generator protection

54
GENERATOR PROTECTION

Upload: ramanaram

Post on 20-Jun-2015

1.263 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: Generator Protection

GENERATOR PROTECTION

Page 2: Generator Protection

TURBO GENERATOR DIESEL GENERATOR HYDRO GENERATOR WIND GENERATOR

GENERATOR PROTECTION

TYPES OF GENERATORS

Page 3: Generator Protection

SUB SYSTEMS OF GENERATORS

• STATOR

• ROTOR

• TRANSFORMER

GENERATOR PROTECTION

GENERATOR MAIN-SYSTEMS

Page 4: Generator Protection

SUB SYSTEMS OF GENERATORS• STATOR• ROTOR• PRIME MOVER• EXCITATION SYSTEM• VOLTAGE REGULATOR• GOVERNOR• COOLING SYSTEM

GENERATOR PROTECTION

GENERATOR SUB-SYSTEMS

Page 5: Generator Protection

FAULTS IN GENERATOR

EXTERNAL FAULTSINTERNAL FAULTSROTOR EARTH FAULTFAULTS RELATED TO SUB SYSTEMS

GENERATOR PROTECTION

Page 6: Generator Protection

OVER LOADING

UNBALANCE LOADING

SHORT CIRCUIT

EARTH FAULT

GENERATOR PROTECTION

EXTERNAL FAULTS

Page 7: Generator Protection

• PHASE TO PHASE FAULTS IN WINDINGS

• PHASE TO EARTH FAULTS

GENERATOR PROTECTION

INTERNAL FAULTS

Page 8: Generator Protection

FAULTS RELATED TO SUB-SYSTEMS

UNDER VOLTAGEOVER VOLTAGEUNDER FREQUENCYOVER FREQUENCYREVERSE POWERLOSS OF EXCITATIONLOW-FORWARD POWER

GENERATOR PROTECTION

Page 9: Generator Protection

GENERATOR PROTECTIONTYPES OF FAULTS (STATOR SIDE)

VOLTAGE RESTRAINED OVER CURRENTTHERMAL OVER LOADCURRENT UNBALANCEOVER VOLTAGEUNDER VOLTAGEOVER FREQUENCYUNDER FREQUENCYLOSS OF FIELDREVERSE POWERUNDER POWER

OUT OF STEPINADVERTANT ENERGISATIONEARTH FAULT (100%)EARTH FAULT (95%)

GENERATOR DIFFERENTIAL

OVER EXCITATION (V/Hz)

GENERATOR PROTECTION

Page 10: Generator Protection

TYPES OF FAULTS (ROTOR SIDE)

ROTOR EARTH FAULTEXCITATION UNDER VOLTAGEEXCITATION UNDER CURRENTDIODE FAILURE

GENERATOR PROTECTION

Page 11: Generator Protection

SINGLE LINE DIAGRAMGENERATOR PROTECTION

G

49 46 40

81

32

87G

51V 37 64

5927

11 kV

6.6 MW

400/5

400/5

400/5

11000/110v

GENERATOR PROTECTION

Page 12: Generator Protection

PROTECTION PHILOSOPHY

TYPE OF GENERATORGENERATOR SIZENATURE OF GROUNDINGECONOMYTYPE OF CONNECTIONTYPE OF LOADS

GENERATOR PROTECTION

Page 13: Generator Protection

GENERATOR PROTECTION

ANOTOMY OF FAULTS

Page 14: Generator Protection

1.01.0 OVER CURRENT PROTECTIONOVER CURRENT PROTECTION

STATOR FAULTS (EXTERNAL )

PLAIN OVER CURRENT ( SMALL MACHINES)

VOLTAGE DEPENDANT OVER CURRENT(LARGE MACHINES)

Page 15: Generator Protection

1.01.0 PLAIN OVER CURRENT PROTECTIONPLAIN OVER CURRENT PROTECTION

STATOR FAULTS (EXTERNAL )

RELAY ON BREAKER SIDE

RELAY ON NEUTRAL SIDE

Page 16: Generator Protection

1.01.0 PLAIN OVER CURRENT PROTECTIONPLAIN OVER CURRENT PROTECTION

STATOR FAULTS (EXTERNAL )

FAULT AWAY FROM TERMINALS(PLAIN O/C PROTECTION)

FAULT CLOSE TO TERMINALS (VOLTAGE DEPENDENT O/C)

Page 17: Generator Protection

VOLTAGE DEPENDENT OVER CURRENTVOLTAGE DEPENDENT OVER CURRENT

- WHEN O/C FAULT, TERMINAL VOLTAGE REDUCES.- RELAY MAY NOT TRIP, SINCE FAULT CURRENT THROUGH RELAY MAY BE LESS THAN SET POINT

NECESSARY TO VARY THE O/C PICK UP SETTINGWITH RESPECT TO VOLTAGE

STATOR FAULTS

Page 18: Generator Protection

VOLTAGE CONTROLLED OVER CURRENTVOLTAGE CONTROLLED OVER CURRENT

STATOR FAULTS

HAS TWO TRIP CHARACTERISTICS

THE TERMINAL VOLTAGE DECIDESWHICH CHARCTERISTIC WILL BE FOLLOWED BY THE RELAY WHENA FAULT OCCURS

Page 19: Generator Protection

VOLTAGE CONTROLLED OVER CURRENTVOLTAGE CONTROLLED OVER CURRENT

STATOR FAULTS

I >

kI >

Vs >Voltage Level

Pick up level

Page 20: Generator Protection

VOLTAGE RESTRAINED OVER CURRENTVOLTAGE RESTRAINED OVER CURRENT

V/Vs

I*/ [I>]

0.2 0.8

0.2

1.0

GENERATOR PROTECTION

Page 21: Generator Protection

EARTH FAULTEARTH FAULT

STATOR FAULTS

DEPENDS ON HOW THE GENERATOR IS EARTHED

Page 22: Generator Protection

GENERATOR PROTECTION

EARTHING OF GENERATORS

GENERATOR NEUTRAL IS EARTHED

- for stator protection- for operator safety

Page 23: Generator Protection

GENERATOR PROTECTION

EARTHING OF GENERATORS – DIRECT EARTHING

Stator Windings

RELAY

Page 24: Generator Protection

GENERATOR PROTECTION

EARTHING OF GENERATORS – IMPEDANCE EARTHING

Stator Windings

TYPES OF IMPEDANCES

• RESISTOR (CURRENT BASED PROTECTION)B) TRANSFORMER (VOLTAGE BASED PROTECTION)C) TRANSFORMERD) (CURRENT BASED PROTECTION)

Page 25: Generator Protection

GENERATOR PROTECTION

EARTHING OF GENERATORS – RESISTANCE EARTHING

Stator Windings

CURRENTRELAY

Page 26: Generator Protection

GENERATOR PROTECTION

EARTHING OF GENERATORS – TRANSFORMER EARTHING (VOLTAGE BASED)

Stator Windings

VOLTAGE RELAY

Page 27: Generator Protection

GENERATOR PROTECTION

EARTHING OF GENERATORS – TRANSFORMER EARTHING (CURENT BASED)

Stator Windings

CURRENT RELAY

Page 28: Generator Protection

GENERATOR PROTECTION

EARTHING OF GENERATORS – TRANSFORMER EARTHING (OPEN DELTA)

Stator Windings

VOLTAGE RELAY

OPEN DELTA PT

VOLTAGE RELAY

Page 29: Generator Protection

EARTH FAULTEARTH FAULT

STATOR FAULTS

WHEN A FAULT OCCURES CLOSE TO NEUTRAL,WITH IMPEDANCE GROUNDING, THE E/F CURRENT MAY BE LESS THAN THE PICK UP THRESHOLD OF THE NORMALE/F RELAY OR DIFFERENTIAL RELAY

Page 30: Generator Protection

STATOR EARTH FAULT

95% EARTH FAULT NORMAL RELAY

100% EARTH FAULT SPECIAL RELAYSENSES ABSENCEOF 3RD HARMONICS

GENERATOR PROTECTION

Page 31: Generator Protection

STATOR EARTH FAULT0 %

95%95 TO 100%

GENERATOR PROTECTION

Page 32: Generator Protection

GENERATOR PROTECTION

EARTHING OF GENERATORS – (Close to neutral faults)

Stator Windings

CURRENTRELAY

a If

V

If = aV / R

Page 33: Generator Protection

100% STATOR EARTH FAULT

GENERATOR PROTECTION

Measurement of third harmonic voltageacross the earthing impedance

Use of low frequency voltage injectionbetween star point & earth

Page 34: Generator Protection

LOSS OF FIELD IN GENERATORS

GENERATOR WILL OVER SPEED & OPERATE AS AN INDUCTION GENERATOR(OVER SPEEDS OF THE ORDER OF 2 TO 5% )

GENERATOR WILL CONTINUE TO DELIVER POWERWILL DERIVE EXCITATION FROM THE SYSTEM

STATOR CURRENT WILL BE 200%THERE WILL BE HEAVY ROTOR CURRENTRESULTS IN OVER HEATING

GENERATOR PROTECTION

Page 35: Generator Protection

LOSS OF FIELD IN GENERATORS

PHASE ANGLE BETWEEN

ANGLE VOLTAGE & CURRENT

IMPEDANCE REPLICA OF ANGLE PHASE ANGLE

= 360O -

GENERATOR PROTECTION

Page 36: Generator Protection

LOSS OF FIELD IN GENERATORS

I

Z

GENERATOR PROTECTION

Page 37: Generator Protection

= 0o (360O) FORWARD RESISTIVE = +30o FORWARD RESISTIVE + FORWARD CAPACITIVE = +60o FORWARD RESISTIVE + FORWARD CAPACITIVE

= +90o FORWARD CAPACITIVE (LOSS OF FIELD)

= +120o REVERSE RESISTIVE + FORWADRD CAPACITIVE = +150o REVERSE RESISTIVE + FORWARD CAPACITIVE = +180o REVERSE RESISTIVE

= +210o (-150O) REVERSE RESISTIVE + FORWARD INDUCTIVE = +240o (-120O) REVERSE RESISTIVE + FORWARD INDUCTIVE

= +270o (-90O) FORWARD INDUCTIVE

= +300o (-60O) FORWARD INDUCTIVE + FORWARD RESISTIVE = +330o (-30O) FORWARD INDUCTIVE + FORWARD RESISTIVE

GENERATOR PROTECTION

Page 38: Generator Protection

R

X

Z

LOSS OF FIELD

NORMAL

LOSS OF FIELDPROTECTION

GENERATOR PROTECTION

Page 39: Generator Protection

R

X

Z

LOSS OF FIELD

NORMAL

K1

K2

LOSS OF FIELDPROTECTION

GENERATOR PROTECTION

Page 40: Generator Protection

REVERSE POWER GENERATORS

GENERATOR WILL BECOME MOTOR

HARMFUL TO THE PRIME MOVER

( STEAM TURBINE WILL OVER HEAT)(DIESEL ENGINE WILL EXPLODE DUE TO UNBURNT FUEL)(HYDRAULIC TUBINE WILL HAVE CAVITATION)

GENERATOR PROTECTION

Page 41: Generator Protection

INADVERTANT ENERGISATION

- APPLICATION OF FULL VOLTAGE AT STANDSTILL

COASTING TO STOPBEFORE SYNCHRONISM

- PRESENCE OF UNBALANCE VOLTAGE DUE TO FLASH OVER AT IONE OR TWO POLES OF BREAKER

GENERATOR FORCED TO START AS INDUCTION MOTOR RESULTING IN MECHANICAL DAMAGES TO PRIME MOVER AND EXCESSIVEHEATING IN THE ROTOR

GENERATOR PROTECTION

Page 42: Generator Protection

V/Hz PROTECTION

- INCORRECT VOLTAGE REGULATOR ACTION- LOAD THROW - OFF- SUDDEN OVER VOLTAGE / OVER FREQUENCY

RESULTS IN OVER FLUXING OF GENERATORAND OVER HEATING

GENERATOR PROTECTION

Page 43: Generator Protection

GENERATOR PROTECTION PACKAGESGENERATOR PROTECTION PACKAGES

CURRENT

MC11MC61AMC61C

IM30GIM3G-V

VOLTAGE

MV11MND11MVP-01

DIFFERENTIAL

MD32-GSC14S

ROTOR

UBO/CR

SYNCHRONISING

SCM21 / SPM21

ISLANDING

UFD34UM30MW33

LOAD SHEDDING

UFD34MW33MX7/5REX-8

LOAD SHARING

RRS

Page 44: Generator Protection

-

BC1 BC2

B1 B2 B3

G1 G2 G3

PT1 PT2 PT3

CT1 CT2 CT3

BUS-1 BUS-2 BUS-3

PULSES FORGOVERNOR &EXCITER

PULSES FORGOVERNOR &EXCITER

PULSES FORGOVERNOR &EXCITER

LOAD SHARING OF GENERATORS

LSR = LOAD SHARING RELAY

Fig. -1

LSR

LSR

LSR

LSR

LSR

LSR

Page 45: Generator Protection

GRID ISLANDING SCHEME

REVERSE POWER RELAYLOW FORWARD POWER RELAYUNDER VOLTAGE RELAYDIRECTIONAL O/C + E/F RELAY

dF/dT RELAYUNDER FREQ. RELAYOVER FREQ. RELAYVECTOR SURGE RELAY

DG

GRID INCOMERTRANSFORMER

PLANTLOADS

Fig. -2

Page 46: Generator Protection

SYNCHRONISATION OF GENERATORS

Page 47: Generator Protection

SYNCHRONISING IS THE PROCESS OFELECTRICALLY CONNECTING TWO AC POWER SOURCES WITHROTATING MACHINES

WITHOUT ANY DISTURBANCE TOEXISTING SYSTEM AND

WITHOUT ANY DAMAGE TO THEEXISTING SYSTEM

Page 48: Generator Protection

SYNCHRONISATION

SINGLE GENERATOR TO A BUS(DEAD BUS / LIVE BUS SYNCH.)

MULTIPLE GENERATORS TO A BUS(SIZE, VINTAGE, RESPONSE TIMES)

AUTO CHANGEOVER IN BUS CONNECTIONS

MANUAL & AUTO SYNCHRONISATION

REVERSE SYNCHRONISATION

Page 49: Generator Protection

PARAMETERS GOVERNINGSYNCHRONISATION :

VOLTAGE

FREQUENCY

PHASE ANGLE

Page 50: Generator Protection

B1 B2

G1 G2

PT1 PT2

COMMON BUS

SYNCHRONISING OF GENERATORS

SCM 21

Page 51: Generator Protection

RESULTS OF INCORRECT SYNCHRONISATION

FREQUENCY ACTIVE POWER FLOW HIGH FREQ. TO LOW FREQ.

PHASE ANGLE JOLT TO THE SYSTEMFATIGUE TO SHAFTDAMAGE TO BEARINGSOVER HEATING OF STATOR

VOLTAGE REACIVE POWER FLOWHIGH VOLTAGE TO LOW VOLTAGE

Page 52: Generator Protection

TYPES OF SYNCHRONISING RELAYS

CHECK SYNCHRONISING RELAY

AUTO SYNCHRONISING RELAY

Page 53: Generator Protection

ADJUSTABLE SETTINGS FOR F, V, MINIMUM V,F FOR CB CLOSUREDEAD BUS / DEAD LINE SELECTIONCB CLOSURE ONLY IF IS DECREASINGBREAKER OPERATING TIMEMINIMUM RECLOSING TIME2LINE + 1 BUS CONFIGURATIONU/V + O/V PROTECTION

SYNCHRONISING TROLLEY

CHECK SYNCHRONISING RELAY

Page 54: Generator Protection

AUTO SYNCHRONISING RELAY AUTO SYNCHRONISING RELAY

IN ADDITION TO SCM21 FEATURES:

INC / DEC PULSES FOR GOVERNORINC / DEC PULSES FOR AVRADJUSTABLE PULSE WIDTHPULSES PROPORTIONAL TO F, VKICKER PULSE CONTROLANTI MOTORING CONTROL