generator protection
TRANSCRIPT
GENERATOR PROTECTION
TURBO GENERATOR DIESEL GENERATOR HYDRO GENERATOR WIND GENERATOR
GENERATOR PROTECTION
TYPES OF GENERATORS
SUB SYSTEMS OF GENERATORS
• STATOR
• ROTOR
• TRANSFORMER
GENERATOR PROTECTION
GENERATOR MAIN-SYSTEMS
SUB SYSTEMS OF GENERATORS• STATOR• ROTOR• PRIME MOVER• EXCITATION SYSTEM• VOLTAGE REGULATOR• GOVERNOR• COOLING SYSTEM
GENERATOR PROTECTION
GENERATOR SUB-SYSTEMS
FAULTS IN GENERATOR
EXTERNAL FAULTSINTERNAL FAULTSROTOR EARTH FAULTFAULTS RELATED TO SUB SYSTEMS
GENERATOR PROTECTION
OVER LOADING
UNBALANCE LOADING
SHORT CIRCUIT
EARTH FAULT
GENERATOR PROTECTION
EXTERNAL FAULTS
• PHASE TO PHASE FAULTS IN WINDINGS
• PHASE TO EARTH FAULTS
GENERATOR PROTECTION
INTERNAL FAULTS
FAULTS RELATED TO SUB-SYSTEMS
UNDER VOLTAGEOVER VOLTAGEUNDER FREQUENCYOVER FREQUENCYREVERSE POWERLOSS OF EXCITATIONLOW-FORWARD POWER
GENERATOR PROTECTION
GENERATOR PROTECTIONTYPES OF FAULTS (STATOR SIDE)
VOLTAGE RESTRAINED OVER CURRENTTHERMAL OVER LOADCURRENT UNBALANCEOVER VOLTAGEUNDER VOLTAGEOVER FREQUENCYUNDER FREQUENCYLOSS OF FIELDREVERSE POWERUNDER POWER
OUT OF STEPINADVERTANT ENERGISATIONEARTH FAULT (100%)EARTH FAULT (95%)
GENERATOR DIFFERENTIAL
OVER EXCITATION (V/Hz)
GENERATOR PROTECTION
TYPES OF FAULTS (ROTOR SIDE)
ROTOR EARTH FAULTEXCITATION UNDER VOLTAGEEXCITATION UNDER CURRENTDIODE FAILURE
GENERATOR PROTECTION
SINGLE LINE DIAGRAMGENERATOR PROTECTION
G
49 46 40
81
32
87G
51V 37 64
5927
11 kV
6.6 MW
400/5
400/5
400/5
11000/110v
GENERATOR PROTECTION
PROTECTION PHILOSOPHY
TYPE OF GENERATORGENERATOR SIZENATURE OF GROUNDINGECONOMYTYPE OF CONNECTIONTYPE OF LOADS
GENERATOR PROTECTION
GENERATOR PROTECTION
ANOTOMY OF FAULTS
1.01.0 OVER CURRENT PROTECTIONOVER CURRENT PROTECTION
STATOR FAULTS (EXTERNAL )
PLAIN OVER CURRENT ( SMALL MACHINES)
VOLTAGE DEPENDANT OVER CURRENT(LARGE MACHINES)
1.01.0 PLAIN OVER CURRENT PROTECTIONPLAIN OVER CURRENT PROTECTION
STATOR FAULTS (EXTERNAL )
RELAY ON BREAKER SIDE
RELAY ON NEUTRAL SIDE
1.01.0 PLAIN OVER CURRENT PROTECTIONPLAIN OVER CURRENT PROTECTION
STATOR FAULTS (EXTERNAL )
FAULT AWAY FROM TERMINALS(PLAIN O/C PROTECTION)
FAULT CLOSE TO TERMINALS (VOLTAGE DEPENDENT O/C)
VOLTAGE DEPENDENT OVER CURRENTVOLTAGE DEPENDENT OVER CURRENT
- WHEN O/C FAULT, TERMINAL VOLTAGE REDUCES.- RELAY MAY NOT TRIP, SINCE FAULT CURRENT THROUGH RELAY MAY BE LESS THAN SET POINT
NECESSARY TO VARY THE O/C PICK UP SETTINGWITH RESPECT TO VOLTAGE
STATOR FAULTS
VOLTAGE CONTROLLED OVER CURRENTVOLTAGE CONTROLLED OVER CURRENT
STATOR FAULTS
HAS TWO TRIP CHARACTERISTICS
THE TERMINAL VOLTAGE DECIDESWHICH CHARCTERISTIC WILL BE FOLLOWED BY THE RELAY WHENA FAULT OCCURS
VOLTAGE CONTROLLED OVER CURRENTVOLTAGE CONTROLLED OVER CURRENT
STATOR FAULTS
I >
kI >
Vs >Voltage Level
Pick up level
VOLTAGE RESTRAINED OVER CURRENTVOLTAGE RESTRAINED OVER CURRENT
V/Vs
I*/ [I>]
0.2 0.8
0.2
1.0
GENERATOR PROTECTION
EARTH FAULTEARTH FAULT
STATOR FAULTS
DEPENDS ON HOW THE GENERATOR IS EARTHED
GENERATOR PROTECTION
EARTHING OF GENERATORS
GENERATOR NEUTRAL IS EARTHED
- for stator protection- for operator safety
GENERATOR PROTECTION
EARTHING OF GENERATORS – DIRECT EARTHING
Stator Windings
RELAY
GENERATOR PROTECTION
EARTHING OF GENERATORS – IMPEDANCE EARTHING
Stator Windings
TYPES OF IMPEDANCES
• RESISTOR (CURRENT BASED PROTECTION)B) TRANSFORMER (VOLTAGE BASED PROTECTION)C) TRANSFORMERD) (CURRENT BASED PROTECTION)
GENERATOR PROTECTION
EARTHING OF GENERATORS – RESISTANCE EARTHING
Stator Windings
CURRENTRELAY
GENERATOR PROTECTION
EARTHING OF GENERATORS – TRANSFORMER EARTHING (VOLTAGE BASED)
Stator Windings
VOLTAGE RELAY
GENERATOR PROTECTION
EARTHING OF GENERATORS – TRANSFORMER EARTHING (CURENT BASED)
Stator Windings
CURRENT RELAY
GENERATOR PROTECTION
EARTHING OF GENERATORS – TRANSFORMER EARTHING (OPEN DELTA)
Stator Windings
VOLTAGE RELAY
OPEN DELTA PT
VOLTAGE RELAY
EARTH FAULTEARTH FAULT
STATOR FAULTS
WHEN A FAULT OCCURES CLOSE TO NEUTRAL,WITH IMPEDANCE GROUNDING, THE E/F CURRENT MAY BE LESS THAN THE PICK UP THRESHOLD OF THE NORMALE/F RELAY OR DIFFERENTIAL RELAY
STATOR EARTH FAULT
95% EARTH FAULT NORMAL RELAY
100% EARTH FAULT SPECIAL RELAYSENSES ABSENCEOF 3RD HARMONICS
GENERATOR PROTECTION
STATOR EARTH FAULT0 %
95%95 TO 100%
GENERATOR PROTECTION
GENERATOR PROTECTION
EARTHING OF GENERATORS – (Close to neutral faults)
Stator Windings
CURRENTRELAY
a If
V
If = aV / R
100% STATOR EARTH FAULT
GENERATOR PROTECTION
Measurement of third harmonic voltageacross the earthing impedance
Use of low frequency voltage injectionbetween star point & earth
LOSS OF FIELD IN GENERATORS
GENERATOR WILL OVER SPEED & OPERATE AS AN INDUCTION GENERATOR(OVER SPEEDS OF THE ORDER OF 2 TO 5% )
GENERATOR WILL CONTINUE TO DELIVER POWERWILL DERIVE EXCITATION FROM THE SYSTEM
STATOR CURRENT WILL BE 200%THERE WILL BE HEAVY ROTOR CURRENTRESULTS IN OVER HEATING
GENERATOR PROTECTION
LOSS OF FIELD IN GENERATORS
PHASE ANGLE BETWEEN
ANGLE VOLTAGE & CURRENT
IMPEDANCE REPLICA OF ANGLE PHASE ANGLE
= 360O -
GENERATOR PROTECTION
LOSS OF FIELD IN GENERATORS
I
Z
GENERATOR PROTECTION
= 0o (360O) FORWARD RESISTIVE = +30o FORWARD RESISTIVE + FORWARD CAPACITIVE = +60o FORWARD RESISTIVE + FORWARD CAPACITIVE
= +90o FORWARD CAPACITIVE (LOSS OF FIELD)
= +120o REVERSE RESISTIVE + FORWADRD CAPACITIVE = +150o REVERSE RESISTIVE + FORWARD CAPACITIVE = +180o REVERSE RESISTIVE
= +210o (-150O) REVERSE RESISTIVE + FORWARD INDUCTIVE = +240o (-120O) REVERSE RESISTIVE + FORWARD INDUCTIVE
= +270o (-90O) FORWARD INDUCTIVE
= +300o (-60O) FORWARD INDUCTIVE + FORWARD RESISTIVE = +330o (-30O) FORWARD INDUCTIVE + FORWARD RESISTIVE
GENERATOR PROTECTION
R
X
Z
LOSS OF FIELD
NORMAL
LOSS OF FIELDPROTECTION
GENERATOR PROTECTION
R
X
Z
LOSS OF FIELD
NORMAL
K1
K2
LOSS OF FIELDPROTECTION
GENERATOR PROTECTION
REVERSE POWER GENERATORS
GENERATOR WILL BECOME MOTOR
HARMFUL TO THE PRIME MOVER
( STEAM TURBINE WILL OVER HEAT)(DIESEL ENGINE WILL EXPLODE DUE TO UNBURNT FUEL)(HYDRAULIC TUBINE WILL HAVE CAVITATION)
GENERATOR PROTECTION
INADVERTANT ENERGISATION
- APPLICATION OF FULL VOLTAGE AT STANDSTILL
COASTING TO STOPBEFORE SYNCHRONISM
- PRESENCE OF UNBALANCE VOLTAGE DUE TO FLASH OVER AT IONE OR TWO POLES OF BREAKER
GENERATOR FORCED TO START AS INDUCTION MOTOR RESULTING IN MECHANICAL DAMAGES TO PRIME MOVER AND EXCESSIVEHEATING IN THE ROTOR
GENERATOR PROTECTION
V/Hz PROTECTION
- INCORRECT VOLTAGE REGULATOR ACTION- LOAD THROW - OFF- SUDDEN OVER VOLTAGE / OVER FREQUENCY
RESULTS IN OVER FLUXING OF GENERATORAND OVER HEATING
GENERATOR PROTECTION
GENERATOR PROTECTION PACKAGESGENERATOR PROTECTION PACKAGES
CURRENT
MC11MC61AMC61C
IM30GIM3G-V
VOLTAGE
MV11MND11MVP-01
DIFFERENTIAL
MD32-GSC14S
ROTOR
UBO/CR
SYNCHRONISING
SCM21 / SPM21
ISLANDING
UFD34UM30MW33
LOAD SHEDDING
UFD34MW33MX7/5REX-8
LOAD SHARING
RRS
-
BC1 BC2
B1 B2 B3
G1 G2 G3
PT1 PT2 PT3
CT1 CT2 CT3
BUS-1 BUS-2 BUS-3
PULSES FORGOVERNOR &EXCITER
PULSES FORGOVERNOR &EXCITER
PULSES FORGOVERNOR &EXCITER
LOAD SHARING OF GENERATORS
LSR = LOAD SHARING RELAY
Fig. -1
LSR
LSR
LSR
LSR
LSR
LSR
GRID ISLANDING SCHEME
REVERSE POWER RELAYLOW FORWARD POWER RELAYUNDER VOLTAGE RELAYDIRECTIONAL O/C + E/F RELAY
dF/dT RELAYUNDER FREQ. RELAYOVER FREQ. RELAYVECTOR SURGE RELAY
DG
GRID INCOMERTRANSFORMER
PLANTLOADS
Fig. -2
SYNCHRONISATION OF GENERATORS
SYNCHRONISING IS THE PROCESS OFELECTRICALLY CONNECTING TWO AC POWER SOURCES WITHROTATING MACHINES
WITHOUT ANY DISTURBANCE TOEXISTING SYSTEM AND
WITHOUT ANY DAMAGE TO THEEXISTING SYSTEM
SYNCHRONISATION
SINGLE GENERATOR TO A BUS(DEAD BUS / LIVE BUS SYNCH.)
MULTIPLE GENERATORS TO A BUS(SIZE, VINTAGE, RESPONSE TIMES)
AUTO CHANGEOVER IN BUS CONNECTIONS
MANUAL & AUTO SYNCHRONISATION
REVERSE SYNCHRONISATION
PARAMETERS GOVERNINGSYNCHRONISATION :
VOLTAGE
FREQUENCY
PHASE ANGLE
B1 B2
G1 G2
PT1 PT2
COMMON BUS
SYNCHRONISING OF GENERATORS
SCM 21
RESULTS OF INCORRECT SYNCHRONISATION
FREQUENCY ACTIVE POWER FLOW HIGH FREQ. TO LOW FREQ.
PHASE ANGLE JOLT TO THE SYSTEMFATIGUE TO SHAFTDAMAGE TO BEARINGSOVER HEATING OF STATOR
VOLTAGE REACIVE POWER FLOWHIGH VOLTAGE TO LOW VOLTAGE
TYPES OF SYNCHRONISING RELAYS
CHECK SYNCHRONISING RELAY
AUTO SYNCHRONISING RELAY
ADJUSTABLE SETTINGS FOR F, V, MINIMUM V,F FOR CB CLOSUREDEAD BUS / DEAD LINE SELECTIONCB CLOSURE ONLY IF IS DECREASINGBREAKER OPERATING TIMEMINIMUM RECLOSING TIME2LINE + 1 BUS CONFIGURATIONU/V + O/V PROTECTION
SYNCHRONISING TROLLEY
CHECK SYNCHRONISING RELAY
AUTO SYNCHRONISING RELAY AUTO SYNCHRONISING RELAY
IN ADDITION TO SCM21 FEATURES:
INC / DEC PULSES FOR GOVERNORINC / DEC PULSES FOR AVRADJUSTABLE PULSE WIDTHPULSES PROPORTIONAL TO F, VKICKER PULSE CONTROLANTI MOTORING CONTROL