generator set is 8528-1 2005 - definition of power ratings
TRANSCRIPT
Created by J. M. J. Lloyd Uncontrolled once printed Reference ISO8528
GENERATOR SET ISO 8528-1:2005
DEFINITION OF POWER RATINGS CONTINUOUS POWER (COP) Power output with : constant load : unlimited hours PRIME POWER (PRP) Power output with : variable load : unlimited hours LIMITED TIME RUNNING POWER (LTP) Power output with : constant load : 500 hours/year EMERGENCY STANDBY POWER (ESP) Power output with : variable load : 200 hours/year
FG WILSON RATINGS
PRIME POWER : ISO Prime Power (with 10% overload) STANDBY POWER : ISO Limited Time Running Power (500 hrs/year)