MECHANICAL COMPONENT IMPORTANCE FACTOR (Ip) DESIGNATION
IBC-2009 /ASCE 7-05SEISMIC AND WIND REQUIREMENTS FOR MECHANICAL SYSTEMS
COMPONENT IMPORTANCE FACTOR (Ip)
Ip = 1.0 Ip = 1.5
RESTRAIN IF TOTAL WEIGHT OF DUCTSON TRAPEZE > 10 LBS/FT 44
RESTRAIN IF TOTAL WEIGHT OF DUCTSON TRAPEZE > 10 LBS/FTMULTIPLE DUCTS ON TRAPEZE
5- 6 SQ.FT. AND LARGER
RESTRAIN IF ANY PIPEON TRAPEZE > 1"
RESTRAIN IF TOTAL WEIGHT OF PIPESON TRAPEZE > 10 LBS/FT
4
4
4
4 RESTRAIN ALL
RESTRAIN IF ANY PIPEON TRAPEZE > 3"
RESTRAIN IF TOTAL WEIGHT OF PIPESON TRAPEZE > 10 LBS/FT
RESTRAIN ALL
SUSPENDED PIPE ON TRAPEZE
SUSPENDED NON DUCTILE PIPING(CAST IRON, PLASTIC, CERAMIC)
NOTES:
1. EQUIPMENT 20 LBS. OR LESS IS EXEMPT IF FLEXIBLE CONNECTIONS ARE PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, ANDCONDUIT.
2. RESTRAINTS ARE NOT REQUIRED IF THE COMPONENT WEIGHS 400 LBS. OR LESS, IS MOUNTED AT 4 FT. OR LESS ABOVE A FLOOR, AND HAS FLEXIBLE CONNECTIONSBETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.
3. FLEXIBLE CONNECTIONS REQUIRED FOR PIPE CONNECTIONS ONLY.4. RESTRAINT IS NOT REQUIRED IF THE PIPING / DUCTWORK IS SUPPORTED BY HANGERS AND EACH HANGER IN THE PIPING RUN IS 12 IN. OR LESS IN LENGTH FROM
THE TOP OF THE PIPE TO THE SUPPORTING STRUCTURE. WHERE PIPES ARE SUPPORTED ON A TRAPEZE, THE TRAPEZE SHALL BE SUPPORTED BY HANGERSHAVING A LENGTH OF 12 IN. OR LESS. WHERE ROD HANGERS ARE USED, THEY SHALL BE EQUIPPED WITH SWIVELS, EYE NUTS OR OTHER DEVICES TO PREVENTBENDING IN THE ROD.
5. ALL DUCTWORK , REGARDLESS OF SIZE, DESIGNED TO CARRY TOXIC, HIGHLY TOXIC, OR EXPLOSIVE GASES OR USED FOR SMOKE CONTROL MUST BE RESTRAINED.6. COMPONENT CERTIFICATION MUST BE SUPPLIED BY THE EQUIPMENT MANUFACTURER AT TIME OF SUBMITTAL FOR REVIEW BY ENGINEER OF RECORD.
A. PER SECTION 301.12 OF THE 2009 EDITION OF THE INTERNATIONAL MECHANICAL CODE, MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS(INCLUDING ROOF CURBS & ROOF RAILS) EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURESDETERMINED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE. WHERE SEISMIC RESTRAINT IS REQUIRED, THE MORE DEMANDINGFORCE OF WIND AND SEISMIC MUST BE USED. SEE SEISMIC INFORMATION CONTAINED IN THE STRUCTURAL DRAWINGS FOR SITE SPECIFICINFORMATION ON SEISMIC DESIGN CATEGORY.
B. SEE EQUIPMENT SCHEDULES AND DETAILS FOR SPECIFIC COMPONENT IMPORTANCE FACTOR DESIGNATIONS.C. USE APPLICABLE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH MECHANICAL COMPONENT.D. FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND ATTACHMENTS SHALL BE DESIGNED BY A SOUTH
CAROLINA REGISTERED DESIGN PROFESSIONAL. SUBMITTALS MUST INCLUDE STAMPED AND SIGNED DRAWINGS AND CALCULATIONS.E. WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION OF EQUIPMENT UNDER THIS CONTRACT MUST
BE DESIGNED BY THE SEISMIC ENGINEER. DO NOT POUR ANY HOUSEKEEPING PADS PRIOR TO THE RECEIPT OF THE SEISMIC SUBMITTAL.F. SEISMIC RESTRAINTS FOR PIPING AND DUCTWORK MUST BE SHOWN ON LAYOUT DRAWINGS SHOWING SPECIFIC RESTRAINT LOCATIONS ALONG
WITH ACCOMPANYING DETAILS AND CALCULATIONS.
NOTES
1.51.0
6REQUIRED6NOT REQUIREDCOMPONENT CERTIFICATION(SEE NOTE 6)
6 SQ.FT. AND LARGERDUCTWORK
4>1"4>3"SUSPENDED DUCTILE PIPING
(STEEL, ALUMINUM, COPPER, ETC.)
-RESTRAIN ALL1RESTRAIN ALLNOT INLINE W/
DUCT/PIPE
3RESTRAIN IF >75 LBSPROVIDE FLEX. CONN.3RESTRAIN IF >75 LBS
PROVIDE FLEX. CONN.INLINE W/ DUCTSUSPENDEDEQUIPMENT
-RESTRAIN ALL1RESTRAIN ALLCOMPONENT SUPPORTS
-RESTRAIN ALL1, 2RESTRAIN ALLWALL MOUNTED
-RESTRAIN ALL1, 2RESTRAIN ALLFLOOR MOUNTED
-RESTRAIN ALL1RESTRAIN ALLROOF MOUNTED
SEISMIC RESTRAINTREQUIREMENTNOTESSEISMIC RESTRAINT
REQUIREMENTCOMPONENT IDENTIFICATION
SEISMIC DESIGN CATEGORIES D,E,F
· ALL MECHANICAL APPURTENANCES UNO.
DESIGN CONDITIONS
INDOOR: 75F DB / 55% RH
OUTDOOR: 95F DB / 80F WBSUMMER
OUTDOOR: 25F DBWINTER
INDOOR: 70F DB / 55% RH
GENERAL NOTES:1. THE DRAWINGS SHOW THE GENERAL ARRANGEMENT AND LOCATIONS OF EQUIPMENT, DUCTWORK,PIPING, ETC. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE MECHANICALINSTALLATION W/ THE STRUCTURE AND OTHER TRADES AND SHALL PROVIDE ADDITIONAL OFFSETS ANDFITTINGS AS NECESSARY.
2. THE HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS SHALL COMPLY WITH THE 2009 VERSIONOF THE INTERNATIONAL MECHANICAL CODE, NFPA 90A, AND LOCAL / STATE CODE REQUIREMENTS. INTHE EVENT OF A CONFLICT BETWEEN CODES, STANDARDS, AND REQUIREMENTS LISTED ON THECONTRACT DOCUMENTS, THE MOST STRINGENT SHALL ALWAYS GOVERN.
3. DUCT DIMENSIONS ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS.
4. CHECK AND VERIFY ALL CLEARANCES PRIOR TO FABRICATION OR INSTALLATION OF EQUIPMENT,DUCTWORK, AND PIPING SYSTEMS. WHERE CONDITIONS REQUIRE A CHANGE IN DUCT OR PIPEROUTING, NOTIFY THE ARCHITECT FOR AN ACCEPTABLE ALTERNATIVE METHOD. AVOID ROUTINGDUCTWORK DIRECTLY OVER LIGHT FIXTURES, DIFFUSERS, AND OTHER CEILING MTD. DEVICES. LOCATEALL MECHANICAL EQUIPMENT SO THAT FILTERS AND COMPONENTS REQUIRING ACCESS (SERVICE ANDMAINTENANCE) ARE FULLY ACCESSIBLE. ALL MECHANICAL EQUIPMENT, CONTROL PANELS, ETC. SHALLBE INSTALLED A MAXIMUM OF 18" ABOVE ACCESSIBLE CEILINGS. DEMONSTRATE ACCESSIBILITY ONCOORDINATION DRAWINGS. SUBMIT TO A/E FOR REVIEW.
5. PROVIDE CURVED RADIUS ELBOW AT FIRST SUPPLY & RETURN FITTING FOR ALL HVAC UNITS.PROVIDE TURNING VANES IN ALL 90 DEGREE ELBOWS IN ALL RECTANGULAR SUPPLY / RETURN /EXHAUST DUCT SYSTEMS. ANY OFFSETS REQUIRED IN DUCT SYSTEMS SHALL BE INSTALLED PERSMACNA 1995 2ND EDITION MANUAL . SHARP ANGLED TRANSITIONS OR OFFSETS WILL NOT BEALLOWED. PROVIDE DUCT ACCESS DOORS AT LOCATIONS SPECIFIED.
6. INSTALL ALL DUCT MOUNTED DEVICES (DAMPERS, ACCESS DOORS, ETC.) AND PIPING SPECIALTIES INEASILY ACCESSIBLE LOCATIONS. ADVISE THE ARCHITECT IN ADVANCE OF INSTALLATION IF ACCESSWILL BE HINDERED SO AN ALTERNATE LOCATION CAN BE SELECTED. CONTRACTOR SHALL BERESPONSIBLE FOR RELOCATING DEVICES TO EASILY ACCESSIBLE LOCATIONS AS DEEMED NECESSARYBY A/E OR OWNER AT NO ADDITIONAL COST TO OWNER.
7. ALL DUCT TAKE-OFFS SHALL BE INSTALLED AS SHOWN BY DETAILS ON THE PLANS WITH A MANUALBALANCING DAMPER AT EVERY TAKE-OFF. WHERE DUCT RUN-OUT SIZE IS NOT SHOWN PROVIDE DUCTSAME SIZE AS AIR DEVICE NECK SIZE. PRE-INSULATED FLEXIBLE DUCT MAY BE USED FOR FINALCONNECTION TO SUPPLY DEVICES (MAX. LENGTH 5').
8. ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'SINSTALLATION INSTRUCTIONS WITH PRESCRIBED CLEARANCES FOR SERVICE AND MAINTENANCE. THECONTRACTOR SHALL NOTIFY THE ARCHITECT IF RECOMMENDED CLEARANCES ARE NOT POSSIBLEBEFORE INSTALLING EQUIPMENT.
9. ALL ROTATING MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH VIBRATION ISOLATION. PROVIDEFLEXIBLE NEOPRENE DUCT CONNECTORS BETWEEN DUCTWORK AND ISOLATED MECHANICALEQUIPMENT.
10. THE CONTRACTOR SHALL FIRESTOP ALL PENETRATIONS OF FIRE RATED WALLS/FLOORS/CEILINGSBY DUCTWORK PIPING, ETC., WITH U.L. LISTED FIRE STOPPING MATERIAL TO MAINTAIN FIRE RATING OFTHE BARRIER.
11. SEISMIC PROTECTION OF EQUIPMENT, DUCTWORK, PIPING AND UTILITIES SHALL BE PROVIDED INACCORDANCE WITH SECTION 16 OF THE INTERNATIONAL BUILDING CODE, 2009 EDITION. ALL SEISMICRESTRAINTS AND BRACING SHALL BE SUBSTANTIATED BY MANUFACTURER'S SUBMITTALS PER THESPECIFICATIONS. FOR ADDITIONAL INFORMATION, SEE 'SEISMIC AND WIND REQUIREMENTS FORMECHANICAL SYSTEMS' ON THIS SHEET. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATINGINSTALLATION OF SEISMIC BRACING DEVICES WITH THE OWNER'S SEISMIC SPECIAL INSPECTOR.PROVIDE A MINIMUM OF SEVEN DAYS ADVANCED NOTICE OF INSTALLATION.
12. BALANCE ALL AIR DISTRIBUTION DEVICES, EXHAUST FANS, AND OUTSIDE AIR QUANTITIES ASSCHEDULED OR SHOWN ON THE DRAWINGS. PROVIDE MARKERS AT ALL DAMPER LOCATIONSSHOWING FULL OPEN/CLOSED POSITIONS AND DAMPER SETTINGS FOR REQUIRED AIRFLOW. PROVIDEFINAL TEST AND BALANCE REPORT ALONG W/ SCHEMATIC DRAWINGS SHOWING DEVICE LOCATIONS W/DESIGN AND ACTUAL CFM. DEVICE TAGS ON THE DRAWINGS SHALL CORRESPOND TO THE TAGS ONTHE REPORT. THIS REPORT SHALL BE SUBMITTED TWO WEEKS PRIOR TO SUBSTANTIAL COMPLETION.SEE SPECIFICATIONS FOR FURTHER INFORMATION.
13. ALL CONTROL WIRING, CONDUIT AND CONTROLS ACCESSORIES NECESSARY TO IMPLEMENT THEOUTLINED SEQUENCES OF OPERATION SHALL BE PROVIDED BY THE CONTROLS CONTRACTOR.
14. WIND LOAD PROTECTION OF ROOF MOUNTED EQUIPMENT AND DUCTWORK SHALL BE PROVIDED INACCORDANCE WITH SECTION 16 OF THE INTERNATIONAL BUILDING CODE, 2009 EDITION. ALL WIND LOADRESTRAINTS AND BRACING SHALL BE SUBSTANTIATED BY MANUFACTURER'S SUBMITTALS PER THESPECIFICATIONS.
15. ALL EXPOSED PIPING, DUCTWORK, AIR DEVICES, EQUIPMENT, AND ALL ASSOCIATEDAPPURTENANCES SHALL BE PAINTED. COORDINATE W/ ARCHITECTURAL PLANS/SPECIFICATIONS FOREXPOSED LOCATIONS AND PAINTING REQUIREMENTS.
16. ALL PIPE PENETRATIONS THROUGH STUD WALLS SHALL BE CAULKED WITH USG SHEET ROCKBRAND ACOUSTICAL SEALANT.
17. DUCTWORK AND PIPING PENETRATING ACOUSTICALLY SENSITIVE SPACES SHALL NOT BE RIGIDLYATTACHED TO WALLS.
18. ALL DUCTWORK SHALL BE SUSPENDED/ANCHORED TO STIFF STRUCTURAL COMPONENTS SUCH ASCOLUMNS, BEAMS, AND BAR JOISTS. DUCTWORK SHALL NOT BE SUSPENDED/ANCHORED TO ANYWALLS SURROUNDING THE AUDITORIUM AND STAGE SPACES.
19. ALL AUDITORIUM AND STAGE WALL PENETRATIONS SHALL BE SLEEVED, MAINTAIN 1/2" GAP AROUNDDUCT/PIPING AND PACK VOID WITH LOW DENSITY FIBROUS MATERIAL AND CAULK AIR TIGHT WITH USGSHEET ROCK BRAND ACOUSTICAL SEALANT.
20. WHEN PENETRATING A DOUBLE STUD WALL, EACH LAYER SHALL HAVE AN INDEPENDENT SLEEVE.BOTH LAYERS SHALL NOT BE TIED TOGETHER.
21. SEE ARCHITECTURAL DOCUMENTS FOR ROOF PENETRATION AND FLASHING REQUIREMENTS.
22. WHERE "APPROXIMATELY" IS USED TO DEFINE INSTALLATION LOCATIONS, CONTRACTOR SHALLCOORDINATE WITH ALL OTHER TRADES TO VERIFY THERE ARE NO CONFLICTS PRIOR TO INSTALLATIONAT DIMENSIONS LISTED.
23. ALL MECHANICAL EQUIPMENT CONDENSATE PIPING SHALL BE ROUTED SUCH THAT IT IS NOTOBSTRUCTING WALKWAYS OR CREATING TRIP HAZARDS.
24. WHENEVER THE WORD "PROVIDE" IS USED, IT SHALL MEAN FURNISH AND INSTALL COMPLETE ANDREADY FOR USE.
25. ALL MECHANICAL EQUIPMENT NOISE SHALL BE ATTENUATED TO MEET CCU NOISE CRITERIA DEFINEDBY COASTAL CAROLINA UNIVERSITY DESIGN GUIDELINES SECTION 230548.4.a AND ASHRAE HANDBOOK-HVAC APPLICATIONS 2011 CHAPTER 48. SEE NOISE CRITERIA SCHEDULE.
26. ALL EXPOSED PIPING, DUCTWORK, AIR DEVICES, EQUIPMENT, AND OTHER MECHANICAL SYSTEMAPPURTENANCES SHALL BE SUPPLIED WITH PAINT GRIP FINISH AND PAINTED IN ACCORDANCE WITHARCHITECTURAL DOCUMENTS FINISH REQUIREMENTS.
27. MAINTAIN A MINIMUM SEPARATION OF 3' BETWEEN AIR DEVICES AND SMOKE DETECTORS INACCORDANCE W/ NFPA 72.
XY
XY
XY
T
HVAC LEGEND:
CO
S
UNDERGROUND
ABOVE FINISH FLOOR
ABOVE FINISH GRADE
UNLESS NOTED OTHERWISE
AFG
UNO
EF
OA
UG
W/
AFF
OUTSIDE AIR
WITH
EXHAUST FAN
CARBON DIOXIDE SENSOR
90° SQUARE ELBOW W/
DUCT MOUNTED SMOKE DETECTOR
FD FIRE DAMPER
MANUAL BALANCING DAMPER
MOTORIZED DAMPER
(MOUNTED 4'-6" AFF)DDC ZONE TEMPERATURE SENSOR
SUPPLY AIR DUCT
RETURN/EXHAUST AIR DUCT
CEILING GRILLE
SIDEWALL SUPPLY REGISTER
X= TAG; Y= CFM
X= TAG; Y= CFM
X= TAG; Y= CFM
CEILING DIFFUSER
TURNING VANES
LOW PRESSURE RECTANGULAR DUCTBRANCH DUCT TAKE-OFF
LOW PRESSURE RECTANGULAR DUCTBRANCH DUCT TAKE-OFF
VARIABLE SPEED DRIVEVSD
DIAMETERDIA
SA SUPPLY AIR
RETURN AIRRA
ROUND CONE DIFFUSER
MECHANICAL CONTRACTORMC
PC PLUMBING CONTRACTOR
FD/SD COMBINATION FIRE/SMOKE DAMPERVARIABLE FREQUENCY DRIVEVFD
TYPICALTYP
ELECTRICAL CONTRACTOREC
CHILLED WATER SUPPLY
CHILLED WATER RETURN
EXHAUST AIREA
ISOLATION VALVE
SD SMOKE DAMPER
H DDC HUMIDITY SENSOR(MOUNTED 4'-6" AFF)
NORMALLY OPENNO
CONNECTION-NEW WORK TO EXISTING
POINT OF DISCONNECTION
STRAINER WITH VALVED DRAIN ANDQUICK-COUPLE HOSE CONNECTOR
3-WAY CONTROL VALVEM
2-WAY CONTROL VALVEM
EARTHQUAKE VALVE
BALL VALVE
PRESSURE REDUCING VALVE
RELIEF VALVE
M MOTORIZED BUTTERFLY VALVE
END SUNCTION PUMP
PUMP CONNECTOR/FLEX CONNECTOR
PLUG VALVE
CONCENTRIC REDUCER/INCREASER
PIPE
CHF
DRN DRAIN
SS
HD
FD
PSD
CHEMICAL FEED
FLOOR DRAIN
HUB DRAIN
STAINLESS STEEL
AN ACID NEUTRALIZER
CONTROL VALVE
AIR VENT
AUTO FLOW VALVE
AUTO FLOW VALVEAFV
SUCTION DIFFUSER
ABBREVIATIONS:
HEATING HOT WATER SUPPLY
HEATING HOT WATER RETURN
ADJUSTABLEADJ
OED OPEN ENDED DUCT
WMS WIRE MESH SCREEN
DUCT TRANSITION. ARROW INDICATESDIRECTION OF UPWARD SLOPE
CHWS
CHWR
HWS
HWR
CONDENSATE DRAINCD
BOD BOTTOM OF DUCT, BASIS OF DESIGN
DUCT SECTION. POSITIVE PRESSURE.
DUCT SECTION. NEGATIVE PRESSURE (RA).
DUCT SECTION. NEGATIVE PRESSURE (EA).
,
MINIMUMMIN
BOILER EMERGENCY SHUTDOWN MUSHROOM SWITCHES
DIFFERENTIAL PRESSURE SWITCH
AUTOMATIC AIR VENTAAV
DPS
FLOW SWITCHFS
PRESSURE INDICATOR/PRESSURE GAUGE W/RANGEPI
PRESSURE REDUCING VALVEPRV
TEMPERATURE ELEMENTTE
VARIABLE FREQUENCY DRIVEVFD---
TEMPERATURE TRANSMITTERTT
TEMPERATURE INDICATOR/TEMPERATURE GAUGE W/THERMOWELLTI
RELIEF VALVERV
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:46:
16 P
M
As Indicated
M0.00
MECHANICALNOTES &LEGEND
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
DN
UP
DNDN
UP
T
T
TT
T
T
T
T
T
T
T
T
T
T
CO
CO CO
T
T
1K
1J
1H.5
1H
1G.5
1G
1F.5
1F
1E.5
1E
1D
1C
1B.4
1B
1A.4
1A
0.5 1 1.5 1.8 2.3 3 3.7 4 4.5 4.7 5 5.4 6 7 8
8.9 9
TICKET BOOTHA-106A
LOBBYA-106
C-STOREA-105
INTL. OFFICE 4A-109A
INTL. OFFICE 3A-109B
INTL. OFFICE 2A-109C
INTL. OFFICE 1A-109D
28"x
20"
30"x
26"
12"x
10"
WOMEN'S CENTERA-108
OFFICEA-108A
INTERNATIONALCENTER
A-109
ELECTRICALA-115
WOMEN'SA-113
IT ROOMA-112
M.C. CENTEROFFICE 2
A-102B
M.C. CENTEROFFICE 1A-102C
MULTI-CULTURALCENTER
A-102
CINO CARD & TECHSUPPORT
A-103
STUDY/ CONF.ROOMA104
VEST.A-100C
MC CENTEROFFICE 3
A-102A
MEN'SA-111
8"ø
16"x10"
1
OFCA-103A
VAV-8
VAV-10
VAV-6
VAV-7
VAV-
1
VAV-9
VAV-11
VAV-13
VAV-5
M1.312
M1.311
JANITORA-114
20"x14"
10"x8"
40"x
18"
8"x6"
10"x8"
16"x16"
CORRIDORC-101
MECHANICALA-116
RECREATIONROOMA-101
CORRIDORC-103
CORR.C-105 AUDITORIUM
A-110
STOR.A-110B
CHAIR STOR.A-110A
CORR.C-106
CORR.C-104
ELEV MACHINEROOMA-109E
STAIRST-102
CORRIDORC-102
STAIRST-101
STORAGEA-101A22"x20" 18"x16"
12"x
8"
12"x
8"12
"x8"
12"x
8"
12"x
8"12
"x8"
12"x8" 14"x10" 12"x8"
360 CFMA
360 CFMA
360 CFMA
360 CFMA
360 CFMA
360 CFMA
360 CFMA
360 CFMA
360 CFMA
VAV-
2
250 CFMA
100 CFMA
100 CFMA
8"x8
"12
"x8"
250 CFMB
8"x8
"10
"x8"265 CFM
A
265 CFMA
530 CFMB
12"x
10"
135 CFMA
135 CFMA
100 CFMA
210 CFMA
210 CFMA
420 CFMB
170 CFMA
170 CFMA
340 CFMB
VAV-3
16"x12"10"x10"
24"x14" 38"x18"
100 CFMA
100 CFMA
100 CFMB
100 CFMB
100 CFMA
100 CFMB
100 CFMB
100 CFMA
100 CFMA
100 CFMB
220 CFMA
50 CFMB
38"x16"
50 CFMA
100 CFMB
16"x8"
6"ø10"x8"
14"x
10"
16"x10"
12"x
8"
6"ø
8"ø 6"ø
10"x
8"
6"ø
220 CFMA
220 CFMA
14"x
10"
8"ø
8"ø
8"ø
10"x
8"8"
ø
12"x8"
20"x
16"
20"x
12"
16"x
12"
6"ø12"x8"
6"ø
505 CFMA
505 CFMA
1750 CFMB
1750 CFMB
30"x
26"
1750 CFMB
20"x14"
28"x
20"
350 CFMA
625 CFMB
14"x10"
420 CFMEG1
8"ø
210 CFMEG1
42"x
20"
42"x
20"
40"x
18"
6"ø
6"ø
220 CFMB
485 CFMA
485 CFMA
170 CFMEG
240 CFMB
14"x10"
645 CFMB
125 CFMA
85 CFMA
125 CFMA
38"x14"
12"x8"
38"x
16"
6"ø
6"ø
100 CFMB
100 CFMB
14"x
14"
FD
2
3
370 CFMSR1
370 CFMSG1
12"x8"
500 CFMSR1
600 CFMSG1
AV STORA-112A
VAV-4
VAV-
33
VAV-1285 CFM
B
3
950 CFMSR1
FCU-1
4
5
UH-1
24"x14"
2
950 CFMSG-1
STAGEA-110C
10"x10"
10"x10"
12"x
8"
12"x10"
24"x12"
DN34"x18"
FD
UP
170 CFMB
8"x6"
12"x12"970 CFM
B
40"x18"
12"x8"
400 CFMB
12"Wx8"HRA UP
200 CFMA
8"Ø SA UP
300 CFMTG3
TYP 4. CENTEREDBETWEEN RAMP ANDHANDRAIL, SEEARCHITECTURAL
16"x10"16"x10"
7
16"x10"
DN
20"x8"
DN
UP
UP
(VAV-28)
(VAV-29)
14"x8"
10"x8"
200 CFMA
10"x8"
8"x6"8"x6"
34"x10"12"x6"
8"x8"
10"x8"
8"ø 8"ø
12"x
10"
12"x16"
300 CFMTG3
505 CFMA
12"x10"
12"x10"
12"x10"
VAV-
23
415 CFMSR1
16"x
12"
16"x
14"
32"x
30"
16"x
14"
300 CFMSR1
6
10"x8"
10"x
8"
FD
FD
FD FD
10"x4"14"x8"
6"ø 8"x6" 10"x8"
8"x8"
12"x10"
8"x6
"
8"x6
"
UP
100 CFMA
110 CFMA
6"ø
DN
300 CFMSG1
100 CFMSR1
100 CFMSR1
KEY NOTES:
14"x10" EA UP. SEE 2ND FLOOR PLAN FOR CONTINUATION.
TRANSITION TO FULL AHU RA AND SA CONNECTION SIZES INVERTICAL UP TO AHU-2.
TERMINAL UNIT TO SERVE FUTURE C-STORE SPACE. PROVIDEOED W/WMS. PROVIDE VOLUME DAMPER FOR RETURN AIR.
THE UPFIT OF C-STORE AREA WILL BE COMPLETED UNDER ASEPARATE CONTRACT.
DIRECT AIR FLOW WITH SUPPLY DIFFUSER BLADES TO PLANWEST SIDE OF ROOM.
10"x8" SA & RA UP. SEE 2ND FLOOR PLAN FOR CONTINUATION.
TRANSFER GRILLE. TYPICAL OF 2.
1
2
3
4
5
6
7
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:46:
27 P
M
As indicated
M1.11
EXPANSION -FIRST FLOORHVAC PLAN
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: 1/8" = 1'-0"M1.111 EXPANSION - FIRST FLOOR HVAC PLAN
DN
DN
D
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
CO
CO
CO
CO
CO
T
T
KEY NOTES:
14"x10" EA TO GRAVITY ROOF VENTILATOR ABOVE.
14"Ø EA TO GRAVITY ROOF VENTILATOR ABOVE.
NON DUCTED PORTIONS OF LOUVERS SHALL BE BLANKED OFF WITH SHEET METAL. SEAL AIR / WEATHERTIGHT AND INSULATE.
GRAVITY ROOF TOP VENTILATOR ABOVE. BOD: GREENHECK FGR OR EQUAL. BALANCE TO 5000 CFM (ADJ).
NON DUCTED RETURN GRILLE, OPEN TO PLENUM.
PROVIDE MINIMUM 24"x24" WALL OPENING ABOVE CEILING ALONG GRIDLINE 1B.4 AT TRANSITION BETWEENACT CEILING AND GWB CEILING FOR BAROMETRIC RELIEF.
SEE FIRST FLOOR PLAN FOR LOCATIONS OF THERMOSTATS.
THERMOSTAT FOR VAV-17.
THERMOSTAT FOR VAV-22.
THERMOSTAT FOR VAV-23.
PROVIDE MINIMUM 10' SEPARATION BETWEEN EA OUTLET AND OA INTAKE.
10"x8" SA & RA DN. SEE 1ST FLOOR PLAN FOR CONTINUATION.
AIR DEVICES SHALL BE MOUNTED TO UNDERSIDE OF DUCT.
SA AND RA DUCT SHALL BE INSTALLED TIGHT TO BOTTOM OF STRUCTURE.
SIDEWALL REGISTER SERVING MER AT 11'-2" AFF, BELOW EF.
ROUTE DUCT BELOW BEAM AND TIGHT TO UNDERSIDE OF STRUCTURE ON EITHER SIDE OF BEAM.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1K
1J
1H.5
1H
1G.5
1G
1F.5
1F
1E.5
1E
1D
1C
1B.4
1B
1A.4
1A
0.5 1 1.5 1.8 2.3 3 3.7 4 4.5 4.7 5 5.4 6 7 8 8.9 9
CC OFFICEA-203E
CC OFFICEA-203G
CONFERENCEA-203H
CC OFFICEA-203B
CAREER CENTERA-203
LARGE MEETINGA-201
STUDENTORGANIZATIONS
A-202
CORRIDORC-101
FSL STUDY/ MTGROOMA-214
FSL STUDY/ MTGROOMA-213
FSL STUDY/ MTGROOMA-215
WOMENA-209
MENA-212
VEST.A-212A
MECH./ SUPPORTA205
PROJECTIONROOMA-204
STORAGEA-216
14"ø
6"ø
280 CFMEG1
75 CFMEG1
210 CFMEG1
VAV-19
VAV-16
VAV-15
VAV-14
VAV-24
VAV-21
VAV-18
VAV-29
VAV-26
VAV-28
VAV-32
VAV-30
VAV-31
VAV-22
STAGEA-110C
AUDITORIUMA-110
IT ROOMA-211TOILET
A-210VESTA-209A
CORRIDORC-205
CC OFFICEA-203F
ROOF ACCESSA-208D
JANA-208C
ELEC.A-208B
CORRIDORC-204
CC OFFICEA-203D
CC OFFICEA-203C
CC OFFICEA-203A
CORRIDORC-202
STAIRST-201
CORRIDORC201
VEST.A-100C
STAIRST-202
AV STORA-208A
MECHANICALA-217
VAV-25
VAV-17
VAV-27
VAV-20
STORAGEA-206
CORRIDORC-210
CORRIDORC-207
CORRIDORC-206
50"x18"
12"x10"
12"x
8"12
"x10
"
22"x12"
10"x8"
30"x14"
6"ø
6"ø
8"ø
8"ø
12"x10"
10"x8" 10"x8"
10"x8" 10"x8"
10"x8" 10"x8"
10"x8" 10"x8"
10"x8" 10"x8"
14"x
10"
12"x8" 12"x8"
12"x10"
8"x8
"
8"x8"
12"x10"
10"x8" 10"x8"
32"x
22"
32"x
18"
6"ø
50"x24" 50"x22"
24"x18"
10"x
8"10
"x8"
20"x16" 10"x
8"10
"x8"
20"x14"16"x12"
18"x14"
10"x
8"
14"x10"
10"x
8"
50"x16"
14"x12"24"x12"44"x12"
16"x14"
10"x
8"10"x8"
18"x
14"
18"x14"
50"x16"
46"x14"
14"x
8"
14"x
8"
6"ø
10"x8"
8"ø 6"ø
16"x
10"
22"x12"
8"x8
"
14"x12"
8"x8
"
12"x10"
8"x8"
6"ø6"ø 6"ø
6"ø
10"x10"
14"x10"14"x10"
8"x8"
6"ø
10"x8"
8"x6
"
14"x10"
6"ø
22"x16"
18"x
14"
34"x14"
30"x
14"
10"ø
14"x10"16"x12"
10"x
8"
10"x6"
24"x16"
30"x
20"
30"x
16"
12"x10"
32"x12"
16"x12"
6"ø
10"x
8"
12"x10"
10"x
8"
6"ø
14"x8"
22"x
14"
18"x
12"
14"x
10"
14"x8"10"x8"
10"x8"
26"x14" 20"x12"
16"x
12"
40"x14"
34"x12"
12"x10"
16"x
12"
36"x
14"
10"x8"
8"ø10"ø
14"x10"
12"x
10"
24"x
14"
26"x20"
32"x
14"
32"x14"
6"ø
8"ø
12"x
10"
10"ø
6"ø
10"x
8"10
"x8"
14"x10"
10"x
8"10
"x8"
8"ø
350 CFMA
350 CFMA
350 CFMA
350 CFMA
360 CFMA
360 CFMA
360 CFMA
360 CFMA
1440 CFMB
360 CFMA
360 CFMA
360 CFMA
360 CFMA
400 CFMB
250 CFMA
150 CFMB
100 CFMA
260 CFMA
260 CFMA
100 CFMA
210 CFMA
1080 CFMB
100 CFMB
100 CFMB
100 CFMB
100 CFMB
100 CFMB
420 CFMB
730 CFMB
600 CFMB
600 CFMB
50 CFMB
50 CFMA
165 CFMA
305 CFMA
305 CFMA
1400 CFMB
110 CFMB
365 CFMA
365 CFMA
300 CFMA
300 CFMA
300 CFMA
300 CFMA
210 CFMA
1440 CFMB
355 CFMA
355 CFMA
355 CFMA
355 CFMA
355 CFMA
355 CFMA
355 CFMA
355 CFMA
250 CFMA
260 CFMA
260 CFMA
260 CFMA
260 CFMA
140 CFMB
100 CFMA
835 CFMA
835 CFMA
900 CFMA
835 CFMA
100 CFMB
100 CFMB
180 CFMA
180 CFMA
305 CFMA
60 CFMEG1
100 CFMA
50 CFMA
1320 CFMB
1320 CFMB
350 CFMSG1
350 CFMSR1
285 CFMSR1
285 CFMSG1
360 CFMB
360 CFMB
350 CFMSR1
725 CFMSR1
725 CFMSG1
210 CFMC
500 CFMSR2
500 CFMSR2
1000 CFMSG2
900 CFMA
EF-114"x10" EA DN
14"ø
UP
UP
DN
325 CFMB
1260 CFMB
UP UP
AHU-2
AHU-3
3
24"x12" OA DN TOMIXING BOX
50"W x 24"H x 16"DPLENUM.
11
11
AHU-4
3
24"W x24"H x18"D EAPLENUM
24"x24"OAINTAKE
910
7
5
6
4
5
2
8
1
6
18"x12"
100 CFMA
100 CFMA
100 CFMA
AHU-5
26"x18"
32"x22"22"x12"UP DN
10"x8"
12
10"x8"10"x8"
SA
350 CFMSG-1
210 CFMC280 CFM
C
16"x12"
8"Ø SA DN
13
13
13
TYP 3
30"x
16"
26"x14"
32"x22"
34"x14"
12"x8" RADN
900 CFMA
900 CFMA
6"ø
50 CFMA
10"x8"
6"ø
EF-2
280 CFMC
14
15
SA-5RA-5
26"x
14"
18"x
10"
18"x
10"
18"x
10"
DN
2520 CFMB
18"x24"
58"x8"RETURNDUCT OPENTO PLENUM
SOUND TRAP,SEE DETAIL
1610"x8"
DN UP
44"x10"
16
1260 CFMB
28"x14"
14"x14"
14"x14"DN UP
8"x6"100 CFMSG1
100 CFMSR1 8"x6"
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:46:
35 P
M
As indicated
M1.12
EXPANSION -SECONDFLOOR HVACPLAN
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: 1/8" = 1'-0"M1.121 EXPANSION - SECOND FLOOR HVAC PLAN
DN
UP
DNDN
UP
T
CO
T
T
1K
1J
1H.5
1H
1G.5
1G
1F.5
1F
1E.5
1E
1D
1C
1B.4
1B
1A.4
1A
0.5 1 1.5 1.8 2.3 3 3.7 4 4.5 4.7 5 5.4 6 7 8
8.9 9
C-STOREA-105
INTL. OFFICE 4A-109A
INTL. OFFICE 3A-109B
INTL. OFFICE 2A-109C
INTL. OFFICE 1A-109D
WOMEN'S CENTERA-108
OFFICEA-108A
INTERNATIONALCENTER
A-109
STAGEA-110C
WOMEN'SA-113
M.C. CENTEROFFICE 2
A-102B
M.C. CENTEROFFICE 1
A-102C
MULTI-CULTURALCENTER
A-102
CINO CARD & TECHSUPPORT
A-103
STUDY/ CONF.ROOMA104
MC CENTEROFFICE 3
A-102A
MEN'SA-111
M1.313
3/4" HWR3/4" HWS
1 1/
2" H
WR
1 1/
2" H
WS
3" HWR
3" HWS
1" HWS
1" HWR
1 1/2" HWR 1" HWR1" HWS1 1/2" HWS1" HWS
2 1/2" HWR
2 1/2" HWS
4" CHWR
VAV-9
VAV-10
VAV-11
VAV-13
VAV-8
VAV-6
VAV-7
VAV-5
VAV-1
MECHANICALA-116
ELECTRICALA-115
JANITORA-114
IT ROOMA-112
STAIRST-102
ELEV MACHINEROOMA-109E
RECREATIONROOMA-101
STAIRST-101
STORAGEA-101A
CORRIDORC-101
VEST.A-100C
CORRIDORC-102
OFCA-103A
CORRIDORC-103
LOBBYA-106
TICKET BOOTHA-106A
CORR.C-105
AUDITORIUMA-110
CHAIR STOR.A-110A
STOR.A-110B
CORRIDORC-101
VAV-3
VAV-2
3/4" HWR3/4" HWS
1
3/4" HWR3/4" HWS
VAV-4
VAV-12
VAV-33
FCU-1
3
4
53/4" CD
4" CHWS2
1" HWR
3/4" HWS
3/4" HWR
3/4" HWS3/4" HWR
3/4" HWS
3/4"
HW
R3/
4" H
WS
3/4"
HW
R3/
4" H
WS
1" H
WR
1" H
WS
3/4"
HW
R3/
4" H
WS
3/4"
HW
S3/
4" H
WR
1 1/2" HWR
1 1/2" HWS
3/4" HWS3/4" HWR
3/4" HWR
KEY NOTES:
INSTALL ALL HYDRONIC PIPING UP TO SECOND FLOOR TIGHT TO WALL AND STRUCTURE.PIPING INSULATION JACKETING SHALL BE PAINTED. COORDINATE WITH ARCHITECT FORFINISH AND COLOR.
CONNECT TO EXISTING UNDERGROUND CHILLED WATER LOOP. SEE CIVIL FORCONTINUATION.
THE UPFIT OF C-STORE AREA WILL BE COMPLETED UNDER A SEPARATE CONTRACT.
1-1/2" CHWS/CHWR & 1-1/2" HWS/HWR DOWN FROM SECOND FLOOR CONCEALED IN GYPBOARD.
ROUTE CONDENSATE DRAIN ABOVE CEILING TO HUB DRAIN. MAINTAIN MINIMUM SLOPE OF1/8" PER FOOT. SEE PLUMBING FOR HUB DRAIN LOCATION.
1
2
3
4
5
GENERAL NOTES:
1. ALL PIPING WITHIN BUILDING SHALL BE ROUTED AS HIGH AS POSSIBLE AND TIGHT TO STRUCTURE UNLESSNOTED OTHERWISE.
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:46:
40 P
M
As indicated
M1.13
EXPANSION -FIRST FLOORHVAC PIPINGPLAN
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: 1/8" = 1'-0"M1.131 EXPANSION - FIRST FLOOR HVAC PIPING PLAN
DN
DN
CO
1K
1J
1H.5
1H
1G.5
1G
1F.5
1F
1E.5
1E
1D
1C
1B.4
1B
1A.4
1A
0.5 1 1.5 1.8 2.3 3 3.7 4 4.5 4.7 5 5.4 6 7 8
8.9 9
CC OFFICEA-203E
CC OFFICEA-203G
CONFERENCEA-203H
CC OFFICEA-203B
CAREER CENTERA-203
LARGE MEETINGA-201
STUDENTORGANIZATIONS
A-202
CORRIDORC-101
FSL STUDY/ MTGROOMA-214
FSL STUDY/ MTGROOMA-213
FSL STUDY/ MTGROOMA-215
WOMENA-209
MENA-212
VEST.A-212A
MECH./ SUPPORTA205
PROJECTIONROOMA-204
STORAGEA-216
VAV-19
VAV-16
VAV-15
VAV-14
VAV-24
VAV-21
VAV-18
VAV-29
VAV-26
VAV-28
VAV-32
VAV-30
VAV-31
VAV-22
1 1/2" HWS1 1/2" HWR
3" CHWS3" CHWR
2" HWS2" HWR
2" H
WR
2" H
WS
2" HWR2" HWS
1 1/2" HWS
1 1/2" HWR
1 1/
2" H
WS
1 1/
2" H
WR
STAGEA-110C
AUDITORIUMA-110
IT ROOMA-211
TOILETA-210
VESTA-209A
CORRIDORC-205
CC OFFICEA-203F
ROOF ACCESSA-208D
JANA-208C
ELEC.A-208B
CORRIDORC-204
CC OFFICEA-203D
CC OFFICEA-203C
CC OFFICEA-203A
CORRIDORC-202
STAIRST-201
CORRIDORC201
VEST.A-100C
STAIRST-202
AV STORA-208A
MECHANICALA-217
VAV-25
VAV-17
VAV-27
1
VAV-20
STORAGEA-206
1 1/
2" C
HW
R1
1/2"
CH
WS
1 1/
2" H
WS
1 1/
2" H
WR
2
1" HWS1" HWR
1" H
WS
1" H
WR
4" C
HW
S4"
CH
WR
CORRIDORC-210
CORRIDORC-207
CORRIDORC-206
3/4" HWS3/4" HWR
3/4" HWR3/4" HWS
3/4" HWR3/4" HWS
3/4" HWR3/4" HWS
3/4" HWR3/4" HWS 3/4" HWS
3/4" HWR
3/4" HWS
3/4" HWR3/4" HWS
3/4" HWR3/4" HWS
1" HWR1" HWS
3/4" HWS
3/4" HWR3/4" HWS
1" HWR1" HWS
3/4" HWR
3/4" HWS
3/4" HWR
AHU-4
AHU-5
1" H
WS
1" H
WR
2" CHWR
2" CHWS
3" C
HW
R3"
CH
WS
AHU-3
AHU-2
3/4"
HW
S3/
4" H
WR
3/4" HWS3/4" HWR
3/4" HWR
3/4" HWS
2" H
WR
2" H
WS
3/4" HWR
3/4"
HW
R
3/4" HWS
4" C
HW
R4"
CH
WS
4" CHWR4" CHWS
2 1/2" CHWS2 1/2" CHWR3" CHWS
3" CHWR
32-1/2" HWS/HWRDN TO FIRST FLOOR
KEY NOTES:
COORDINATE PIPE ROUTING AND INSTALLATION WITH STAGE CURTAINS, PROJECTION SCREEN,AND ALL ASSOCIATED APPURTENANCES. SHOW ALL ON COORDINATION DRAWINGS FORSUMISSION TO A/E PRIOR TO PERFORMING WORK. PIPING INSULATION JACKETING SHALL BEPAINTED. COORDINATE WITH ARCHITECT FOR FINISH AND COLOR.
HEATING HOT WATER AND CHILLED WATER PIPING DOWN TO FAN COIL UNIT ON FIRST FLOOR.
CHWS/CHWR DN TO FIRST FLOOR LEVEL, SEE FIRST FLOOR HVAC PIPING PLAN FORCONTINUATION. INSTALL TIGHT TO WALL.
1
2
3
GENERAL NOTES:
1. ALL PIPING WITHIN BUILDING SHALL BE ROUTED AS HIGH AS POSSIBLE AND TIGHT TO STRUCTUREUNLESS NOTED OTHERWISE.
HWS/R PIPING TO INDIVIDUAL VAV TERMINAL UNITS SHALL BE 3/4" UNO.2.
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:46:
48 P
M
As indicated
M1.14
EXPANSION -SECONDFLOOR HVACPIPING PLAN
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: 1/8" = 1'-0"M1.141 EXPANSION - SECOND FLOOR HVAC PIPING PLAN
1K
1J
1H.5
1H
1G.5
1G
1F.5
1F
1E.5
1E
1D
1C
1B.4
1B
1A.4
1 1.5 1.8 2.3 3 3.7 4 4.5 4.7 5 5.4 6 7 8 8.9 9
2
1
GRV-3
1
GRV-1
1GRV-2
KEY NOTES:
INSTALL ALL MECHANICAL EQUIPMENT SUCH THAT A MINIMUM OF 10 FEET EXISTS BETWEENEDGE OF ROOF AND CLOSEST EDGE OF MECHANICAL EQUIPMENT.
ROOF ACCESS HATCH.
1
2
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:46:
49 P
M
As indicated
M1.15
EXPANSION -MECHANICALROOF PLAN
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: 1/8" = 1'-0"M1.151 EXPANSION - ROOF PLAN
UPUP
UPUP
UPUP
DNDN
DN
DN
UPUP
T
T
COT
T
T
1E
1D
1C
1B.4
1B
1A
8.9 9 10.8
11
13.5 15.5
Y4
Y3 Y2
Y1
G
18.4 19 2012 13 14 15 16 17 18
VEST.A-100A
LOBBYA-100
VEST.A-100B
690 CFMSR3
-TG2
1
18"x8"
12x10 SA UP1
-TG218"x8"
12x10 SA UP
515 CFMSR3
22
KEY NOTES:
MOUNT TRANSFER GRILLE 12" AFF. TYPICAL OF 4.
MOUNT SUPPLY REGISTER AT 11'-0" AFF AND CENTER HORIZONTALLY WITHIN THE SPACE.TYPICAL OF BOTH VESTIBULES.
1
2
GENERAL NOTES:
1. SEE ARCHITECTURAL FOR AIR DEVICE PAINTING REQUIREMENTS.
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:46:
53 P
M
As indicated
M1.21
ADDITION -FIRST FLOORHVAC PLAN
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: 1/8" = 1'-0"M1.211 ADDITION - FIRST FLOOR HVAC PLAN
DN
1E
1B.4
1B
1A
10.8
11
13.5 X7 15.5
Y4
Y3 Y2
Y1
18.4 19 2012
13
14 15 16 17 18
LOBBYA-100
590 CFMA
590 CFMA
380 CFMA
380 CFMA
380 CFMA
380 CFMA
410 CFMA
410 CFMA
650 CFMA
650 CFMA
410 CFMA
410 CFMA
58"x18"
40"x12"20"x12"18"x12"
12"x
10"
12"x
12"
12"x
12"
10"x
10"
12"x
12"
50"x12"
12"x10"12"x10"
10"ø 10"ø
33
12"x
12"
10"x
10"
14"x12"
14"x
12"
4
55
6
1580 CFMB
1580 CFMB
1580 CFMB 1580 CFM
B
1580 CFMB
1580 CFMB
5
555
64"x16"
36"x24"
36"x24"SA UP
60"x24"
24"x18"20"x12"UP
UP20"x12"
8
10"ø
14"x18"44"x18"
64"x
18"
UPUP
60"x12"
10"ø
10"ø10"ø10"ø10"ø
UP
UP
UP
UP
UP UPUP
UPUP
UP UP
UP
UP
UP
UP
UP
UP
UP
10"ø
10"ø
2M1.22
KEY NOTES:
50"x18" RA UP TO AHU-6 IN ATTIC.
26"x26" SA UP TO AHU-6 IN ATTIC.
12"x10" SA TO VESTIBULE BELOW.
DIFFUSER TYPE D, 360 CFM. TYPICAL OF 9. DIFFUSERS SHALL BE EQUALLY SPACED BETWEENCOLUMNS. SEE ARCHITECTURAL FOR DEVICE LAYOUT. METAL AND FLEXIBLE DUCTWORKWITHIN THE UNINSULATED CAVITY SHALL BE INSULATED WITH MINIMUM R-8 INSULATION INACCORDANCE WITH THE 2009 IECC.
NON DUCTED RETURN GRILLE, OPEN TO PLENUM.
60"x24" OED W/ WMS ABOVE CEILING.
50"x28" RA.
60"x24" RA TRANSITION TO 24"x60" IN VERTICAL.
1
2
3
4
5
6
7
8
GENERAL NOTES:
1. COORDINATE LOCATION OF DUCTWORK WITH EXISTING TRADES (CONDUIT, CABLING, PIPING, ETC)ABOVE THE 2ND FLOOR CEILING. WHERE CONFLICTS ARISE, REROUTE/EXTEND EXISTING CONDUITTIGHT TO DECK. PROVIDE ANY CHANGES TO EXISTING INFRASTRUCTURE IN COORDINATIONAFFIDAVIT. SEE DIVISION 26 SPECIFICATIONS.
360 CFMD
10"øSA
UP THROUGH BUILDINGTHERMAL ENVELOPE.
60"x12" SA
NOTE: COORDINATE DUCTWORK CONFIGURATION WITH FRAMING.
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:46:
58 P
M
As indicated
M1.22
ADDITION -SECONDFLOOR HVACPLAN
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: 1/8" = 1'-0"M1.221 ADDITION - SECOND FLOOR HVAC PLAN
SCALE: 1/4" = 1'-0"M1.222 LOBBY A-100 DUCTWORK (TYP.)
14"x8" DN
AD AD
SD
36"x36"
72"x36"
72"x36"
M
36"x36" 36"x36"
(E)RAF-1
1B.4
1B
1A
13.5 15.5
Y4
Y3 Y2
Y1
13 14 15 16
ELECTRICALEQUIPMENT
ELEC
TRIC
ALEQ
UIP
MEN
T
(E)AHU-1
60"x34"
4" C
HW
R
1 1/2" HWR60"x34"
2
3
1 1/2" HWS
1
36"x36"
5
120"W x 96"H x 24"DPLENUM
DN
26"x22" DNTO FLOOR
26"x22"(9'-0" BOD)
42"x36"
42"x36"
FS
RELOCATEDFIRE RISER.SEE FP PLAN.
AHU-6
40"x22"
4" C
HW
S
3" CHWS3" CHWR
3" CHWS3" CHWR
1 1/2" HWS1 1/2" HWR
60"x34" OA DNTO (E) AHU-1
36"x24" SADN TO 2NDFLR.
4
1 1/
2" H
WS
1 1/
2" H
WR
26"x22"
20"x16"
1" CD
1" CD
3M1.23
4M1.23
2M1.23
KEY NOTES:
PROVIDE NEW MOTORIZED DAMPER. EXTEND CONTROLS WIRING FROM ORIGINAL DAMPERLOCATION. RECOMMISSION TO INCLUDE ALL EXISTING CONTROL POINTS AND SEQUENCESOF OPERATION.
NON DUCTED PORTIONS OF LOUVER SHALL BE BLANKED OFF WITH SHEET METAL. SEAL AIR/ WEATHER TIGHT AND INSULATE.
AIR HANDLING UNIT MOUNTED VFD.
20"x16" OA DN TO AHU-6.
PROVIDE DUCT ACCESS DOOR FOR (E) FIRE DAMPER.
MAINTAIN MINIMUM 2-8"H x 2'-5"W SPACING FOR TRAVEL AROUND AHU.
1
2
3
4
5
6
GENERAL NOTES:
1.
2.
3.
4.
5.
MINIMUM OVERHEAD CLEARANCE HEIGHT BENEATH ALL PIPING AND DUCTWORK SHALL NOTBE LESS THAN 6'-8" AFF.
EXTEND ALL POWER AND CONTROL WIRING TO NEW LOCATION OF (E) AHU-1.RECOMMISSION (E) AHU-1 TO INCLUDE ALL EXISTING CONTROL POINTS AND SEQUENCES OFOPERATION.
SCOPE OF WORK INCLUDES RELOCATING (E) AHU-1 TO THE LOCATION SHOWN. PROVIDENEW CONCRETE CURBS FOR (E) AHU-1 AND AHU-6. PROVIDE CONDENSATE DRAIN PIPING TONEW FLOOR DRAIN WITH FUNNEL, CONNECT TO EXISTING WASTE PIPING ABOVE 2ND FLOORCEILING. PIPING AND DUCTWORK SHALL BE CONNECTED TO EXISTING AS SHOWN. UPONCOMPLETION OF (E) AHU-1 INSTALLATION, PERFORM TEST AND BALANCE TO RESTORESYSTEM TO PREVIOUS OPERATION. SEE AHU SCHEDULE FOR RECORD DATA FOR (E) AHU-1.
FOR WORK OCCURRING IN OCCUPIED SPACES ON THE 2ND FLOOR, ALL WORK SHALL OCCURDURING UNOCCUPIED HOURS. COORDINATE ALL WORK AND SYSTEM OUTAGES WITH CCUAT LEAST 4 WEEKS IN ADVANCE.
PROVIDE 5" LIGHTWEIGHT CONCRETE HOUSEKEEPING PADS FOR AHU-6 AND (E)AHU-1. PADSHALL EXTEND 6" BEYOND UNITS EXTERIORS. 5" PAD ALLOWS FOR SUFFICIENT DEPTH FORDRAIN TRAP FOR BOD AHU. IF DEEPER PAD IS REQUIRED, IT MUST BE APPROVED BY THESTRUCTURAL ENGINEER PRIOR TO PERFORMING WORK.
JOIST BEARING30'-8"
34"x60"
3" CHWR
3" CHWR
(E)AHU-1
22"x22" SA96"x120"x24"D
OA
6
JOIST BEARING30'-8"
22"x40"
22"x40"
36"x24"60"x28"
AHU-6
16"x20" OA
SA
RA
JOIST BEARING30'-8"
36"x
42"
36"x
42"
36"x
36"
42"x
36"
(E)AHU-1
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:47:
03 P
M
As indicated
M1.23
ADDITION -ATTIC HVACPLAN
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: 1/4" = 1'-0"M1.231 ADDITION - ATTIC HVAC PLAN
SCALE: 1/4" = 1'-0"M1.233 RELOCATED (E) AHU-1 DUCTWORK
SCALE: 1/4" = 1'-0"M1.234 AHU-6 LOOKING WEST
SCALE: 1/4" = 1'-0"M1.232 (E)AHU-1 RETURN DUCTWORK
1J
1H
6 7
3" H
WS
3" C
HW
R3" CHWS
3" HWR
3" H
WS
6" C
HW
S
1 1/
2" C
HW
S
3/4" HWS
4" CHWS
3" HWS
12
14
13
11
16
15
10
EXT-1
EXT-2
CWP-1CWP-2
HWP-1HWP-2
CWAP-1
HWAP-1
MECHANICALA-116
FUTURE BOILER
AHU-1
B-1
4M1.31
6" C
HW
S
10
10
6" CHWS/CHWRBYPASS
3" HWS
1" HWS
1" H
WR
4" CHWR
6" CHWR
6" CHWS
ISOLATION VALVESAND BLIND FLANGESFOR FUTURE BOILERCONNECTION.
1J
1H
6 7
CWP-1CWP-2
HWP-1HWP-2
EXT-1
EXT-2
CWAP-1
HWAP-1
1
2
34
5
AHU-1 VFD
NEC REQUIRED 3'WORKINGCLEARANCE (TYP.)
6
B-1
AHU-1
FUTUREBOILERMECHANICAL
A-116
19
2' PERIMETERINERTIA BASECLEARANCE
LIGHTING CONTROL PANELPROVIDED BY EC. COORDINATESIZE AND LOCATION W/ EC PRIORTO ORDERING MATERIAL.
4M1.31
AREA DESIGNATED FOR HOTAND CHILLED WATER CHEMICALTREATMENT EQUIPMENT
AHU-1MAINTENANCECLEARANCE
1J
1H
6 7
8
9
MECHANICALA-116
6
FUTUREBOILERFD
FD FD
AHU-1
VAV-
23
17
18
20
7
18
8"ø
8"ø
WATER HEATERAIR INTAKE/FLUE.SEE PLUMBING.
21
415 CFMSR1
950 CFMSR1
950 CFMSG-1
16"x
14"
16"x
12"
16"x
14"
32"x
30"
20"x18"
4M1.31
FD
360 CFMSG-1
BREAK TYPICALALL 3 VIEWS
OA-1 DUCT SILENCERIN VERTICAL.
KEY NOTES:
AREA DESIGNATED FOR NATURAL GAS RISER.
AREA DESIGNATED FOR FIRE RISER.
AREA DESIGNATED FOR DOMESTIC WATER RISER.
CWP-1 AND CWP-2 VFD. VFD PROVIDED BY CONTROLS CONTRACTOR. INSTALL SIDEBY SIDE TO PROVIDE SIMULTANEOUS READINGS. DO NOT INSTALL PIPING DIRECTLYABOVE VFDS.
HWP-1 AND HWP-2 VFD. VFD PROVIDED BY CONTROLS CONTRACTOR. INSTALL SIDEBY SIDE TO PROVIDE SIMULTANEOUS READINGS. DO NOT INSTALL PIPING DIRECTLYABOVE VFDS.
WATER HEATER PROVIDED BY PC.
PROVIDE MANUFACTURER'S EXHAUST FLUE KIT WITH WALL CAP. BOTTOM OF FLUETERMINATION AT EXTERIOR SHALL BE NO LOWER THAN 7' AFF.
EXHAUST AND INTAKE DUCT TO B-1 SHALL BE MOUNTED TIGHT TO CEILING. INTAKEAND EXHAUST SHALL BE SEPARATED BY 10' MINIMUM.
1
2
3
4
5
6
PROVIDE 40"Lx20"Wx12"D SHEET METAL PLENUM. BLANK OFF UNUSED SECTION OF LOUVER.PLENUM BOX SHALL TRANSITION TO 50"x50" DUCT.
SEE FIRST FLOOR PIPING PLAN FOR CONTINUATION.
6" CHWS AND CHWR PIPING TO CAMPUS LOOP. SEE CIVIL.
BOTTOM OF CHWS AND CHWR PIPING SHALL BE MINIMUM 11'-2" AFF. NO PIPING SHALL BEINSTALLED ABOVE ELECTRICAL EQUIPMENT.
INSTALL HWS AND HWR PIPING SUCH THAT BOTTOM OF PIPING SHALL BE 9'-0" AFF MINIMUM.
INSTALL 3" CHWS/CHWR PIPING SUCH THAT BOTTOM OF PIPING SHALL BE 9'-10" AFF MINIMUM.
BOTTOM OF HWS PIPING SHALL BE 10'-6" AFF MINIMUM.
6" CHWS PIPING WITH WYE FITTING. ANGLE SHALL NOT EXCEED 45°.
9
10
7
8
11
12
BLANK OFF PORTION OF LOUVER NOT USED FOR INTAKE WITH SHEET METAL PANEL. SEALAIR/WEATHER TIGHT AND INSULATE.
FUTURE BOILER AIR INTAKE/FLUE CONNECTION POINT SHOWN FOR INFORMATION ONLYAND OWNER'S FUTURE USE.
DDC CONTROL PANEL PROVIDED BY CONTROLS CONTRACTOR.
PROVIDE MANUFACTURER'S COMBUSTION AIR INTAKE KIT WITH WALL CAP.
DUCT SIZES ARE SHOWN FOR BASIS OF DESIGN BOILERS (NEW AND FUTURE). AIRINTAKE/FLUE DUCTS SHALL BE SIZED TO SUPPORT MANUFACTURER'S COMMON AIRINTAKE/VENTING WRITTEN REQUIREMENTS FOR NEW AND FUTURE BOILERS. FUTUREBOILER SHALL BE SAME CAPACITY AS B-1.
17
18
13
14
19
20
21
15
16
AHU-1EXT-1EXT-2
VAV-23
6" CHWS
3" CHWS
3" HWS
32"x30"
3" CHWRBEHIND
CWAP-1 16"x14"
MECHANICALA-116
3" HWS
1" HWR 1" HWSBEHIND
OA-1
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:47:
11 P
M
As indicated
M1.31
MECHANICALENLARGEDPLANS
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: 1/4" = 1'-0"M1.313 MECHANICAL ROOM ENLARGED PIPING PLAN
SCALE: 1/4" = 1'-0"M1.311 MECHANICAL ROOM ENLARGED EQUIPMENT PLAN
SCALE: 1/4" = 1'-0"M1.312 MECHANICAL ROOM ENLARGED DUCT PLAN
1. NO PIPING OR DUCTWORK SHALL BE INSTALLED ABOVE ELECTRICAL EQUIPMENT.
2. ALL DRAIN PIPING TO FLOOR DRAINS SHALL BE ROUTED EITHER ON EQUIPMENT PADSOR DOWN WALLS DIRECTLY TO FLOOR DRAINS TO ELIMINATE TRIP HAZARDS.COORDINATE ROUTING OF DRAIN PIPING WITH ALL DISCIPLINES PRIOR TO INSTALLATIONOF FLOOR DRAINS AND EQUIPMENT.
3. DUCTWORK, PIPING, ETC. SHALL BE INSTALLED AS HIGH AS POSSIBLE WITHIN SPACE.BOTTOM OF DUCTWORK, PIPING, ETC. SHALL BE MINIMUM 8'-0" AFF.
4. REFER TO BOILER MANUFACTURER'S REQUIREMENTS FOR TERMINATION LOCATIONSOF EXHAUST FLUE AND COMBUSTION AIR INTAKE.
GENERAL NOTES:
SCALE: 1/4" = 1'-0"M1.314 MECHANICAL A-116 LOOKING NORTH
NOTES:
1. REFER TO THE ELECTRICAL DRAWINGS FOR POWER REQUIREMENTS.2. VFD SHALL BE PROVIDED BY CONTROLS CONTRACTOR.
PUMP SCHEDULE
CWP -1,2
ITEM GPM
290 60
HEADFT. W.G.
74.34
MIN.EFF.
7.5
MAX.MOTOR
HPTYPE BASIS OF
DESIGNMODEL
CENTRIFUGAL
VFD
YES BELL AND GOSSETT 1510-2-1/2BBBASE MOUNTED
RPM
17506.04
MAX.BHP
HWP -1,2 80 50 47.393CENTRIFUGAL
IN-LINEMOUNTED
YES BELL AND GOSSETT 80 1-1/2 x 1-1/2 x 9-1/217502.17
EXPANSION TANK SCHEDULE
BASIS OFDESIGN
ITEM
EXT-1 TACO
MODELTANK
DIAMETER(INCHES)
20
DESCRIPTION
CA-90ASME BLADDER-TYPE PRESSUREVESSEL
SYSTEMCONNECTION
(INCHES)
1-1/2
TANK ANDACCEPTANCE
VOLUME(GALLONS)
23
NOTE:
1. REFER TO SPECIFICATIONS DIVISION 23 FOR FURTHER INFORMATION.
EXT-2 TACO24 CBX-254ASME BLADDER-TYPE PRESSUREVESSEL1-1/234
FAN SCHEDULE
CEILING MTD. CENTRIFUGAL
ITEM
EF-1 0.55
CAPACITYCFM
800DIRECT DRIVE
TYPE
1027 1.3
MANUFACTURER
GREENHECK CSP-A1410
MODEL
NOTES:
1. PROVIDE SPEED CONTROLLER.2. CONTROLLED BY BUILDING BAS.3. PROVIDE BACKDRAFT DAMPER.4. SEE ELECTRICAL DRAWINGS FOR EQUIPMENT POWER REQUIREMENTS. PROVIDE MANUFACTURER'S OPTIONAL TRANSFORMER WHERE REQUIRED.5. PROVIDE MANUFACTURER'S DISCONNECT SWITCH, SEE DIVISION 26 FOR REQUIREMENTS.
E.S.P.INCHES
W.G.FRPM
MAXIMUMSOUNDRATING(SONES)
CEILING MTD. CENTRIFUGALEF-2 625
DIRECT DRIVE1005 1.2 GREENHECK CSP-A7000.50
FRPM(MAX)
1450
1100
2020 54.94
VAV-4
VAV-1 24"X16" 0.23
55
55
15
15
VAV-2 55 15
VAV-3 55 15
VAV-5 55 15
VAV-6
VAV-8 55 15
VAV-9 55 15
8
10
10
8
10
8
10
55 15
55 15
VAV-7 8
1055
VAV TERMINAL UNIT SCHEDULEHEATING CAPACITY @ 150F EWT
LAT (°F)COIL CAPACITY(MBH)
TAG EAT (°F)
1. INLET DUCT SHALL BE SAME SIZE AS VAV TERMINAL UNIT INLET.2. MULTI-POINT, MULTI-AXIS FLOW RING OR CROSS SENSOR TO BE PROVIDED BY TERMINAL UNIT MANUFACTURER. SINGLE-POINT OR FLOW BAR SENSORS SHALL NOT BE ACCEPTABLE.
5. INSULATION SHALL BE 1" FOIL FACED OR DOUBLE WALL. ALL CUT EDGES OF INSULATION SHALL BE COMPLETELY ENCLOSED BY METAL TO ARREST CUT FIBERS
10. SEE ELECTRICAL DRAWINGS FOR EQUIPMENT POWER REQUIREMENTS.
MODELBASIS OFDESIGN
COOLINGMAX.CFM
COOLINGMIN.CFM
PRIMARYINLET
(INCHES)
APD @COOLINGAIRFLOW(IN H2O)
DISCHARGEVALVE NOISE
CRITERIANC
FLOW SENSING DEVICE SHALL BE CAPABLE OF MAINTAINING AIRFLOW TO WITHIN +/- 5 PERCENT.3. PROVIDE FACTORY MOUNTED DISCONNECT SWITCH AND CONTROL POWER TRANSFORMER.4. UNIT DDC CONTROLLER AND ACTUATOR SHALL BE PROVIDED BY THE CONTROLS CONTRACTOR AND FACTORY MOUNTED BY THE VAV BOX MANUFACTURER.
VAV BOX MANUFACTURER SHALL INCLUDE SHEET METAL CONTROLS ENCLOSURE.
AND PREVENT EROSION INTO THE AIRSTREAM. ADHESIVE EDGE ENCAPSULATION SHALL NOT BE ACCEPTABLE.6. PROVIDE ALL HIGH AND LOW VOLTAGE COMPONENTS ON THE SAME SIDE FOR EASE OF MAINTENANCE.
7. UNITS SHALL BE ARI-880 PERFORMANCE CERTIFIED. UNITS SHALL BE ACOUSTICALLY TESTED AND RATED PER ARI-885 LISTED AT ARI'S WEBSITE.8. UNIT SHALL BE LISTED AND LABELED BY UL AS A COMPLETE ASSEMBLY.9. REFER TO MECHANICAL SPECIFICATIONS FOR FURTHER INFORMATION.
11. PROVIDE MANUFACTURER'S 5 YEAR PARTS AND LABOR WARRANTY. ALL CONTROL DEVICES SHALL BE WARRANTED FOR 5 YEARS PARTS AND LABOR BY CONTROLS VENDOR.
VAV-10 55 155
VAV-11 55 1516
VAV-13 55 1524"X16"
VAV-14 55 158
TRANE VCWF
VCWF
VCWF
VCWF
VCWF
VCWF
VCWF
VCWF
VCWF
VCWF
VCWF
VCWF
VCWF
TRANE
TRANE
TRANE
TRANE
TRANE
TRANE
TRANE
TRANE
TRANE
TRANE
TRANE
TRANE
VAV-15 55 158 VCWFTRANE
VAV-16 55 158 VCWFTRANE
VAV-17 55 1510 VCWFTRANE
VAV-18 55 1510 VCWFTRANE
VAV-19 55 158 VCWFTRANE
VAV-20 55 1514 VCWFTRANE
VAV-21 55 155 VCWFTRANE
VAV-22 55 1510 VCWFTRANE
VAV-23 55 1512 VCWFTRANE
VAV-24 55 155 VCWFTRANE
VAV-25 55 1524"X16" VCWFTRANE
VAV-26 55 1514 VCWFTRANE
VAV-27 55 1512 VCWFTRANE
VAV-28 55 15 VCWFTRANE
VAV-29 55 1524"x16" VCWFTRANE
VAV-30 55 1524"x16" VCWFTRANE
VAV-31 55 1512 VCWFTRANE
VAV-32 55 1510 VCWFTRANE
GPM COIL PD(FT H2O)
450 0.12165
530 21.260.17340
800 9.620.16255
580 0.19225
660 0.19420
400 0.17190
440 0.27275
570 17.300.15350
295 0.16295
1940 57.450.291310
2230 49.010.27895
600 6.840.20205
600 0.20215
730 0.28220
810 0.16275
565 0.15270
420 0.11160
1560 0.24515
300 0.09105
825 0.17220
1365 0.23430
335 0.11160
3230 0.411375
1400 0.20800
1015 0.27620
3600 0.612400
2805 0.401800
3040 0.462570
1000 0.27595
600 0.17520
85 3.67 0.76
0.5 0.67
1.42 0.48
1.43
0.67
0.30
0.03
0.09
1.16 0.24
0.77 0.38
3.84 0.66
3.27 0.62
0.50 0.67
0.67
0.67
1.54
0.17
0.67
1.77 0.15
0.50 0.50
1.25
0.59
0.50
4.36 1.05
2.45 0.27
1.75 0.19
5.97 1.89
5.11 1.41
6.19 2.02
1.71 0.18
0.82 0.13
ADJUSTED HEATINGAIRFLOW (CFM)
1055
165
340
255
225
420
190
275
350
295
1310
895
205
215
220
275
270
160
515
105
220
430
160
1375
800
620
2400
1800
2570
595
520
VAV-33
0.64
0.50
1.31
0.50
0.90
0.50
0.50
0.67
0.96
0.50
0.59
0.95
0.50
NOTES:
78
78
78
78
78
78
78
78
78
85
85
85.75
85
85
85
85
85
85
85
78
78
85
85
85
90
85
85
85
85
85
11.59
13.49
7.37
19.55
7.08
6.3
6.96
7.02
10.00
14.37
6.21
26.47
4.51
8.90
14.29
5.35
65.26
36.76
26.27
89.47
76.58
92.64
25.54
16.92
24"X16"
VAV-12 5 55 15 TRANE VCWF335 4.600.11110 0.5 0.50110 78
LWT (°F)
120
120
120
120
131.6
120
122.6
122.1
121.9
120
120
125.1
120
132.0
120
120
128.6
120
120
120
120
120
120
120
108.6
120.5
120
121.6
120
120
124.8
120
24"X16" 55 15 TRANE VCWF3240 97.070.512825 6.48 2.202825 85 120
EWT (°F)
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
BASIS OFTAG CFM DESCRIPTIONDESIGN
MODEL
0-150A PRICE
SIZEFACE
24"x24" SQUARE PLAQUE STYLE DIFFUSER
151-275 24"x24" SQUARE PLAQUE STYLE DIFFUSER
276-400 24"x24" SQUARE PLAQUE STYLE DIFFUSER
PRICE
PRICE ASPD
ASPD
ASPD
SG1 0-300 12"x10" PRICE
451-950 18"x18"
301-450 14"x12" PRICE
PRICE
630 DAL
SIZENECK
6"
8"
10"
10"x8"
16"x16"
12"x10"
0-75EG 10"x10" LOUVERED FACE SINGLE DEFLECTION
151-225
0-150 10"x10"
PRICE
PRICE
PRICE 630
LOUVERED FACE SINGLE DEFLECTION
LOUVERED FACE SINGLE DEFLECTION
8"x8"
10"x8"
8"x8"
0-2600
C
24"x24" PRICE 80
401-550 24"x24" SQUARE PLAQUE STYLE DIFFUSER PRICE ASPD12"
551-750 24"x24" SQUARE PLAQUE STYLE DIFFUSER PRICE ASPD14"
NOTES:
1. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL CEILING MOUNTED AIR DISTRIBUTION DEVICES.2. ALL AIR DISTRIBUTION DEVICES SHALL BE ALUMINUM CONSTRUCTION WITH BAKED ENAMEL, 'WHITE' FINISH UNLESS NOTED OTHERWISE.3. ALL CEILING DIFFUSERS SHALL BE 4-WAY BLOW UNLESS NOTED OTHERWISE ON THE DRAWINGS.4. RUN OUT SIZE SHOWN ON DRAWINGS. PROVIDE NECESSARY CONNECTION AND TRANSITION TO MANUFACTURER'S LISTED NECK SIZE.5. ALL LOUVERED FACE AND PERFORATED FACE AIR DISTRIBUTION DEVICES MOUNTED IN LAY-IN CEILING SYSTEMS SHALL BE EITHER TEGULAR OR FLAT FRAME TYPE TO MATCHCEILING TILE. SEE ARCHITECTURAL DRAWINGS FOR CEILING TILE TYPES AND LOCATIONS.6. REFER TO THE MECHANICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.7. ALL TAPS FROM MAIN DUCTS SHALL BE PROVIDED WITH BALANCING DAMPERS.8. SEE ARCHITECTURAL DRAWINGS FOR CEILING/WALL TYPES FOR PROPER SELECTION OF MOUNTING ACCESSORIES.9. PROVIDE YOUNG REGULATOR REMOTE DAMPER CONTROLLERS FOR ALL AIR DEVICES REQUIRING DAMPERS IN INACCESSIBLE LOCATIONS, COORDINATE WITHARCHITECTURAL DOCUMENTS FOR LOCATIONS.10. ALL AIR DEVICES IN AREAS WITHOUT CEILINGS SHALL BE MOUNTED NO LOWER THAN 96" ABOVE FINISHED FLOOR.11. PROVIDE MANUFACTURER'S OPTIONAL ENGINEERED PLENUM FOR LINEAR SLOT DIFFUSERS.12. ALL SIDEWALL AIR DEVICES SHALL BE PROVIDED WITH OPPOSED BLADE DAMPERS.13. ALL AIR DEVICES MOUNTED IN GWB (INCLUDES, BUT IS NOT LIMITED TO SOFFITS, WALLS AND CEILINGS) SHALL BE PRIMED WITH PAINT GRIP FINISH, READY FOR PAINTING.SEE ARCHITECTURAL DOCUMENTS FOR PAINTING REQUIREMENTS.14. FOR NOZZLE DIFFUSERS, PROVIDE "B15 ALUMINUM" FINISH BY PRICE OR APPROVED EQUAL BY THE ARCHITECT.15. FOR LOUVERED FACE TYPE DEVICES (610, 620, 630) IN ACT CEILINGS, PROVIDE PANEL-MOUNT OPTION.
AIR DISTRIBUTION SCHEDULE
EG1
12"x10"
B
0-530 8012"x24" PRICE9"x21"
3/4" BLADE SPACING, SINGLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
SG2
226-500 24"x24"22"x22" LOUVERED FACE SINGLE DEFLECTION PRICE 630
3/4" BLADE SPACING, SINGLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
3/4" BLADE SPACING, SINGLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
22"X22"
0-300 12"x10" PRICE
451-900
301-450 14"x12" PRICE
PRICE
10"x8"
12"x10"
3/4" BLADE SPACING, SINGLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
3/4" BLADE SPACING, SINGLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
3/4" BLADE SPACING, SINGLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
SR1 0-300 620 DAL12"x10" PRICE
601-900 18"x18"
301-600 14"x12" PRICE
PRICE
10"x8"
16"x16"
12"x10"
3/4" BLADE SPACING, DOUBLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
SR2
3/4" BLADE SPACING, DOUBLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
0-300 12"x10" PRICE
601-950 18"x18"
301-600 14"x12" PRICE
PRICE
3/4" BLADE SPACING, DOUBLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
3/4" BLADE SPACING, DOUBLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
10"x8"
16"x16"
12"x10"
0-360D NDSIZE 10 AIR NOZZLE DIFFUSER PRICE
EGG CRATE FACE
EGG CRATE FACE
630 DAL
630 DAL
630 DAL
630 DAL
630 DAL
620 DAL
620 DAL
620 DAL
620 DAL
620 DAL
630
630
3/4" BLADE SPACING, DOUBLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
3/4" BLADE SPACING, DOUBLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
TG1
- 20"x10" PRICE18"x8" 630 DAL
751-940 24"x24" SQUARE PLAQUE STYLE DIFFUSER PRICE ASPD15"
10"
515-690 14"x12" PRICE3/4" BLADE SPACING, SINGLE DEFLECTION, WITH
DAMPER12"x10" 610 DAL
0-300 14"x14" PRICE12"x12" 630 DAL
SR3
3/4" BLADE SPACING, SINGLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
3/4" BLADE SPACING, SINGLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
TG2
18"x12" PRICE16"x10" 630 DAL3/4" BLADE SPACING, SINGLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
TG3 300
18"x18"16"x16"
901-1200 PRICE3/4" BLADE SPACING, SINGLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER 630 DAL26"x16"24"x14"
901-1200 PRICE 630 DAL20"x18"18"x16" 3/4" BLADE SPACING, DOUBLE-DEFLECT.45 DEGREE DEFLECTION, WITH DAMPER
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:47:
13 P
M
NOT TO SCALE
M7.01
MECHANICALSCHEDULES
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
AIR HANDLING UNIT SCHEDULEHEATING COIL
MODELBASIS OFDESIGN
ITEM
O/A(MIN)
AIR CAPACITY
TOTAL
CFMT.S.P.
W.G.INCHES
EAT°FSENS. MB LAT °F
NOTES:
1. SEE ELECTRICAL DRAWINGS FOR POWER REQUIREMENTS.2. PROVIDE ELECTRICAL DISCONNECT.3. MANUFACTURER TO PROVIDE ALL ACCESSORIES REQUIRED TO SUPPORT CONTROL BY CMI AS DETAILED ON THE DRAWINGS AND SPECIFICATIONS.4. SCHEDULE DATA FOR (E)AHU-1 IS TAKEN FROM EXISTING RECORD DRAWINGS, SHEET M10 DATED 4/22/10, AND IS SHOWN FOR TESTING AND BALANCING PURPOSES.5. CAREFUL CONSIDERATION SHALL BE GIVEN TO SA DISCHARGE DUCT ARRANGEMENT WHEN SELECTING FAN CONFIGURATION TO MINIMIZE SYSTEM EFFECT.6. INCLUDE CLEAN AND LOADED FILTER ALLOWANCE IN TSP CALCULATIONS. FAN SELECTION SHALL BE BASED ON LOADED CONDITION.7. INCLUDE DISCHARGE PLENUMS AND MIXING BOXES WHERE SHOWN ON DRAWINGS.8. PROVIDE OPTIONAL MARINE LIGHT.9. INCLUDE ACCESS PANEL BETWEEN COIL SECTIONS.10. AHU-2 OA QUANTITIES REPRESENT SUMMER/WINTER DESIGN CONDITIONS.
AHU-2
AHU-1 7360 2155 7.6 91.30 TRANE
7500 1000/2000 6.7 CLIMATE
CHANGERTRANE
6455 1430 7.8 TRANEAHU-3
11810 1350 6.5 TRANEAHU-4
EWT °F LWT °F
10200 1120 5.8 205.78 86 TRANEAHU-6 180 140 CLIMATECHANGER
TOTALMBH
COOLING COIL
D.B.°F
ENTERING AIR
W.B. °F
400.1 251.7 81 68
389.5 248.2 81 68
343.3 217.9 81 68
446.0 350.4 78 64
EWT °F LWT °F
42
42
42
42 54
54
54
54
358.4 313.4 79 63 44 54
57.51
47.40
-
51
- -
FAN MAX.RPM
FAN MAX.BHP
HEATINGCFM
5500
4820
4325
2500
-
45
- -
WATERP.D. (FT
W.G.)
COIL P.D.(FT OFHEAD)
2558 13.7
NOMINALFAN HP
20 CLIMATECHANGER
252241 18.6 CLIMATECHANGER
2056 14.0 20
202454 12.5
152954 12.8 CLIMATECHANGER
18500 3390 3.1 160 56.5 TRANE(E) AHU-1 180 140 MCCB-035622.0 485.0 80.8 66.8 44 54 203390- - 20
7.3
11.1
17.8
18.6
11.0
-
0.27
8.0 -
E.S.P.
W.G.INCHES
3.5
3.5
3.5
3.5
3.5
1.80
45
42
57.46
57.26
59.48
150
150
150
108.43
101.98
120
0.02
0.06
D.B.°F
LEAVING AIR
W.B. °F
50.0 49.9
51.0 50.8
51.0 50.9
51.0 50.6
57.0 56.0
GPM
66.40
64.66
56.99
74.04
71.43
124.3
AIR P.D.(IN W.G.)
0.65
1.32
1.04
1.15
0.95
0.62
CHWROWS;
FINS / INCH
6; 12
6; 9
8; 7.25
6; 11
-
HWROWS;
FINS / INCH
1; 7
-
1; 8
-
8; 10
2; 6
MAX FV(FPM)
350
-
-
300
200
300
AIR P.D.(IN W.G.)
-
0.038
0.030
-
0.052
GPM
4.40
2.40
-
10.289
8.0
MAX FV(FPM)
450
400
565
450
475
500
EFFICIENCY EFFICIENCY
MERV 8 MERV 13
MERV 8 MERV 13
MERV 8 MERV 13
MERV 8 MERV 13
MERV 8 -
- -
SENS.MBH
0.024.420.01450.4 50.3 1; 7
MAXCLEANAIR P.D.
0.2
MAXMID-LIFE
AIR P.D.
0.6
PRE-FILTER FINAL-FILTER
MAXCLEANAIR P.D.
0.3
MAXMID-LIFE
AIR P.D.
0.8
-
0.2 0.6
0.3 0.6
0.2 0.6
0.2 1.2(DIRTY)
0.3 0.8
0.4 0.8
0.3 0.8
- -
- - -
AIR SEPARATOR SCHEDULE
BASIS OFDESIGN
ITEM
CWAP-1 TACO
MODELFLOW(GPM)
288
DESCRIPTION
4900AIR/DIRT SEPARATOR
PD(FT HD)
.9
INLET/OUTLETCONNECTION
SIZE
6
NOTES:1. REFER TO SPECIFICATIONS FOR FURTHER INFORMATION.
HWAP-1 TACO87 4900AIR/DIRT SEPARATOR23
MAXIMUMALLOWED DESIGNPRESSURE (PSI)
125
125
COALESCENCERING SURFACEAREA (SQ. FT)
41.0
20.7
NOTES:
1. REFER TO THE ELECTRICAL DRAWINGS FOR POWER REQUIREMENTS.2. REFER TO DIVISION 23 SPECIFICATIONS FOR FURTHER INFORMATION.3. PROVIDE NATURAL GAS REGULATING VALVE.4. BOILER BURNERS SHALL BE CAPABLE OF 20 TO 1 TURN DOWN, MINIMUM.5. SEE PLUMBING DOCUMENTS FOR NATURAL GAS PIPING REQUIREMENTS. MC SHALL BE RESPONSIBLE FOR FINAL CONNECTION TO BOILER AND SHALL COORDINATE WITH PC.
GAS FIRED BOILER SCHEDULE
B-1
ITEMMAX.INPUT
CAPACITY(MBH)
1500 1409
EWT(F)
NATURAL GAS
BURNER BASIS OFDESIGN MODEL
AERCO BMK-1.5LN
FLOWGPM
160
DESIGNPRESSURE
(PSIG)
MAX.OUTPUT
CAPACITY(MBH)
LWT(F)
87 120 150 90.9 89.1 88.5
THERMAL EFFICIENCY(5%/50%/100% INPUT)
ELECTRIC HEATER SCHEDULE
BASIS OF
NOTES:1. ELECTRIC UNIT HEATER SHALL BE CONTROLLED BY INTEGRAL THERMOSTAT2. ELECTRIC UNIT HEATER SHALL BE EQUIPPED WITH PRIMARY AND SECONDARY SAFETY SWITCHES.3. ELECTRIC UNIT HEATER SHALL BE EQUIPPED WITH SUPPORT KIT.4. INCLUDE OPTIONAL SURFACE MOUNTING FRAME.
ITEM
UH-1 MARKEL
DESIGN
F3326TD-RP
MODEL
KWCAPACITY
4.0
REMARKS
SURFACE MOUNT
(+/-) THE SYMBOL (+) DESIGNATES FORWARD FLOW AND THE SYMBOL (-) DESIGNATES REVERSE FLOW.
NOTES:1. PROVIDE, FOR APPROVAL AS PART OF SUBMITTALS, ACOUSTICAL CALCULATIONS FOR ALL SYSTEMS WITH SILENCER TO DEMONSTRATE THAT THE RESULTANT NOISELEVEL WILL MEET NC-25.2. PROVIDE, FOR APPROVAL AS PART OF SUBMITTALS, ACOUSTICAL CALCULATIONS FOR ALL SYSTEMS WITH SILENCER TO DEMONSTRATE THAT THE RESULTANT NOISELEVEL MEASURED ON GROUND LEVEL 10 FT AWAY FROM OA LOUVER WILL BE 40 dBA.3. ELBOW SILENCER.4. STRAIGHT SILENCER.5. CUSTOM BUILT RLP SILENCER ON THE VERTICAL.6. THE SCHEDULED SILENCER PRESSURE DROP(S) ARE REPORTED IN ACCORDANCE WITH ASTM E477 TEST METHODS. THE PRESSURE DROP(S) ARE AT IDEAL FLOWCONDITIONS (3-4 DUCT DIAMETERS OF STRAIGHT DUCT ON SILENCER INLET AND 4-5 DUCT DIAMETERS OF STRAIGHT DUCT ON SILENCER OUTLET). LESS THAN IDEALCONDITIONS WILL RESULT IN INCREASE IN PRESSURE DROP - SEE VA REPRESENTATIVE FOR ASSISTANCE.
SILENCER SCHEDULE
SA-5
ITEM
1
QUANTITY
14
FACEDIMENSION
32
W(in) H(in)
144
LENGTH
(in)
FLOW
cfm
4300
VELOCITY
ft/min
1382
SILENCER P.D.INCL SYSTEM
EFFECTin wg
0.2
AMBIENT NOISE LEVEL /DYNAMIC INSERTION LOSS /
GENERATED NOISE
THE RESULTANT NOISE LEVEL IN THEAUDITORIUM: MAX NC-25
NOTES
1,3,6
RA-5 1 14 40 144 4300 -1191 0.2 1,3,6
OA-1 1 22 54 60 7250 -879 0.19 2,4,5,6
VIBRO-ACOUSTICS
MODEL
RED
RD
RLP
THE RESULTANT NOISE LEVEL IN THEAUDITORIUM: MAX NC-25
THE RESULTANT NOISE LEVEL AT 10FT AWAYFROM OA LOUVER AT GROUND LEVEL: MAX 40 dBA.
TAG SUPPLYAIR CFM
1200FCU-1
NOTES:
1. FAN COIL UNIT SHALL BE SUPLIED WITH SINGLE POINT POWER CONNECTION AND UNIT MOUNTED TRANSFORMER FOR CONTROL POWER.2. SEE ELECTRICAL DRAWINGS FOR POWER REQUIREMENTS.3. PROVIDE UNIT WITH INTEGRAL NON-FUSED DISCONNECT.4. REFER TO THE MECHANICAL SPECIFICATIONS FOR FURTHER INFORMATION.
4-PIPE FAN COIL UNIT SCHEDULE
ESPIN. WG
COOLING CAPACITY
TOTALMBH
SENS.MBH DB °F WB °F
ENTERING AIRDB °F WB °FLEAVING AIR
GPM IN °F OUT °F P.D.FTCHILLED WATER TOTAL
MBHENTERING
AIR °FLEAVING
AIR °F GPM IN °F OUT °F P.D.FTHOT WATER
HEATING CAPACITYBASIS OFDESIGN MODEL
0.206 23.1 22.6 76 62 58.2 55.3 4.0 42 54 6.5 54.1 67 90 4.0 150 123 5.9 FCCB10TRANE
NOTES:
1. PROVIDE GALVANIZED BIRDSCREEN.2. PROVIDE VOLUME DAMPER AND BACKDRAFT DAMPER.3. TRANSITION DUCTWORK TO FULL THROAT SIZE.4. PROVIDE MOTORIZED CONTROL DAMPER. SEE SECTION 233300 FOR REQUIREMENTS. DAMPER SHALL BECONTROLLED BY THE BAS TO MAINTAIN BUILDING POSITIVE PRESSURE SETPOINT (ADJ). HOOD SHALL BE HINGEDTO PROMOTE EASY ACCESS TO DAMPER AT ROOF LEVEL.
GRAVITY ROOF VENTILATOR SCHEDULE
GRV-1
ITEM SIZE
16"X16" 800
AIRFLOWCFM
.05"
MAX.PRESSURE
DROPBASIS OFDESIGN
MODEL
GREENHECK
GRV-2 14"X14" 625 .05" FGR
GRV-3 38"X38" 5000 .05"
GREENHECK
GREENHECK
FGR
FGR
NOTES
1,2,3
1,2,3
1,2,3,4
AHU-5 4510 1005/2005 3.5
AIR CAPACITYCFM
TOTAL OA EA
ITEMSF ESP
(IN W.G.)
ENERGY RECOVERY WHEEL PERFORMANCE
WINTER DESIGN CONDITIONS
ENERGY RECOVERY AIR HANDLING UNIT SCHEDULE
6.239
SF TSP(IN W.G.)
SF MAXBHP / MHP
2504
SF MAXRPM
1.65
EF ESP(IN W.G.)
3.751
EF TSP(IN W.G.)
6.653
EF MAXBHP / MHP
7.5 1279
EF MAXRPM OUTSIDE AIR LEAVING
65.1 58.5
DB °F WB °F
OUTSIDE AIR ENTERING
25.0 18.0
DB °F WB °F
EXHAUST AIR ENTERING
70.0 58.0
DB °F WB °F
SUMMER DESIGN CONDITIONS
OUTSIDE AIR LEAVING
77.8 66.0
DB °F WB °F
OUTSIDE AIR ENTERING
95.0 78.0
DB °F WB °F
EXHAUST AIR ENTERING
75.0 62.5
DB °F WB °F
7.99 10.03505/2505
RA1005/2005
TRANE/CLIMATE
BASIS OF DESIGNMANFUFACTURER
/ MODEL
CHANGER
EFFECTIVENESS
TOTALSUMMER
TOTALWINTER
85.41% 85.99%
EFFICIENCY MAXCLEANAIR P.D.
PRE-FILTER
0.175 0.511
MAXMID-
LIFE AIRP.D.
EFFICIENCY MAXCLEANAIR P.D.
FINAL-FILTER
0.278 0.644
MAXMID-
LIFE AIRP.D.
MERV 8 MERV 13
NOTES:
1. SEE ELECTRICAL FOR POWER REQUIREMENTS.2. PROVIDE ELECTRICAL DISCONNECT.3. MANUFACTURER TO PROVIDE ALL ACCESSORIES REQUIRED TO SUPPORT CONTROL BY CMI AS DETAILED ON THE DRAWINGS AND SPECIFICATIONS.4. SCHEDULE DATA FOR (E)AHU-1 IS TAKEN FROM EXISTING RECORD DRAWINGS, SHEET M10 DATED 4/22/10, AND IS SHOWN FOR TESTING AND BALANCING PURPOSES.5. CAREFUL CONSIDERATION SHALL BE GIVEN TO SA DISCHARGE DUCT ARRANGEMENT WHEN SELECTING FAN CONFIGURATION TO MINIMIZE SYSTEM EFFECT.6. INCLUDE CLEAN AND DIRTY FILTER ALLOWANCE IN TSP CALCULATIONS.7. INCLUDE DISCHARGE PLENUMS AND MIXING BOXES WHERE SHOWN ON DRAWINGS.8. PROVIDE OPTIONAL MARINE LIGHT.9. OA/RA/EA QUANTITIES REPRESENT SUMMER/WINTER DESIGN CONDITIONS.
COOLING COIL HEATING COIL
500
MAX FV(FPM)
179.19
MIN.TOTALMBH
127.70
MIN.SENS.MBH
0.035
TOTALMBH
82.07
AIR P.D.(IN W.G.)
ENTERING AIR LEAVING AIR
WB °F
-25.0
DB °F
- 65.6
WB °F DB °FGPM IN °F OUT °F
HOT WATER
5.48 150 120 0.11
WATERPD (FTW.G.)
GPM IN °F OUT °F
CHILLED WATER
29.75 42.0 54.0 2.58
ENTERING AIR LEAVING AIR
WB °F
49.975.8
DB °F
63.8 50.0
WB °F DB °F
0.564
AIR P.D.(IN W.G.)
WATERPD (FTW.G.)
2005
HEATINGCFM(OA)
ROWS;FINS/INCH
6; 13.4
ROWS;FINS/INCH
1; 7330
MAX FV(FPM)
COASTAL CAROLINA UNIVERSITYNOISE CRITERIA
TYPE OF ROOM NCLEVEL
25AUDITORIUMS, THEATERS
40BATHROOMS AND TOILET ROOMS
35CONFERENCE ROOMS
40CORRIDORS (PUBLIC)
40LOBBIES
40OFFICES, LARGE OPEN (3 OR MORE OCCUPANTS)
35OFFICES, SMALL PRIVATE (2 OR FEWER OCCUPANTS)
50RECREATION ROOMS
50SHOPS
ENTHALPY WHEEL
EXHAUST AIR FANSUPPLY AIR FAN
EA/RA INTAKE
OA INTAKE
HOT WATER COILCHILLED WATER COIL
BYPASS DAMPER(TYP 2)
RECIRCULATIONDAMPER
MERV 8/MERV 13COMBINATIONFILTER BANK
MERV 8 FILTER
MERV 13 FILTER
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:47:
16 P
M
As indicated
M7.02
MECHANICALSCHEDULES
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: NOT TO SCALEM7.021 AHU-5 ELEVATION DETAIL
NOTES:
NYLON CLAMP
NYLON CLAMP
DUCT WRAP OVERENTIRE DIFFUSER
LAY-IN CEILING DIFFUSER
PREINSULATEDFLEX. DUCT
DUCT WRAP (TYP.)
OPPOSED BLADEDAMPER
NYLON CLAMP
LAY-IN EGGCRATERETURN AIR GRILLE
RETURN AIRBOX W/LINER
NYLON CLAMP
PREINSULATEDFLEX. DUCT
DUCT WRAP (TYP.)
MANUAL DAMPER
ROUND METAL DUCT
TAKE-OFF FITTINGSUPPLY DUCTW/ WRAP
METAL COLLAR
RETURN DUCTW/ WRAP
INSTALL NYLON CLAMPS ON INNER FLEX DUCT LINER AND OUTER JACKET. TAPE ENDS OFPREINSULATED FLEX. DUCT AT THE DIFFUSER AND THE BRANCH DUCT CONNECTION.RETURN AIR BOX SHALL BE MINIMUM 12" HIGH. RETURN DUCT MAY TAP INTO THE SIDE OFTHE BOX A MINIMUM OF 6" ABOVE GRILLE.
1.
2.
NOTES:
MANUAL
3. SPIN-IN FITTINGS WITH INTEGRAL SCOOP AND DAMPER SHALL ONLY BE USED ON LOW PRESSURE DUCT.2. TAKE-OFFS IN MEDIUM PRESSURE DUCT SHALL HAVE AN OVERSIZED INTAKE.1. CONTRACTOR MAY SUBSTITUTE A MANUFACTURED FITTING FOR THE DETAILED TAKE-OFF ABOVE.
ELEVATION
1" MIN
ROUND BRANCHDUCT
PLAN
DAMPER
RECTANGULARBRANCH DUCT
1" MIN
ELEVATION
PLAN
6"
DAMPER
60°
6"
MAIN DUCT
AIRFLOW
MAIN DUCT
SUPPLY
RETURN OR EXHAUST
45°
MANUAL
6"
4. FITTINGS SHALL BE SCREWED TO THE TRUNK DUCT AND SEALED WITH MASTIC. MASTIC TAPE IS NOT ACCEPTABLE, SEE SPECIFICATIONS.5. IF VAV BOX IS LOCATED IN BRANCH DUCT, BALANCE DAMPER SHALL NOT BE INSTALLED IN TAKEOFF
FROM MAIN TRUNK DUCT.6. VOLUME DAMPERS ARE NOT SHOWN ON PLANS, BUT ARE REQUIRED AT EVERY DUCT TAKEOFF TO AIR
DEVICES (SUPPLY, RETURN, EXHAUST).7. PROVIDE YOUNG REGULATOR REMOTE DAMPER CONTROLLERS FOR ALL AIR DEVICES REQUIRING DAMPERS
IN INACCESSIBLE LOCATIONS COORDINATE WITH ARCHITECTURAL DOCUMENTS FOR LOCATIONS.
NOTES:
DUCT WRAP
FIR
E D
AMPE
R
DUCT
BREAKAWAYCONNECTION
MOUNTINGANGLE
SLEEVE
WALL OPENINGS SHALL BE 1/8" PER FOOT LARGER THAN THE OVERALL ASSEMBLY. MINIMUMOPENING SIZE SHALL BE 1/4" ALL AROUND.
DAMPER RATING SHALL BE 1 1/2 HOUR UNLESS NOTED OTHERWISE.
PROVIDE ACCESS DOOR IN DUCTWORK AS NEAR AS POSSIBLE TO FIRE DAMPER. LOCATION MAYVARY TO SUIT FIELD CONDITIONS.
FIRESTOPPING COMPOUND SHALL BE 3M CP 25 CAULK OR EQUIVALENT BY NELSON.
WALL SLEEVE, MOUNTING ANGLES AND FASTENERS SHALL BE PER NFPA 90A AND THEMANUFACTURER'S U.L. LISTED INSTALLATION INSTRUCTIONS.
4.
5.
3.
1.
2.
CAULK (IFREQUIRED BYMANUFACTURER)
45° "Y" TEE
2-WAY 45° "Y" TEE
90° CONICAL TEE
90° TEE WITH 45° TAKE-OFF
DIRECTIONOF AIRFLOW
DIRECTIONOF AIRFLOW
1-1/2 D
D
1-1/2 DD
BRANCH DUCT
BRANCH DUCT
BRANCH DUCT
TRUNKDUCT
TRUNK DUCTDIRECTION OF
AIR FLOW
DIRECTIONOF AIRFLOW
BRANCH DUCT
TRUNKDUCT TRUNK
DUCT
6" THICK
CLEARANCE1" OPERATING
CONCRETE PAD
FILL BASE WITH 3500 PSICONCRETE
EQUIPMENT ANCHORBOLT TEMPLATE
CHANNEL PERIMETERFRAME
ISOLATOR SUPPORTCLIP
STABLE SPRING ISOLATOR
FIBERGLASS NOISE ISOLATION PAD
HOOKS AND REINFORCINGAS REQUIRED
P&T
1-1/2" NPTDRAIN CONN.
RELIEF VALVE (TYP.)
HEATING SYSTEM RETURN
HEATINGSYSTEMSUPPLY
AT MAXIMUM BTU/HR INPUT,MAINTAIN MINIMUM GAS PRESSUREAT 4.0" W.C.(FM GAS TRAIN); 4.5" W.C.(IRI) MAX. GAS PRESSURE = 14" W.C.(SEE NOTE 6)
MANUAL SHUTOFFVALVE
DIRT TRAP
GAS SUPPLY
TEMPERATURE GAUGEP&T PRESSURE &
BALANCING VALVE
ISOLATION VALVEUNION
Y STRAINERLEGEND
1. FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER, SEE PLANS.2. SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN FREELY,
BY GRAVITY, TO A CONVENIENT FLOOR DRAIN. PIPING OF RELIEF VALVE MUST COMPLY WITH LOCAL CODES.3. LOCATE WATER INLET AND OUTLET FITTINGS (i.e. UNIONS, ELBOWS, ETC.) A MINIMUM OF 6'' FROM BOILER FITTINGS TO
PREVENT INTERFERENCE WITH REMOVAL OF BOILER PANELS AND COVERS. ALL PIPING AND ELECTRIC CONNECTIONS(SERVICE SWITCHES, CONDUIT BOXES) SHOULD LIKEWISE BE 6'' AWAY FROM SIDE PANELS.
4. PROVIDE MANUFACTURER'S CONDENSATE NEUTRALIZER KIT.5. CONTROLS CONTRACTOR SHALL PROVIDE HEATING HOT WATER RESET CONTROL TO BAS.6. REFERENCE PLUMBING DOCUMENTS FOR NATURAL GAS PIPING DIAMETER, ROUTING, AND OTHER REQUIREMENTS.
COORDINATE WITH PC.
NOTES:
6" HOUSEKEEPING PAD
PRESSURE REDUCING VALVE- SET AT 4 PSIG HIGHERTHAN THE PRESSURE ATTHE HIGH POINT IN THESYSTEM
AIR CHARGING VALVE-PRESSURIZE DRYTANK EQUAL TO FILLVALVE PRESSURE
TO DRAIN
FILL LINE
UNDERSLUNG CONNECTION CREATESTHERMAL TRAP (12"MIN. DROP)
SYSTEM CONNECTION - (CONNECTTO SIDE OR BOTTOM OF MAINHEADER)
BLOWDOWN AND DRAINVALVE WITH HOSECONNECTION
PRESSURE GAUGEW/ NEEDLE VALVE
PRESSURE GAUGEW/ NEEDLE VALVE
GLOBE VALVE
REDUCED PRESSUREBACKFLOW PREVENTERWITH OPEN AIR GAP
REDUCER (WHERE REQ'D.)
EXPANSION TANK
TOPUMPSUCTION
RELIEF VALVE - (WHENNOT PROVIDED ON HEATTRANSFER DEVICE)PIPED TO FLOOR DRAIN.
DRAIN VALVE W/HOSE CONNECTION
INSTALL UNIT WITH ADEQUATEDISTANCE TO REMOVESTRAINER
INTERNAL STRAINER
BRACKET SUPPORTSWITH OVERHEADSUPPORTS
GATE VALVES
UNION
CENTRIFUGAL AIRSEPARATOR 8"INLET
LOW CAPACITYAIR VENT
HIGH CAPACITYAIR VENT
FROM SYSTEM
FACTORY BUILT CURB
ROOFING MATERIAL
HOOD COVER
COORDINATE ROOF WORKWITH ARCHITECTURAL PLANSAND ROOFING CONTRACTOR.ATTACH DUCT
AT ROOF CURB
SECURE HOOD TOCURB WITH CADMIUMPLATED STEEL SCREWSAT EACH CORNER
BIRD SCREEN ALLAROUND
FLASHING ANDCOUNTERFLASHING
NOTE:1. PROVIDE DATA SHEETS FOR CAULKING MATERIALS FOR REVIEW.FAILURE TO COMPLY PRIOR TO INSTALLATION OF ANY CAULKINGMATERIALS SHALL REQUIRE THE REMOVAL OF ALL PIPE CAULK MATERIALS.
OMIT PIPEINSULATION INSIDEPIPE SLEEVE
FIRE SAFINGMATERIAL
PROVIDE CAULKING-THICKNESS ANDMATERIAL PER U.L. 1479AND ASTM E814. (TYP)
PIPE
PROVIDE CHROME PLATED CASTBRASS ESCUTCHEON FOR FINISHEDAREAS. SIZE AS REQUIRED.
RATED WALL (SEE ARCH DRAWINGSFOR RATINGS AN LOCATIONS)
INSULATION (AS APPLICABLE)
SIZE SLEEVE AS REQUIRED TO MAINTAINTHE U.L. LISTING AND IN ACCORDANCEWITH SEALANT MFR REQT'S
NOTES:
1. CHEMICAL SHOT FEEDER SHALL BE 2'-0" AFF MIN.
2. SEE SPECIFICATIONS FOR FURTHER INFORMATION.COORDINATE WITH CHEMICAL TREATMENT PROVIDER.
3/4" PIPING ROUTED TOWATER LOOP. CONNECT TODISCHARGE SIDE OF PUMPS.
3/4" PIPING ROUTED TO WATERLOOP. CONNECT TO SUCTION SIDEOF PUMPS UPSTREAM OF AIRSEPARATOR.
CHECK VALVE
BALL VALVE(TYP.)
1/2" DRAINVALVE
FINISHED FLOOR
HOSE CONNECTION
CHEMICAL SHOT FEEDER
MANUFACTURER'S STANDARDSUPPORT LEG, BOLTED DOWNTO FLOOR (TYPICAL 3X)
5 FT
7
6 8 10
9 1110 12
1312 14 16
1614 17 19
864 532 2 1/21 1/21 1 1/4THRU 3/4
7 7
7 98
SIDE VIEW TRAPEZE HANGER FOR UPTO 1000 LB. UNIFORM LOAD
ADJUSTABLE CLEVIS HANGERTYPE 1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGERTYPE 43 - SEE SPECIFICATIONS
PROVIDE INSULATION SHIELD& INSERT FOR ALL PIPING (8" MIN.)
BAND
1-5/8" 12 GAUGECHANNEL OR2"x2"x1/4" ANGLE
1/2" DIA. HANGER RODSWITH 36" MAX. SPACINGON EACH CHANNEL
WELD
SADDLE
INSULATION SHIELDAT HANGER
PROVIDE HIGHCOMPRESSIVE STRENGTHINSULATION (9 PSF MIN.DENSITY) UNDERINSULATION SHIELD
INSULATION (VAPORBARRIER TYPE ISREQUIRED FOR LOWTEMPERATURE PIPE)
THREADED HANGER ROD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN.
FT.
FT.
1" MAX.
NOTES:SEE SPECIFICATIONS FORDETAILED HANGER REQUIREMENTS
1"x 1" CHAMFER
TO PROVIDE BONDROUGH UP FLOOR
EACH WAYNo. 4 @ 6"O.C.
TROWELFINISH
FIN FLR
ALL AROUND
LINING1" INTERIOR ACOUSTICAL
CEILING T-BARCEILING TILE
OR OTHER OBSTRUCTIONSTO CLEAR LIGHTS, PIPING3" OR HEIGHT REQUIRED
2'-0" (MIN)
RETURN GRILLEDEPTH SAME AS
TO DUCTWORKSUPPORT SIMILARLY
CEILING TILELAY-INRETURN GRILLE
DUCT SIZE SAMEAS TERMINALCONNECTION
22 GAUGE (MIN)SHEETMETALSKIN
NOTES:1.. ENSURE RA SOUND TRAP BOOTS ARE SEISMICALLY SUPPORTED.
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:47:
18 P
M
As indicated
M8.01
MECHANICALDETAILS
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: NOT TO SCALEM8.011 TYPICAL DIFFUSER/GRILLE INSTALLATION DETAIL
SCALE: NOT TO SCALEM8.012 TYPICAL DUCT TAKE OFF INSTALLATION DETAIL
SCALE: NOT TO SCALEM8.013 FIRE DAMPER INSTALLATION DETAIL
SCALE: NOT TO SCALEM8.016 ROUND DUCT BRANCH TAKE OFF DETAIL
SCALE: NOT TO SCALEM8.019 PUMP INERTIA BASE DETAIL
SCALE: NOT TO SCALEM8.017 SINGLE BOILER PIPING DETAIL
SCALE: NOT TO SCALEM8.015 HOT WATER AIR SEPARATOR AND EXPANSION TANK PIPING DETAIL
SCALE: NOT TO SCALEM8.018 INTAKE/EXHAUST HOOD INSTALLATION DETAIL
SCALE: NOT TO SCALEM8.014 MECHANICAL PIPE THRU RATED ASSEMBLY
SCALE: NOT TO SCALEM8.0110 CHEMICAL TREATMENT INSTALLATION DETAIL
SCALE: NOT TO SCALEM8.0111 TYPICAL PIPE SUPPORT DETAIL
SCALE: NOT TO SCALEM8.0112 CONCRETE PAD
SCALE: NOT TO SCALEM8.0113 SOUND TRAP INSTALLATION DETAIL
NOTES:
J"
ACCESSIBLE FOR CLEANING.
2. "RUNNING" TYPE TRAPS SHALL BE UNACCEPTABLE.
1. LOCATE TRAPS SO AS TO BE
PIPE FULL SIZE OFH"
UNIT CASING
UNIT DRAIN
SCREWED CAP
OPEN END (VENT)
3. DRAIN LINE SIZES AND TRAP DIMENSIONS SHALL BE PROVIDED IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.
OTHER OBSTACLE
DUCT SEALANT
DUCT CLAMP
FLEXIBLE DUCTWORK
SUSPENDED CEILING
DUCTWORK OR
SLAB
FLAT OVAL CONNECTION
SQUARE CEILINGDIFFUSER
INSULATEDSUPPLY AIRPLENUM
1. THIS DETAIL SHALL APPLY TO CEILING OUTLETS AND INLETS THAT ARE LOCATED BELOW DUCTWORK OROTHER OBSTACLES WHERE CLEARANCES ARE MINIMAL.2. THE SIZE OF THE SUPPLY AIR PLENUM SHALL BE A MINIMUM OF 1" LARGER IN HEIGHT AND WIDTH THAN THEFLAT OVAL DUCTWORK CONNECTION.3. THE SUPPLY AIR PLENUM IS REQUIRED TO BE INSULATED. THE PLENUM/DIFFUSER CONNECTION SHALL BESEALED WITH AN APPROVED DUCTWORK SEALANT.4. PROVIDE A ROUND TO FLAT OVAL TRANSITION SECTION OF DUCTWORK AS REQUIRED.5. THE FOLLOWING SCHEDULE SHALL BE USED FOR ROUND TO FLAT OVAL DUCTWORK SIZE EQUIVALENTS:
ROUND (INCHES) FLAT OVAL (HxW INCHES)3x11, 4x9, 5x84x15, 5x12, 6x116x15, 7x13, 8x11, 9x127x20, 8x17, 9x15, 10x139x20, 10x18, 11x17, 12x1510x23, 8x30, 6x4410x30, 12x26, 14x2212x32, 14x28, 16x2412x38, 14x32, 18x3014x38, 16x34, 18x3016x38, 18x34, 20x32
68101214161820222426
NOTES:
ROUND METAL BRANCH DUCTSAME SIZE AS VAV CONNECTIONUNLESS NOTED OTHERWISE
HANGER RODS ORSTRAPS UP TOSTRUCTURE
AIR TERMINAL UNIT
HOT WATER HEATING COIL
ACOUSTIC DUCT LININGDOWNSTREAM OF VAVBOX (MIN. 10'-0" RUN)
TAKE-OFF FITTING
SUPPLY AIR TRUNK
PROVIDE MIN. 5'-0"STAIGHT RUNDUCTWORKBEFORE FIRSTBRANCH TAKEOFF
4'-0"(MIN & MAX)STRAIGHT RUN OR ASDICTATED BY MANUFACTURER'SWRITTEN INSTALLATION INSTRUCTIONS.
AIR VENT
PETES PLUG (TYP)
TO DDC CONTROLLER
WATER COIL
DRAIN VALVE
TEMPERATURE GAUGE
BALL VALVE(TYP.)
STRAINERW/BLOWDOWNBALL VALVE
AUTOMATIC FLOW CONTROLVALVE WITH TEST PORTS
MOTORIZED FULLY MODULATINGCONTROL VALVE
PROVIDE BYPASSLINE WITH VALVE FORFLUSHING SYSTEM.
NOTE:
1. PROVIDE 2-WAY VALVES FOR ALL VARIABLE AIR VOLUME UNITSAND AIR HANDLER UNITS; EXCEPT FOR AHU-5, VAV-13, VAV-29AND VAV-33 WHICH SHALL BE PROVIDED WITH A 3-WAY VALVE.
B. FILL, VOID, OR CAVITY MATERIALC. STEEL RETAINING ANGLES
4A 4A
21B
34B
4C
4B4C 1AA
A Section A-A
1. WALL ASSEMBLYA. STUDSB. GYPSUM BOARD
2. DUCT
FIRESTOP SYSTEMA. PACKING MATERIAL
4.3. DUCT INSULATION
A Section A-A
A
2
3A
3A
3A1A
1B
1. WALL ASSEMBLYA. STUDSB. GYPSUM BOARD
2. PIPEFIRESTOP SYSTEM
A. PACKING MATERIAL3.
PROVIDE POWER EXHAUST WITH STAINLESSSTEEL FLUE PIPE UP AND OVER TO SIDE WALL.PROVIDE MANUFACTURER'S RECOMMENDEDSIDE WALL CAP. BOTTOM OF FLUETERMINATION AT EXTERIOR SHALL BE NOLOWER THAN 7'-0" AFF.
PROVIDEMANUFACTURER'SINTAKE CAPPING DEVICEABOVE FLASHING ANDALL STAINLESS STEELINTAKE DUCT
BOILER
1. INSTALL ALL DUCTWORK IN ACCORDANCE WITH THE INTERNATIONALFUEL/GAS CODE 2009 EDITION
EXTERIOR WALL
NOTE:
SEAL PENETRATIONS
TRAP
FLOOR SINK WITH1/2 GRATE / FULLGRATE
TIE ROD
CLEVIS HANGER
PROVIDE TRAPGUARD DRAIN INSERT
1. SEE PLUMBING SCHEDULE FOR FLOOR SINK REQUIREMENTS
NOTE:
SUPPLY DUCT
COILSFAN
FAN ACCESS PANEL
1. PROVIDE FULL SIZE PRIMARY CONDENSATE DRAIN WITH TRAP AND VENT. SECONDARY DRAIN SHALLBE ROUTED TO EMERGENCY DRAIN PAN. ROUTE DRAIN LINE TO NEW HUB DRAIN AS NOTED ON PLANS.
2. EMERGENCY DRAIN PAN SHALL BE LOCATED UNDER COIL SECTION ONLY. DRAIN PAN SHALL BE SIZEDTO NOT INTERFERE WITH FAN ACCESS PANEL.
24 GAUGE GALV. STEEL EMERGENCY DRAIN PAN, DRAIN PANSHALL BE SIZED AND INSTALLED AS CLOSE TO FAN ACCESSDOOR AS POSSIBLE AND 3" LARGER THAN UNIT ON REMAINING 3SIDES. DRAIN PAN SHALL BE 2" DEEP.
FLOAT SWITCH WIREDINTO CONTROL CIRCUIT
DRAIN PAN DRAIN LINE WITHBALL VALVE. DRAIN LINE SHALLTERMINATE W/ A CAPPED 3/4"MALE HOSE END FITTING. DRAINPAN SHALL BE INDEPENDENTLYSUPPORTED FROM UNIT.
FLEXIBLE CONNECTIONTYPICAL
SECURE TOSTRUCTURE ABOVE
THREADED HANGER RODS WITH VIBRATION ISOLATORS.PROVIDE SUPPORTING STEEL AS REQUIRED. DO NOT USECLAMPS. SIZE AND NUMBER OF RODS SHALL MATCH HOLESON TOP OF UNIT.
NOTES:
NOTE:
DRAIN VALVE
TO DDC CONTROLLER
WATER COIL
AIR VENT
REDUCERS AS REQ'D (TYPICAL)
ISOLATION VALVE(TYP.)
MOTORIZED MODULATINGCONTROL VALVE (BYCONTROLS CONTRACTOR)
CIRCUIT SETTER, B&G OR EQ(TYPICAL)
FITTING WITH PRESSURE/TEMPERATURE TEST PLUG(TYPICAL)
STRAINERW/BLOWDOWNVALVE & CAP
1. PROVIDE 2-WAY VALVES FOR ALL AIR HANDLING UNITS; EXCEPTAHU-3 AND AHU-5 WHICH SHALL BE PROVIDED WITH A 3-WAY VALVE.
PROVIDE BYPASSLINE WITH VALVEFOR FLUSHINGSYSTEM.
1" OPER.CLEARANCE.
TO SYSTEM
FROM SYSTEM
PIPE HANGERS(SPRING &NEOPRENE TYPE)
ISOLATION VALVETRI-4 THERMOFLO INIDICATOROR APPROVED EQUAL
DOUBLE SPHEREFLEXIBLE CONNECTOR
CHECK VALVE
9" INDUSTRIAL THERMOMETERW/ 3/4" NPT COPPER WELL
1/4" O.D. COPPER TUBINGW/COMP. FITTINGS
SUCTION DIFFUSER WITHSTRAINER
FIELD FABRICATED SUPPORT LEG
DRAIN: TERMINATE NEAR F.D.
CONCRETE INERTIA VIBRATIONPUMP BASE W/ SPRING ISOLATORS
6" THICK CONCRETE HOUSEKEEPING PAD W/ CHAMFEREDEDGES TO EXTEND 6" PAST ALLSIDES OF PUMP BASE.
FINISH FLOOR
GROUTABLE FABRICATEDSTEEL BASE PLATE
BASE MOUNTED ENDSUCTION PUMP (LONGCOUPLED)
OSHA/ANSI COUPLERGUARD
MULTIPORT PRESSUREINDICATOR (4-PORT)
ISOLATION VAVE(BUTTERFLY VALVE TYP.)
DOUBLE SPHERE FLEXIBLECONNECTOR
CHECK VALVE
FROM SYSTEMTO SYSTEM
BI-METAL THERMOMETERW/ BRASS THERMOWELL,TRERICE OR EQUAL
PRESSURE GAUGE, TRERICEOR EQ. FLOW COND. CORP.MULTIPORT PRESSUREINDICATOR (3-PORT)
WYE-STRAINER WITHBLOWDOWN GATE VALVE
PUMP BASE SUPPORT BOLTEDTO PUMP & BASEPLATE. BOLTBASEPLATE TO PAD.
BASE ELBOW SUPPORT WELDEDTO ELBOW & BASEPLATE.BOLT BASEPLATE TO PAD.(TYPICAL)
REDUCING ELBOW
CONCRETE HOUSEKEEPINGW/ CHAMFERED EDGES PAD SIZEDTO BE TO WEIGH 3X WEIGHT OFPUMP-MOTOR VIBRATIONFOR VIBRATION ISOLATION.COORDINATE WITH GC FORREBAR & DOWELLINGREQUIREMENTS TO TIE INTOFLOOR
1/4" O.D. COPPER TUBINGW/ COMP. FITTINGS (TYPICAL)
BALL ISOLATION VALVE(TYPICAL)
FINISH FLOOR
VERTICAL IN-LINE PUMP
RUBBER SPHERE PUMPCONNECTOR W/STOP LINK CABLEFLEX HOSE CO. FLEXSORBER NNSOR EQ (TYPICAL)
PIPE HANGERS (SPRING& NEOPRENE TYPE)
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:47:
21 P
M
NOT TO SCALE
M8.02
MECHANICALDETAILS
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: NOT TO SCALEM8.022 CONDENSATE DRAIN TRAP INSTALLATION DETAIL
SCALE: NOT TO SCALEM8.025 CEILING DIFFUSER/GRILLE & DUCT OBSTRUCTION DETAIL
SCALE: NOT TO SCALEM8.021 TYPICAL VAV INSTALLATION DETAIL
SCALE: NOT TO SCALEM8.026 HOT WATER COIL PIPING DETAIL
SCALE: NOT TO SCALEM8.024 WALL DUCT PENETRATION DETAIL
SCALE: NOT TO SCALEM8.028 WALL PIPE PENETRATION DETAIL
SCALE: NOT TO SCALEM8.029 BOILER AIR VENT / INTAKE INSTALLATION DETAIL
SCALE: NOT TO SCALEM8.023 FLOOR SINK DETAIL
SCALE: NOT TO SCALEM8.0210 FAN COIL UNIT INSTALLATION DETAIL
SCALE: NOT TO SCALEM8.027 CHILLED WATER COIL PIPING DETAIL
SCALE: NOT TO SCALEM8.0211 END SUCTION PUMP DETAIL
SCALE: NOT TO SCALEM8.0212 VERTICAL INLINE PUMP DETAIL
T
T P
PCHWS
CHWR
M
TS
VAV POINTS LISTAHU POINTS LIST
LEGEND SEQUENCE OF OPERATION: VARIABLE AIR VOLUME (VAV)TERMINAL UNITS
SEQUENCE OF OPERATION: AIR HANDLING UNITS
VAV BOX WITH HOT WATER REHEAT
A DEDICATED UNIT MOUNTED VAV CONTROLLER WILL CONTROL EACH UNIT.
UNOCCUPIED MODE
NIGHT SET-BACK OPERATION:
IN UNOCCUPIED MODE THE PRIMARY AIR DAMPER WILL REMAIN CLOSED. UPON A DROP IN SPACETEMPERATURE BELOW NIGHT LOW LIMIT SETPOINT (ADJ.), THE VAV CONTROLLER WILL REQUEST AHU FANOPERATION. UPON PROOF OF AHU OPERATION, VAV HEATING SHALL BE ENABLED AND VAV BOX PRIMARY AIRDAMPER SHALL MODULATE OPEN TO MAINTAIN HEATING CFM SETPOINT (ADJ.) AND HOT WATER CONTROL VALVESHALL AUTOMATICALLY ADJUST AS REQUIRED TO MAINTAIN THE SPACE NIGHT LOW LIMIT SETPOINT. ON A RISEIN SPACE TEMPERATURE, THE REVERSE WILL OCCUR
AFTER HOURS OPERATION:
EACH VAV ZONE MAY BE OVERRIDDEN INTO OCCUPIED MODE. DURING AFTER HOURS OPERATION, VAV BOXSHALL MAINTAIN OCCUPIED HEATING AND COOLING SETPOINTS.
OCCUPIED MODE
IN OCCUPIED MODE, THE PRIMARY AIR DAMPER WILL BE ENABLED TO MODULATE TO MAINTAIN MINIMUMCOOLING CFM SETPOINT (ADJ.). WHEN THE SPACE TEMPERATURE RISES ABOVE THE COOLING SETPOINT (ADJ.),THE PRIMARY AIR DAMPER WILL MODULATE OPEN TOWARDS MAXIMUM AIRFLOW SETPOINT (ADJ.). THECONTROLLER WILL COMPARE THE COOLING SETPOINT WITH THE SPACE TEMPERATURE AND DETERMINE THEDESIRED AIRFLOW QUANTITY BETWEEN MAXIMUM AND MINIMUM AIRFLOW SETTINGS. ON A FALL IN SPACETEMPERATURE, THE PRIMARY AIR DAMPER WILL MODULATE CLOSED TO MAINTAIN MINIMUM COOLING CFMSETPOINT. IF SPACE TEMPERATURE CONTINUES TO FALL BELOW SPACE HEATING SETPOINT (ADJ.), THEPRIMARY AIR DAMPER SHALL MODULATE TO MAINTAIN HEATING CFM SETPOINT (ADJ.) AND THE ELECTRIC HEATSTAGES WILL BE INDEXED AS REQUIRED TO MAINTAIN HEATING SETPOINT. ON A RISE IN SPACE TEMPERATURE,THE REVERSE WILL OCCUR
VAV AIR HANDLING UNIT
UNIT SHALL HAVE A UNIT MOUNTED MICROPROCESSOR BASED PROGRAMMABLE CONTROLLER CAPABLE OFSTANDALONE OPERATION OR AS DIRECTED BY THE ENERGY MANAGEMENT SYSTEM (EMS). THE UNIT MOUNTEDCONTROLLER SHALL MONITOR AND CONTROL THE UNIT. THE CONTROLLER SHALL HAVE A HUMAN INTERFACEPANEL CONSISTING OF 2-LINE LCD DISPLAY SCREEN AND A MULTI-BUTTON KEYPAD FOR MONITORING, SETTING,EDITING, AND CONTROLLING THE UNIT.
SUPPLY FAN CONTROL (GENERAL) : THE SUPPLY FAN WILL BE CONTROLLED THROUGH A HAND-OFF-AUTO(H-O-A) SWITCH INTEGRAL WITH THE VARIABLE FREQUENCY DRIVE (VFD). WHEN THE SWITCH IS IN THE"AUTO" POSITION, THE SUPPLY FAN WILL BE STARTED AND STOPPED AND FAN SPEED WILL BE CONTROLLEDTHROUGH THE EMS. WHEN THE SWITCH IS IN THE "HAND" POSITION, THE SUPPLY FAN WILL RUN AND THEFAN SPEED WILL BE CONTROLLED THROUGH A MANUAL SPEED ADJUSTMENT INTEGRAL TO THE VFD. WHENTHE SWITCH IS IN THE "OFF" POSITION, THE SUPPLY FAN AND DRIVE WILL REMAIN OFF. WHEN THE STARTINGCIRCUIT IS ACTIVATED BY THE EMS OR BY PLACING THE SELECTOR SWITCH IN "HAND" POSITION, THE VFDWILL START UNLOADED AND WILL RAMP UP TO SPEED AS PROGRAMMED INTO THE VFD'S SAFETY CIRCUIT.
UNOCCUPIED MODE : IN UNOCCUPIED MODE, UNIT SUPPLY AND EXHAUST FANS WILL BE INDEXED OFF AND WILLREMAIN OFF UNTIL THE START OF AN OCCUPIED CYCLE OR A CALL FROM THE VAV ZONES FOR NIGHT SET-UPOR SET-BACK OPERATION. THE OUTSIDE AIR CONTROL DAMPER WILL REMAIN CLOSED TO OUTSIDE AIR DURINGUNOCCUPIED, NIGHT SET-UP AND SET-BACK OPERATION. DURING NIGHT SET-BACK OPERATION THEDISCHARGE AIR TEMPERATURE SHALL BE SET AT 60 DEGREES F (ADJ.). ALL FURTHER SPACE HEATING SHALLBE ACCOMPLISHED LOCALLY WITH THE VAV BOX REHEAT. UPON A CALL FOR NIGHT SET-UP OPERATION,DISCHARGE AIR TEMPERATURE CONTROL SHALL BE AS DURING OCCUPIED MODE.
AFTER HOURS OPERATION : UPON A CALL FOR AFTER HOURS OPERATION FROM VAV ZONES, AHU SHALLOPERATE IN THE OCCUPIED MODE FOR 4 HOURS.
OCCUPIED MODE : IN OCCUPIED MODE, THE SUPPLY FAN WILL BE ENABLED TO RUN THROUGH THE VARIABLEFREQUENCY DRIVE (VFD); WILL RUN CONTINUOUSLY AND; THE OUTSIDE AIR CONTROL DAMPER WILL BE ENABLED.
OUTSIDE AIR DAMPER CONTROL : OUTSIDE AIRFLOW SHALL BE MONITORED BY THE FACTORY MOUNTED AIRFLOWMONITORING STATION. IN OCCUPIED MODE, THE OUTSIDE AIR DAMPER WILL BE MODULATED TO MAINTAINRETURN AIR CO2 SETPOINT AS SENSED BY THE SPACE MOUNTED CO2 MONITOR. WHEN THE CO2 SENSORSENSES A CO2 CONCENTRATION OF 400 PPM, THE OUTDOOR AIR DAMPER SHALL BE AT THE MINIMUMPOSITION. AS CO2 CONCENTRATION LEVELS RISE, THE DAMPER SHALL MODULATE OPEN. THE DAMPER SHALLBE AT THE FULL OPEN POSITION WHEN CO2 LEVELS EQUAL 1100 PPM. MINIMUM OUTSIDE AIR DAMPERPOSITION SHALL BE ESTABLISHED DURING SYSTEM AIR BALANCE.
DISCHARGE AIR TEMPERATURE CONTROL (RESET PROGRAM) : DISCHARGE AIR TEMPERATURE FROM THE UNIT WILLBE RESET IN ACCORDANCE WITH THE RESET SCHEDULE. THE CONTROLLER WILL INDEX STAGES OF DXCOOLING TO MAINTAIN THE TEMPERATURE OF THE AIR LEAVING THE COIL AT THE SETPOINT DETERMINED BYTHE RESET SCHEDULE. DISCHARGE AIR TEMPERATURE SETPOINT WILL VARY BETWEEN A MINIMUM OF 50° F(ADJ.) AND A MAXIMUM OF 60° F (ADJ.). RESET OF DISCHARGE AIR SETPOINT SHALL BE BASED UPONCOOLING DEMAND FROM VAV ZONES ASSOCIATED WITH EACH AHU.
SUPPLY DUCT STATIC PRESSURE CONTROL : THE SUPPLY FAN VFD WILL BE MODULATED TO MAINTAIN THESUPPLY DUCT STATIC PRESSURE SETPOINT AS SENSED BY DUCT STATIC PRESSURE SENSOR LOCATEDDOWNSTREAM IN THE SUPPLY MAIN. UPON STARTUP, THE VFD WILL BE IN THE "UNLOADED" POSITION. THEVFD SPEED WILL BE ADJUSTED THROUGH A CONTROL LOOP IN RESPONSE TO THE DUCT STATIC PRESSURESETPOINT. AS THE DUCT STATIC PRESSURE RISES ABOVE SETPOINT, THE FAN SPEED WILL BE REDUCEDTHROUGH THE VFD SPEED SIGNAL CONTROLLER DOWN TO THE PROGRAMMED MINIMUM SPEED (ADJ.). AS THESTATIC PRESSURE INCREASES ABOVE THE ACTIVE SETPOINT, THE FAN SPEED WILL BE INCREASED. DUCTSTATIC PRESSURE SETPOINT SHALL RESET BETWEEN AN ADJUSTABLE MINIMUM AND MAXIMUM SETPOINT. RESETOF STATIC PRESSURE SETPOINT SHALL BE BASED UPON AIRFLOW DEMANDS FROM VAV ZONES. IF THE FANSPEED IS AT 100 PERCENT AND THE SUPPLY DUCT STATIC PRESSURE IS STILL BELOW SETPOINT, THEDISCHARGE AIR TEMPERATURE RESET CONTROL LOOP WILL BE OVERRIDDEN TO DECREASE THE ACTIVEDISCHARGE AIR TEMPERATURE SETOINT UNTIL THE STATIC PRESSURE SETPOINT IS SATISFIED.
MORNING WARM-UP CYCLE : IN THE MORNING WARM-UP CYCLE, THE AHU SUPPLY FAN SHALL START, THEOUTSIDE AIR DAMPERS WILL REMAIN CLOSED, AND UNIT COOLING SHALL BE DISABLED. ALL BUILDING HEATINGWILL BE ACCOMPLISHED LOCALLLY AT THE REHEAT VAV TERMINAL UNITS. MORNING WARM-UP CYCLE SHALLBE INITIATATED FROM VAV ZONES AS REQUIRED. AN ADJUSTABLE MINIMUM NUMBER OF VAV ZONES SHALLREQUIRE MORNING WARM-UP BEFORE AHU SHALL BE STARTED.
MORNING COOL-DOWN CYCLE : IN THE MORNING COOL-DOWN CYCLE, THE AHU SUPPLY FAN START, OUTSIDEAIR DAMPERS WILL REMAIN CLOSED, AND UNIT COOLING SHALL BE ENABLED. MORNING COOL-DOWN CYCLESHALL BE INITIATATED FROM VAV ZONES AS REQUIRED. AN ADJUSTABLE MINIMUM NUMBER OF VAV ZONESSHALL REQUIRE MORNING COOL-DOWN BEFORE AHU SHALL BE STARTED. DISCHARGE AIR TEMPERATURECONTROL SHALL BE AS IN OCCUPIED MODE.
SENSORS: A DRY CONTACT FROM THE VFD CONTROLLER WILL PROVIDE FAN STATUS FOR UNIT SUPPLY FAN.AN ALARM WILL BE INITIATED WHENEVER THE FAN COMMAND AND STATUS DO NOT MATCH. A FAULT CONTACTWILL BE INPUT TO THE CONTROLLER TO INDICATE AN INTERNAL PROBLEM WITH THE SUPPLY FAN VFD. ADUCT TEMPERATURE SENSOR DOWNSTREAM OF THE COOLING COIL SECTION WILL MONITOR SUPPLY AIRTEMPERATURE FROM THE UNIT. A DUCT TEMPERATURE SENSOR IN THE MIXED AIR STREAM WILL MONITOR THEMIXED AIR CONDITION UPSTREAM OF THE COIL.
SAFETIES: UPON A SIGNAL FROM THE BUILDING FIRE ALARM PANEL, THE SUPPLY FAN WILL BE DE-ENERGIZED(HARDWIRED INTERLOCK), THE OUTSIDE AIR DAMPER WILL BE CLOSED AND AN ALARM WILL BE DISPLAYED ATTHE OPERATOR'S WORKSTATION.
RETURNAHU
AIR
CHILLED WATER
MIXINGBOX
COIL
MM
FILTER
VFD
FANC
EMCS
OUTSIDE
P
M
SUPPLYAHU
EMCS
SPACE
T
ENERGY MANAGEMENT CONTROL SYSTEM UNIT CONTROLLER
MOTORIZED ACTUATOR
EMCS
M
TEMPERATURE SENSOR
CURRENT SWITCHC
T
T
VAVBOX
FLOW RING SENSOR(BY VAV BOX MANUFACTURER)
VARIABLE FREQUENCY DRIVEVFD
HOT WATER REHEAT COIL
CO2 SENSORO
T
LOCATE 2/3OF THE WAYDOWN THELENGTH OFDUCT.
SPACE
O
FIRE ALARMPANEL
PRESSURE SENSORP
STATIONAIR MONITORING
AI-1 AIR FLOW SENSORAI-2 SPACE TEMP SENSORAI-3 DAMPER POSITIONAI-4 SPACE CO2 SENSOR (SEE DRAWINGS FOR LOCATIONS)AI-5 MINIMUM CFMAI-6 MAXIMUM CFM
AO-1 DAMPER CONTROLDO-1 ELECTRIC HEAT (AHU-2)
DI-1 AHU FAN STATUS (CURRENT)
AI-2 DISCHARGE AIR TEMPAI-3 DUCT STATIC PRESSURE
DI-2 FIRE ALARM PANEL CONTACT
AI-1 MIXED AIR TEMP
AO-5 VARIABLE FREQUENCY DRIVE
DO-1 START/STOP AHU
AO-1 DISCHARGE STATIC PRESSURE SETPOINTAO-2 SUPPLY AIR TEMP SETPOINTAO-3 OA MOTORIZED DAMPERAO-4 RA MOTORIZED DAMPER
AI-4 OUTDOOR AIR FLOWRATE (CFM)
FREEZE STATF
LOW / HIGH LIMIT STATIC PRESSURE LIMIT SWITCHPL
F PL PL
ON A FALL IN CHILLED WATER COIL DISCHARGE AIR TEMPERATURE BELOW THE LIMIT SETPOINT OF OF LOWTEMPERATURE FREEZE STAT (38°F ADJUSTABLE). FREEZE STAT SHALL ALARM EMCS, PRE-ENERGIZE THESUPPLY AND RETURN FANS, CLOSE OUTSIDE AIR DAMPERS, CLOSE RELIEF AIR DAMPER AND OPEN CHILLEDWATER VALVE.
SUPPLY AIR HIGH LIMIT STATIC PRESSURE SWITCH AND RETURN AIR HIGH LIMIT STATIC PRESSURE SWITCHSHALL OVERRIDE THE CONTROL SIGNAL WHEN THE STATIC PRESSURE EXCEEDS ITS SETTING AND DE-ENERGIZES THE SUPPLY AND RETURN FANS AND ALARM TO THE EMCS. RETURN AIR LOW LIMIT STATICPRESSURE SWITCH AND SUPPLY AIR LOW LIMIT STATIC PRESSURE SWITCH SHALL OVERRIDE THE CONTROLSIGNAL WHEN STATIC PRESSURE EXCEEDS ITS (NEGATIVE PRESSURE) SETTING AND DE-ENERGIZE THESUPPLY AND RETURN FANS AND ALARM THE EMCS.
SINGLE ZONE VAV AHU:
ALL VAV AHU SEQUENCES OF OPERATION LISTED ABOVE SHALL ALSO APPLY TO THE SINGLE ZONE VAV AHU.TEMPERATURE IN THE ZONE SHALL BE MAINTAINED BY VARYING THE QUANTITY OF AIR DELIVERED TO THEZONE, RATHER THAN BY VARYING THE DISCHARGE AIR TEMPERATURE. CHILLED WATER AND HEATING HOTWATER CONTROL VALVES SHALL MODULATE TO MAINTAIN A CONSTANT DISCHARGE AIR TEMPERATURE (ADJ).THE ZONE TEMPERATURE (OR TEMPERATURES WHERE MULTIPLE TEMPERATURE SENSORS EXIST) SHALL BEINPUT TO THE BAS TO DETERMINE IF THE UNIT IS TO BE INDEXED INTO COOLING OR HEATING MODE AND TODETERMINE THE VOLUME OF AIR THAT IS TO BE DELIVERED TO THE ZONE. ON A DECREASE IN LOAD IN THEZONE, THE AHU SHALL REDUCE THE VOLUME OF AIR BEING DELIVERED TO THE ZONE TO SATISFY THE ZONETEMPERATURE SETPOINT. ON AN INCREASE IN LOAD IN THE ZONE, THE AHU SHALL INCREASE THE VOLUME OFAIR BEING DELIVERED TO THE ZONE TO SATISFY THE ZONE TEMPERATURE SETPOINT.
FLOW METERING STATION
ENERGY MANAGEMENT CONTROL SYSTEM UNIT CONTROLLER
MOTORIZED ACTUATOR
EMCS
M
TEMPERATURE SENSOR
SMOKE DETECTOR (DIV. 26)
FLOW SWITCH
PRESSURE SENSOR
CURRENT SWITCHC
S
P
T
LEGEND
VARIABLE FREQUENCY DRIVEVFD
3-WAY CONTROL VALVEM
CHWS
CHWR
HEATING
SBOX
MIXINGFILTER
P
COIL
P
M
COOLINGCOIL
FFANC
M
EMCS
AHUSUPPLYT
FAN C AHURETURN
S
M
P
P P
HWR
HWS
P
M
EMCS
M
SPACE
T
VAVBOX
FLOW RING SENSOR(BY VAV BOX MANUFACTURER)
REHEATCOIL
M
STATIONAIR MONITORING
VFD
VFD
CO2
STATIONAIR MONITORING
2-WAY CONTROL VALVEM
CARBON DIOXIDE SENSORC02
VFD VARIABLE FREQUENCY DRIVE
PL PL AF
AF
PL LOW / HIGH LIMIT STATIC PRESSURE LIMIT SWITCH
FLOW SWITCHF
FANCHW
WH
T
UNITCONTROLLER
EMSBUILDING
N.C.
CHWS
CHWR
HWR
HWS
N.C.
T
(BY SIEMENS)
T
EMS
SPACETSTAT
ENERGY MANAGEMENT SYSTEM
TEMPERATURE SENSOR
CONTROL VALVE
SEQUENCE OF OPERATION: FAN COIL UNIT AND EXHAUST FANS
LEGEND (THIS DETAIL)
FAN COIL:OCCUPIED/UNOCCUPIED MODE CONTROLTHE OCCUPIED MODE WILL BE SCHEDULED OR MANUALLY AT OWNERS WORK STATION.
OCCUPIED MODEFAN SHALL RUN CONTINUOUSLY. THE FAN SPEED IS SET BY THE DDC SYSTEM. NORMALLY THE FAN RUNS ON MEDIUM SPEED. IF THE ROOM TEMPERATURE IS MORE THANTWO DEGREES FROM SETPOINT, THE FAN SPEED WILL BE SET TO HIGH.
SPACE TEMPERATURE SETPOINT (ADJ.) SHALL BE CONTROLLED BY A SPACE MOUNTED TEMPERATURE SENSOR (LOCATION AS SHOWN ON FLOOR PLANS). UPON RAISE INTEMPERATURE ABOVE THE SPACE SETPOINT, THE TWO-WAY CHILLED WATER CONTROL VALVE SHALL MODULATE TO LOWER SPACE TEMPERATURE TO WITHIN SPACETEMPERATURE TOLERANCE. UPON A DROP IN TEMPERATURE BELOW THE SPACE TEMPERATURE, THE TWO-WAY HOT WATER CONTROL VALVE SHALL MODULATE TO RAISESPACE TEMPERATURE TO WITHIN SPACE TEMPERATURE TOLERANCE.
UPON RECEIVING A DISABLE SIGNAL FROM THE BUILDING EMS SYSTEM, THE FAN SHALL BE DE-ENERGIZED, BOTH CONTROL VALVES SHALL CLOSE AND A DISABLE SIGNALSHALL BE SENT TO THE FAN COIL.
SAFETIES:UPON DETECTION OF WATER FROM FLOAT SWITCH IN THE SECONDARY DRAIN LINE THE UNIT SHALL SIGNAL AN ALARM TO THE DDC SYSTEM AND SHUT UNIT OFF.
SA TO ROOM SIDECEILING DIFFUSERS
RA FROM ROOM SIDE FILTERRETURN GRILLES
EXHAUST FANS: EXHAUST FANS SHALL BE CONTROLLED AS INDICATED ON EQUIPMENT SCHEDULE. FANS INDICATED TO BE CONTROLLED BY THE BAS SHALL BESCHEDULED TO BE ON OR OFF. COORDINATE WITH OWNER FOR SCHEDULE PREFERENCE.
GENERAL NOTES:
1.
2.
THE WORK FOR THE HVAC CONTROLS SYSTEM WILL BE PERFORMED BY SIEMENS BUILDINGTECHNOLOGIES UNDER DIRECT CONTRACT WITH COASTAL CAROLINA UNIVERSITY.
SEE SPECIFICATION SECTION 23 09 23 FOR DELINEATION OF WORK.
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:47:
22 P
M
12" = 1'-0"
M9.01
MECHANICALCONTROLSDIAGRAMS
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SETSCALE: NOT TO SCALEM9.012 NEW AHU SCHEMATIC DIAGRAM AND SEQUENCE OF OPERATION
SCALE: NOT TO SCALEM9.013 VARIABLE AIR VOLUME AHU WITH ENERGY RECOVERY FLOW DIAGRAM
SCALE: NOT TO SCALEM9.011 FAN COIL SYSTEM CONTROL DIAGRAM
3/4"
-DR
N
3"-H
WS
M
M M M M
M
LOAD
0-100
AFV
0-100
HDSSHDSS
INSIDEOUTSIDE
BY MCBY PC
SEE PLUMBING PLANS1-1/2"-DCW
B&GMODEL 7(SET @ 45PSIG)
1"-NC BYPASS
0-100HIGHCAPACITYAIR VENT
0-100
LOW CAPACITYAIR VENT
HDSS
B&GMODEL 1170-75(SET @ 75 PSIG)
FLEX-HOSE CO.MODEL NNS(TYP THIS DWG)
3/4"-DRN
SS FD
3"-H
WS
HWP-1HOT WATER PUMP(OPERATING)
0-100
TDV
CMI
PSD
3"-H
WS
SS
PIPE ALL PSD DRAINS TOFLOOR DRAIN LOCATED ATEACH PUMP (TYPICAL)
FD
3"-H
WS
HWP-2HOT WATER PUMP(STANDBY)
0-100
CMI
PSD
3"-H
WS
SS FD
3/4"
-CH
F
HOT WATERSHOT FEEDER(5 GALLONS)
HSF-1
BY MCBY PC
4" COMBUSTIONAIR INTAKE (TYP)
4" FLUEGASEXHAUST
0-100
0-100
1-1/
2"-D
RN
1-1/
2"-
DR
N
BY BOILERMANUFACTURER.
AFV
12"(MAX)
3/4"
-DR
N
EXPANSION TANKEXT-2
3"-HWS
2-1/2"-G
(PROVIDE MIN. 10' LENGTHBETWEEN PRV & BOILER-TYP)
3"-HWR
3"-H
WR
3"-H
WS
3"-HWR
BOILERCIRCULATINGPUMP BP-2
BOILERCONTROLPANEL
BCP-2
3"-HWS
BOILER(FUTURE)
B-2
BOILERCIRCULATINGPUMP BP-1
NORTH WALL INSIDEOUTSIDE
4" FLUEGASEXHAUST
SLEEVE &LINK SEAL
4" COMBUSTIONAIR INTAKE (TYP)
3/4"
-DR
N
EARTHQUAKE VALVE
BY BOILERMANUFACTURER
CMI
BOILERCONTROL BYCMI. PROVIDEBACNET I/FACETO BMS
OUTSIDE ABV GRADE
OA TEMPRESET
BOILER EMERGENCYSHUTDOWN SWITCH
BOILERCONTROLPANEL
BCP-1
1"-D
RN
1-1/
2"-
DR
N
1-1/
2"-D
RN
2-1/2"-G
3"-H
WR
3"-H
WS
BOILER(LEAD)
B-1
3"-HWS
3/4"-CHF
3"-HWS
INSIDE
OUTSIDE BELOWGRADE
OUTSIDE
IN-LINE AIRSEPARATOR
AS-2
NATURAL GAS DISTRIBUTION
3"-G
FUTURECONNECTION
FUTURECONNECTION
POINT
POINT
PIPRV
PI
AAVAAV
RV
PI PI
TE
RV
FSTIPI
TIPI
PRV
RV
PI TI FS
TIPI
PRV
ES
PRV
TT
VFD---
VFD---
SIEMENSCONTROLLER
LOAD
LOAD
LOAD
4
DPS
3
1
2
1
1
1-1/
2" C
HW
S
3/4"
DR
N
1-1/2" DCW
1" NC BYPASS
6" C
HW
S
6" C
HW
S
1" D
RN
CWP-1SECONDARYCHILLEDWATER PUMP(OPERATING)SS
PSD
FD
3/4"
DR
N
0-100
B&GMODEL 7(SET @ 45PSIG)
B&GMODEL 1170-75(SET @ 75 PSIG)
HIGHCAPACITYAIR VENT
SEE PLUMBING PLANS
HDSS
M M
LOW CAPACITYAIR VENT
EXT-1EXPANSION TANK0-100
3/4"
DR
N
6" CHWR
6" CHWS6" CHWS
6"CHWS
LOAD
BY PC BY MC
CWP-2SECONDARYCHILLEDWATER PUMP(STANDBY)
6" C
HW
S
6" C
HW
S
PSD
FD
CMIVFD---
SS
CMIVFD---
0-100
0-100
3/4" DRN
1
CWAP-1
BTU METER
1/2" CIRCUIT SETTER BYPASSTO ALLOW MINIMUM FLOW ATALL TIMES TO ALLOW TT3TEMPERATURE READING
CHWRCAMPUSLOOP(56°F)
T IN=42ºF
T OUT=54ºF
OUTSIDE INSIDE
6" CHWBYPASS
CONTROLS TOLOCAL DDCCONTROLLER
PIPE ALL INDICATEDDRAINS TO HUB DRAIN,SEE PLANS (TYP).
CONTROL VALVE V-1
CIRCUITSETTERBALANCINGVALVE
4
LOAD
4 52
1
SIEMENSCONTROLLER
BUILDING LOOP DP TOCENTRAL PLANT FORMAIN DISTRIBUTIONPUMP VFD CONTROL
6
SS FD
3/4"
CH
F
CHILLED WATERSHOT FEEDER(5 GALLONS)
CSF-1
1
3/4" CHF
NORMALLYCLOSED BY-PASS
CHWSCAMPUSLOOP(40°F)
TT1
FE TT2
TT3
PI PI
PI
PIPRV
DPS
DPS
7
AAV
RV
AAV
KEY NOTES:
PROVIDE INSULATION AND JACKETING ON ALL EQUIPMENT.
PIPE ALL INDICATED DRAINS TO HUB DRAIN.
BYPASS WITH PRESSURE RELIEF VALVE SET TO 35% OFMAXIMUM PUMP FLOW (ADJ.).
CONTROLS CONTRACTOR SHALL PROVIDE DIFFERENTIALPRESSURE TRANSMITTER IN SYSTEM DISTRIBUTION PIPINGAPPROXIMATELY 2/3 DISTANCE OF LONGEST PIPE RUN.
PIPE ALL PSD DRAINS TO FLOOR DRAIN LOCATED AT EACHPUMP (TYP).
FLEX-HOSE CO. MODEL NNS (TYP THIS DRAWING).
3-WAY VALVE AT LAST AIR HANDLING UNIT FOR PUMPBYPASS FLOW, CHILLED WATER AT END OF LOOP, ANDCHEMICAL TREATMENT IN ALL PARTS OF SYSTEM.
1
2
3
4
5
6
7
GENERAL NOTES:
1.
2.
THE WORK FOR THE HVAC CONTROLS SYSTEM WILL BEPERFORMED BY SIEMENS BUILDING TECHNOLOGIES UNDERDIRECT CONTRACT WITH COASTAL CAROLINA UNIVERSITY.
SEE SPECIFICATION SECTION 23 09 23 FOR DELINEATION OFWORK.
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:47:
24 P
M
12" = 1'-0"
M9.02
MECHANICALCONTROLSDIAGRAMS
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: NOT TO SCALEM9.021 HEATING HOT WATER AND GAS SYSTEM FLOW DIAGRAM
SCALE: 12" = 1'-0"M9.022 CHILLED WATER SYSTEM FLOW DIAGRAM
DN
T
T
1H.5
1H
1G.5
1G
1F.5
1F
1E.5
1E
1D
1C
0.5 1 1.5 2.3 3
??
VAV-13
CORRIDORC-103
STUDY ROOM/LOUNGE
A107CORR.C-105
STOR.A-110B
350 CFMA
470 CFMA
470 CFMA
470 CFMA
24"x
14"
14"x
12"
1880 CFMB
125 CFMA
3
UP
38"x14"
200 CFMA
8"Ø SA UP
300 CFMTG3
16"x10"
TYP 4. CENTEREDBETWEEN RAMP ANDHANDRAIL, SEEARCHITECTURAL
12"x6"
24"x
14"
24"x14"
470 CFMA
18"x
12"
10"x10"
10"x10"
10"x10"
10"x10"
24"x12"
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:47:
27 P
M
1/8" = 1'-0"
M10.01
EXPANSION -HVAC PLAN -ALTERNATENO. 1
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: 1/8" = 1'-0"M10.011 EXPANSION - FIRST FLOOR HVAC PLAN - ALTERNATE NO. 1
1_2 HWS
1_2 HWR
COPIER/STOR
8∅
8∅
6∅5∅
10x10
8∅
8∅
T
4∅
10∅
4∅ 5∅
201C
OFFICE201A
OFFICE201B
3_
4 HWS
3_
4 HWR
T
T
CONF202
OFFICE203B
OFFICE203A
OFFICE203
OFFICE203C
OFFICE203D
OFFICE206A
STOR CAB206Q
OFFICE206B
STAIR #2200
1B.4
1B
1A
X14 X12 13.5
X11
X10 X9 X8 X7 15.5
XA
XA.2
XB
XC
XD
XE.0
12
13
14 15 16 17X6
3
1 2
1
KEY NOTES:
REMOVE DUCTWORK BACK TO POINT INDICATED, CAP AND SEAL.
REMOVE HEATING HOT WATER PIPING BACK TO POINTS INDICATED, CAP AND SEAL.
REMOVE TERMINAL UNIT AND ALL ASSOCIATED DUCTWORK, AIR DEVICES, PIPING,THERMOSTAT, CONTROL WIRING, ETC. TYPICAL OF 2.
1
2
3
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:47:
28 P
M
As indicated
MD1.11
SECONDFLOORMECHANICALDEMOLITIONPLAN
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: 1/4" = 1'-0"MD1.111 ADDITION - SECOND FLOOR HVAC DEMOLITION PLAN
36"x30"
11 _ 4"
HW
R
11 _ 4"
HW
S
(E) AHU-1
3" C
HW
S3"
CH
WR
36"x10" DN
108"x30"
120"x48"x24"(WxHxD) PLENUM
MD
36"x36"
26"x22"
36"x20"
SD
72"x36"TOP
36"x36"
36"x42"
36"x42" RAPLENUM
(E)COOLINGCOIL MODULE
(E) SUPPLYFAN MODULE
SLOPEDN
AD
ELEV.BELOW
(E)RAF-1
36"x36"18"x18"
36"x36"36"x36"
M
72"x36"
36"x36"
26"x22"
72"x36" DN. TOLOWER LEVELCLG.
72"x36"
36"x36"
SD
(E)EF-1
3" C
HW
S3"
CH
WR
18"x12"
11 _ 4"
HW
R
11 _ 4"
HW
S
11_2"
AD
26"x22" DN
18"x12" DN
18"x20" DN
11_2" DN
3" DN
11_2"
AD
36"x30"
11 _ 4"
HW
R
11 _ 4"
HW
S
(E) AHU-1
3" C
HW
S3"
CH
WR
36"x10" DN
108"x30"
120"x48"x24"(WxHxD) PLENUM
MD
36"x36"
26"x22"
36"x20"
SD
72"x36"TOP
36"x36"
36"x42"
36"x42" RAPLENUM
(E)COOLINGCOIL MODULE
(E) SUPPLYFAN MODULE
SLOPEDN
AD
ELEV.BELOW
(E)RAF-1
36"x36"18"x18"
36"x36"36"x36"
M
72"x36"
36"x36"
26"x22"
72"x36" DN. TOLOWER LEVELCLG.
72"x36"
36"x36"
SD
(E)EF-1
3" C
HW
S3"
CH
WR
18"x12"
11 _ 4"
HW
R
11 _ 4"
HW
S
11_2"
AD
26"x22" DN
18"x12" DN
18"x20" DN
11_2" DN
3" DN
11_2"
AD
36"x30"
11 _ 4"
HW
R
11 _ 4"
HW
S
(E) AHU-1
3" C
HW
S3"
CH
WR
36"x10" DN
108"x30"
120"x48"x24"(WxHxD) PLENUM
MD
36"x36"
26"x22"
36"x20"
SD
72"x36"TOP
36"x36"
36"x42"
36"x42" RAPLENUM
(E)COOLINGCOIL MODULE
(E) SUPPLYFAN MODULE
SLOPEDN
AD
ELEV.BELOW
(E)RAF-1
36"x36"18"x18"
36"x36"36"x36"
M
72"x36"
36"x36"
26"x22"
72"x36" DN. TOLOWER LEVELCLG.
72"x36"
36"x36"
SD
(E)EF-1
3" C
HW
S3"
CH
WR
18"x12"
11 _ 4"
HW
R
11 _ 4"
HW
S
11_2"
AD
26"x22" DN
18"x12" DN
18"x20" DN
11_2" DN
3" DN
11_2"
AD
1B.4
1B
X12 13.5
X11
X10 X9 X8 X7 15.5
Y3Y2
XA
XA.2
XB
XC
XD
XE.0
14 17
ELECTRICALEQUIPMENT
ELEC
TRIC
ALEQ
UIP
MEN
T
X6 X4
3
3 33
2
(E) FIRERISER TO BERELOCATED.SEE FP PLAN.
(E) FLOOR OPENINGTO BE FILLED. SEEARCHITECTURAL /STRUCTURAL.
1
GENERAL NOTES:
1.
2.
EXTEND ALL POWER AND CONTROL WIRING TO NEW LOCATION OF (E) AHU-1. RECOMMISSION (E) AHU-1 TOINCLUDE ALL EXISTING CONTROL POINTS AND SEQUENCES OF OPERATION.
SCOPE OF WORK INCLUDES RELOCATING (E) AHU-1 TO THE LOCATION SHOWN ON THE NEW WORK PLAN.REMOVE EXISTING CONCRETE CURBS FOR (E) AHU-1, CONDENSATE DRAIN PIPING AND PIPING/DUCTWORKTO EXTENTS SHOWN FOR FUTURE RECONNECTION. REMOVE FLOOR SINK AND ASSOCIATED WASTEPIPING TO ABOVE 2ND FLOOR CEILING AND CAP AND SEAL FOR FUTURE RECONNECTION. COORDINATEALL WORK AND SYSTEM OUTAGES WITH CCU AT LEAST 4 WEEKS IN ADVANCE. FOR WORK OCCURRING INOCCUPIED SPACES ON THE 2ND FLOOR, ALL WORK SHALL OCCUR DURING UNOCCUPIED HOURS.
MECHANICAL KEY NOTES:
REMOVE STAIRS AND ALL ASSOCIATED APPURTENANCES.
INSPECT (E) MOTORIZED DAMPER TO DETERMINE IF IT CAN BE REUSED / RELOCATED TO NEWLOCATION. SEE NEW WORK PLAN. ALERT A/E.
REMOVE PIPING AND DUCTWORK BACK TO POINTS INDICATED. CAP AND SEAL FOR FUTURERECONNECTION. SEE NEW WORK PLAN.
1
2
3
No.
P
E
K
T
N
O
S DT
AJ
GS
ISR
EE
U
GEA. LU
N
A A
26587
RR
G
USE
E
NIEN
L
O
OH AC RFOR
SES I NIN
L
KI
OCERTI F IC
AT E O F A U THO
RIZAT
ION
SOUTH CAROLINA
CONSULTINGENGINEERS
DWG, INC.
No.C03649
SHEET NO.
TITLE
CORPORATE SEAL
A/E SEAL
PROJECT TITLE
SHEET INFORMATION
Date
Project No.
Scale
Drawn By
Checked By
NO REVISION DATE
Conditions of Use: This drawing and the design thereon are theproperty of Quackenbush Architects + Planners. Thereproduction, copying, or use of this drawing without the writtenconsent of Quackenbush Architects + Planners is prohibited andany infringement will be subject to legal action.
T: 803.771.2999F: 803.771.2858
REVISIONS
1217 Hampton StreetColumbia, SC 29201
State Project No. H17-9582-AC
Timber Court127 Anderson StreetPittsburgh, PA 15212Tel. 412-321-0550Fax 412-321-2431
4/22
/201
3 12
:47:
29 P
M
As indicated
MD1.12
ATTICMECHANICALDEMOLITIONPLAN
11.120.00
KMM
JAK
4/07/13
CoastalCarolinaUniversity
CONWAY, SC
STUDENTCENTERANNEXCONSTRUCTION
BID SET
SCALE: 1/4" = 1'-0"MD1.121 ADDITION - ATTIC HVAC DEMOLITION PLAN