REMOVE EXISTING PATIO PAVERS AND SALVAGE FOR REUSE. SALVAGE ALL PEDESTALS THAT ARE IN GOOD CONDITION FOR REUSE. REMOVE MEMBRANE ROOF SYSTEM DOWN TO CONCRETE SUBSTRATE.
REMOVE WOODEN PLANTERS, BENCHES & ASSOCIATED STRUCTURAL SUPPORTS ENTIRELY.
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOFEXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF UNDER PATIO PAVERS TO BE REMOVED
CAREFULLY REMOVE EXISTING FLASHING ALONG WALLS
CAREFULLY REMOVE EXISTING FLASHING ALONG WALLS
CAREFULLY REMOVE EXISTING FLASHING ALONG WALLS
REMOVE WALL & RAILING SYSTEM ENTIRELY
B5
R1.01
B8
R1.01
B8
R1.01
B5
R1.01K3
R1.01
B5
R1.01
B8
R1.01B5
R1.01
B8
R1.01
B8
R1.01 B5
R1.01
GENERAL NOTES - DEMOLITION
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEMOLITION AND REMOVAL NECESSARY TO COMPLETE THE WORK. THE CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR THE REMOVAL AND PROPER DISPOSAL, INCLUDING ALL COSTS FOR CARRYING AND DUMPING, OF ALL MATERIAL DEMOLISHED FROM THE PROJECT. THE CONTRACTOR SHALL PROVIDE OWNER WITH FIRST RIGHTS TO ALL MATERIALS, BEFORE REMOVING FROM SITE.
2. THE CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND REPAIR ALL EXISTING TO REMAIN AREAS AND SURFACES AS NOTED AND/OR SHOWN. THIS INCLUDES ALL WORK NECESSARY TO READY SURFACES FOR NEW FINISH (N.I.C.) TO FOLLOW IN CONSTRUCTION PHASE. MATCH ALL ADJACENT MATERIALS WHERE PATCHING OCCURS.
3. IT IS NOT THE INTENT TO SHOW EVERY PIECE OR ITEM TO BE REMOVED IN DEMOLITION WORK. MECHANICAL, ELECTRICAL AND OR OTHER WORK RELATED TO A WALL OR AREA SCHEDULED FOR DEMOLITION AND REMOVAL SHALL BE PERFORMED WHETHER SO NOTED OR NOT. PROTECT ALL ITEMS INTENDED FOR SALVAGE AND REUSE OR SCHEDULED TO REMAIN.
NOT IN CONTRACT
ROOF REPLACEMENT
ROOF KEY PLAN
CALLED NORTH
Drawing Number
DescriptionDateNo.Revisions
DescriptionDateIssues
Issue Date:
Key Plan
Project No:
12 11 10 9 8 7 6 5 4 3
Scale:
Seals
Project
Client/ Contractor
2 1
A
12 11 10 9 8 7 6 5 4 3 2 1
Production Leader:Project Manager:
Project Architect: Peer Reviewer:
Notice:This drawing is the property of Tecton Architects | pc The use, re-use or reproduction of this drawing for any purpose whatsoever without an expressed written agreement between Tecton Architects | pc and the user is prohibited. Rights to use the information on this sheet are not transferred until payment has been received for services rendered. Any rights so granted are non-transferable to other parties without the prior expressed written consent of Tecton Architects | pc
© 2018 Tecton Architects | pc
Tecton Architects | pcHartford CT, Westerly RI860 548 0802www.tectonarchitects.com
Drawing Title
B
C
D
E
F
G
H
J
K
A
B
C
D
E
F
G
H
J
K
03/08/19
As indicated
3/7
/20
19 2
:56
:00
PM
C:\U
se
rs\J
ustin
H\D
ocum
en
ts\L
RN
01A
R_
AR
CH
ITE
CT
UR
AL_
CE
NT
RA
L_R
18
_ju
stin
h.r
vt
R1.01
Ocean AvenueLEARNing Academy
582 Ocean AvenueNew London, CT 06320
LEARN RegionalEducational Service
Center
CONSTRUCTION DOCUMENTS
LRN01AR
44 Hatchetts Hill RoadOld Lyme, CT 06371
CRJH
JH
DEMOLITIONROOF PLAN
1/8" = 1'-0"
DEMOLITION ROOF PLANK12
B8B5
K3 EXISTING CONDITION
EXISTING CONDITION
EXISTING CONDITION
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOFEXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
EXISTING ROOF
INSTALL NEW METAL FLASHING ALONG WALLS WHERE FORMER FLASHING WAS REMOVED. SEAL ALL JOINTS
SofTILE WALKWAY PADS
INSTALL NEW METAL FLASHING ALONG WALLS WHERE FORMER FLASHING WAS REMOVED. SEAL ALL JOINTS
INSTALL NEW METAL FLASHING ALONG WALLS WHERE FORMER FLASHING WAS REMOVED. SEAL ALL JOINTS
EXISTING ROOF
NEW RAILING SYSTEM
E5R1.03
K8R1.03
CONDUCTOR & R.W.L.
CONTRACTOR STAGING AREA
K11R1.03
K8R1.03
SIM. O.H.
K4R1.03
K4R1.03
SIMILAR SIMILAR
EXISTING STAIRS
SCUPPER OPENING
GENERAL NOTES - CONSTRUCTION
1. PATCH, REPAIR, AND REFINISH ALL SURFACES EXPOSED BY DEMOLITION WORK OR CUTTING TO ALIGN WITH EXISTING SURFACES SCHEDULED TO REMAIN OR NEW FINISHES SPECIFIED.
2. CAULK ALL JOINT OR CRACKS WHICH OCCUR WHERE DISSIMILAR MATERIALS INTERSECT PERPENDICULAR TO EACH OTHER AND THE INTERSECTION IS EXPOSED TO VIEW UNLESS INDICATED OTHERWISE ON THE DRAWINGS.
3. WHERE NEW ROOF MATERIAL IS REQUIRED TO REPAIR EXISTING ROOFS, PROVIDE MATERIALS EQUAL TO THE EXISTING MATERIALS. MATCH FINISH AND TYPE.
4. PROVIDE STAINLESS STEEL TERMINATION BAR WITH LAP SEALANT WHERE NECESSARY TO FASTEN ROOF MEMBRANE TERMINATIONS.
5. REINSTALL SALVAGED PAVER SYSTEM, INCLUDING PEDESTALS AND PRECASTPAVERS. REPLACE ALL PAVERS DAMAGED DURING DEMOLITION WITH PEDESTAL SET LARGE SCALE CALARC PAVER, BY STEPSTONE, INC., OR EQUAL.”
NOT IN CONTRACT
ROOF REPLACEMENT
ROOF KEY PLAN
CALLED NORTH
Drawing Number
DescriptionDateNo.Revisions
DescriptionDateIssues
Issue Date:
Key Plan
Project No:
12 11 10 9 8 7 6 5 4 3
Scale:
Seals
Project
Client/ Contractor
2 1
A
12 11 10 9 8 7 6 5 4 3 2 1
Production Leader:Project Manager:
Project Architect: Peer Reviewer:
Notice:This drawing is the property of Tecton Architects | pc The use, re-use or reproduction of this drawing for any purpose whatsoever without an expressed written agreement between Tecton Architects | pc and the user is prohibited. Rights to use the information on this sheet are not transferred until payment has been received for services rendered. Any rights so granted are non-transferable to other parties without the prior expressed written consent of Tecton Architects | pc
© 2018 Tecton Architects | pc
Tecton Architects | pcHartford CT, Westerly RI860 548 0802www.tectonarchitects.com
Drawing Title
B
C
D
E
F
G
H
J
K
A
B
C
D
E
F
G
H
J
K
03/08/19
As indicated
3/7
/20
19 2
:56
:00
PM
C:\U
se
rs\J
ustin
H\D
ocum
en
ts\L
RN
01A
R_
AR
CH
ITE
CT
UR
AL_
CE
NT
RA
L_R
18
_ju
stin
h.r
vt
R1.02
Ocean AvenueLEARNing Academy
582 Ocean AvenueNew London, CT 06320
LEARN RegionalEducational Service
Center
CONSTRUCTION DOCUMENTS
LRN01AR
44 Hatchetts Hill RoadOld Lyme, CT 06371
CRJH
JH
ROOF PLAN
1/8" = 1'-0"
ROOF PLANK7
UPPER LEVEL10' - 0"
1
SofTILE WALKWAY PAD SYSTEM
FULLY ADHERED EPDM ROOF MEMBRANE
POLYISO. ROOF INSULATION (MIN. R-15)
EXISTING CONCRETE SLAB 1/2"
PV
C F
AS
CIA
BO
AR
D
11"
+/-
P.T. 2X WOOD BLOCKING - TYPICAL
STEEL SUPPORT POST WELDED TO STEEL PLATE ANCHORED TO EXISTING CONCRETE SLAB - WRAP IN MEMBRANE FLASHING BELOW STEEL PLATE - TYPICAL
2X P.T. WOOD BLOCKING
1/2" PVC TRIM BOARD - RECESS 1/2" FROM BOTTOM OF CONCRETE
3' -
6"
1 1/2" STEEL POSTS GALV. & PAINTED
1 1/2" STEEL TOP RAIL GALV. & PAINTED
1 1/2" STEEL BOTTOM RAIL GALV. & PAINTED
1 1/
2"1
1/2"
1"
8 GA. 2" X 2" STEEL MESH PANEL
"U" CHANNEL
CONT. 3/8" FLAT PLATE - GALV. & PAINTED
EXTEND WATERPROOF MEMBRANE
1 1/
2"3
1/2"
1 1/
2"
CONT. 1/2" X 1 1/2" PVC TRIM
EXTEND ROOF MEMBRANE OVER BLOCKING
CONT. 1/2" X 1 1/2" PVC TRIM
SEALANT
1/2" PVC BOARD
3 1/
2"
V.I.
F.
8 3/
4"+
/-
1/2" PVC FASCIA BOARD
1/2" PVC FASCIA BOARD
SEAL ROOF MEMBRANE PENETRATION
ALIGN
UPPER LEVEL10' - 0"
123
R1.03
K4
WATERPROOF MEMBRANE
SofTILE WALKWAY PAD SYSTEM
R1.03
B3
UPPER LEVEL10' - 0"
1
3" POLYISO. ROOF INSULATION (R-15)
EXISTING CONCRETE SLAB
1/2"
PV
C F
AS
CIA
BO
AR
D
10 7
/16"
+/-
ROOF METAL EDGE TRIM
MEMBRANE FLASHING FULLY ADHERED
STEEL SUPPORT POST BEYOND
EXTEND ROOF MEMBRANE
2X P.T. WOOD BLOCKING - TYPICAL
1/2" PVC TRIM BOARD - RECESS 1/2" FROM BOTTOM OF CONCRETE
R.W.L. AT EACH EXISTING COLUMNPROVIDE ATTACHMENT ACCESSORIES
SCUPPER - LINED WITH MEMBRANE FLASHING
6"
5"
3"
135.
00°
ALUMINUM CONDUCTOR
1 1/2" STEEL POSTS GALV. & PAINTED
1 1/2" STEEL TOP RAIL GALV. & PAINTED
1 1/2" STEEL BOTTOM RAIL GALV. & PAINTED
1 1/
2"1
1/2"
1"
8 GA. 2" X 2" STEEL MESH PANEL
"U" CHANNEL
CONT. 3/8" FLAT PLATE - GALV. & PAINTED
6"
EXTEND WATERPROOF MEMBRANE
EXISTING STEEL PIPE COLUMN
CONT. PVC TRIM
INTERRUPT PVC TRIM AT CONDUCTORS - TYPICAL
ALIGN
SofTILE WALKWAY PAD SYSTEM
FULLY ADHERED EPDM ROOF MEMBRANE
EXISTING STAIR RAILING POST
3" POLYISO. ROOF INSULATION (R-15)
EXISTING CONCRETE SLAB
EXTEND ROOF MEMBRANE TO BEHIND PVC FASCIA BOARD
EXISTING STAIR TREAD
EXISTING STAIR STRINGER
WATERPROOFING MEMBRANE
2X P.T. WOOD BLOCKING - TYPICAL
1/2" PVC TRIM BOARD - RECESS 1/2" FROM BOTTOM OF CONCRETE
PV
C F
AS
CIA
BO
AR
D
11"
+/-
CONT. 1/2" X 1 1/2" PVC TRIM
1/2" PVC FASCIA BOARD
SEALANT
ALIGN
EXTEND WATERPROOFING MEMBRANE
SofTILE WALKWAY PAD SYSTEMSHIM LAST FEW ROWS OF PADS TO MAKE LEVEL WITH STAIR TREAD - SEE FLOOR PLAN
FULLY ADHERED EPDM ROOF MEMBRANE
UPPER LEVEL10' - 0"
3
GROSS
MOTOR/CLASSROOM
110
6"
SofTILE WALKWAY PAD SYSTEM TO FOLLOW EXISTING CONCRETE SLOPE
ROOF INSULATION THICKNESS TO BE DETERMINED IN FIELD BY CONTRACTOR. BASE INSULATION SHALL NOT BE LESS THAN 3" THICK (R-15).
EXISTING CONCRETE DECK
BITHUTHENE FLASHING MEMBRANE
EPDM ROOM MEMBRANE FULLY ADHERE TO EXISTING CONCRETE DECK
EXISTING STOREFRONT SYSTEM
Drawing Number
DescriptionDateNo.Revisions
DescriptionDateIssues
Issue Date:
Key Plan
Project No:
12 11 10 9 8 7 6 5 4 3
Scale:
Seals
Project
Client/ Contractor
2 1
A
12 11 10 9 8 7 6 5 4 3 2 1
Production Leader:Project Manager:
Project Architect: Peer Reviewer:
Notice:This drawing is the property of Tecton Architects | pc The use, re-use or reproduction of this drawing for any purpose whatsoever without an expressed written agreement between Tecton Architects | pc and the user is prohibited. Rights to use the information on this sheet are not transferred until payment has been received for services rendered. Any rights so granted are non-transferable to other parties without the prior expressed written consent of Tecton Architects | pc
© 2018 Tecton Architects | pc
Tecton Architects | pcHartford CT, Westerly RI860 548 0802www.tectonarchitects.com
Drawing Title
B
C
D
E
F
G
H
J
K
A
B
C
D
E
F
G
H
J
K
03/08/19
As indicated
3/7
/20
19 2
:56
:01
PM
C:\U
se
rs\J
ustin
H\D
ocum
en
ts\L
RN
01A
R_
AR
CH
ITE
CT
UR
AL_
CE
NT
RA
L_R
18
_ju
stin
h.r
vt
R1.03
Ocean AvenueLEARNing Academy
582 Ocean AvenueNew London, CT 06320
LEARN RegionalEducational Service
Center
CONSTRUCTION DOCUMENTS
LRN01AR
44 Hatchetts Hill RoadOld Lyme, CT 06371
CRJH
JH
ROOF SECTIONSAND DETAILS
1 1/2" = 1'-0"
SECTION @ GUARDRAIL SUPPORTSK4
1/2" = 1'-0"
PATIO ROOF SECTIONE5
1 1/2" = 1'-0"
SECTION DETAIL @ SCUPPERK8
1 1/2" = 1'-0"
SECTION DETAIL @ EXISTING TOP STAIR TREADK11
1 1/2" = 1'-0"
SECTION DETAIL @ FLASHINGB3