11-14

Page 34: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

34

D

GB

F

E

9625

9-03

.201

6-DG

b

6| Commissioning

6.1 Preparations for start-up

The compressor has undergone trials in the factory and all functions have been tested. There are therefore no special running-in instructions.

Checkthecompressorfortransportdamage!

INFO In order to protect the compressor against inadmissible operating conditions,high-pressureandlow-pressurepressostatscontrolsare mandatory on the installation side.

WARNING When the compressor is not running, depending on ambient temperature and amount of refrigerant charge, it is possiblethat the pressure may rise and exceed permitted levels for the compressor.Adequateprecautionsmustbetakentopreventthishappening(e.g.usingacoldstoragemedium,areceivertank,asecondaryrefrigerantsystem,orpressurereliefdevices).

6.3 Leaktest

Carry out the leak test on the refrigerating plant in accordance with EN 378-2 or a corresponding safety standard, while always observing the maximum permissible overpressure for the compressor.

DANGER Riskofbursting!The compressor must only be pressurised using nitrogen (N2). Never pressurise with oxygen or other gases!The maximum permissible overpressure of the compressor must not be exceeded at any time during the testing process (see name plate data)! Do not mix any refrigerant with the nitrogen as this could cause the ignition limit to shift into the critical range.

6.2 Pressure integrity test

The compressor has been tested in the factory for pressure integrity. If however the entire system is to be subjected to a pressure integrity test, this should be carried out in accordance with EN 378-2 or a corresponding safety standard without the inclusion of the compressor.

Page 35: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

35

9625

9-03

.201

6-DG

b

6.4 Evacuation

First evacuate the system and then include the compressor in the evacuation process. Relieve the compressor pressure. Open the suction and pressure line shut-off valves. Turn on the oil sump heater. Evacuate the suction and discharge pressure sides using the vacuum pump. The vacuum has to be broken with nitrogen several times between the evacuation. At the end of the evacuation process, the vacuum should be < 1.5 mbar when the pump is switched off. Repeatthisprocessasoftenasisrequired.

6| Commissioning

Make sure that the suction and pressure line shut-off valves are open.

6.5 Refrigerant charge

Fillingtheliquidrefrigerant:Itisrecommendedthatthesystemfirstbefilledat standstill with gas on the high-pressure side up to a system pressure of at least5.2bar(ifitisfilledbelow5.2barwithliquid,thereisariskofdryiceformation).Furtherfillingaccordingtosystem.

To eliminate the possibility of dry ice formation when the system is operating (duringandafter thefillingprocess), theshut-offpointof the low-pressureswitch should be set to a value of at least 5.2 bar.

Arefrigerantsupplement,whichmaybecomenecessaryafterstart-up,canbe topped up in vapour form on the suction side.

ATTENTION Do not start the compressor if it is under vacuum. Do not apply any voltage - even for test purposes (must only be operated with refrigerant).Under vacuum, the spark-over and creepage current distances of the terminal board connection bolts shorten; this can result in winding and terminal board damage.

ATTENTION Avoidoverfillingthemachinewithrefrigerant! Do not charge liquid refrigerant into the suction-side on the

compressor. Do not mix additives with the oil and refrigerant.

CAUTION Wear personal protective clothing such as goggles and protective gloves!

WARNING Never exceed the max. permissible pressures while charging. Precautionsmustbetakenintime.

INFO Depending upon design of the CO2 refrigerant filling bottle(with/without tubing) CO2 can be filled in liquid after weight or gaseously.Use only high-dried CO2quality(see chapter 3.1)!

Page 36: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

36

D

GB

F

E

9625

9-03

.201

6-DG

b

6| Commissioning

6.7 Pressure switch

Check that the safety and protection devices (pressure switch, motor protection, electrical contact protection measures, etc.) are functioning properly.

Switch on the compressor and let it run for at least 10 minutes. Themachineshouldreachastateofequilibrium. Check the oil level: The oil level must be visible in the sight glass. After a compressor is replaced, the oil level must be checked again. If the level is too high, oil mustbedrainedoff(dangerofoilliquidshocks;reducedcapacityoftherefrigeratingsystem).

Suitably adjusted pressure switches that switch off the compressor before reaching the maximum permissible operating pressure must be installed in the system. The pressure reduction for the pressure switches can occur either at the suction and pressure lines between the shut-off valve and compressor or at the non-lockable connections for the shut-off valves (connections A and B, see Chapter 9).

WARNING Ensure that both shut-off valves are open before starting the compressor!

ATTENTION Iflargerquantitiesofoilhavetobetoppedup,thereisariskofoilimpacteffects.Ifthisisthecase,checktheoilreturn!

6.6 Start-up

Page 37: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

37

9625

9-03

.201

6-DG

b

CO2 streaming out

6.8 Decompression valves

6| Commissioning

Fig. 31

ATTENTION Thecompressorisfittedwithtwodecompressionvalves.Onevalveeach on the suction and discharge side. If excessive pressures are reached,thevalvesopenandpreventfurtherpressureincrease.Thereby CO2 is blown off to the ambient!Intheeventthatapressurereliefvalveactivatesrepeatedly,checkvalve and replace if necessary as during blow-off extreme condi-tionscanoccure,whichmayresult inapermanent leak.Alwayschecksystemforrefrigerantlossafteractivationofpressurereliefvalve!

The decompression valves do not replace any pressure switches and the additional safety valves in the system. Pressure switches mustalwaysbeinstalledinthesystemanddesignedoradjustedinaccordance with EN 378-2 or appropriate safety standards.FailuretoobservecanresultinriskofinjuryfromCO2 streaming out of the two decompression valves!

Page 38: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

38

D

GB

F

E

9625

9-03

.201

6-DG

b

6| Commissioning

6.9 Avoid slugging

7.1 Preparation

7| Maintenance

Topreventslugging: The complete refrigeration plant must be properly designed. All components must be compatibly rated with each other with regard to output (particularly the

evaporator and expansion valves). Suction gas superheating at the compressor input should be > 10 K (check the setting of the

expansion valve). Regard oil temperature and pressure gas temperature. (The pressure gas temperature has to be

high enough min. 50°C, so the oil temperature is > 30°C). Thesystemmustreachastateofequilibrium. Particularlyincriticalsystems(e.g.severalevaporatorpoints),measuressuchastheuseofliquidtraps,solenoidvalveintheliquidline,etc.arerecommended.

There should be no movement of refrigerant in the compressor while the system is at a standstill.

ATTENTION Slugging can result in damage to the compressor and cause refrigeranttoleak.

WARNING Beforestartinganyworkonthecompressor: Switch off the compressor and secure it to prevent a restart. Relieve compressor of system pressure.Preventairfrominfiltratingthesystem!Aftermaintenancehasbeenperformed: Connect safety switch. Evacuate compressor.Releaseswitch-onlock.

WARNING The decompression has to be carried out in a way that no dry ice respectively solid CO2 is producedwhich blocks the outlet andcould hinder the streaming out of CO2. Otherwise, there is the danger that pressure can be built up again.

6.10 Filter dryerGaseous CO2hasasignificantlylowersolubilityinwaterthanotherrefrigerants.Atlowtemperaturesitcanthereforecauseblockingofvalvesandfiltersduetoiceorhydrate.Forthisreasonwerecom-mendtheuseofanadequatelysizedfilterdrierandasightglasswithamoistureindicator

Page 39: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

39

9625

9-03

.201

6-DG

b

7.2 Worktobecarriedout

In order to guarantee optimum operational reliability and service life of the compressor, we recommend carrying out servicing and inspection work at regular intervals: Oilchange:

- not mandatory for factory-produced series systems. - forfieldinstallationsorwhenoperatingneartheapplicationlimit:forthefirsttimeafter100

to 200 operating hours, then approx. every 3 years or 10,000 - 12,000 operating hours. Dispose of used oil according to the regulations; observe national regulations.

Annual checks: Oil level, leak tightness, running noises, pressures, temperatures, function of auxiliary devices such as oil sump heater, pressure switch.

Only use genuine GEA spare parts!

7.3 Spare part recommendation

7| Maintenance

HGX46 / ... CO2 T 250-4 280-4 310-4 345-4 440-4

Designation Ref. No. Ref. No. Ref. No. Ref. No. Ref. No.

Set of gaskets until AS 036 80909 80908 --

Set of gaskets from AS 037 81180 81181 81182

Set of valve plate kit until AS 036 80760 80761 --

Set of valve plate kit from AS 037 81175 81176 81177

Set oil pump kit 80774

Set oil sump heater,230VAC 80854

Available accessories can be found on the Internet at www.gea.com.

7.4 Accessories

7.6 DecommissioningClose the shut-off valves on the compressor. CO2 does not need to be recycled and can therefore be blown off into the environment. It is essential to ensure good ventilation or conduct the CO2 into the outdoors to avoid danger of suffocation. When releasing CO2, avoid a fast drop in pressure to prevent oil from exiting with it. If the compressor is unpressurized, remove the piping on the pressure- and suction-side (e.g. dismantling of the shut-off valve, etc.) and remove the compressor using an appropriate hoist. Dispose of the oil inside in accordance with the applicable national regulations.When decommissioning the compressor (eg. for service or replacement of the compressor) larger amounts of CO2intheoilcanbesetfree.Ifthedecompressionofthecompressorisnotsufficientenough, closed shut-off valves may lead to intolerable excessive pressure. For this reason the suction side (LP) and the high pressure side (HP) of the compressor have to be secured by decompression valves.

7.5 LubricantsFor operation with CO2 the GEA oil C 85 E is necessary!

Page 40: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

40

D

GB

F

E

9625

9-03

.201

6-DG

b

8| Technical dataTy

pe

No. of cylinders

Disp

lace

men

t50

/60

Hz

(145

0 / 1

740

rpm

)

Elec

tric

al d

ata

Weight

Conn

ectio

ns

Oil chargeVo

ltage

Max

.Op

erat

ing

curr

ent

PW

1 +

2

Max

. pow

er

cons

ump-

tion

Star

ting

curr

ent

(rotorlock

ed)

PW 1

/ PW

1 +

2

Disc

harg

elin

e DV

Suct

ion

line

SV

m3 /

hA

kWA

kgm

mm

m /

inch

Ltr.

HGX4

6/25

0-4

ML

CO2

T

6

21,8

0 / 2

6,20

53,4

31,7

231

/ 283

239

2228

/ 11

/ 8

2,5

HGX4

6/25

0-4

S CO

2 T

21,8

0 / 2

6,20

65,9

38,5

253

/ 330

247

HGX4

6/25

0-4

SH C

O2

T21

,80

/ 26,

2065

,938

,525

3 / 3

3024

7

HGX4

6/28

0-4

ML

CO2

T24

,40

/ 29,

3059

,335

,523

1 / 2

8324

7

HGX4

6/28

0-4

S CO

2 T

24,4

0 / 2

9,30

73,0

43,1

253

/ 330

247

HGX4

6/28

0-4

SH C

O2

T24

,40

/ 29,

3073

,443

,425

3 / 3

3024

7

HGX4

6/31

0-4

ML

CO2

T27

,20

/ 32,

6066

,239

,823

1 / 2

8324

7

2835

/ 13

/ 8

HGX4

6/31

0-4

S CO

2 T

27,2

0 / 3

2,60

81,4

48,4

253

/ 330

265

HGX4

6/31

0-4

SH C

O2

T27

,20

/ 32,

6082

,048

,825

3 / 3

3026

5

HGX4

6/34

5-4

ML

CO2

T30

,20

/ 36,

2074

,444

,025

3 / 3

3024

7

HGX4

6/34

5-4

S CO

2 T

30,2

0 / 3

6,20

90,9

53,4

289

/ 374

265

HGX4

6/34

5-4

SH C

O2

T30

,20

/ 36,

2092

,354

,328

9 / 3

7426

5

HGX4

6/44

0-4

ML

CO2

T38

,20

/ 45,

8099

,358

,728

9 / 3

7426

5

12

3

24

5

380-420VY/YY-3-50HzPW440-480VY/YY-3-60HzPW PW = Part Winding, Winding ratios: 66%/33%

2

Page 41: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

41

9625

9-03

.201

6-DG

b

8| Technical data

Tole

ranc

e (±

10%

) rel

ativ

e to

the

mea

n va

lue

of th

e vo

ltage

rang

e.Othe

rvoltage

san

dtype

sofcurrentonrequ

est.

The

seareprelim

inaryvaluesand

can

differfrom

theac

tualvalue

s!

-Th

especifica

tionsfo

rmax

.pow

ercon

sumptionap

plyfor5

0Hzop

eration.

F

or60H

zop

eration,th

especifica

tionshavetobemultip

liedbyth

efactor

1

.2. T

he m

ax. w

orki

ng c

urre

nt re

mai

ns u

ncha

nged

.

- Ta

ke a

ccou

nt o

f the

max

. ope

ratin

g cu

rren

t / m

ax. p

ower

con

sum

ptio

n fo

r des

ign

of fu

ses,

sup

ply

lines

and

saf

ety

devi

ces.

Fus

e: C

onsu

mpt

ion

cate

gory

AC3

Allspe

cific

ationsarebased

ontheaverag

eofth

evolta

gera

nge

Cutti

ng ri

ng c

onne

ctor

for s

teel

tube

s.Fo

r sol

der c

onne

ctio

ns

1 432 5

Page 42: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

42

D

GB

F

E

9625

9-03

.201

6-DG

b

9| Dimensions and connections

Dimensions in mmFig. 32

369

(364

)

2804x 12

94 9

450ca.280

ca.1

65

ca.775

AA1

X

SV

DV

X

660 ca.795

9 94

SchwingungsdämpferVibration absorbers

1030 25 M50

B1 B

Typ / type Teile-Nr. / part-no. Typ / type Teile-Nr. /

part-no. Typ / type Teile-Nr. / part-no.

HGX46/250-4 ML CO2 T 10932 HGX46/280-4 S CO2 T 10797 HGX46/310-4 SH CO2 T 10938HGX46/250-4 S CO2 T 10796 HGX46/280-4 SH CO2 T 10937 HGX46/345-4 ML CO2 T 10935HGX46/250-4 SH CO2 T 10936 HGX46/310-4 ML CO2 T 10934 HGX46/345-4 S CO2 T 10799HGX46/280-4 ML CO2 T 10933 HGX46/310-4 S CO2 T 10798 HGX46/345-4 SH CO2 T 10939HGX46/440-4 ML CO2 T 11003

Halbhermetischer Verdichter HG / Semi-hermetic compressor HG

1.0850-10799.0 0b

Maße in ( ) für HGX46/250+280-4 ML+S+SH CO2 TDimensions in ( ) for HGX46/250+280-4 ML+S+SH CO2 TMaße in [ ] für HGX46/440-4 MLCO2 TDimensions in [ ] for HGX46/440-4 ML CO2 T

Änderungen vorbehaltenSubject to change without notice

Maße in mmDimensions in mm

MassenschwerpunktCentre of gravity

Anschlüsse /Connections

HGX46/250+280

HGX46/310+345+440

SVSaugabsperrventil, Rohr (L/SW, SR)* mm - Zoll

28 - 1 1/8" 35 - 1 3/8"Suction line valve, tube (L/SW, SR)* mm - inch

DVDruckabsperrventil, Rohr (L/SW, SR)* mm - Zoll

22 - 7/8" 28 - 1 1/8"Discharge line valve, tube (L/SW, SR)* mm - inch

AAnschluss Saugseite, nicht absperrbar Zoll

7/16“ UNFConnection suction side, not lockable inch

A1Anschluss Saugseite, absperrbar Zoll

7/16“ UNFConnection suction side, lockable inch

A2Anschluss Druckseite, nicht absperrbar Zoll

7/16“ UNFConnection discharge side, not lockable inch

BAnschluss Druckseite, nicht absperrbar Zoll

7/16“ UNFConnection discharge side, not lockable inch

B1Anschluss Druckseite, absperrbar Zoll

7/16“ UNFConnection discharge side, lockable inch

B2Anschluss Druckseite, nicht absperrbar Zoll

1/8“ NPTFConnection discharge side, not lockable inch

D1Anschluss Ölrückführung vom Ölabscheider Zoll

1/4“ NPTFConnection oil return from oil separator inch

EAnschluss Öldruckmanometer Zoll

1/8“ NPTFConnection oil pressure gauge inch

FÖlablass

mm M26x1,5Oil drain

HStopfen Ölfüllung

mm M22x1,5Oil charge plug

J1Ölsumpfheizung

mm 15oil sump heater

KSchauglas Zoll

1 1/8"-18 UNEFSight glass inch

LAnschluss Wärmeschutzthermostat Zoll

1/8“ NPTFConnection thermal protection thermostat inch

OAnschluss Ölspiegelregulator Zoll

1/2" NPTFConnection oil level regulator inch

X1Schraderanschluss, Saugseite Zoll

7/16“ UNFConnection for schrader valve, suction side inch

X2Schraderanschluss, Druckseite Zoll

7/16“ UNFConnection for schrader valve, Discharge side inch

(L/SW, SR)* = Löt-/Schweissanschluss, Schneidring(L/SW. SR)* = solder/welding connection, cutting ring

Maße und Anschlüsse mit Absperrventilemeasures and connections with shut-off valve

Alt.bezug /

Part-No.

F

E

D

C

A

F

E

D

C

4 1

A

B

5678

12345678

Zeichn.-Nr. / Drawing no. :

B

3 2

1132

70

z

über / above

Freigabe / Approved

Extranet:-

-Alt.supply:

Der Lieferant muss sicherstellen, dass die Ware in einwandfreiem Zustand angeliefert wird (Korrosionsschutz, Verpackung für sicheren

Layh

Allgemeintoleranzen / General tolerances

Drawing-No.

bis / up to

Dok

-ID:

Maßstab /

±0.1

yxwutpackaging for safe transportation).

model or design.

V4000in proper conditions (corrosion prevention,

DIN ISO 2768-mK

Ra Rz

08.11.13

Ersatz für / replacement for:The supplier has to ensure the delivery of parts

Transport).

prohibited. Offenders will be held liable for the

Dimension Passung / Clearance

Baumustergeprüft / Type examination:

--

K.-Auftrag / C.-Task:Projektleiter / Project leader:

120400±0.5

0.56

GEA Bock GmbH - Benzstraße 7 - 72636 Frickenhausen - Germany - www.bock.de

-

-

-Unbemaßte Radien / Undimensioned radii:

-

Bearb. / EditedDatum / Datepayment of damages. All rights reserved in the event

Änd.-Nr. / Mod-No.

Werkstoff (Zeile 2+3 alternativ) /

Base part, Raw part:

-

-

Geprüft / Appr.

NameDatum / Date07.11.13

Material (Line 2+3 alternative):

Ausgangsteil, Rohteil /

Workpiece edgesDIN ISO 13715

Erstellt / DrawnGeprüft / Verified Bauknecht

Zuder

1/3

Oberflächenbehandlung, Härte / Treatment of surface, Hardness:

07.11.13

Werkstückkanten /

Page:

400Benennung / Description:

±0.81000

30 6

-

±0.312030

-

Blatt /

±0.2

of the grant of a patent, utility /

DIN EN ISO 1302

Zust. / Rev.

Gußtoleranzen / General casting tolerances:

Gewicht / Weight: (kg)

Zeichnungs-Nr. /

Indication of surface texture

Scale:

%

MC- HGX46/345-4 S CO2 T

Rz 25Rz 16025 0,05 Rz 1,60,30,71,62 Rz 166,3 Rz 63 Rz 6,3Rz 12,5Status:

-

-

Frei (CAD)

Nein / No 10799 .0

19.12.13

26.09.14

Zuder

Zuder

0a | betrifft Blatt 2

0b | Verdichter HGX46/440-4 ML in Zeichnung aufgenommen.

8776

9099

Keuerleber

Keuerleber

MK- HGX46/345-4 S CO2 T

-08501.

Kunde / Customer:-

s

Weitergabe sowie Vervielfältigung dieses Dokuments, Verwertung und Mitteilung seines Inhalts sind ver-boten, soweit nicht ausdrücklich gestattet. Zuwider-handlungen verpflichten zu Schadenersatz. Alle Rechte für den Fall der Patent-, Gebrauchsmuster- oder Geschmacksmustereintragung vorbehalten.

The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization is

Maß

Oberflächenangaben /

Teile-Nr. /

Layh

B2

OEK

J1

A2

330

150

ca.4

20

ca.415 [470] X2 D1 L H

F

B2

X1

369

(364

)

2804x 12

94 9

450ca.280

ca.1

65

ca.775

AA1

X

SV

DV

X

660 ca.795

9 94

SchwingungsdämpferVibration absorbers

1030 25 M50

B1 B

Typ / type Teile-Nr. / part-no. Typ / type Teile-Nr. /

part-no. Typ / type Teile-Nr. / part-no.

HGX46/250-4 ML CO2 T 10932 HGX46/280-4 S CO2 T 10797 HGX46/310-4 SH CO2 T 10938HGX46/250-4 S CO2 T 10796 HGX46/280-4 SH CO2 T 10937 HGX46/345-4 ML CO2 T 10935HGX46/250-4 SH CO2 T 10936 HGX46/310-4 ML CO2 T 10934 HGX46/345-4 S CO2 T 10799HGX46/280-4 ML CO2 T 10933 HGX46/310-4 S CO2 T 10798 HGX46/345-4 SH CO2 T 10939HGX46/440-4 ML CO2 T 11003

Halbhermetischer Verdichter HG / Semi-hermetic compressor HG

1.0850-10799.0 0b

Maße in ( ) für HGX46/250+280-4 ML+S+SH CO2 TDimensions in ( ) for HGX46/250+280-4 ML+S+SH CO2 TMaße in [ ] für HGX46/440-4 MLCO2 TDimensions in [ ] for HGX46/440-4 ML CO2 T

Änderungen vorbehaltenSubject to change without notice

Maße in mmDimensions in mm

MassenschwerpunktCentre of gravity

Anschlüsse /Connections

HGX46/250+280

HGX46/310+345+440

SVSaugabsperrventil, Rohr (L/SW, SR)* mm - Zoll

28 - 1 1/8" 35 - 1 3/8"Suction line valve, tube (L/SW, SR)* mm - inch

DVDruckabsperrventil, Rohr (L/SW, SR)* mm - Zoll

22 - 7/8" 28 - 1 1/8"Discharge line valve, tube (L/SW, SR)* mm - inch

AAnschluss Saugseite, nicht absperrbar Zoll

7/16“ UNFConnection suction side, not lockable inch

A1Anschluss Saugseite, absperrbar Zoll

7/16“ UNFConnection suction side, lockable inch

A2Anschluss Druckseite, nicht absperrbar Zoll

7/16“ UNFConnection discharge side, not lockable inch

BAnschluss Druckseite, nicht absperrbar Zoll

7/16“ UNFConnection discharge side, not lockable inch

B1Anschluss Druckseite, absperrbar Zoll

7/16“ UNFConnection discharge side, lockable inch

B2Anschluss Druckseite, nicht absperrbar Zoll

1/8“ NPTFConnection discharge side, not lockable inch

D1Anschluss Ölrückführung vom Ölabscheider Zoll

1/4“ NPTFConnection oil return from oil separator inch

EAnschluss Öldruckmanometer Zoll

1/8“ NPTFConnection oil pressure gauge inch

FÖlablass

mm M26x1,5Oil drain

HStopfen Ölfüllung

mm M22x1,5Oil charge plug

J1Ölsumpfheizung

mm 15oil sump heater

KSchauglas Zoll

1 1/8"-18 UNEFSight glass inch

LAnschluss Wärmeschutzthermostat Zoll

1/8“ NPTFConnection thermal protection thermostat inch

OAnschluss Ölspiegelregulator Zoll

1/2" NPTFConnection oil level regulator inch

X1Schraderanschluss, Saugseite Zoll

7/16“ UNFConnection for schrader valve, suction side inch

X2Schraderanschluss, Druckseite Zoll

7/16“ UNFConnection for schrader valve, Discharge side inch

(L/SW, SR)* = Löt-/Schweissanschluss, Schneidring(L/SW. SR)* = solder/welding connection, cutting ring

Maße und Anschlüsse mit Absperrventilemeasures and connections with shut-off valve

Alt.bezug /

Part-No.

F

E

D

C

A

F

E

D

C

4 1

A

B

5678

12345678

Zeichn.-Nr. / Drawing no. :

B

3 2

1132

70

z

über / above

Freigabe / Approved

Extranet:-

-Alt.supply:

Der Lieferant muss sicherstellen, dass die Ware in einwandfreiem Zustand angeliefert wird (Korrosionsschutz, Verpackung für sicheren

Layh

Allgemeintoleranzen / General tolerances

Drawing-No.

bis / up to

Dok

-ID:

Maßstab /

±0.1

yxwutpackaging for safe transportation).

model or design.

V4000in proper conditions (corrosion prevention,

DIN ISO 2768-mK

Ra Rz

08.11.13

Ersatz für / replacement for:The supplier has to ensure the delivery of parts

Transport).

prohibited. Offenders will be held liable for the

Dimension Passung / Clearance

Baumustergeprüft / Type examination:

--

K.-Auftrag / C.-Task:Projektleiter / Project leader:

120400±0.5

0.56

GEA Bock GmbH - Benzstraße 7 - 72636 Frickenhausen - Germany - www.bock.de

-

-

-Unbemaßte Radien / Undimensioned radii:

-

Bearb. / EditedDatum / Datepayment of damages. All rights reserved in the event

Änd.-Nr. / Mod-No.

Werkstoff (Zeile 2+3 alternativ) /

Base part, Raw part:

-

-

Geprüft / Appr.

NameDatum / Date07.11.13

Material (Line 2+3 alternative):

Ausgangsteil, Rohteil /

Workpiece edgesDIN ISO 13715

Erstellt / DrawnGeprüft / Verified Bauknecht

Zuder

1/3

Oberflächenbehandlung, Härte / Treatment of surface, Hardness:

07.11.13

Werkstückkanten /

Page:

400Benennung / Description:

±0.81000

30 6

-

±0.312030

-

Blatt /

±0.2

of the grant of a patent, utility /

DIN EN ISO 1302

Zust. / Rev.

Gußtoleranzen / General casting tolerances:

Gewicht / Weight: (kg)

Zeichnungs-Nr. /

Indication of surface texture

Scale:

%

MC- HGX46/345-4 S CO2 T

Rz 25Rz 16025 0,05 Rz 1,60,30,71,62 Rz 166,3 Rz 63 Rz 6,3Rz 12,5Status:

-

-

Frei (CAD)

Nein / No 10799 .0

19.12.13

26.09.14

Zuder

Zuder

0a | betrifft Blatt 2

0b | Verdichter HGX46/440-4 ML in Zeichnung aufgenommen.

8776

9099

Keuerleber

Keuerleber

MK- HGX46/345-4 S CO2 T

-08501.

Kunde / Customer:-

s

Weitergabe sowie Vervielfältigung dieses Dokuments, Verwertung und Mitteilung seines Inhalts sind ver-boten, soweit nicht ausdrücklich gestattet. Zuwider-handlungen verpflichten zu Schadenersatz. Alle Rechte für den Fall der Patent-, Gebrauchsmuster- oder Geschmacksmustereintragung vorbehalten.

The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization is

Maß

Oberflächenangaben /

Teile-Nr. /

Layh

B2

OEK

J1

A2

330

150

ca.4

20

ca.415 [470] X2 D1 L H

F

B2

X1

369

(364

)

2804x 12

94 9

450ca.280

ca.1

65

ca.775

AA1

X

SV

DV

X

660 ca.795

9 94

SchwingungsdämpferVibration absorbers

1030 25 M50

B1 B

Typ / type Teile-Nr. / part-no. Typ / type Teile-Nr. /

part-no. Typ / type Teile-Nr. / part-no.

HGX46/250-4 ML CO2 T 10932 HGX46/280-4 S CO2 T 10797 HGX46/310-4 SH CO2 T 10938HGX46/250-4 S CO2 T 10796 HGX46/280-4 SH CO2 T 10937 HGX46/345-4 ML CO2 T 10935HGX46/250-4 SH CO2 T 10936 HGX46/310-4 ML CO2 T 10934 HGX46/345-4 S CO2 T 10799HGX46/280-4 ML CO2 T 10933 HGX46/310-4 S CO2 T 10798 HGX46/345-4 SH CO2 T 10939HGX46/440-4 ML CO2 T 11003

Halbhermetischer Verdichter HG / Semi-hermetic compressor HG

1.0850-10799.0 0b

Maße in ( ) für HGX46/250+280-4 ML+S+SH CO2 TDimensions in ( ) for HGX46/250+280-4 ML+S+SH CO2 TMaße in [ ] für HGX46/440-4 MLCO2 TDimensions in [ ] for HGX46/440-4 ML CO2 T

Änderungen vorbehaltenSubject to change without notice

Maße in mmDimensions in mm

MassenschwerpunktCentre of gravity

Anschlüsse /Connections

HGX46/250+280

HGX46/310+345+440

SVSaugabsperrventil, Rohr (L/SW, SR)* mm - Zoll

28 - 1 1/8" 35 - 1 3/8"Suction line valve, tube (L/SW, SR)* mm - inch

DVDruckabsperrventil, Rohr (L/SW, SR)* mm - Zoll

22 - 7/8" 28 - 1 1/8"Discharge line valve, tube (L/SW, SR)* mm - inch

AAnschluss Saugseite, nicht absperrbar Zoll

7/16“ UNFConnection suction side, not lockable inch

A1Anschluss Saugseite, absperrbar Zoll

7/16“ UNFConnection suction side, lockable inch

A2Anschluss Druckseite, nicht absperrbar Zoll

7/16“ UNFConnection discharge side, not lockable inch

BAnschluss Druckseite, nicht absperrbar Zoll

7/16“ UNFConnection discharge side, not lockable inch

B1Anschluss Druckseite, absperrbar Zoll

7/16“ UNFConnection discharge side, lockable inch

B2Anschluss Druckseite, nicht absperrbar Zoll

1/8“ NPTFConnection discharge side, not lockable inch

D1Anschluss Ölrückführung vom Ölabscheider Zoll

1/4“ NPTFConnection oil return from oil separator inch

EAnschluss Öldruckmanometer Zoll

1/8“ NPTFConnection oil pressure gauge inch

FÖlablass

mm M26x1,5Oil drain

HStopfen Ölfüllung

mm M22x1,5Oil charge plug

J1Ölsumpfheizung

mm 15oil sump heater

KSchauglas Zoll

1 1/8"-18 UNEFSight glass inch

LAnschluss Wärmeschutzthermostat Zoll

1/8“ NPTFConnection thermal protection thermostat inch

OAnschluss Ölspiegelregulator Zoll

1/2" NPTFConnection oil level regulator inch

X1Schraderanschluss, Saugseite Zoll

7/16“ UNFConnection for schrader valve, suction side inch

X2Schraderanschluss, Druckseite Zoll

7/16“ UNFConnection for schrader valve, Discharge side inch

(L/SW, SR)* = Löt-/Schweissanschluss, Schneidring(L/SW. SR)* = solder/welding connection, cutting ring

Maße und Anschlüsse mit Absperrventilemeasures and connections with shut-off valve

Alt.bezug /

Part-No.

F

E

D

C

A

F

E

D

C

4 1

A

B

5678

12345678

Zeichn.-Nr. / Drawing no. :

B

3 2

1132

70

z

über / above

Freigabe / Approved

Extranet:-

-Alt.supply:

Der Lieferant muss sicherstellen, dass die Ware in einwandfreiem Zustand angeliefert wird (Korrosionsschutz, Verpackung für sicheren

Layh

Allgemeintoleranzen / General tolerances

Drawing-No.

bis / up to

Dok

-ID:

Maßstab /

±0.1

yxwutpackaging for safe transportation).

model or design.

V4000in proper conditions (corrosion prevention,

DIN ISO 2768-mK

Ra Rz

08.11.13

Ersatz für / replacement for:The supplier has to ensure the delivery of parts

Transport).

prohibited. Offenders will be held liable for the

Dimension Passung / Clearance

Baumustergeprüft / Type examination:

--

K.-Auftrag / C.-Task:Projektleiter / Project leader:

120400±0.5

0.56

GEA Bock GmbH - Benzstraße 7 - 72636 Frickenhausen - Germany - www.bock.de

-

-

-Unbemaßte Radien / Undimensioned radii:

-

Bearb. / EditedDatum / Datepayment of damages. All rights reserved in the event

Änd.-Nr. / Mod-No.

Werkstoff (Zeile 2+3 alternativ) /

Base part, Raw part:

-

-

Geprüft / Appr.

NameDatum / Date07.11.13

Material (Line 2+3 alternative):

Ausgangsteil, Rohteil /

Workpiece edgesDIN ISO 13715

Erstellt / DrawnGeprüft / Verified Bauknecht

Zuder

1/3

Oberflächenbehandlung, Härte / Treatment of surface, Hardness:

07.11.13

Werkstückkanten /

Page:

400Benennung / Description:

±0.81000

30 6

-

±0.312030

-

Blatt /

±0.2

of the grant of a patent, utility /

DIN EN ISO 1302

Zust. / Rev.

Gußtoleranzen / General casting tolerances:

Gewicht / Weight: (kg)

Zeichnungs-Nr. /

Indication of surface texture

Scale:

%

MC- HGX46/345-4 S CO2 T

Rz 25Rz 16025 0,05 Rz 1,60,30,71,62 Rz 166,3 Rz 63 Rz 6,3Rz 12,5Status:

-

-

Frei (CAD)

Nein / No 10799 .0

19.12.13

26.09.14

Zuder

Zuder

0a | betrifft Blatt 2

0b | Verdichter HGX46/440-4 ML in Zeichnung aufgenommen.

8776

9099

Keuerleber

Keuerleber

MK- HGX46/345-4 S CO2 T

-08501.

Kunde / Customer:-

s

Weitergabe sowie Vervielfältigung dieses Dokuments, Verwertung und Mitteilung seines Inhalts sind ver-boten, soweit nicht ausdrücklich gestattet. Zuwider-handlungen verpflichten zu Schadenersatz. Alle Rechte für den Fall der Patent-, Gebrauchsmuster- oder Geschmacksmustereintragung vorbehalten.

The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization is

Maß

Oberflächenangaben /

Teile-Nr. /

Layh

B2

OEK

J1

A2

330

150

ca.4

20

ca.415 [470] X2 D1 L H

F

B2

X1 3

69 (3

64)

2804x 12

94 9

450ca.280

ca.1

65

ca.775

AA1

X

SV

DV

X

660 ca.795

9 94

SchwingungsdämpferVibration absorbers

1030 25 M50

B1 B

Typ / type Teile-Nr. / part-no. Typ / type Teile-Nr. /

part-no. Typ / type Teile-Nr. / part-no.

HGX46/250-4 ML CO2 T 10932 HGX46/280-4 S CO2 T 10797 HGX46/310-4 SH CO2 T 10938HGX46/250-4 S CO2 T 10796 HGX46/280-4 SH CO2 T 10937 HGX46/345-4 ML CO2 T 10935HGX46/250-4 SH CO2 T 10936 HGX46/310-4 ML CO2 T 10934 HGX46/345-4 S CO2 T 10799HGX46/280-4 ML CO2 T 10933 HGX46/310-4 S CO2 T 10798 HGX46/345-4 SH CO2 T 10939HGX46/440-4 ML CO2 T 11003

Halbhermetischer Verdichter HG / Semi-hermetic compressor HG

1.0850-10799.0 0b

Maße in ( ) für HGX46/250+280-4 ML+S+SH CO2 TDimensions in ( ) for HGX46/250+280-4 ML+S+SH CO2 TMaße in [ ] für HGX46/440-4 MLCO2 TDimensions in [ ] for HGX46/440-4 ML CO2 T

Änderungen vorbehaltenSubject to change without notice

Maße in mmDimensions in mm

MassenschwerpunktCentre of gravity

Anschlüsse /Connections

HGX46/250+280

HGX46/310+345+440

SVSaugabsperrventil, Rohr (L/SW, SR)* mm - Zoll

28 - 1 1/8" 35 - 1 3/8"Suction line valve, tube (L/SW, SR)* mm - inch

DVDruckabsperrventil, Rohr (L/SW, SR)* mm - Zoll

22 - 7/8" 28 - 1 1/8"Discharge line valve, tube (L/SW, SR)* mm - inch

AAnschluss Saugseite, nicht absperrbar Zoll

7/16“ UNFConnection suction side, not lockable inch

A1Anschluss Saugseite, absperrbar Zoll

7/16“ UNFConnection suction side, lockable inch

A2Anschluss Druckseite, nicht absperrbar Zoll

7/16“ UNFConnection discharge side, not lockable inch

BAnschluss Druckseite, nicht absperrbar Zoll

7/16“ UNFConnection discharge side, not lockable inch

B1Anschluss Druckseite, absperrbar Zoll

7/16“ UNFConnection discharge side, lockable inch

B2Anschluss Druckseite, nicht absperrbar Zoll

1/8“ NPTFConnection discharge side, not lockable inch

D1Anschluss Ölrückführung vom Ölabscheider Zoll

1/4“ NPTFConnection oil return from oil separator inch

EAnschluss Öldruckmanometer Zoll

1/8“ NPTFConnection oil pressure gauge inch

FÖlablass

mm M26x1,5Oil drain

HStopfen Ölfüllung

mm M22x1,5Oil charge plug

J1Ölsumpfheizung

mm 15oil sump heater

KSchauglas Zoll

1 1/8"-18 UNEFSight glass inch

LAnschluss Wärmeschutzthermostat Zoll

1/8“ NPTFConnection thermal protection thermostat inch

OAnschluss Ölspiegelregulator Zoll

1/2" NPTFConnection oil level regulator inch

X1Schraderanschluss, Saugseite Zoll

7/16“ UNFConnection for schrader valve, suction side inch

X2Schraderanschluss, Druckseite Zoll

7/16“ UNFConnection for schrader valve, Discharge side inch

(L/SW, SR)* = Löt-/Schweissanschluss, Schneidring(L/SW. SR)* = solder/welding connection, cutting ring

Maße und Anschlüsse mit Absperrventilemeasures and connections with shut-off valve

Alt.bezug /

Part-No.

F

E

D

C

A

F

E

D

C

4 1

A

B

5678

12345678

Zeichn.-Nr. / Drawing no. :

B

3 2

1132

70

z

über / above

Freigabe / Approved

Extranet:-

-Alt.supply:

Der Lieferant muss sicherstellen, dass die Ware in einwandfreiem Zustand angeliefert wird (Korrosionsschutz, Verpackung für sicheren

Layh

Allgemeintoleranzen / General tolerances

Drawing-No.

bis / up to

Dok

-ID:

Maßstab /

±0.1

yxwutpackaging for safe transportation).

model or design.

V4000in proper conditions (corrosion prevention,

DIN ISO 2768-mK

Ra Rz

08.11.13

Ersatz für / replacement for:The supplier has to ensure the delivery of parts

Transport).

prohibited. Offenders will be held liable for the

Dimension Passung / Clearance

Baumustergeprüft / Type examination:

--

K.-Auftrag / C.-Task:Projektleiter / Project leader:

120400±0.5

0.56

GEA Bock GmbH - Benzstraße 7 - 72636 Frickenhausen - Germany - www.bock.de

-

-

-Unbemaßte Radien / Undimensioned radii:

-

Bearb. / EditedDatum / Datepayment of damages. All rights reserved in the event

Änd.-Nr. / Mod-No.

Werkstoff (Zeile 2+3 alternativ) /

Base part, Raw part:

-

-

Geprüft / Appr.

NameDatum / Date07.11.13

Material (Line 2+3 alternative):

Ausgangsteil, Rohteil /

Workpiece edgesDIN ISO 13715

Erstellt / DrawnGeprüft / Verified Bauknecht

Zuder

1/3

Oberflächenbehandlung, Härte / Treatment of surface, Hardness:

07.11.13

Werkstückkanten /

Page:

400Benennung / Description:

±0.81000

30 6

-

±0.312030

-

Blatt /

±0.2

of the grant of a patent, utility /

DIN EN ISO 1302

Zust. / Rev.

Gußtoleranzen / General casting tolerances:

Gewicht / Weight: (kg)

Zeichnungs-Nr. /

Indication of surface texture

Scale:

%

MC- HGX46/345-4 S CO2 T

Rz 25Rz 16025 0,05 Rz 1,60,30,71,62 Rz 166,3 Rz 63 Rz 6,3Rz 12,5Status:

-

-

Frei (CAD)

Nein / No 10799 .0

19.12.13

26.09.14

Zuder

Zuder

0a | betrifft Blatt 2

0b | Verdichter HGX46/440-4 ML in Zeichnung aufgenommen.

8776

9099

Keuerleber

Keuerleber

MK- HGX46/345-4 S CO2 T

-08501.

Kunde / Customer:-

s

Weitergabe sowie Vervielfältigung dieses Dokuments, Verwertung und Mitteilung seines Inhalts sind ver-boten, soweit nicht ausdrücklich gestattet. Zuwider-handlungen verpflichten zu Schadenersatz. Alle Rechte für den Fall der Patent-, Gebrauchsmuster- oder Geschmacksmustereintragung vorbehalten.

The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization is

Maß

Oberflächenangaben /

Teile-Nr. /

Layh

B2

OEK

J1

A2

33015

0ca

.420

ca.415 [470] X2 D1 L H

F

B2

X1

369

(364

)

2804x 12

94 9

450ca.280

ca.1

65

ca.775

AA1

X

SV

DV

X

660 ca.795

9 94

SchwingungsdämpferVibration absorbers

1030 25 M50

B1 B

Typ / type Teile-Nr. / part-no. Typ / type Teile-Nr. /

part-no. Typ / type Teile-Nr. / part-no.

HGX46/250-4 ML CO2 T 10932 HGX46/280-4 S CO2 T 10797 HGX46/310-4 SH CO2 T 10938HGX46/250-4 S CO2 T 10796 HGX46/280-4 SH CO2 T 10937 HGX46/345-4 ML CO2 T 10935HGX46/250-4 SH CO2 T 10936 HGX46/310-4 ML CO2 T 10934 HGX46/345-4 S CO2 T 10799HGX46/280-4 ML CO2 T 10933 HGX46/310-4 S CO2 T 10798 HGX46/345-4 SH CO2 T 10939HGX46/440-4 ML CO2 T 11003

Halbhermetischer Verdichter HG / Semi-hermetic compressor HG

1.0850-10799.0 0b

Maße in ( ) für HGX46/250+280-4 ML+S+SH CO2 TDimensions in ( ) for HGX46/250+280-4 ML+S+SH CO2 TMaße in [ ] für HGX46/440-4 MLCO2 TDimensions in [ ] for HGX46/440-4 ML CO2 T

Änderungen vorbehaltenSubject to change without notice

Maße in mmDimensions in mm

MassenschwerpunktCentre of gravity

Anschlüsse /Connections

HGX46/250+280

HGX46/310+345+440

SVSaugabsperrventil, Rohr (L/SW, SR)* mm - Zoll

28 - 1 1/8" 35 - 1 3/8"Suction line valve, tube (L/SW, SR)* mm - inch

DVDruckabsperrventil, Rohr (L/SW, SR)* mm - Zoll

22 - 7/8" 28 - 1 1/8"Discharge line valve, tube (L/SW, SR)* mm - inch

AAnschluss Saugseite, nicht absperrbar Zoll

7/16“ UNFConnection suction side, not lockable inch

A1Anschluss Saugseite, absperrbar Zoll

7/16“ UNFConnection suction side, lockable inch

A2Anschluss Druckseite, nicht absperrbar Zoll

7/16“ UNFConnection discharge side, not lockable inch

BAnschluss Druckseite, nicht absperrbar Zoll

7/16“ UNFConnection discharge side, not lockable inch

B1Anschluss Druckseite, absperrbar Zoll

7/16“ UNFConnection discharge side, lockable inch

B2Anschluss Druckseite, nicht absperrbar Zoll

1/8“ NPTFConnection discharge side, not lockable inch

D1Anschluss Ölrückführung vom Ölabscheider Zoll

1/4“ NPTFConnection oil return from oil separator inch

EAnschluss Öldruckmanometer Zoll

1/8“ NPTFConnection oil pressure gauge inch

FÖlablass

mm M26x1,5Oil drain

HStopfen Ölfüllung

mm M22x1,5Oil charge plug

J1Ölsumpfheizung

mm 15oil sump heater

KSchauglas Zoll

1 1/8"-18 UNEFSight glass inch

LAnschluss Wärmeschutzthermostat Zoll

1/8“ NPTFConnection thermal protection thermostat inch

OAnschluss Ölspiegelregulator Zoll

1/2" NPTFConnection oil level regulator inch

X1Schraderanschluss, Saugseite Zoll

7/16“ UNFConnection for schrader valve, suction side inch

X2Schraderanschluss, Druckseite Zoll

7/16“ UNFConnection for schrader valve, Discharge side inch

(L/SW, SR)* = Löt-/Schweissanschluss, Schneidring(L/SW. SR)* = solder/welding connection, cutting ring

Maße und Anschlüsse mit Absperrventilemeasures and connections with shut-off valve

Alt.bezug /

Part-No.

F

E

D

C

A

F

E

D

C

4 1

A

B

5678

12345678

Zeichn.-Nr. / Drawing no. :

B

3 2

1132

70

z

über / above

Freigabe / Approved

Extranet:-

-Alt.supply:

Der Lieferant muss sicherstellen, dass die Ware in einwandfreiem Zustand angeliefert wird (Korrosionsschutz, Verpackung für sicheren

Layh

Allgemeintoleranzen / General tolerances

Drawing-No.

bis / up to

Dok

-ID:

Maßstab /

±0.1

yxwutpackaging for safe transportation).

model or design.

V4000in proper conditions (corrosion prevention,

DIN ISO 2768-mK

Ra Rz

08.11.13

Ersatz für / replacement for:The supplier has to ensure the delivery of parts

Transport).

prohibited. Offenders will be held liable for the

Dimension Passung / Clearance

Baumustergeprüft / Type examination:

--

K.-Auftrag / C.-Task:Projektleiter / Project leader:

120400±0.5

0.56

GEA Bock GmbH - Benzstraße 7 - 72636 Frickenhausen - Germany - www.bock.de

-

-

-Unbemaßte Radien / Undimensioned radii:

-

Bearb. / EditedDatum / Datepayment of damages. All rights reserved in the event

Änd.-Nr. / Mod-No.

Werkstoff (Zeile 2+3 alternativ) /

Base part, Raw part:

-

-

Geprüft / Appr.

NameDatum / Date07.11.13

Material (Line 2+3 alternative):

Ausgangsteil, Rohteil /

Workpiece edgesDIN ISO 13715

Erstellt / DrawnGeprüft / Verified Bauknecht

Zuder

1/3

Oberflächenbehandlung, Härte / Treatment of surface, Hardness:

07.11.13

Werkstückkanten /

Page:

400Benennung / Description:

±0.81000

30 6

-

±0.312030

-

Blatt /

±0.2

of the grant of a patent, utility /

DIN EN ISO 1302

Zust. / Rev.

Gußtoleranzen / General casting tolerances:

Gewicht / Weight: (kg)

Zeichnungs-Nr. /

Indication of surface texture

Scale:

%

MC- HGX46/345-4 S CO2 T

Rz 25Rz 16025 0,05 Rz 1,60,30,71,62 Rz 166,3 Rz 63 Rz 6,3Rz 12,5Status:

-

-

Frei (CAD)

Nein / No 10799 .0

19.12.13

26.09.14

Zuder

Zuder

0a | betrifft Blatt 2

0b | Verdichter HGX46/440-4 ML in Zeichnung aufgenommen.

8776

9099

Keuerleber

Keuerleber

MK- HGX46/345-4 S CO2 T

-08501.

Kunde / Customer:-

s

Weitergabe sowie Vervielfältigung dieses Dokuments, Verwertung und Mitteilung seines Inhalts sind ver-boten, soweit nicht ausdrücklich gestattet. Zuwider-handlungen verpflichten zu Schadenersatz. Alle Rechte für den Fall der Patent-, Gebrauchsmuster- oder Geschmacksmustereintragung vorbehalten.

The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization is

Maß

Oberflächenangaben /

Teile-Nr. /

Layh

B2

OEK

J1

A2

330

150

ca.4

20

ca.415 [470] X2 D1 L H

F

B2

X1

Anti-vibration pads

Centre of gravity

Dimensions in ( ) = HGX46/250-4 ML CO2 T HGX46/280-4 ML CO2 T HGX46/250-4 S CO2 T HGX46/280-4 S CO2 T HGX46/250-4 SH CO2 T HGX46/280-4 SH CO2 T

Dimensions in [ ] = HGX46/440-4 ML CO2 T

Dimensions and connections with shut-off valves

369

(364

)

2804x 12

94 9

450ca.280

ca.1

65

ca.775

AA1

X

SV

DV

X

660 ca.795

9 94

SchwingungsdämpferVibration absorbers

1030 25 M50

B1 B

Typ / type Teile-Nr. / part-no. Typ / type Teile-Nr. /

part-no. Typ / type Teile-Nr. / part-no.

HGX46/250-4 ML CO2 T 10932 HGX46/280-4 S CO2 T 10797 HGX46/310-4 SH CO2 T 10938HGX46/250-4 S CO2 T 10796 HGX46/280-4 SH CO2 T 10937 HGX46/345-4 ML CO2 T 10935HGX46/250-4 SH CO2 T 10936 HGX46/310-4 ML CO2 T 10934 HGX46/345-4 S CO2 T 10799HGX46/280-4 ML CO2 T 10933 HGX46/310-4 S CO2 T 10798 HGX46/345-4 SH CO2 T 10939HGX46/440-4 ML CO2 T 11003

Halbhermetischer Verdichter HG / Semi-hermetic compressor HG

1.0850-10799.0 0b

Maße in ( ) für HGX46/250+280-4 ML+S+SH CO2 TDimensions in ( ) for HGX46/250+280-4 ML+S+SH CO2 TMaße in [ ] für HGX46/440-4 MLCO2 TDimensions in [ ] for HGX46/440-4 ML CO2 T

Änderungen vorbehaltenSubject to change without notice

Maße in mmDimensions in mm

MassenschwerpunktCentre of gravity

Anschlüsse /Connections

HGX46/250+280

HGX46/310+345+440

SVSaugabsperrventil, Rohr (L/SW, SR)* mm - Zoll

28 - 1 1/8" 35 - 1 3/8"Suction line valve, tube (L/SW, SR)* mm - inch

DVDruckabsperrventil, Rohr (L/SW, SR)* mm - Zoll

22 - 7/8" 28 - 1 1/8"Discharge line valve, tube (L/SW, SR)* mm - inch

AAnschluss Saugseite, nicht absperrbar Zoll

7/16“ UNFConnection suction side, not lockable inch

A1Anschluss Saugseite, absperrbar Zoll

7/16“ UNFConnection suction side, lockable inch

A2Anschluss Druckseite, nicht absperrbar Zoll

7/16“ UNFConnection discharge side, not lockable inch

BAnschluss Druckseite, nicht absperrbar Zoll

7/16“ UNFConnection discharge side, not lockable inch

B1Anschluss Druckseite, absperrbar Zoll

7/16“ UNFConnection discharge side, lockable inch

B2Anschluss Druckseite, nicht absperrbar Zoll

1/8“ NPTFConnection discharge side, not lockable inch

D1Anschluss Ölrückführung vom Ölabscheider Zoll

1/4“ NPTFConnection oil return from oil separator inch

EAnschluss Öldruckmanometer Zoll

1/8“ NPTFConnection oil pressure gauge inch

FÖlablass

mm M26x1,5Oil drain

HStopfen Ölfüllung

mm M22x1,5Oil charge plug

J1Ölsumpfheizung

mm 15oil sump heater

KSchauglas Zoll

1 1/8"-18 UNEFSight glass inch

LAnschluss Wärmeschutzthermostat Zoll

1/8“ NPTFConnection thermal protection thermostat inch

OAnschluss Ölspiegelregulator Zoll

1/2" NPTFConnection oil level regulator inch

X1Schraderanschluss, Saugseite Zoll

7/16“ UNFConnection for schrader valve, suction side inch

X2Schraderanschluss, Druckseite Zoll

7/16“ UNFConnection for schrader valve, Discharge side inch

(L/SW, SR)* = Löt-/Schweissanschluss, Schneidring(L/SW. SR)* = solder/welding connection, cutting ring

Maße und Anschlüsse mit Absperrventilemeasures and connections with shut-off valve

Alt.bezug /

Part-No.

F

E

D

C

A

F

E

D

C

4 1

A

B

5678

12345678

Zeichn.-Nr. / Drawing no. :

B

3 2

1132

70

z

über / above

Freigabe / Approved

Extranet:-

-Alt.supply:

Der Lieferant muss sicherstellen, dass die Ware in einwandfreiem Zustand angeliefert wird (Korrosionsschutz, Verpackung für sicheren

Layh

Allgemeintoleranzen / General tolerances

Drawing-No.

bis / up to

Dok

-ID:

Maßstab /

±0.1

yxwutpackaging for safe transportation).

model or design.

V4000in proper conditions (corrosion prevention,

DIN ISO 2768-mK

Ra Rz

08.11.13

Ersatz für / replacement for:The supplier has to ensure the delivery of parts

Transport).

prohibited. Offenders will be held liable for the

Dimension Passung / Clearance

Baumustergeprüft / Type examination:

--

K.-Auftrag / C.-Task:Projektleiter / Project leader:

120400±0.5

0.56

GEA Bock GmbH - Benzstraße 7 - 72636 Frickenhausen - Germany - www.bock.de

-

-

-Unbemaßte Radien / Undimensioned radii:

-

Bearb. / EditedDatum / Datepayment of damages. All rights reserved in the event

Änd.-Nr. / Mod-No.

Werkstoff (Zeile 2+3 alternativ) /

Base part, Raw part:

-

-

Geprüft / Appr.

NameDatum / Date07.11.13

Material (Line 2+3 alternative):

Ausgangsteil, Rohteil /

Workpiece edgesDIN ISO 13715

Erstellt / DrawnGeprüft / Verified Bauknecht

Zuder

1/3

Oberflächenbehandlung, Härte / Treatment of surface, Hardness:

07.11.13

Werkstückkanten /

Page:

400Benennung / Description:

±0.81000

30 6

-

±0.312030

-

Blatt /

±0.2

of the grant of a patent, utility /

DIN EN ISO 1302

Zust. / Rev.

Gußtoleranzen / General casting tolerances:

Gewicht / Weight: (kg)

Zeichnungs-Nr. /

Indication of surface texture

Scale:

%

MC- HGX46/345-4 S CO2 T

Rz 25Rz 16025 0,05 Rz 1,60,30,71,62 Rz 166,3 Rz 63 Rz 6,3Rz 12,5Status:

-

-

Frei (CAD)

Nein / No 10799 .0

19.12.13

26.09.14

Zuder

Zuder

0a | betrifft Blatt 2

0b | Verdichter HGX46/440-4 ML in Zeichnung aufgenommen.

8776

9099

Keuerleber

Keuerleber

MK- HGX46/345-4 S CO2 T

-08501.

Kunde / Customer:-

s

Weitergabe sowie Vervielfältigung dieses Dokuments, Verwertung und Mitteilung seines Inhalts sind ver-boten, soweit nicht ausdrücklich gestattet. Zuwider-handlungen verpflichten zu Schadenersatz. Alle Rechte für den Fall der Patent-, Gebrauchsmuster- oder Geschmacksmustereintragung vorbehalten.

The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization is

Maß

Oberflächenangaben /

Teile-Nr. /

Layh

B2

OEK

J1

A2

330

150

ca.4

20

ca.415 [470] X2 D1 L H

F

B2

X1

Page 43: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

43

9625

9-03

.201

6-DG

b

9| Dimensions and connections

SVDV

Suction lineDischarge line see technical data, chapter 8

A Connection suction side, not lockable 7/16“ UNF

A1 Connection suction side, lockable 7/16“ UNF

A2 Connection suction side, not lockable 7/16“ UNF

B Connection discharge side, not lockable 7/16“ UNF

B1 Connection discharge side, lockable 7/16“ UNF

B2 Connection discharge side, not lockable 1/8“ NPTF

D1 Connection oil return from oil separator 1/4“ NPTF

E Connection oil pressure gauge 1/8“ NPTF

F Oil drain M26 x 1,5

H Oil charge plug M22 x 1,5

J1 Oil sump heater Ø 15 mm

K Sight glass 1 1/8“ - 18 UNEF

L* Connection thermal protection thermostat 1/8“ NPTF

O Connection oil level regulator 1 1/8“ - 18 UNEF

X1 Connection for Schrader valve, suction side 7/16“ UNF

X2 Connection for Schrader valve, discharge side 7/16“ UNF

* No connection discharge side

Page 44: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

44

D

GB

F

E

9625

9-03

.201

6-DG

b

10| Declaration of installation

DECLARATION OF INSTALLATION

for using the compressors within the European Union(in accordance with Machinery Directive 2006/42/EC)

The manufacturer: GEA Bock GmbH, Benzstraße 7 72636 Frickenhausen, Tel.: 07022/9454-0

hereby declares that the refrigerating compressor HGX46 CO2 T complies with the basic requirementsofAppendixII1BoftheMachineryDirective2006/42/EC. Applied harmonised standard:

EN 12693:2008 and the corresponding standards referenced

A partly completed machine may only be put into operation when it has been established that the machine, into which the partly completed machine is to be installed, conforms to the regulations of the Machinery Directive (2006/42/EC).

Themanufacturerundertakestotransmitelectronicallythespecialdocumentationrequiredbyindividualstatesforpartlycompletedmachineryonrequest.

ThespecialtechnicaldocumentationrequiredforpartlycompletedmachineryhasbeencreatedinaccordancewithAppendixVIIPartB.

Person responsible for documentation is: Wolfgang Sandkötter, Benzstraße 7, 72636 Frickenhausen.

Frickenhausen, 25.09.2012 ppa. Wolfgang Sandkötter, ChiefDevelopmentOfficer

Page 45: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

D

GB

F

E

45

9625

9-03

.201

6-DG

b

Dear customer,

GEAcompressorsaretop-quality,reliableandservice-friendlyqualityproducts. Ifyouhaveanyquestionsaboutinstallation,operationandaccessories,pleasecontactourtechnicalservice or specialist wholesaler and/or our representative. The GEA service team can be contacted by phone with a toll-free hotline 00 800 / 800 000 88 or via e-mail:[email protected].

Yours faithfully

GEABockGmbH

Benzstraße7

72636Frickenhausen

Germany

11| Service

Page 46: GEA Compressor HGX46 CO 2 T Assembly instructions Documents/Bock...D GB F E 3 96259-03.2016-DGb Contents Page 4Compressor assembly 12 4.1 Storage and transportation 4.2 Setting up

46

D

GB

F

E

9625

9-03

.201

6-DG

b96

259-

03.2

016-

DG

b ©

GEA

Gro

up A

G. A

ll rig

hts

rese

rved

.

GEA Bock GmbH

Benzstraße 7, 72636 Frickenhausen, GermanyTelephone: +49 7022 9454-0, Fax: +49 7022 [email protected], www.gea.com

We live our values.Excellence • Passion • Integrity • Responsibility • GEA-versity

GEA Group is a global engineering company with multi-billion euro sales and operations in more than 50 countries. Founded in 1881, the company is one of the largest providers of innovative equipment and process technology. GEA Group is listed in the STOXX® Europe 600 index.