  • Medium-Voltage AC-Converter SINAMICS GL150

    Closed-Loop-Control-System Type 6SL385

    Manual 09/2009

  • 03.09.2009 09:57

  • Introduction 1

    Safety information 2

    Technical data 3

    Description 4

    Mechanical installation 5

    Electrical installation 6

    Commissioning 7

    Operation 8

    Functions 9

    Maintenance and servicing 10

    Fault and system messages 11

    Medium-Voltage AC-ConverterSINAMICS GL150

    Manual

    Edition 09/2009

  • Legal information Warning notice system

    This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.

    DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

    WARNING

    indicates that death or severe personal injury may result if proper precautions are not taken.

    CAUTION with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.

    CAUTION without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.

    NOTICE indicates that an unintended result or situation can occur if the corresponding information is not taken into account.

    If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.

    Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation for the specific task, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.

    Proper use of Siemens products Note the following:

    WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be adhered to. The information in the relevant documentation must be observed.

    Trademarks All names identified by are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.

    Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.

    Siemens AG Industry Sector Postfach 48 48 90026 NRNBERG GERMANY

    Ordernumber: A5E01098517P 09/2009

    Copyright Siemens AG 2007, ,, 2008,, 2009. Technical data subject to change

  • Siemens AG Manual 2.01 6SL385 03.09.2009 3

    Table of contents 1 Introduction................................................................................................................................................ 9

    1.1 Description of this document..........................................................................................................9 2 Safety information.................................................................................................................................... 11

    2.1 General product-related safety information .................................................................................11 2.2 Notes on operator protection .......................................................................................................12 2.3 Electromagnetic fields..................................................................................................................13

    3 Technical data ......................................................................................................................................... 15 3.1 Notes about technical specifications............................................................................................15 3.2 Type plate ....................................................................................................................................16 3.3 General technical data .................................................................................................................16 3.4 Terminal blocks............................................................................................................................17 3.4.1 Preassignment and description of the customer terminal blocks ................................................17

    4 Description............................................................................................................................................... 19 4.1 Structure of the open-loop and closed-loop control cabinet ........................................................19 4.2 Components in the door of the open-loop and closed-loop control cabinet ................................21 4.2.1 Overview ......................................................................................................................................21 4.2.2 Display elements..........................................................................................................................22 4.2.3 Operator panel AOP30 ................................................................................................................23 4.2.3.1 Overview ......................................................................................................................................23 4.2.3.2 The keys of the AOP30................................................................................................................24 4.2.4 Switches and pushbuttons ...........................................................................................................25 4.3 Description of the components ....................................................................................................26 4.3.1 Control Unit 320 (CU320) ............................................................................................................26 4.3.1.1 Overview ......................................................................................................................................26 4.3.1.2 Description of the interfaces and other elements of the CU320..................................................28 4.3.2 Terminal Modules TM31 and TM15.............................................................................................36 4.3.3 Voltage Sensing Module (VSM10)...............................................................................................38 4.3.4 Interconnecting optional connections ..........................................................................................41 4.3.5 Circuit-breaker (provided by the customer) .................................................................................42 4.3.6 Actual value acquisition ...............................................................................................................42 4.3.7 Power Stack Adapter (PSA).........................................................................................................42 4.3.8 DC/DC converter..........................................................................................................................43 4.3.9 Line filter.......................................................................................................................................44 4.3.10 Sirius safety relay.........................................................................................................................44 4.4 Description of options ..................................................................................................................45 4.4.1 Triggering additional circuit breakers (option A04) ......................................................................45 4.4.2 Expanded remote control via terminal block (option A06) ...........................................................45 4.4.3 Motor monitoring (option A09) .....................................................................................................46 4.4.4 Control and monitoring of the inrush circuit breaker via the internal SIMATIC S7 (option

    A11)..............................................................................................................................................46

  • Table of contents

    4 Siemens AG Manual 2.01 6SL38503.09.2009

    4.4.5 Control and monitoring of the filter circuit breaker via the internal SIMATIC S7 (option A12)............................................................................................................................................. 46

    4.4.6 Integrated SIMATIC S7 open-loop control with matching components (option A13) ................. 47 4.4.7 Speed measurement with SMC30 for a single motor (option A51)............................................. 48 4.4.8 Speed measurement for two motors with two SMC30s (starting converters only) (option

    A52)............................................................................................................................................. 51 4.4.9 Speed measurement for 3 motors with 3 SMC30s (starting converters only) (option A53). ...... 54 4.4.10 Speed measurement for 4 motors with 4 SMC30s (starting converters only) (option A54). ...... 57 4.4.11 Demagnetization device monitoring (option A71) ....................................................................... 60 4.4.12 Dry-type transformer monitoring (option A72)............................................................................. 60 4.4.13 Oil-immersed transformer monitoring (option A73)..................................................................... 60 4.4.14 Output transformer monitoring (option A81) ............................................................................... 60 4.4.15 Monitoring binary and analog signals from the output transformer (option A82)........................ 61 4.4.16 Starting converter for a motor (interfaces for parallel switching device and static excitation

    equipment) (option A91).............................................................................................................. 61 4.4.17 Starting converter for two motors (interfaces for parallel switching device and static

    excitation equipment) (option A92) ............................................................................................. 61 4.4.18 Starting converter for three motors (interfaces for parallel switching device and static

    excitation equipment) (option A93) ............................................................................................. 61 4.4.19 Starting converter for four motors (interfaces for parallel switching device and static

    excitation equipment) (option A94) ............................................................................................. 62 4.4.20 CBE20 communications card for PROFINET (option G24) ........................................................ 62 4.4.21 Extended measured value and data acquisition with Customat (option G67) ............................ 63 4.4.22 Redundant electronic power supply with wide-range power supply unit 1 AC 93 - 253

    V/88 - 360 V (option K71)............................................................................................................ 65 4.4.23 Redundant electronic power supply with DC 18 V infeed (option K72) ...................................... 66 4.4.24 Redundant electronic power supply with DC 24 V infeed (option K73) ...................................... 66 4.4.25 Redundant electronic power supply with 1 AC 230 V infeed (option K74) ................................. 66 4.4.26 400 V 3 AC demagnetization device for output transformer for starting converters (option

    L30) ............................................................................................................................................. 66 4.4.27 Line-side grounding switch (option L48) ..................................................................................... 69 4.4.28 Motor-side grounding switch (option L49)................................................................................... 69 4.4.29 Cabinet illumination and service socket in control section (option L50) ..................................... 69 4.4.30 IP54 degree of protection (option M54) ...................................................................................... 70 4.4.31 Grounding switch with disconnector on the converter input (motor operated) (option N48) ...... 70 4.4.32 Grounding switch with disconnector on the converter output (motor operated) (option

    N49)............................................................................................................................................. 71 5 Mechanical installation............................................................................................................................. 73

    5.1 Preparatory steps........................................................................................................................ 73 5.2 Shipping ...................................................................................................................................... 74 5.3 Mounting...................................................................................................................................... 74

    6 Electrical installation ................................................................................................................................ 75 6.1 Observing the five safety rules.................................................................................................... 75 6.2 The five safety rules .................................................................................................................... 75 6.3 EMC (electromagnetic compatibility) .......................................................................................... 76 6.4 Connection .................................................................................................................................. 79 6.4.1 General information about connection ........................................................................................ 79 6.4.2 Connecting the ground................................................................................................................ 82 6.4.3 Connecting auxiliary voltage ....................................................................................................... 83 6.4.4 Connecting the line-side circuit breaker...................................................................................... 83 6.4.5 Connecting the line-side circuit breaker...................................................................................... 84

  • Table of contents

    Siemens AG Manual 2.01 6SL385 03.09.2009 5

    6.4.6 Connecting the motor-side circuit breaker ...................................................................................84 6.4.7 Connecting the motor-side circuit breaker ...................................................................................85 6.4.8 Connecting the external safety loop ............................................................................................86

    7 Commissioning ........................................................................................................................................ 87 7.1 Commissioning the converter ......................................................................................................87

    8 Operation................................................................................................................................................. 89 8.1 Operation of the converter ...........................................................................................................89 8.2 Notes about parameters and function diagrams..........................................................................89

    9 Functions ................................................................................................................................................. 91 9.1 Note on function diagrams ...........................................................................................................91 9.2 Setpoint channel and closed-loop control....................................................................................91 9.2.1 Setpoint channel ..........................................................................................................................91 9.2.1.1 Setpoint addition ..........................................................................................................................91 9.2.1.2 Direction of rotation reversal ........................................................................................................92 9.2.1.3 Skip frequency bands and minimum speed.................................................................................92 9.2.1.4 Speed limitation............................................................................................................................93 9.2.1.5 Ramp-function generator .............................................................................................................94 9.2.2 Vector speed/torque control.........................................................................................................95 9.2.2.1 Properties of vector speed/torque control....................................................................................95 9.2.2.2 Benefits of vector speed/torque control with encoder..................................................................95 9.3 Monitoring, functions, and protective functions............................................................................96 9.3.1 Safety shutdown of the converter ................................................................................................96 9.3.2 Potential concept .........................................................................................................................96 9.3.3 Speed monitoring with incremental encoder................................................................................97

    10 Maintenance and servicing ...................................................................................................................... 99 10.1 Observing the five safety rules.....................................................................................................99 10.2 The five safety rules.....................................................................................................................99 10.3 Safety information regarding maintenance and repairs.............................................................100 10.4 Contacts and technical support..................................................................................................100 10.5 Opening the doors .....................................................................................................................102 10.6 Preventive maintenance ............................................................................................................102 10.6.1 Checklist for preventive maintenance........................................................................................102 10.6.2 Inspection...................................................................................................................................103 10.6.3 Visual inspections ......................................................................................................................104 10.7 Maintenance...............................................................................................................................104 10.7.1 Replacing the backup battery for the cabinet operator panel (AOP30).....................................104 10.8 Cleaning .....................................................................................................................................106 10.8.1 Contact for cleaning measures ..................................................................................................106 10.8.2 Removing dust deposits.............................................................................................................106 10.9 Repairs.......................................................................................................................................107 10.9.1 Safety-relevant checks...............................................................................................................107 10.9.2 Replacing the cabinet operator panel ........................................................................................108 10.9.3 Replacing the CompactFlash card.............................................................................................108

    11 Fault and system messages .................................................................................................................. 111 11.1 External alarms and faults .........................................................................................................111

  • Table of contents

    6 Siemens AG Manual 2.01 6SL38503.09.2009

    11.2 Diagnostics................................................................................................................................ 111 11.2.1 Diagnosis via LEDs ................................................................................................................... 111 11.2.2 Diagnostics via parameters....................................................................................................... 113 11.2.3 Indicating and rectifying faults................................................................................................... 115

    Index...................................................................................................................................................... 117

    Tables Table 3-1 General technical data ................................................................................................................ 16 Table 4-1 Meaning of the indicator lights in the door of the open-loop and closed-loop control

    cabinet......................................................................................................................................... 22 Table 4-2 Pointer instruments for operating variables in the door of the control cabinet............................ 23 Table 4-3 Overview of Control Unit 320 (CU320) ....................................................................................... 27 Table 4-4 PROFIBUS address switches ..................................................................................................... 29 Table 4-5 Measuring sockets T0, T1 and T2 .............................................................................................. 30 Table 4-6 PROFIBUS interface X126.......................................................................................................... 31 Table 4-7 Terminal block X124 ................................................................................................................... 32 Table 4-8 Terminal block X122; X132......................................................................................................... 33 Table 4-9 -X500 DRIVE-CliQ interface........................................................................................................ 40 Table 4-10 -X524 electronic power supply.................................................................................................... 40 Table 4-11 -X520 analog inputs/temperature sensor connection ................................................................. 41 Table 4-12 -X522 690 V phase inputs........................................................................................................... 41 Table 4-13 Description of the LEDs on the SMC30 ...................................................................................... 50 Table 4-14 Connectable encoders ................................................................................................................ 50 Table 4-15 Maximum signal cable length...................................................................................................... 51 Table 4-16 Description of the LEDs on the SMC30 ...................................................................................... 53 Table 4-17 Connectable encoders ................................................................................................................ 53 Table 4-18 Maximum signal cable length...................................................................................................... 54 Table 4-19 Description of the LEDs on the SMC30 ...................................................................................... 56 Table 4-20 Connectable encoders ................................................................................................................ 56 Table 4-21 Maximum signal cable length...................................................................................................... 57 Table 4-22 Description of the LEDs on the SMC30 ...................................................................................... 59 Table 4-23 Connectable encoders ................................................................................................................ 59 Table 4-24 Maximum signal cable length...................................................................................................... 60 Table 6-1 Circuit breaker 1.......................................................................................................................... 84 Table 6-2 Circuit breaker 2.......................................................................................................................... 84 Table 6-3 Circuit breaker 1.......................................................................................................................... 85 Table 6-4 Circuit breaker 2.......................................................................................................................... 86 Table 10-1 Technical specifications of the backup battery ......................................................................... 104

  • Table of contents

    Siemens AG Manual 2.01 6SL385 03.09.2009 7

    Table 11-1 Description of the LEDs on the CU320......................................................................................111 Table 11-2 Description of the LEDs .............................................................................................................112

    Figures Figure 3-1 Example: Type plate for closed-loop control................................................................................16 Figure 4-1 Open-loop and closed-loop control cabinet .................................................................................19 Figure 4-2 Door of the open-loop and closed-loop control cabinet ...............................................................21 Figure 4-3 Structure of the operator panel (AOP30) .....................................................................................23 Figure 4-4 Control Unit 320 (without cover) ..................................................................................................27 Figure 4-5 DRIVE-CLiQ interface..................................................................................................................28 Figure 4-6 Serial interface (RS232) X140 .....................................................................................................28 Figure 4-7 PROFIBUS address switches......................................................................................................29 Figure 4-8 CompactFlash card slot ...............................................................................................................30 Figure 4-9 Serial interface (RS232) X140 .....................................................................................................31 Figure 4-10 Bus terminating resistor ...............................................................................................................32 Figure 4-11 CU320 LEDs ................................................................................................................................34 Figure 4-12 Terminal Modules TM15, TM31...................................................................................................36 Figure 4-13 Voltage Sensing Module VSM10 .................................................................................................39 Figure 4-14 DC/DC converter..........................................................................................................................43 Figure 4-15 Line filter.......................................................................................................................................44 Figure 4-16 SIRIUS safety relay......................................................................................................................44 Figure 4-17 SMC30 Sensor Module................................................................................................................49 Figure 4-18 SMC30 Sensor Module................................................................................................................52 Figure 4-19 SMC30 Sensor Module................................................................................................................55 Figure 4-20 SMC30 Sensor Module................................................................................................................58 Figure 4-21 Block diagram of the demagnetization device .............................................................................68 Figure 4-22 Cabinet lighting with service socket.............................................................................................69 Figure 4-23 Fan with option M54.....................................................................................................................70 Figure 4-24 Option N48...................................................................................................................................70 Figure 4-25 Option N49...................................................................................................................................71 Figure 6-1 Bridging shield gaps.....................................................................................................................76 Figure 6-2 Shield connection with clip...........................................................................................................78 Figure 6-3 Connecting cabinets ....................................................................................................................79 Figure 6-4 Equipotential bonding strip...........................................................................................................80 Figure 6-5 Shield bus ....................................................................................................................................80 Figure 6-6 Grounding lug...............................................................................................................................82

  • Table of contents

    8 Siemens AG Manual 2.01 6SL38503.09.2009

    Figure 9-1 Potential concept......................................................................................................................... 97 Figure 10-1 Replacing the backup battery in the cabinet panel ................................................................... 105 Figure 10-2 Replacing the operator panel .................................................................................................... 108 Figure 10-3 Inserting the CompctFlash card ................................................................................................ 109

  • Siemens AG Manual 2.01 6SL385 03.09.2009 9

    Introduction 11.1 Description of this document Description

    This documentation contains information about the safe handling of your medium-voltage converter's control cabinet as well as its components and modules. It provides instructions on assembling, installing, and maintaining the equipment safely and properly. It also contains the following comprehensive information: Description of all the options Comprehensive technical data

    Note

    This manual is only one part of the documentation for this equipment. Use this manual only in conjunction with the "General Manual".

    Note

    The ID number at the end of a chapter indicates the section for documentation purposes.

    [ID 5027.00]

  • Siemens AG Manual 2.01 6SL385 03.09.2009 11

    Safety information 2

    WARNING Note safety information Operating the equipment without taking the safety information into consideration can result in property damage, serious injury, and even death. You must not operate the converter without taking this safety information into consideration.This document is to be regarded as an integrated whole along with the "General Manual". Therefore, you must pay particular attention to the safety information provided in the "Safety information" chapter of the "Closed-Loop Control Manual" and the "General Manual".

    2.1 General product-related safety information

    Note In addition to the safety information provided here, you must also comply with the safety information provided in the section of the same name in the "General Equipment Manual".

    Safety-relevant information

    WARNING Correct usage Improper use of the devices described here can result in damage to property, serious injury and even death. Therefore, please adhere strictly to all instructions for proper usage. Operating modes, overload conditions, load cycles and ambient conditions different from those described in this document are allowed only in exceptional circumstances and only by special arrangement with the manufacturer.

  • Safety information 2.2 Notes on operator protection

    12 Siemens AG Manual 2.01 6SL38503.09.2009

    2.2 Notes on operator protection

    Note In addition to the safety information provided here, you must also comply with the safety information provided in the section of the same name in the "General Equipment Manual".

    The five safety rules The five safety rules must be observed. 1. Disconnect the system. 2. Protect against reconnection. 3. Make sure that the equipment is de-energized. 4. Ground and short-circuit. 5. Cover or enclose adjacent components that are still live.

    Safety-related information for working on the converter

    DANGER Dangerous parts Depending on their degree of protection, converters can have live, and possibly moving or rotating, parts during operation. There is a risk of death or severe injury/material damage if the required covers are removed or if the converter is used or operated incorrectly. Always take the appropriate precautions before touching any components.

  • Safety information 2.3 Electromagnetic fields

    Siemens AG Manual 2.01 6SL385 03.09.2009 13

    High voltages

    DANGER Dangerous high voltages High voltages can cause death or serious injury if the safety rules are not observed or if the equipment is handled incorrectly. When this equipment is in operation, very high voltages occur and can be still present for quite some time after the equipment has been shut down or for as long as the motor is still rotating. Make sure that work is only carried out by qualified personnel under due observance of the five safety rules, the warning information in this documentation and the safety information on the product itself.

    Hot surfaces

    CAUTION High temperatures If the converter is not in operation, the anti-condensation heating is activated when the limit value of the temperature control is reached. Once activated, the anti-condensation heating can generate a great deal of heat. Serious injury (scalding) may occur if you come into contact with these components.

    2.3 Electromagnetic fields

    WARNING Electromagnetic fields "electro smog" Electromagnetic fields are generated by the operation of electrical power engineering installations such as transformers, converters or motors. Electromagnetic fields can interfere with electronic devices, which could cause them to malfunction. For example, the operation of heart pacemakers can be impaired, potentially leading to damage to a person's health or even death. It is therefore forbidden for persons with heart pacemakers to enter these areas. The plant operator is responsible for taking appropriate measures (labels and hazard warnings) to adequately protect operating personnel and others against any possible risk.

  • Safety information 2.3 Electromagnetic fields

    14 Siemens AG Manual 2.01 6SL38503.09.2009

    Observe the relevant nationally applicable health and safety regulations. In Germany, "electromagnetic fields" are subject to regulations BGV B11 and BGR B11 stipulated by the German statutory industrial accident insurance institution.

    Display adequate hazard warning notices.

    Place barriers around hazardous areas. Take measures, e.g. using shields, to reduce electromagnetic fields at their source. Make sure that personnel are wearing the appropriate protective gear.

  • Siemens AG Manual 2.01 6SL385 03.09.2009 15

    Technical data 33.1 Notes about technical specifications

    The following section contains an overview of general and specific technical specifications of the device as well as specifications about conditions that must be observed when the device described here is implemented.

  • Technical data 3.2 Type plate

    16 Siemens AG Manual 2.01 6SL38503.09.2009

    3.2 Type plate Type plate (example)

    Siemens AG / Automation & DrivesMade in Germany

    AC

    AC

    V

    V

    V

    A

    A

    A

    Hz

    Hz

    Hz

    kg

    AC Drive / Supply Rated voltage Rated current Rated frequency

    Supply

    Redundant supply

    Auxiliary supply

    Cubicle Type

    Cooling method

    Coolant temperature

    A part of:

    Serial number

    Explanations: see documentation

    Degree of Protection

    Weight

    Year of manufacture

    Digital open- and closed-loop control

    max. 16

    DC

    C

    A

    Frequenzumrichter

    Stromart Nennspannung Nennstrom Nennfrequenz

    Versorgung

    redundante Versorgung

    Hilfsversorgung

    Schrank Typ

    Khlart

    Khlmitteltemperatur

    Digitale Steuerung und Regelung

    Erluterungen: siehe Dokumentation

    Schutzart

    Gewicht

    Baujahr

    Komponente von:

    Fabriknummer

    SINAMICS GL150

    SIEMENS

    6SL3850-5UM10-9AA0-ZA21+A71+A91+K74+L30+L50+L55+M06+Y09

    IEC 61800-5-1

    IEC 62103

    EN 50178

    N-TU117123456000

    1

    230 501

    24

    110 5

    15

    50

    5 - 45 IP41

    350

    2007

    Figure 3-1 Example: Type plate for closed-loop control

    3.3 General technical data General technical data Table 3-1 General technical data Auxiliary power supply With option K71 1 AC 93 V - 253 V, 40 - 70 Hz

  • Technical data 3.4 Terminal blocks

    Siemens AG Manual 2.01 6SL385 03.09.2009 17

    With option K72 18 V DC With option K73 24 V DC With option K74 1 AC 50-60Hz 100-120 V/220-240 V -15% +10% Degree of protection according to DIN EN 60529/VDE 0470 Part 1 (IEC 60529): Standard IP41 Option IP54 Cooling method Air cooling Self-cooled at IP41

    Forced-air cooling with fan at IP54 (option M54)

    3.4 Terminal blocks

    3.4.1 Preassignment and description of the customer terminal blocks

    Default setting of the Customer Terminal Blocks The default setting and description of the Customer Terminal Blocks can be found in the "Wiring Manual" section of the operating instructions that came with the converter. For information about the position of the customer terminal blocks within the cabinet, see the layout diagrams in the "Layout diagram, dimension drawing" section of the converter's operating instructions. The customer terminal block interfaces are documented in the circuit manual on the CD that comes with the converter.

    Structure The signals are allocated to various terminal blocks according to voltage level. The cables are visually distinguished from one another by various colors. Further information is provided in the section headed "Overview diagram, circuit diagram, terminal diagram" in the "Circuit manual for closed-loop control" chapter. Barriers mechanically separate cables carrying different potentials on one terminal block.

  • Siemens AG Manual 2.01 6SL385 03.09.2009 19

    Description 44.1 Structure of the open-loop and closed-loop control cabinet Overview

    Figure 4-1 Open-loop and closed-loop control cabinet The exact arrangement of the components is shown in the layout diagram.

    Structure of the central panel The central panel is organized into three racks: First rack: Terminal Modules TM15 (standard = 1 unit, max. up to 7 units) Terminal Modules TM31 (standard = 2 units, max. up to 3 units) Voltage Sensing Module VSM10 Encoder module SMC30 (optional, max. up to 4 units) DriveCliq HUB DMC20 (optional) Second rack (optional open-loop and closed-loop control components): SIMATIC S7 components Third rack:

  • Description 4.1 Structure of the open-loop and closed-loop control cabinet

    20 Siemens AG Manual 2.01 6SL38503.09.2009

    Contactors for the circuit breakers Contactor safety combinations Terminals for the circuit breaker connections Miniature circuit breakers for the power supply Cable-clamping bar/shielding bus

    Structure of the left-hand side panel The left-hand side panel contains: 2 rows of customer terminals Cable-clamping bar/shielding bus

    Structure of the right-hand side panel The right-hand side panel contains: Control Unit CU320 with PROFIBUS DP interface CBP10 Temperature relay for anti-condensation heating DC/DC converter for the internal power supply of the terminal modules TM15/TM31 DC/DC converter for SIMATIC S7 signals (optional) DC/DC converter for external circuit breaker (optional) Reference bus 30 x 10 230V/24V power supply (optional) Line filter (optional) Terminals for supply and distribution Socket outlets [ID 800.00]

  • Description 4.2 Components in the door of the open-loop and closed-loop control cabinet

    Siemens AG Manual 2.01 6SL385 03.09.2009 21

    4.2 Components in the door of the open-loop and closed-loop control cabinet

    4.2.1 Overview

    Description

    Figure 4-2 Door of the open-loop and closed-loop control cabinet The following components are integrated in the door of the open-loop and closed-loop control cabinet: Indicator lights Indicating instruments Operator panel AOP30 Key-operated switch S11 Mushroom pushbutton S100 for safety shutdown

  • Description 4.2 Components in the door of the open-loop and closed-loop control cabinet

    22 Siemens AG Manual 2.01 6SL38503.09.2009

    4.2.2 Display elements

    Indicator lights The four indicator lights (H1 to H4) are installed in the door of the open-loop and closed-loop control cabinet.

    Table 4-1 Meaning of the indicator lights in the door of the open-loop and closed-loop control cabinet

    Indicator light Action Meaning green Continuous light The converter is in operation, the circuit breakers are

    switched on and the converter pulses are enabled. H1

    green Flashing light The converter is just starting operation, i.e., the auxiliary circuits and the circuit breakers are being switched on.

    The auxiliary circuits and the circuit breakers are switched on, the converter pulses are disabled.

    Shutdown cycle OFF1, OFF2 or OFF3 is running. The demagnetization device is in operation (only in

    the case of a starting converter). Test mode is selected.

    white Continuous light The converter is ready to be switched on, all circuit breakers are switched off and there is no OFF2 or OFF3 shutdown cycle.

    H2

    white Flashing light All circuit breakers are switched off, but the converter is not ready to be switched on or there is an OFF2/OFF3 shutdown cycle or an error pending.

    H3 yellow Flashing / continuous light

    If an alarm occurs, the light flashes for 5 s. It then switches to the continuous light status. If a new alarm occurs when the light is in continuous mode, it begins to flash again for 5 s and then returns to a continuous light. Once the reason for the alarm has been corrected, the light goes out.

    H4 Red Flashing / continuous light

    If a fault occurs, the light flashes for 5 s. It then switches to the continuous light status. If a new fault message occurs when the light is in continuous mode, it begins to flash again for 5 s and then returns to a continuous light. Once the reason for the fault has been corrected, the light goes out.

    Indicating instruments in the door Four pointer instruments (P1 to P4) for operating variables are located in the door of the control cabinet.

    Table 4-2 Pointer instruments for operating variables in the door of the control cabinet Gauge Display range Indicated operating variable P1 - 120 ... + 120 % Motor speed / frequency P2 0 ... + 120 % Machine voltage

  • Description 4.2 Components in the door of the open-loop and closed-loop control cabinet

    Siemens AG Manual 2.01 6SL385 03.09.2009 23

    Gauge Display range Indicated operating variable P3 - 120 ... + 120 % DC link power P4 0 ... + 120 % DC link current

    4.2.3 Operator panel AOP30

    4.2.3.1 Overview

    Description You can use the advanced operator panel (AOP30) for commissioning, operating, and diagnosing the converter. The AOP30 communicates with the SINAMICS drive via a serial RS232 interface with PPI protocol. The interface is a point-to-point connection. During communication, the AOP30 is the master and the connected drive is the slave.

    Features of the AOP30

    21JUHHQ

    $ODUP\HOORZ

    )DXOWUHG

    0DVWHUFRQWUROVHOHFWLRQ

    'LVSOD\

    ,QFUHDVHGHFUHDVH

    IXQFWLRQNH\V

    1XPHULFNH\SDG

    'LUHFWLRQRIURWDWLRQFKDQJHRYHU

    -RJJLQJ212))

    0HQXNH\

    .H\ERDUGLQWHUORFN

    2SHUDWLQJVWDWXV/('V

    Figure 4-3 Structure of the operator panel (AOP30)

    The AOP30 has the following features and functions: Graphical LCD with:

    Green backlighting for plain-text display A resolution of 240 x 64 pixels Quasi-analog "bar display" of process variables

    Keypad for controlling drives during operation

  • Description 4.2 Components in the door of the open-loop and closed-loop control cabinet

    24 Siemens AG Manual 2.01 6SL38503.09.2009

    Numeric keypad for the numeric input of parameter values 4 LEDs for indicating the operating status of the drive unit:

    RUN: green ALARM: yellow FAULT: red LOCAL/REMOTE: green

    Help function describing causes of and remedies for faults and alarms Function keys for prompted navigation through the menus Realtime clock for the time stamping of faults and for setting up simple time controls LOCAL/REMOTE switchover for selecting the operating location Two-stage security concept to protect against unintentional or unauthorized changes to

    settings. Time and date memory powered by internal battery backup

    4.2.3.2 The keys of the AOP30

    Functions of the control keys

    0(18

    Calls up the main menu of the AOP30

    Calls up the "inhibit functions" menu. More detailed information is available in Chapter "Inhibit Functions".

    Numeric keys for direct entry of values.

    /2&$/5(027(

    Switches between remote and local mode. In local mode, the LED illuminates. More detailed information is available in Chapter Control Settings.

    On/off button. The "On" key is always in effect in local mode, if no inhibit function is activated. The "Off" key is only active in local mode and acts as "OFF1" in the default setting. More detailed information is available in Chapter Control Settings.

  • Description 4.2 Components in the door of the open-loop and closed-loop control cabinet

    Siemens AG Manual 2.01 6SL385 03.09.2009 25

    Clockwise/counter-clockwise switchover. The key is only in effect in local mode. You can find more detailed information in Chapter Control Settings.

    -2*

    JOG Mode (Jogging) The key is only in effect in local mode in "Ready to switch on" status (not when "operating"). The system is accelerated to the set speed.

    Setpoint "increase" and setpoint "decrease". These keys can be used to enter the speed setpoint. Alternatively, the setpoint can also be entered via the alphanumeric keys. Note the labeling of the function keys that is shown. Using the number keys, any speed ranging between the maximum and minimum speed can be entered.

    ) )

    Function keys. These keys have different functions depending on the menu. The respective function appears in plain text above the key.

    4.2.4 Switches and pushbuttons

    Key-operated switch S11 Use the key-operated switch to select remote control or local operation. The position of the key-operated switch is evaluated using a TM15 terminal module. With the keyswitch position set to "Local", and once the "LOCAL/REMOTE" key has been pressed on the AOP30, priority for operation is given to the AOP30 or the starter. The AOP30 takes command. In local operation, the ON command in control word 1 and the main setpoint come from the AOP30 or the starter.

    Mushroom pushbutton S100 The mushroom pushbutton is used for safety shutdown. When the safety shutdown is actuated, the converter shuts down with a fault and a corresponding message appears on the display of the operator panel. Before you restart the converter you must acknowledge the fault.

  • Description 4.3 Description of the components

    26 Siemens AG Manual 2.01 6SL38503.09.2009

    WARNING Dangerous high voltage Residual voltages can cause serious injury or death. This function cannot ensure that the drive stops immediately, nor can it rule out residual voltages at the output terminals and within the device. Wait until the drive is stationary before you touch the converter.

    4.3 Description of the components

    4.3.1 Control Unit 320 (CU320)

    4.3.1.1 Overview

    Description The CU320 is the central control unit of the converter's open-loop and closed-loop control system. The connections are wired internally to the customer terminal block (for details, see the circuit manual).

  • Description 4.3 Description of the components

    Siemens AG Manual 2.01 6SL385 03.09.2009 27

    Overview

    5'

  • Description 4.3 Description of the components

    28 Siemens AG Manual 2.01 6SL38503.09.2009

    Item no. Designation Number X122 Digital inputs

    Digital inputs/outputs 4 4

    X132 Digital inputs Digital inputs/outputs

    4 4

    4.3.1.2 Description of the interfaces and other elements of the CU320 In this section, you will find descriptions of both the interfaces and the other elements of the CU320, such as PROFIBUS address switches, etc. To make these easier to find, you can refer to the item number from the overview that relates to each element.

    X100 - X102 DRIVE-CLiQ interface

    Figure 4-5 DRIVE-CLiQ interface Pin Signal name Technical data 1 TXP Transmit data + 2 TXN Transmit data - 3 RXP Receive data + 4 Reserved, do not use 5 Reserved, do not use 6 RXN Receive data - 7 Reserved, do not use 8 Reserved, do not use A + (24 V) Power supply B GND (0 V) Electronic ground Blanking plate for DRIVE-CLiQ interface: Molex, order number: 85999-3255. The maximum DRIVE-CLiQ cable length is 50 m.

    X140 Serial interface (RS232) The AOP30 for operating/parameterizing the device is connected via the serial interface. The interface is located on the underside of the CU.

    Figure 4-6 Serial interface (RS232) X140

  • Description 4.3 Description of the components

    Siemens AG Manual 2.01 6SL385 03.09.2009 29

    Pin Designation Technical data 2 RxD Receive data

    3 TxD Transmit data

    5 Ground Ground reference

    PROFIBUS address switches The PROFIBUS address switches are located under the cover. Significance Example

    21

    2))

    6

    21

    2))

    6

    6 6 Figure 4-7 PROFIBUS address switches

    Table 4-4 PROFIBUS address switches Switch Significance S1 20 = 1 S2 21 = 2 S3 22 = 4 S4 23 = 8 S5 24 = 16 S6 25 = 32 S7 26 = 64

    Note The PROFIBUS address switches are defaulted to 0 or 127. In these two settings, addresses are assigned via parameters. The address switch is behind the blanking plate. The blanking plate is part of the scope of supply.

    RESET key The RESET key is located under the cover. When the RESET key is pressed, the drive is shut down and a message indicating that the converter is in OFFLINE mode appears.

  • Description 4.3 Description of the components

    30 Siemens AG Manual 2.01 6SL38503.09.2009

    A restart is performed when the message is acknowledged.

    Measuring sockets T0; T1 and T2 Table 4-5 Measuring sockets T0, T1 and T2 Socket Function Technical data T0 Measuring socket 0 T1 Measuring socket 1 T2 Measuring socket 2 M Ground

    Voltage: 0 V to 5 V Resolution: 8 bits Load current: max. 3 mA Sustained-short-circuit-proof The reference potential is terminal M

    The measuring sockets are only suitable for bunch pin plugs with a diameter of 2 mm.

    CompactFlash card slot

    Figure 4-8 CompactFlash card slot

    CAUTION The CompactFlash card may only be inserted as shown in the figure (arrow top right). The CompactFlash card may only be inserted or removed when the Control Unit is disconnected from the power supply.

  • Description 4.3 Description of the components

    Siemens AG Manual 2.01 6SL385 03.09.2009 31

    X126 PROFIBUS interface

    Figure 4-9 Serial interface (RS232) X140

    Table 4-6 PROFIBUS interface X126 Pin Signal name Meaning Range 1 - Not assigned 2 M24_SERV Power supply for teleservice, ground 0 V 3 RxD/TxDP Receive/transmit data P (B) RS485 4 CNTRP Control signal TTL 5 DGND PROFIBUS data reference potential 6 VP Supply voltage plus 5 V +- 10 % 7 P24_SERV Power supply for teleservice, + (24 V) 24 V (20.4 V -

    28.8 V) 8 RxD/TxDN Receive/transmit data N (A) RS485 9 - Not assigned

    NOTICE No CAN cables must be connected to interface X126. If CAN cables are connected, the CU320 and other CAN bus nodes may be destroyed.

    Note A teleservice adapter can be connected to the PROFIBUS interface (X126) for remote diagnostics purposes. The power supply for the teleservice terminals 2 and 7 can have a max. load of 150 mA.

    Note PROFIBUS connectors The first and last nodes in a bus must contain terminating resistors. Otherwise, data transmission will not function correctly. The cable shield must be connected at both ends over wide-area contacts. The terminating resistors are activated in the connector.

  • Description 4.3 Description of the components

    32 Siemens AG Manual 2.01 6SL38503.09.2009

    7RQH[WEXVQRGH

    )LUVWEXVQRGH

    %XVWHUPLQDWRU%XVWHUPLQDWRU

    )URPSUHYLRXVEXVQRGH

    /DVWEXVQRGH

    RQRII

    RQRII

    RQRII

    Figure 4-10 Bus terminating resistor

    X124 Electronic power supply

    + M

    Table 4-7 Terminal block X124 Terminal Function Technical data + Electronic power supply + Electronic power supply M Electronic ground M Electronic ground

    Voltage: 24 V DC (20.4 V - 28.8 V) Current consumption: max. 0.8 A (without DRIVE-CLiQ or digital outputs) Max. current via bridge in connector: 20 A at 55C

    Max. connectable cross-section: 2.5 mm2

    Note The two "+" and "M" terminals are jumpered in the connector. This ensures the supply voltage is looped through. The current consumption increases by the value for the DRIVE-CLiQ node.

  • Description 4.3 Description of the components

    Siemens AG Manual 2.01 6SL385 03.09.2009 33

    / X122; X132 Digital inputs/outputs

    Table 4-8 Terminal block X122; X132 Terminal Designation1) Technical data 1 DI 0 2 DI 1 3 DI 2 4 DI 3 5 M1/M2 6 M

    Voltage: -3 V to 30 V Current consumption (typical): 10 mA at 24 V DC X122: Isolation: Reference potential is terminal M1 X132: Isolation: Reference potential is terminal M2 Signal level (incl. ripple) High-level: 15 V to 30 V Low-level: -3 V to 5 V Signal propagation delays: L H approx. 50 s H L: approx. 100 s

    7 DI/DO 8 8 DI/DO 9 9 M 10 DI/DO 10 11 DI/DO 11 12 M

    As input: Voltage: -3 V to 30 V Current consumption (typical): 10 mA at 24 VDC Signal level (incl. ripple) High-level: 15 V to 30 V Low-level: -3 V to 5 V Terminal numbers 8, 10, and 11 are "fast inputs" Signal propagation times for inputs/"fast inputs": L H: approx. 50 s/5 s H L: approx. 100 s/50 s As output: Voltage: 24 V DC Max. load current per output: 500 mA Sustained-short-circuit-proof

    Max. connectable cross-section: 0.5mm2

  • Description 4.3 Description of the components

    34 Siemens AG Manual 2.01 6SL38503.09.2009

    1) DI: Digital input; DI/DO: Bidirectional digital input/output; M: Electronic ground M1/M2 Ground reference

    Note The digital inputs and outputs are fixed and cannot be parameterized. An open input is interpreted as "low". The "fast inputs" can be used in conjunction with a measuring system for position sensing. X122: To enable digital inputs (DI) 0 to 3 to function, terminal M1 must be connected. X132: To enable digital inputs (DI) 4 to 7 to function, terminal M2 must be connected. The available options are as follows: Connect the included ground reference of the digital inputs, or a bridge to terminal M (Notice: This removes isolation for these digital inputs).

    Note If a momentary interruption in the voltage occurs in the 24 V supply, the digital outputs will be deactivated until the interruption has been rectified.

    Description of the LEDs

    Figure 4-11 CU320 LEDs LED Color State Description

    - OFF Electronic power supply is missing or lies outside the permissible tolerance range.

    Continuous light

    The component is ready for operation and cyclic DRIVE-CLiQ communication is taking place.

    Green

    2 Hz flashing light

    Writing to CompactFlash card.

    Continuous light

    At least one fault is present in this component.

    RDY (Ready)

    Red

    0.5 Hz flashing light

    Boot error

  • Description 4.3 Description of the components

    Siemens AG Manual 2.01 6SL385 03.09.2009 35

    LED Color State Description Green/ Red

    0.5 Hz flashing light

    Control Unit 320 is ready for operation. However, there are no software licenses.

    Continuous light

    DRIVE-CLiQ communication is being established.

    0.5 Hz flashing light

    Unable to load firmware to RAM

    Orange

    2 Hz flashing light

    Firmware checksum error, CRC error.

    - Off Cyclic communication is not (yet) running. Note: The PROFIdrive is ready for communication when the Control Unit is ready for operation (see RDY LED).

    Continuous light

    Cyclic communication is running. Green

    0.5 Hz flashing light

    Cyclic communication is not yet running fully. Possible reasons: The controller is not transferring setpoints. During isochronous (clock synchronous) operation, no Global Control (GC) or a faulty Global Control (GC) is transferred by the controller.

    DP1 (PROFIBUS cyclic operation)

    Red Continuous light

    Cyclic communication has been interrupted.

    Off Electronic power supply is missing or outside permissible tolerance range. Component is not ready. Option Board not installed or no associated drive object has been created.

    Continuous light

    Option Board is ready. Green

    0.5 Hz flashing light

    Depends on the Option Board used.

    OPT (option)

    Red Continuous light

    At least one fault is pending in this component. The Option Board is not ready (e.g., after switching on).

    MOD - Off Reserved

  • Description 4.3 Description of the components

    36 Siemens AG Manual 2.01 6SL38503.09.2009

    4.3.2 Terminal Modules TM31 and TM15

    Terminal Modules TM31 and TM15 Terminal Modules TM31 and TM15 in the converters are the central customer interface for digital and analog inputs and outputs. (The inputs and outputs are fixed and cannot be parameterized). The connections are wired internally to the customer terminal block (for details, see the circuit manual).

    Figure 4-12 Terminal Modules TM15, TM31 You have the option of expanding the customer interface to include additional TM31 and TM15 terminal modules.

    Terminal Module TM31 8 digital inputs 4 bidirectional digital inputs and outputs 2 relay outputs with changeover contact 2 analog inputs 2 analog outputs 1 temperature sensor input (KTY84-1C130 or PTC) 2 DRIVE-CLiQ sockets

  • Description 4.3 Description of the components

    Siemens AG Manual 2.01 6SL385 03.09.2009 37

    Digital inputs Voltage - 3 V to + 30 V Low level (an open digital input is interpreted as "LOW") - 3 V to + 5 V High level 15 V to 30 V Current input (at 24 V DC) typ.10mA Signal propagation times of the digital inputs L H:approx.50s

    H L:approx.100s Max. connectable cross section 1.5 mm2

    Digital outputs (sustained-short-circuit-proof) Voltage 24 V DC Max. load current per digital output 100 mA Max. total current of digital outputs 400mA Max. connectable cross section 1.5 mm2

    Analog inputs (switching between the voltage and current input via the switch) As voltage input Voltage range Internal resistance Ri

    10 V to +10V 100 kOhm

    As current input Current range Internal resistance Ri Resistance

    4mA to 20mA 20mA to +20mA 0mA to 20mA 250Ohm 11 bits + sign

    Max. connectable cross section 1.5 mm2

    Analog outputs (sustained-short-circuit-proof) Voltage range 10 V to +10 V Max. load current 3mA to +3mA Current range 4mA to 20mA,

    20mA to +20mA, 0mA to 20mA

    Max. load resistance 500 Ohm for outputs in the range 20mA to +20mA

    Resolution 11 bits + sign Max. connectable cross section 1.5 mm2

    Relay outputs (two-way contacts) Max. load current 8 A Max. switching voltage 250 V AC, 30 V DC Max. switching capacity (at 250 V AC) 2000VA (cosphi = 1)

    750 VA (cosphi = 0.4)

  • Description 4.3 Description of the components

    38 Siemens AG Manual 2.01 6SL38503.09.2009

    Relay outputs (two-way contacts) Max. switching capacity (at 30 V DC) 240 W (ohmic load) Required minimum current 100mA Max. connectable cross section 2.5 mm2

    Terminal Module TM15 24 bidirectional digital inputs and outputs (isolation in three groups of eight channels) 24 green status LEDs for indicating the logical signal status of the relevant terminal 2 DRIVE-CLiQ sockets Digital inputs Voltage 30 V to + 30 V Low-level (an open digital input is interpreted as "low") 30 V to + 5 V High level 15 V to 30 V Current consumption (at 24 V DC) 5 mA to 11 mA Typical signal propagation times for digital inputs L H: approx. 50 s

    H L: approx. 100 s Max. connectable cross section 1.5 mm2

    Digital outputs (sustained-short-circuit-proof) Voltage 24 V DC Max. load current per digital output 0.5A Output delay (ohmic load) typical max.

    L H:approx.50s H L:approx.150s L H:approx.100s H L:approx.225s

    Max. total current of the outputs (for each group) up to 60C up to 50C up to 40C When all outputs are assigned

    2A 3A 4A < 500mA/channel

    Max. connectable cross section 1.5 mm2

    4.3.3 Voltage Sensing Module (VSM10)

    Function of the Voltage Sensing Module The Voltage Sensing Module VSM10 measures the actual supply voltage values for the line-side converter. The connections are wired internally to the customer terminal block (for details, see the circuit manual).

  • Description 4.3 Description of the components

    Siemens AG Manual 2.01 6SL385 03.09.2009 39

    Interface description

    Figure 4-13 Voltage Sensing Module VSM10 1 -X500 DRIVE-CLiQ interface 2 -X524 Electronic power supply 3 -X520 analog inputs/temperature sensor connection 4 -X521 100V interface 5 -X522 690V phase voltage inputs

    Note It is not permissible to connect voltage to the 100V input (-X521) on the VSM10. Only the input for 690V(-X522) may be used

  • Description 4.3 Description of the components

    40 Siemens AG Manual 2.01 6SL38503.09.2009

    -X500 DRIVE-CLiQ interface

    %

    $ Table 4-9 -X500 DRIVE-CliQ interface Pin Signal name Technical data 1 TXP Transmit data + 2 TXN Transmit data - 3 RXP Receive data + 4 Reserved 5 Reserved 6 RXN Receive data - 7 Reserved 8 Reserved A + (24V) Power supply B M (0V) Electronic ground The maximum cable length that can be connected is 50 m.

    -X524 electronic power supply

    + M

    Table 4-10 -X524 electronic power supply Terminal Designation Technical data + Electronic power supply + Reserved G Electronic ground G Electronic ground

    Voltage: 24 VDC (20.4V 28.8V) Power consumption: max. 0.2 A Max. current via bridge in connector: 20A at 55C

    Max. connectable cross-section: 2.5 mm The two "+" and "G" terminals are jumpered in the connector and not in the unit. This ensures that the supply voltage is looped through. The maximum cable length that can be connected is 10m.

  • Description 4.3 Description of the components

    Siemens AG Manual 2.01 6SL385 03.09.2009 41

    -X520 analog inputs/temperature sensor connection

    Table 4-11 -X520 analog inputs/temperature sensor connection Terminal Designation Technical data 1 AI 0+ 2 AI 0- 3 AI 1+ 4 AI 1-

    Inputs can be parameterized in the software - Resolution: 12-bit

    5 +Temp 6 -Temp

    Temperature sensor connection KTY84-1C130/PTC

    Max. connectable cross-section: 1.5 mm In order to minimize environmental disturbances, the use of shielded cables is appropriate. The common-mode range must not be violated. This means that the analog differential voltage signals can have a maximum offset voltage of 30 V with respect to the ground potential.

    -X521 100 V inputs The 100 V inputs must not be connected.

    -X522 690 V phase inputs

    Table 4-12 -X522 690 V phase inputs Terminal Designation Technical data 1 Phase voltage U 2 Phase voltage V 3 Phase voltage W

    Phase differential voltages UUV and UVW are acquired.

    Connectable cross-section: 0.5 mm to 6 mm. The phase voltage measurement is differential. The inputs are connected to logic potential by a safety impedance

    4.3.4 Interconnecting optional connections Depending on the range of options installed, further connections have to be interconnected. For detailed information about interconnecting these options with the interfaces, see "Circuit manual". [ID 5061.00]

  • Description 4.3 Description of the components

    42 Siemens AG Manual 2.01 6SL38503.09.2009

    4.3.5 Circuit-breaker (provided by the customer)

    Requirements for the circuit-breaker provided by the customer To ensure adequate protection for converters, the circuit breaker provided by the customer must fulfill the following requirements: The maximum time between when the circuit breaker command is issued to when a

    current-free state (I = 0) is reached is 60 ms. The circuit breaker must be equipped with an undervoltage release and opened using the

    circuit breaker ON command to ensure wire-break protection. The circuit breaker is triggered and enabled by the converter closed-loop control using a

    contactor safety combination. It must never be switched on by electrical or external mechanical means without having been enabled.

    To protect the converter transformer, ensure that overcurrent protection is in place. [ID 802.00]

    4.3.6 Actual value acquisition The AVT combinations used for actual value acquisition are installed in the power unit. The relevant description can be found in the equipment documentation for the power unit.

    4.3.7 Power Stack Adapter (PSA) The Power Stack Adapter (PSA) is installed in the power unit. The relevant description can be found in the equipment documentation for the power unit.

  • Description 4.3 Description of the components

    Siemens AG Manual 2.01 6SL385 03.09.2009 43

    4.3.8 DC/DC converter

    Description DC/DC converters are used to provide a stable and safe 24 V power supply to the TM15/TM31, the circuit breaker and the SIMATIC S7 (optional).

    Figure 4-14 DC/DC converter You will find the technical data and other information in the supplementary operating instructions on the CD supplied with the converter.

  • Description 4.3 Description of the components

    44 Siemens AG Manual 2.01 6SL38503.09.2009

    4.3.9 Line filter

    Description A line filter is used to suppress interference in a power supply. You will find the technical data and other information in the supplementary operating instructions on the CD supplied with the converter.

    Figure 4-15 Line filter

    4.3.10 Sirius safety relay

    Description The 3TK2825 safety relay has two release circuits (safe circuits) in the form of normally open contact circuits.

    Figure 4-16 SIRIUS safety relay

  • Description 4.4 Description of options

    Siemens AG Manual 2.01 6SL385 03.09.2009 45

    The operating state and the function is indicated by means of three LEDs. LED Operation POWER CHANNEL1 CHANNEL2 Line

    supply EMERGENCY STOP

    ON Release circuits

    Not actuated Actuated Closed Actuated Not

    actuated Open

    On

    Not actuated Not actuated

    Open

    Fault Relay jammed

    Motor contactor jammed Defect in electronics

    Cross-circuit/ground fault in EMERGENCY STOP circuit/no supply voltage

    Open

    When the EMERGENCY STOP buttons or limit switches are released and the ON button is pressed, the internal circuit of the safety relay and the external contactors are monitored to ensure that they are functioning correctly.

    4.4 Description of options

    4.4.1 Triggering additional circuit breakers (option A04)

    Description This option can be used to trigger additional circuit breakers using TM31 and TM15.

    4.4.2 Expanded remote control via terminal block (option A06)

    Description With this option, an expanded quantity structure of control and status signals is provided on the terminal block by means of an additional TM31 and TM15 terminal module.

  • Description 4.4 Description of options

    46 Siemens AG Manual 2.01 6SL38503.09.2009

    4.4.3 Motor monitoring (option A09)

    Description With this option, the internal SIMATIC S7 is used to monitor the motor. The SIMATIC S7 transfers messages to the CU320 as message vectors and assigns them to the texts.

    4.4.4 Control and monitoring of the inrush circuit breaker via the internal SIMATIC S7 (option A11)

    Description With this option, the internal SIMATIC S7 is used to control and monitor the inrush circuit breaker. The ON command and the OFF command of the inrush circuit breaker each go to a contactor relay. In the hardware, the "inrush circuit breaker ON command" to the contactor relay for "inrush circuit breaker ON" is interlocked with an NO contact of the contactor relay for "inrush circuit breaker OFF". From the contactor relays for "inrush circuit breaker ON", two NO contacts are routed to terminals and connected in series by means of a bridge. If necessary, the bridge can be opened, making two contacts available for "inrush circuit breaker ON". From the contactor relays for "inrush circuit breaker OFF", two NO contacts in series connection and two NC contacts in series connection are made available for "inrush circuit breaker OFF". From the back-up combination unit, one contact is made available via terminals for the undervoltage tripping. The "inrush circuit breaker OFF" feedback message also goes to a contactor relay. The OFF feedback message is required in the power unit to enable grounding switch ON.

    4.4.5 Control and monitoring of the filter circuit breaker via the internal SIMATIC S7 (option A12)

    Description With this option, the internal SIMATIC S7 is used to control and monitor the filter circuit breaker. In general, the filter switch is connected upstream of the circuit breaker. However, the filter switch can also be de-energized during operation. Connection during operation depends on the power supply conditions.

  • Description 4.4 Description of options

    Siemens AG Manual 2.01 6SL385 03.09.2009 47

    4.4.6 Integrated SIMATIC S7 open-loop control with matching components (option A13)

    Description

    '3'3

    &38

    ',

    $,

    ',

    $,

    +LJKHUOHYHODXWRPDWLRQV\VWHP

    3URILEXVWR&8

    3URILEXVWRKLJKHUOHYHODXWRPDWLRQV\VWHP

    3URILEXVFDQDOVREHXVHGIRUWKH&8LQWHUIDFH

    0RGHPDQGWHOHVHUYLFHDGDSWHU

    %LQDU\WUDQVIRUPHUPRQLWRULQJVLJQDOVLQSXWRXWSXWVLGH

    [VLJQDOVZLWKRXWUHVHUYH

    $QDORJWUDQVIRUPHULQSXWRXWSXWPRQLWRULQJVLJQDOV

    [37LQSXWV

    [37ELQDU\VLJQDOV

    7UDQVIRUPHU 0RWRU

    ([DPSOHIRURSWLRQDOPRGXOHV

    6EXV

    The optional monitoring functions (e.g., modem, transformer monitoring, motor monitoring, etc.) are implemented in this open-loop control system with the associated input and output modules. Customer-specific functions (e.g., communication with a higher-level controller) can also be implemented here. During the engineering phase, these requirements were examined for feasibility, and the required modules were combined. You will find details of this in the circuit manual.

    Connecting to the excitation control unit Lateral communication between the CU320 and the excitation control unit takes place by means of the SIMATIC S7.

  • Description 4.4 Description of options

    48 Siemens AG Manual 2.01 6SL38503.09.2009

    4.4.7 Speed measurement with SMC30 for a single motor (option A51)

    Function of the SMC30 Sensor Module The SMC30 (Sensor Module Cabinet-Mounted 30) evaluates motor encoder signals. It transfers the speed and actual position value to the Control Unit via the internal DRIVE-CLiQ communication interface.

    Note If an encoder fails, you can switch to control type "encoderless".

  • Description 4.4 Description of options

    Siemens AG Manual 2.01 6SL385 03.09.2009 49

    Overview

    $ %

    A Slim type of construction B Wide type of construction X500 DRIVE-CLiQ interface X524 Electronic power supply LED displays X520 TTL with open-circuit monitoring X521 TTL, HTL, without open-circuit monitoring, motor temperature sensor KTY X531 TTL, HTL, without open-circuit monitoring, motor temperature sensor KTY Shield connection Protective conductor connection M4/1.8 Nm Figure 4-17 SMC30 Sensor Module

  • Description 4.4 Description of options

    50 Siemens AG Manual 2.01 6SL38503.09.2009

    LED displays Table 4-13 Description of the LEDs on the SMC30 LED Color State Description

    - Off Electronic power supply is missing or outside permissible tolerance range.

    Green Continuous light The component is ready for operation and cyclic DRIVE-CLiQ communication is taking place.

    Orange Continuous light DRIVE-CLiQ communication is being established. Red

    Continuous light

    At least one fault is present in this component. Note: The LED is driven irrespective of the corresponding messages being reconfigured.

    Green/ Red

    0.5 Hz flashing light

    Firmware is being downloaded.

    2 Hz flashing light

    Firmware download is complete. Waiting for POWER ON.

    READY RDY

    Green/Orange or Red/Orange

    Flashing light Component recognition via LED is activated (p0144). Note: Both options depend on the LED status when component recognition is activated via p0144 = 1.

    - Off Electronic power supply is missing or outside permissible tolerance range. Power supply 5 V.

    OUT > 5 V

    Orange

    Continuous light

    Electronic power supply for measuring system is available. Power supply >5 V. Notice You must ensure that the connected encoder can be operated with a 24 V power supply. If an encoder that is designed for a 5 V power supply is operated with a 24 V power supply, this can destroy the encoder electronics.

    Supported interfaces The SMC30 Sensor Module supports TTL/HTL incremental encoders with or without open-circuit monitoring.

    Connectable encoders Table 4-14 Connectable encoders Encoder type X521 (terminal) without

    open-circuit monitoring X531 (terminal) without open-circuit monitoring

    X520 with open-circuit monitoring

    HTL bipolar 24 V Yes Yes No TTL bipolar 24 V Yes Yes Yes TTL bipolar 5 V Yes Yes Yes

  • Description 4.4 Description of options

    Siemens AG Manual 2.01 6SL385 03.09.2009 51

    Maximum signal cable length Table 4-15 Maximum signal cable length Encoder type Maximum signal cable length in m HTL bipolar 300 TTL bipolar 100

    Because the physical transmission media is more robust, the bipolar connection should always be used. The unipolar connection should only be used if the encoder type does not output push-pull signals.

    4.4.8 Speed measurement for two motors with two SMC30s (starting converters only) (option A52).

    Function of the SMC30 Sensor Module The SMC30 (Sensor Module Cabinet-Mounted 30) evaluates motor encoder signals. It transfers the speed and actual position value to the Control Unit via the internal DRIVE-CLiQ communication interface. Two SMC30s are used to monitor two motors. This option includes the HUB 20.

    Note If an encoder fails, you can switch to control type "encoderless".

  • Description 4.4 Description of options

    52 Siemens AG Manual 2.01 6SL38503.09.2009

    Overview

    $ %

    A Slim type of construction B Wide type of construction X500 DRIVE-CLiQ interface X524 Electronic power supply LED displays X520 TTL with open-circuit monitoring X521 TTL, HTL, without open-circuit monitoring, motor temperature sensor KTY X531 TTL, HTL, without open-circuit monitoring, motor temperature sensor KTY Shield connection Protective conductor connection M4/1.8 Nm Figure 4-18 SMC30 Sensor Module

  • Description 4.4 Description of options

    Siemens AG Manual 2.01 6SL385 03.09.2009 53

    LED displays Table 4-16 Description of the LEDs on the SMC30 LED Color State Description

    - Off Electronic power supply is missing or outside permissible tolerance range.

    Green Continuous light The component is ready for operation and cyclic DRIVE-CLiQ communication is taking place.

    Orange Continuous light DRIVE-CLiQ communication is being established. Red

    Continuous light

    At least one fault is present in this component. Note: The LED is driven irrespective of the corresponding messages being reconfigured.

    Green/ Red

    0.5 Hz flashing light

    Firmware is being downloaded.

    2 Hz flashing light

    Firmware download is complete. Waiting for POWER ON.

    READY RDY

    Green/Orange or Red/Orange

    Flashing light Component recognition via LED is activated (p0144). Note: Both options depend on the LED status when component recognition is activated via p0144 = 1.

    - Off Electronic power supply is missing or outside permissible tolerance range. Power supply 5 V.

    OUT > 5 V

    Orange

    Continuous light

    Electronic power supply for measuring system is available. Power supply >5 V. Notice You must ensure that the connected encoder can be operated with a 24 V power supply. If an encoder that is designed for a 5 V power supply is operated with a 24 V power supply, this can destroy the encoder electronics.

    Supported interfaces The SMC30 Sensor Module supports TTL/HTL incremental encoders with or without open-circuit monitoring.

    Connectable encoders Table 4-17 Connectable encoders Encoder type X521 (terminal) without

    open-circuit monitoring X531 (terminal) without open-circuit monitoring

    X520 with open-circuit monitoring

    HTL bipolar 24 V Yes Yes No TTL bipolar 24 V Yes Yes Yes TTL bipolar 5 V Yes Yes Yes

  • Description 4.4 Description of options

    54 Siemens AG Manual 2.01 6SL38503.09.2009

    Maximum signal cable length Table 4-18 Maximum signal cable length Encoder type Maximum signal cable length in m HTL bipolar 300 TTL bipolar 100

    Because the physical transmission media is more robust, the bipolar connection should always be used. The unipolar connection should only be used if the encoder type does not output push-pull signals.

    4.4.9 Speed measurement for 3 motors with 3 SMC30s (starting converters only) (option A53).

    Function of the SMC30 Sensor Module The SMC30 (Sensor Module Cabinet-Mounted 30) evaluates motor encoder signals. It transfers the speed and actual position value to the Control Unit via the internal DRIVE-CLiQ communication interface. Three SMC30s are used to monitor three motors. This option includes the HUB 20.

    Note If an encoder fails, you can switch to control type "encoderless".

  • Description 4.4 Description of options

    Siemens AG Manual 2.01 6SL385 03.09.2009 55

    Overview

    $ %

    A Slim type of construction B Wide type of construction X500 DRIVE-CLiQ interface X524 Electronic power supply LED displays X520 TTL with open-circuit monitoring X521 TTL, HTL, without open-circuit monitoring, motor temperature sensor KTY X531 TTL, HTL, without open-circuit monitoring, motor temperature sensor KTY Shield connection Protective conductor connection M4/1.8 Nm Figure 4-19 SMC30 Sensor Module

  • Description 4.4 Description of options

    56 Siemens AG Manual 2.01 6SL38503.09.2009

    LED displays Table 4-19 Description of the LEDs on the SMC30 LED Color State Description

    - Off Electronic power supply is missing or outside permissible tolerance range.

    Green Continuous light The component is ready for operation and cyclic DRIVE-CLiQ communication is taking place.

    Orange Continuous light DRIVE-CLiQ communication is being established. Red

    Continuous light

    At least one fault is present in this component. Note: The LED is driven irrespective of the corresponding messages being reconfigured.

    Green/ Red

    0.5 Hz flashing light

    Firmware is being downloaded.

    2 Hz flashing light

    Firmware download is complete. Waiting for POWER ON.

    READY RDY

    Green/Orange or Red/Orange

    Flashing light Component recognition via LED is activated (p0144). Note: Both options depend on the LED status when component recognition is activated via p0144 = 1.

    - Off Electronic power supply is missing or outside permissible tolerance range. Power supply 5 V.

    OUT > 5 V

    Orange

    Continuous light

    Electronic power supply for measuring system is available. Power supply >5 V. Notice You must ensure that the connected encoder can be operated with a 24 V power supply. If an encoder that is designed for a 5 V power supply is operated with a 24 V power supply, this can destroy the encoder electronics.

    Supported interfaces The SMC30 Sensor Module supports TTL/HTL incremental encoders with or without open-circuit monitoring.

    Connectable encoders Table 4-20 Connectable encoders Encoder type X521 (terminal) without

    open-circuit monitoring X531 (terminal) without open-circuit monitoring

    X520 with open-circuit monitoring

    HTL bipolar 24 V Yes Yes No TTL bipolar 24 V Yes Yes Yes TTL bipolar 5 V Yes Yes Yes

  • Description 4.4 Description of options

    Siemens AG Manual 2.01 6SL385 03.09.2009 57

    Maximum signal cable length Table 4-21 Maximum signal cable length Encoder type Maximum signal cable length in m HTL bipolar 300 TTL bipolar 100

    Because the physical transmission media is more robust, the bipolar connection should always be used. The unipolar connection should only be used if the encoder type does not output push-pull signals.

    4.4.10 Speed measurement for 4 motors with 4 SMC30s (starting converters only) (option A54).

    Function of the SMC30 Sensor Module The SMC30 (Sensor Module Cabinet-Mounted 30) evaluates motor encoder signals. It transfers the speed and actual position value to the Control Unit via the internal DRIVE-CLiQ communication interface. Four SMC30s are used to monitor four motors. This option includes the HUB 20.

    Note If an encoder fails, you can switch to control type "encoderless".

  • Description 4.4 Description of options

    58 Siemens AG Manual 2.01 6SL38503.09.2009

    Overview

    $ %

    A Slim type of construction B Wide type of construction X500 DRIVE-CLiQ interface X524 Electronic power supply LED displays X520 TTL with open-circuit monitoring X521 TTL, HTL, without open-circuit monitoring, motor temperature sensor KTY X531 TTL, HTL, without open-circuit monitoring, motor temperature sensor KTY Shield connection Protective conductor connection M4/1.8 Nm Figure 4-20 SMC30 Sensor Module

  • Description 4.4 Description of options

    Siemens AG Manual 2.01 6SL385 03.09.2009 59

    LED displays Table 4-22 Description of the LEDs on the SMC30 LED Color State Description

    - Off Electronic power supply is missing or outside permissible tolerance range.

    Green Continuous light The component is ready for operation and cyclic DRIVE-CLiQ communication is taking place.

    Orange Continuous light DRIVE-CLiQ communication is being established. Red

    Continuous light

    At least one fault is present in this component. Note: The LED is driven irrespective of the corresponding messages being reconfigured.

    Green/ Red

    0.5 Hz flashing light

    Firmware is being downloaded.

    2 Hz flashing light

    Firmware download is complete. Waiting for POWER ON.

    READY RDY

    Green/Orange or Red/Orange

    Flashing light Component recognition via LED is activated (p0144). Note: Both options depend on the LED status when component recognition is activated via p0144 = 1.

    - Off Electronic power supply is missing or outside permissible tolerance range. Power supply 5 V.

    OUT > 5 V

    Orange

    Continuous light

    Electronic power supply for measuring system is available. Power supply >5 V. Notice You must ensure that the connected encoder can be operated with a 24 V power supply. If an encoder that is designed for a 5 V power supply is operated with a 24 V power supply, this can