Page 1: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

GRID INDIA POWER CABLES PVT. LTD.

Product Information 2009

Page 2: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO 9001:2008

c e r t i f i e d c o m p a n y

manufacturing a range of cables for the

power sector. With state-of the art

manufacturing facilities at IMT-Manesar, Gurgaon

& Bhiwadi (Rajasthan), products such as LT PVC /

XLPE Insulated Power Cables, Copper Control Cables,

Aerial Bunched Cables, Instrumentation cables and

Conductors are among the best selling products from the

company. However this is just the beginning, Ambitious

expansion plans are afoot and the company is further investing to

set a world class facility for manufacture of Power Cables upto 1.1KV

including a large expansion in MV and LT Cables. The HV cables

plant and this expansion project shall be on stream by

December’2009.

With a rapidly expanding sales and marketing footprint across the

country, the company is expected to close the year 2009 with estimated sales of

Rupees 130 Cores. Some of the prominent customers of the company are various

State Electricity Boards & PSU’s like NTPC, PWD, UPSEB, HPSEB, APTRANSCO,

KESCO, MES, DOT, DGS&D and Railways etc.

Quality and commitment are the keywords at Grid Cables. The company has in house

testing facilities as per Bureau of Indian Standards & ISO:9001:2008 Quality

Management. The company is also registered with quality Marketing Department

New Delhi.

In order to further validate the in-house quality standards, the company, has got its

products tested as per Bureau of Indian Standards by outside Govt. Laboratories like

Quality Marketing Centre Faridabad, Haryana. Regional Test Centre – New Delhi,

ERDA – Vadodara, Gujrat and Quality Marketing Centre – Mohali. The company had

been assessed technically and financially by the Quality Assurance wing of DGS&D,

New Delhi. Grid Cables is on the approved list of NTPC, approved and sole suppliers of

Uttar Pradesh Power Corporation Limited, Rajasthan Electricity Board amongst

others.

An unswerving commitment to quality, ethical business practices and constant quest

to bring better products to the market have been the guiding principles for this

relatively young and on-the-go company in the power cables industry.

GRID INDIA POWER CABLES PVT. LTD.

Page 3: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

Product Rangel LT XLPE / PVC Power Cables l LT Control Cables

l Single / Multicore Flexible Cables

l Aerial Bunched Cables

l Instrumentation Cables

l House Wires

l Concentric Cables

l Any type of Special Cables

l All type of Conductors

Log on to www.gridcables.com

Page 4: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

Sector wise List of Prominent Customers

Ajmer Vidyut Vitran Nigam Ltd.Chhatisgarh State Electricity BoardCentral Electricity Supply Co. Ltd.Dakshin Gujarat Vij Company LimitedGujarat Energy Transmission Company Ltd.Himachal Pradesh State Electricity BoardIndian Railway Project Management UnitJaipur Vidyut Vitran Nigam Ltd.Jodhpur Vidyut Vitran Nigam LimitedKanpur Electricity Supply Co. Ltd.Kerala State Electricity BoardMP Poorva Kshetra Vidyut Vitran Co. Ltd.Madhya Gujarat Vij Company LimitedMizoram Electricity BoardPaschimanchal Vidyut Vitran Nigam Ltd.Purvanchal Vidyut Vitran Nigam Ltd.Uttar Gujarat Vij Company LimitedUP Corporation Sugar Factories Federation LimitedUttar Pradesh Power Corporation Ltd.

Bharat Heavy Electricals LimitedBharat Coking Coal LimitedIndian Oil Corporation Ltd.Mahanadi Coalfields LimitedNational Thermal Power CorporationNorthern Central RailwayNorthern Coalfields LimitedOrissa Small Industries Ltd.Rastriya Chemical FertilizerTehri Hydro Development Corporation Ltd.

ABB LimitedAngelique International Ltd.Annapurna Construction & TransmissionAvadh Transformers Pvt. Ltd.A2Z Maintenance & Engineering Services Pvt. Ltd.Bajaj Hindustan Sugar Works Pvt. Ltd.Darshan Sugar Pvt. Ltd.Easun Reyrolle Ltd. Godrej & Boyce Mfg. Co. Ltd. ICOMM Tele Ltd.Job Power Infra Engineering Ltd.KEC International Ltd.Kirloskar Brothers Ltd.KVK Construction Pvt. Ltd.Maytas Infra Ltd.National Steel and Agro India Ltd.Omaxe Construction Ltd.Ramky Infrastructure Ltd.RPG Transmission Ltd.Sonalika Tractor Pvt. Ltd.The Energy & Research Institute (TERI)TATA Projects Ltd.Vaishali Steels Pvt. Ltd.Vertex EngineersVijay Electricals Ltd.

State Electricity Boards

Public Sector

Private Sector

Page 5: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

1) POWER CABLES

2) CONTROL CABLES

3) INSTRUMENTATION CABLES

4) SPECIAL CABLES

5) TEMPERATURE RESISTANT CABLES

6) MATERIAL HANDLING CABLES

7) DATA TRANSMISSION CABLES

Complete range of LT Power Cables armoured / unarmoured are available in Cu and Al Conductor to serve all applications.

Grid Cables provides LT Cu / Al Control cables with PVC / XLPE insulation. These are available in armoured / unarmoured version. The cores available are upto 1 to 61 in number and various cross sections. As an alternative to armoured cables, Grid Cables also provide Steel Wire Braided Cables (YSY) as these cables offers the advantage of mechanical strength along with high flexibility.

Grid Cables provide LT Copper Cables made from virgin PVC, Polyurethane and PE. The cores available are upto 1 to 100 in number and various cross sections. The cables are made up of bare / tinned copper wires. These cables can be provided with or without EMI protection with copper screening or aluminium foil screening. As an alternative to armoured cables, also provides Steel Wire Braided Cables (YSY) as these cables offer the advantage of mechanical strength along with flexibility.

Grid Cables has the capabilities to manufacture as per clients requirement. We can design and develop composite cables to serve our customer’s highest requirements.

We offer cables made of Teflon (250°C) for high temperature.

A wide range of PVC based cables can be used for material handling systems like lifts, EOT cranes and other similar systems.

A wide range of copper cables in screened, screened twisted, metal foiled etc. are available used for high speed data transmission with various factory automation systems involving PLC’s and other distributed control systems (DCS) and also heat resistant signal cables.

APPLICATION AREAS OF GRID CABLES PRODUCTS

Page 6: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

www.gridcables.com

LT XLPE / PVC Power Cables

Page 7: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

CROSS LINKED POLYETHYLENE (XLPE)XLPE means cross-linked polyethylene or vulcanized polyethylene. The basic material is low density polyethylene. Polyethylene is a thermoplastic material consisting of long chain of hydrocarbon molecules. At elevated temperatures these molecules tend to move relative to one another so that the material becomes increasingly deformable and will eventually melt at the temperature around 110°C.

By means of process similar to the vulcanization of rubber the polyethylene molecules can be cross-linked. The process of cross-linking or vulcanization consists of producing chemical bonds at interval between the long molecular chain to give a “ladder” effect which prevents slippage between molecules as a result of cross-linking the material becomes heat resistant and does not soften at higher temperatures. Further it has better resistance to stress cracking and good resistance to ageing in hot air. Wit the change of structure there is no adverse effect on electrical properties.

Advantage of “GRID CABLES” XLPE Cables

n Dielectric losses are very small.

n Higher current carrying capacity.

n Higher short circuit rating 250°C as against 160°C for PVC.

n “GRID CABLES” XLPE can retain flexibility down upto - 40°C

n Jointing and Termination is easy.

n Light in weight

n They are not prone to fatigue damages due to vibrations or loading cycles.

n Has better resistance to most chemicals, oils, acids, etc.

n Can be installed along cable routes without elevation limitations.

COMPARISON OF MAIN PROPERTIES BETWEEN PVC AND XLPE INSULATION

Characteristics

Permitivity (50Hz , 20°C)Dielectric loss factor (50Hz, 20°C)Volume resistivity (27°C)Max. conductor temp.Max. short circuit temp.Tensile strength Elongation at breakFlexibility at -10°CResistance to abrasion

Unit

--Ohms cm (min.)°C°CN / mm2 (min.)---

PVC

4 - 60.05 - 0.07

131x107016012.5ExcellentPoorMedium

XLPE

2.30.0004

141X109025012.5MediumGoodGood

Page 8: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

1. Maximum conductor temperature 70°C2. Ambient air temperature 40°C3. Ground temperature 30°C4. Depth of laying ( for cable laid 75cm directly in group) (1.1KV)

Ground Temp °CRating factor

Depth of laying (cms)Rating factor upto 25 sq.mm

No. of cablesSingle core D.C. Cables & multicore power cablesSingle core A.C. Cables

Air temp. °CRating factor

No. of cables

2 cables3 cables4 cables6 cables8 cables

No. of cables

4 cables5 cables8 cables

151.17

751.00

11.0

1.0

251.25

Touching0.780.680.610.530.48

Touching0.600.510.45

201.12

900.99

20.90

0.80

301.16

15cm0.810.710.650.580.54

15cm0.670.570.51

251.06

1050.98

30.80

0.75

351.09

30cm0.850.770.720.660.62

30cm0.730.630.57

301.0

1200.97

40.75

0.70

401.00

45cm0.880.810.760.710.67

45cm0.760.670.59

350.94

1500.96

50.70

0.65

350.94

60cm0.900.830.790.760.72

60cm0.780.690.61

400.87

150 & above0.95

60.65

0.60

450.90

450.79

500.80

500.70

550.69

550.60

5. Thermal resistivity of soil 150°C cm/watt6. Thermal resistivity of cable 650°C7. Max. short circuit conductor temp. 160°C8. Max Ambient Air Temperature 55°C

The current ratings in table 1& 2 based on the normal conditions of installation as described below :-

Installation method and rating factors are given in tables 1 to 6.

TABLE 1 : Rating for variations in ground temperature for cables laid directly in ground and in ducts

TABLE 5 : Rating factors for variation in depth of laying in ground

TABLE 6 : Group rating factors for cables installed in ground, separated by more than 7 cms.

TABLE 2 : Rating factors for variation in ambient air temperature

TABLE 3 : Rating factors of ground of twin and multicore cables laid directly in ground in horizontal formation

TABLE 4 : Rating factors of ground of twin and multicore cables laid directly in ground in tier formation

Rating factor for axial spacing

Rating factor for axial spacing

Page 9: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

CURRENT RATINGS (XLPE)Basic assumption and condition for installation

Max. conductor temperature at continuous operation…………………..90°C Ambient air

Temperature…………………………………………………...................40°C

Ground temperature…………………………………………..…..…..…30°C

Thermal resistivity of soil…………………………….………………….150°C Cm/W

Depth of laying……………………………………….…...……………..750mm

Max. conductor temperature for short circuit…………………………...250°C

151.12

251.14

Ground temperature °CRating factor

Air temperature °CRating factor

201.08

301.10

251.03

351.04

301.00

401.00

350.96

450.95

400.91

500.90

Rating factors for variation in ground temperature

Rating factors for vibration in ambient air temperature

No. of cables 23456

Depth of laying

7590105120150180>

Touching0.790.690.620.580.54

Upto 25 mm21.000.990.980.970.960.95

15cm0.820.750.690.650.61

25 to 300 mm21.000.980.970.960.940.93

30cm0.870.790.740.720.69

Above 300mm21.000.970.960.950.920.91

45cm0.900.830.790.760.75

Rating factors cables laid directly laid in ground in horizontal formation

Rating factor for variation in depth of laying in ground

Distance of cables

Size

Page 10: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

1 Core Aluminium PVC Armoured Power Cables

Nominal Dimensions of Armour Wire (mm)1.401.401.401.401.401.401.401.401.601.601.601.601.602.002.002.002.002.002.50

Min. Thickness of PVC Outer Sheath (mm)1.241.241.241.241.241.241.241.401.401.401.401.401.561.561.561.721.881.882.04

Overall Dia-meter (approx.) (mm)

11121314151618202224272831353940485257

Approx. Net Wt. of Cable (Kg/Km)

16018021024031036045056072083098011601450171021902730344041205090

Max. D.C. Resis-tance

0 at 20 C (Ohms/Km)7.41004.61003.08001.91001.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.07780.06050.04690.03670.0291

Max. A.C. Resist-ance at

070 C (Ohms/Km)8.89005.53003.70002.29001.44001.04000.77000.53000.38000.30000.25000.20000.15000.12000.09340.07260.05630.04400.0349

Approx. Reactance at 50 Hz (Ohms / Km)

0.1580.1480.1380.1280.1200.1140.1100.1030.1010.0960.0940.0920.0900.0880.0880.0870.0860.0830.082

Approx. Capac-itance (mFd/Km)

0.470.560.670.810.871.001.031.211.271.421.421.441.531.561.561.571.571.751.94

Direct in Ground

2 Cables Amps3644597597120145175210240270305335370410435485525570

In Duct

2 Cables Amps3342567193110130155195200220240270295335355395420445

In Air

2 Cables Amps3241567299120150185215240270305350395455490560640740

3 Cables Amps3139516686100120140175195220240270295325345390442485

3 Cables Amps3037516584100115135155170190210225245275295320350380

3 Cables Amps2735476484105130155190220250290335380435480550600720

Thick-nessof PVCInsulatio(Nom.) (mm)1.301.301.301.301.501.501.701.701.901.902.102.302.502.803.003.403.903.904.00

Min.No.of wires

1116666121515153030305353535353

No. of cores and cross sectional area

1C x 41C x 61C x 101C x 161C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000

CURRENT RATINGS

1 Core Aluminium PVC Unarmoured Power Cables

Nom. Thickness of Outer Sheath (mm)

891011121315171921232528303539444853

Overall Diameter (approx.) (mm)

1001101301602202603304105306407709201160139017602200282034304180

Net Wt. of Cable (Approx.) (Kg/Km)

7.41004.61003.08001.91001.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.07780.06050.04690.03670.0291

Max. D.C. Resis-tance

0at 20 C (Ohms/Km)

8.89005.53003.70002.29001.44001.04000.77000.53000.38000.30000.25000.20000.15000.12000.09340.07260.05630.04400.0349

Max. A.C. Resis-tance

0at 70 C (Ohms/Km)

0.1370.1270.1180.110.0.1050.1000.0980.0910.0880.0860.0850.0840.0820.0800.0800.0790.0770.0770.076

Approx. Capa-citance (mFd/Km)

0.580.680.831.011.051.221.221.431.471.621.621.621.721.741.811.761.771.982.20

Direct in Ground

2 Cables Amps

3644547597120145170205230265300335370410435485525570

In Duct

2 Cables Amps

3342567193110130155180200220240270295335355395420445

In Air

2 Cables Amps

3241567299120150185215240270305350395455490560650735

3 Cables Amps

3139516686100120140175195220240270295325345390440490

3 Cables Amps

3037516584100115135155170190210225245275295320350380

3 Cables Amps

2735476484105130155190220250290335380435480550640720

Min. No. of wires

1.001.001.001.001.201.201.401.401.601.601.802.002.202.402.603.003.403.403.40

Thickness of Insul-ation (Nom.) (mm)

1.801.801.801.801.801.801.801.801.802.002.002.002.002.002.202.202.402.402.60

No. of cores and cross secti-onal area1116666121515153030305353535353

Type

1C x 41C x 61C x 101C x 161C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000

CURRENT RATINGS

Page 11: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

1 Core Copper PVC Armoured Power Cables

1 Core Copper PVC Unrmoured Power Cables

Min. Thick-ness of PVC Outer Sheath (mm)1.241.241.241.241.241.241.241.401.401.401.401.401.561.561.561.721.881.882.04

Net Wt. of Cable(Approx.) (Kg/Km)

115143189246357456595802108313321616204825623159401949966570824810219

Overall Diameter (approx.) (mm)

11121314151618202224272831353940485257

Max. D.C. Resistance

0 at 20 C (Ohms/Km)

4.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.04700.03660.02830.02210.0176

Approx. Net Wt. of Cable (Kg/Km)

178212264325448555705941126015121819227128543464442655047161900011091

Max. A.C. Resistance

0at 70 C (Ohms/Km)

5.523.692.191.380.870.6270.4630.3210.2310.1840.1490.1200.09120.0740.05920.04680.03790.03140.0271

Max. D.C. Resis-tance

0 at 20 C (Ohms/Km)4.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.04700.03660.02830.02210.0176

Max. A.C. Resis-tance

0at 70 C (Ohms/Km)

5.523.692.191.380.8700.6270.4630.3210.2310.1840.1490.1200.09120.07390.05920.04680.03790.03140.0271

Approx. Reac-tance at 50 Hz (Ohms/ Km)

0.1580.1480.1380.1280.1200.1140.1100.1030.1010.0960.0940.0920.0900.0880.0880.0870.0860.0830.082

Approx. Reactance at 50 Hz (Ohm/Km)

0.1580.1480.1380.1280.1200.1140.1100.1030.1010.0960.0940.0920.0900.0880.0880.0870.0860.0830.082

Approx. Capaci-tance (mFd/Km)

0.470.560.670.810.871.001.031.211.271.421.421.441.531.561.561.571.571.751.94

Approx. Capaci-tance (mFd/Km)

0.470.560.670.810.871.001.031.211.271.421.421.441.531.561.561.571.571.751.94

Direct in Ground

2 Cables Amps

46577594125150180220265300340380420465500540590664733

Direct in Ground

2 Cables Amps

46577594125150180220265300340380420465500540590664733

In Duct

2 Cables Amps

42547292120140165200230255280305340370405430465523579

In Duct

2 Cables Amps

42547292120140165200230255280305340370405430465523579

In Air

2 Cables Amps

43547292125155190235275310345390445500570610680766856

In Air

2 Cables Amps

43547292125155190235275310345390445500570610680766856

3 Cables Amps

39496585110135155190220250280305345375400425470530585

3 Cables Amps

39496585110135155190220250280305345375400425470530585

3 Cables Amps

38486483110125150175200220245260285310335355375425467

3 Cables Amps

38486483110125150175200220245260285310335355375425467

3 Cables Amps

35446082110130165205245280320370425475550590660743830

3 Cables Amps

35446082110130165205245280320370425475550590660743830

Thick-ness of PVC Insu-lation (Nom.) (mm)1.31.31.31.31.51.51.71.71.91.92.12.32.52.83.03.43.93.94.0

Over all Diameter (approx.) (mm)

891011121315171921232528303539444853

Nominal Dimen-sions of Armour Wire (mm)

1.401.401.401.401.401.401.401.401.601.601.601.601.602.002.002.002.002.002.50

Normal Dimen-sions of Armour Wire

1.801.801.801.801.801.801.801.801.802.002.002.002.002.002.202.202.402.402.60

Min. No.of wires

1166666121518183034345353535353

No. of cores and cross sectional area

1C x 41C x 61C x 101C x 161C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000

No. of cores and cross sectional area

1C x 41C x 61C x 101C x 161C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000

CURRENT RATINGS

CURRENT RATINGS

Page 12: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

1 Core Aluminium XLPE Armoured Power Cables

No. of cores and cross sectional area

1C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000

Min. No. of wires

666121518183034345353535353

Thickness of XLPE Insulation (Nom.) (mm)

1.201.201.301.401.401.501.701.902.002.102.402.602.803.103.30

Nominal Dimensions of Armour Wire (mm)

1.401.401.401.401.601.601.601.601.601.602.002.002.002.002.50

Min. Thickness of PVC Outer Sheath (mm)1.24001.24001.24001.24001.40001.40001.40001.40001.40001.56001.56001.56001.72001.88002.0400

Overall Diameter (Approx.)

140001500017000190002100023000250002700029000320003700040000450005000056000

Approx. Net Wt. of Cable (Approx.)

27032039049065076088010501280153020002410299037304730

Max. D.C.Resistance

0at 20 C (Ohm/Km)

1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.07780.06050.04690.03670.0291

Max. A.C.Resistance

0at 90 C (Ohms/Km)

1.54001.11000.82000.56700.41000.32500.26500.21000.16200.13000.10230.08080.06480.05300.0444

Approx. Reactance at 50 Hz (Ohm/Km)

0.1160.1100.1030.0990.0970.0930.0910.0900.0860.0850.0850.0830.0820.0810.081

Approx. Capac-itance (mFd/Km)

0.400.470.500.550.640.670.670.670.720.750.750.770.810.880.88

Direct in Ground

Amps96114135166198225253286332376431490557600650

CURRENT RATINGS

In Air

Amps981211501872302683093604335015966938148901050

1 Core Aluminium XLPE Unrmoured Power Cables

No. of cores and cross sectional area

1C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000

Min. No. of wires

666121515153030305353535353

Thickness of Insulation (Nom.) (mm

0.900.901.001.101.101.201.401.601.701.802.002.202.402.602.80

Nom. Thickness of Outer Sheath (mm)

1.801.801.801.801.801.802.002.002.002.002.202.202.202.402.60

Overall Diameter (Approx.)

121315161820222427293336414651

Net Wt. of Cable (Approx.) (Kg/Km)

1902302803704605606908401030124015901960246031003850

Max. D.C. Resis-tance

0at 20 C (Ohms/Km)1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.07750.06050.04690.03670.0291

Max. A.C. Resistance

0at 90 C (Ohms/Km)

1.54001.11000.82000.56700.41000.32500.26500.21100.16200.13000.10230.08080.06480.05300.0444

Approx. Reactance at 50 Hz (Ohm/Km)

0.1020.0970.0920.0880.0850.0820.0820.0820.0790.0780.0770.0760.0750.0750.068

Approx. Capacitance (mFd/Km)

0.520.600.630.680.790.790.790.790.840.860.880.900.940.971.01

Direct in Ground

Amps96114135166198225253286332376431490557600650

CURRENT RATINGS

In Air

Amps981211501872302683093604335015966938148901050

1 Core Aluminium XLPE Armoured Power Cables

1 Core Aluminium XLPE Unrmoured Power Cables

Page 13: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

1 Core Copper XLPE Unarmoured Power Cables

Thickness of XLPE Insulation (Nom.) (mm)

0.900.901.001.101.101.201.401.601.701.802.002.202.402.602.80

Nom. Thickness of PVC Outer Sheath (mm)1.81.81.81.801.801.802.002.002.002.002.22.22.22.42.6

Max. D.C. Resistance

0at 20 C(Ohms/Km)

0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.04700.03660.02830.02110.0176

Approx. Net Wt. of Cable (Kg/Km)

3154095327319731207149118382356291637204708602276769587

Max. A.C. Resistance

0at 90 C(Ohms/Km)

0.930.6710.4950.3430.2470.1960.1590.1270.09650.07690.06020.04680.03620.02830.0225

Direct in Ground

Amps132156186228264300336366414450480570564660723

In Air

Amps1321561982462943363844445105706607088259451063

Approx. Reactance at 50 Hz (Ohm/Km)

0.1020.0970.0920.0880.0850.0820.0820.0820.0790.0780.0770.0760.0750.0750.068

Approx. Capacitance (mFd/Km)

0.520.600.630.680.790.790.790.790.840.860.880.900.940.971.01

CURRENT RATINGSOverall Diameter (Approx.)

121315161820222427293336414651

Min. No. of wires

666121518183034345353535353

No. of cores and cross sectional area

1C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000

1 Core Copper XLPE Armoured Power Cables

Thickness of XLPE Insulation (Nom.) (Mm)

1.201.201.301.401.401.501.701.902.002.102.402.602.803.103.30

Nom. Thickness of PVC Outer Sheath (mm)1.401.401.401.401.601.601.601.601.601.602.002.002.002.002.50

Max. D.C. Resistance

0at 20 C(Ohms/Km)

0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.04700.03660.02830.02210.0176

Approx. Net Wt. of Cable (Kg/Km)

395500634846113913901667203925843184409951186511825010386

Max. A.C. Resistance

0 at 90 C(Ohms/Km)

0.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.06020.04680.03620.02830.0225

Direct in Ground

Amps132156186228264300336366414450480570564660723

In Air

Amps11321561982462943363844445105706607088259451063

Approx. Reactance at 50 Hz (Ohm/Km)

0.1160.1100.1030.0990.0970.0930.0910.0900.0860.0850.0850.0830.0820.0810.081

Approx. Capacitance (mFd/Km)

0.400.470.500.550.640.670.670.670.720.750.750.770.810.880.88

CURRENT RATINGSOverall Diameter (Approx.)

141517192123252729323740455056

Min. Thickness of PVC Outer Sheath (mm)1.241.241.241.241.401.401.401.401.401.561.561.561.721.882.04

Min. No. of wires

666121518183034345353535353

No. of cores and cross sectional area

1C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000

1 Core Copper XLPE Unarmoured Power Cables

1 Core Copper XLPE Armoured Power Cables

Page 14: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

No. of cores and cross sectional area

2C x 1.52C x 2.52C x 42C x 62C x 102C x 162C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400

2 Core Aluminium PVC Unarmoured Power Cables

No. of cores and cross sectional area

2C x 1.52C x 2.52C x 42C x 62C x 102C x 162C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400

2 Core Aluminium PVC Armoured Power Cables

2 Core Aluminium PVC Armoured Power Cables

2 Core Aluminium PVC Unamoured Power Cables

Min. No. of wires

1111166661215151530303053

Min. No. of wires

1111166661215151530303053

Thick-ness of PVC Insulation (Nom.) (Mm)0.80.91.01.01.01.01.21.21.41.41.61.61.82.02.22.42.6

Thick-ness of PVC Insulation(Nom.) (mm)0.800.901.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60

Min. Thicknessof PVCInner-sheath(mm)0.30.30.30.30.30.30.30.30.30.30.40.40.40.50.50.60.7

Min. Thicknessof PVC Innersheath (mm)0.300.300.300.300.300.300.300.300.300.300.400.400.400.500.500.600.70

Nominal Dimensions of Armour (mm)

Strip-----4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Nom. Thickness of Outer Sheath (mm)

1.801.801.801.801.801.802.002.002.002.002.202.202.402.402.602.803.20

Wire1.401.401.401.401.401.601.601.601.601.602.002.002.002.002.502.503.15

Overall Diameter (Approx.)

10.4011.9013.4014.4015.9017.8018.7020.2022.7025.3029.0031.0034.5037.5042.5046.5052.50

Min. Thickness of PVC Outer Sheath (mm)

Strip Armour-----1.401.401.401.401.561.561.561.721.882.042.202.36

Wire Armour1.241.241.241.241.241.401.401.401.561.561.561.721.721.882.042.202.52

Net Wt. of Cable(Approx.)

1702102653203903304605506908501125131015751910236529603755

Overall Diameter (Approx.) (mm)

Strip Armour-----20.521.022.525.028.031.533.537.041.045.550.055.5

Max. D.C. Resist-ance

0 at 20 C (Ohms/Km)18.1012.107.414.613.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778

Wire Armour13.515.016.517.519.022.523.024.027.029.534.036.539.543.049.053.560.5

Max. A.C. Resistance

0 at 70 C (Ohms/Km)

21.7214.528.895.533.702.291.441.040.770.530.380.300.250.200.150.120.09

Approx. Net. Wet. Of Cable

Strip Armour (Kg/Km)-----565700810100012301520176520802500307537604560

Wire Armour(Kg/Km)3904505506407458309051040129015102060236027003175423049506560

Approx. Reactance at 50 Hz (Ohm/Km)

0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Max.D.C.Resis-tanc at

020 C (Ohms/Km)18.1012.107.414.613.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778

Approx. Capacitance (mFd/Km)

0.1400.1500.1600.1900.2200.2900.3200.3700.3700.4400.4400.4900.4900.4900.5000.5200.530

Max. A.C. Resis-tance at

070 (Ohms/Km)21.7214.528.895.533.702.291.441.040.770.530.380.300.250.200.150.120.09

Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Direct in Ground

Amps18253240557090110135160190210240275320355385

CURRENT RATINGS

Approx. Capacitance (mFd/Km)

0.140.150.160.190.220.290.320.370.370.440.440.490.490.490.500.520.53

IIn duct

Amps1621273445587692115140170190210240275305345

Direct in Ground

Amps18253240557090110135160190210240275320355385

CURRENT RATINGS

in duct

Amps1621273445587692115140170190210240275305345

In Air

Amps1621273547597899125150185210240275325365420

In Air

Amps1621273547597899125150185210240275325365420

Page 15: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

2 Core Copper PVC Armoured Power Cables

2 Core Copper PVC Armoured Power Cables

2 Core Copper PVC Unarmoured Power Cables

2 Core Copper PVC Unarmoured Power Cables

Min. Thicknessof PVCInner-sheath(mm)0.30.30.30.30.30.30.30.30.30.30.40.40.40.50.50.60.7

Nominal Dimensions of Armour (mm)

Strip-----4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Min. Thickness of PVC Outer Sheath (mm)

Strip Armour-----1.401.401.401.401.561.561.561.721.882.042.202.36

Overall Diameter (Approx.) (mm)

Strip Armour-----20.521.022.525.028.031.533.537.041.045.550.055.5

Approx. Net. Wet. Of Cable

Strip Armour (Kg/Km)-----7499941222155020352649318538354689596273849188

Max.D.C.Resis-tanc at

020 C (Ohms/Km)12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

Max. A.C. Resis-tance at

070 C (Ohms/Km)14.58.875.523.692.191.380.870.6270.4630.3210.2310.1840.1490.1200.09120.07390.0592

Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Approx. Capacitance (mFd/Km)

0.140.150.160.190.220.290.320.370.370.440.440.490.490.490.500.520.53

Direct in Ground

Amps233241507090115140165205240275310350405450490

In Air

Amps202735456078105125155195230265305350410465530

Thick-ness of PVC Insulation (Nom.) (Mm)0.80.91.01.01.01.01.21.21.41.41.61.61.82.02.22.42.6

Min. No. of wires

1111666661215181830343453

No. of cores and cross sectional area

2C x 1.52C x 2.52C x 42C x 62C x 102C x 162C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400

CURRENT RATINGS

Wire1.401.401.401.401.401.601.601.601.601.602.002.002.002.002.502.503.15

Wire Armour1.241.241.241.241.241.401.401.401.561.561.561.721.721.882.042.202.52

Wire Armour13.515.016.517.519.022.523.024.027.029.534.036.539.543.049.053.560.5

Wire Armour(Kg/Km)407482596711863912119715311836231631873775444953597100856211171

Min. Thickness of PVC Innersheath (mm)0.300.300.300.300.300.300.300.300.300.300.400.400.400.500.500.600.70

Nom. Thickness of Outer Sheath (mm)1.801.801.801.801.801.802.002.002.002.002.202.202.402.402.602.803.20

Overall Diameter (Approx.)

10.4011.9013.4014.4015.9017.8018.7020.2022.7025.3029.0031.0034.5037.5042.5046.5052.50

Net Wt. of Cable (Approx.)

194248316397515521766971125816762276276033664143535366548466

Max. A.C. Resistance

0at 20 C(Approx.) (Ohm/Km)12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

Max. D.C. Resistance

0at 70 C (Ohms/Km)14.58.875.523.692.191.380.870.6270.4630.3210.2310.1840.1490.1200.09120.07390.0532

Approx. Reactance at 50 Hz (Ohm/Km)

0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Approx. Capac-itance (mFd/Km)

0.140.150.410.470.560.760.860.981.021.181.201.311.311.311.341.411.45

Direct inGroundAmps233241507090115140165205240275310350405450491

In duct

Amps20273544587597120145180215235270300345385425

In Air

Amps202735456078105125155195230265305350410465530

Thickness of PVCInsulation (Nom.) (mm)0.800.901.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60

Min. No. of wires

1111666661215181830343453

No. of cores and cross sectional area

2C x 1.52C x 2.52C x 42C x 62C x 102C x 162C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400

CURRENT RATINGS

Page 16: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

2 Core Aluminium XLPE Armoured Power Cables

2 Core Aluminium XLPE Unarmoured Power Cables

No. of cores and cross sectional area

2C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400

No. of cores and cross sectional area

2C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400

Min. No. of wires

6661215151530303053

Min. No. of wires

6661215151530303053

Thick-ness of PVC Insulation (Nom.) (Mm)0.900.901.001.101.101.201.401.601.701.802.00

Thickness of Insulation(Nom.) (mm)

0.900.901.001.101.101.201.401.601.701.802.00

Min. Thicknessof PVCInner-sheath(mm)0.30.30.30.30.40.40.40.50.50.60.6

Nominal Dimensions of Armour (mm)

Strip1.601.601.601.602.002.002.002.002.502.502.50

Min. Thickness of inner sheath (mm)

0.30.30.30.30.40.40.40.50.50.60.6

Wire4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Min. Thickness of PVC Outer Sheath (mm)

Strip Armour1.401.401.401.561.561.561.721.882.042.202.36

Nom. Thickness of Outer Sheath (mm)

2.002.002.002.002.202.202.202.402.602.803.00

Wire Armour1.401.401.401.561.561.561.721.721.882.042.36

Overall Diameter (Approx.)

1820222528303336404449

Overall Diameter (Approx.) (mm)

Strip Armour2122242731333639454854

Wire Armour1921232628313437414450

Net Wt. of Cable (Approx.)

420.00510.00630.00800.001040.001260.001480.001840.002250.002810.003530.00

Approx. Net. Wet. Of Cable

Strip Armour (Kg/Km)840970115014301900222025503030393046505600

Max. D.C. Resistance

0at 20 C (Ohms/Km)

1.200.870.640.440.320.250.210.160.130.100.08

Wire Armour(Kg/Km)63074090011401390166019302320279033904230

Max. A.C. Resistance

0at 90 C (Ohms/Km)

1.541.110.820.570.410.330.270.210.160.130.10

Max.D.C.Resis-tanc at

020 C (Ohms/Km)1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778

Max. A.C. Resis-tance at

090 C (Ohms/Km)1.54001.11000.82000.56700.41000.32500.26500.21100.16200.13000.1023

Approx. Reactance at 50 Hz (Ohm/Km)

0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

Approx. React-ance at 50 Hz (Ohm/Km)0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

Approx. Capacitance (mFd/Km)

0.200.230.240.260.290.290.290.290.310.330.33

Approx. Capacitance (mFd/Km)

0.200.230.240.260.290.290.290.290.310.330.33

CURRENT RATINGS

Direct in Ground

Amps112138169200238262300344400444481

CURRENT RATINGS

Direct in Ground

Amps112138169200238262300344400444481

In Air

Amps98124156188231262300344406456525

In Air

Amps98124156188231262300344406456525

2 Core Aluminium XLPE Armoured Power Cables

2 Core Aluminium XLPE Unarmoured Power Cables

Page 17: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

2 Core Copper XLPE Armoured Power Cables

2 Core Copper XLPE Armoured Power Cables

2 Core Copper XLPE Unamoured Power Cables

Thick-ness of XLPE Insu-lation (Nom.) (Mm)

0.900.901.001.101.101.201.401.601.701.802.00

Min. Thick-ness of PVC inner sheath (mm)

0.30.30.30.30.40.40.40.50.50.60.6

Max.D.C. Resis-tance at

020 C (Ohms/Km)

0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

Max. A.C. Resis-tance at

090 C (Ohms/Km)

0.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602

Approx. Reac-tance at 50 Hz (Ohm/Km)

0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

Approx. Capac-itance (mFd/Km)

0.200.230.240.260.290.290.290.290.310.330.33

Nominal Dimensions of Armour (mm)

Strip4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Min. Thickness of PVC Outer Sheath (mm)

Strip Armour1.401.401.401.561.561.561.721.882.042.202.36

Overall Diameter (Approx.) (mm)

Strip Armour21.122.024.027.031.033.036.039.045.048.054.0

Approx. Net. Wet of Cable

Strip Armour (Kg/Km)10591299160721062847342940624936648778319688

Direct in GroundAmps144175206256300344388438506562612

In Air

Amps131150194244288331381438512581662

Wire1.601.601.601.602.002.002.002.002.502.502.50

Wire Armour1.401.401.401.561.561.561.721.721.882.042.36

Wire Armour19.021.023.026.028.031.034.037.041.044.050.0

Wire Armour (Kg/Km)8721087137918452388291835004295544966788437

CURRENT RATINGSMin. No. of wires

6661215181830343453

No. of cores and cross sectional area

2C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400

Thickness of XLPE Insulation (Nom.) (mm)

0.900.901.001.101.101.201.401.601.701.802.00

Min. Thickness of PVC inner sheath (mm)0.30.30.30.30.40.40.40.50.50.60.6

Overall Diameter (Approx.)

18.020.022.025.028.030.033.036.040.044.049.0

Approx. Net Wt. of Cable (Approx.)

672865111415192048252630623813491761077732

Max. D.C. Resistance

0 at 20 C(Ohms/Km)

0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

Direct in Ground

Amps144175206256300344388438506562612

In Air

Amps131150194244288331381438512581662

Max. A.C. Resistance

0at 90 C (Ohms/Km)

0.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602

Approx. Reactance at 50 Hz (Ohm/Km)

0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

Approx. Capacitance (mFd/Km)

0.200.230.240.260.290.290.290.290.310.330.33

CURRENT RATINGSNom. Thickness of PVC Outer Sheath (mm)2.002.002.002.002.202.202.202.402.602.803.00

Min. No. of wires

6661215181830343453

No. of cores and cross sectional area

2C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400

2 Core CopperXLPE Unarmoured Power Cables

Page 18: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

3 Core Aluminium pvc Armoured Power Cables

3 Core Aluminium pvc Armoured Power Cables

3 Core Aluminium pvc Unarmoured Power Cables

No. of cores and cross sectional area3C x 1.53C x 2.53C x 43C x 63C x 103C x 163C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400

3 Core Aluminium PVC Unarmoured Power Cables

No. of cores and cross sectional area

3C x 1.53C x 2.53C x 43C x 63C x 103C x 163C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400

Min. No. of wires

1111166661215151530303053

Min. No.Of wires

1111166661215151530303053

Thickness of pvc Insulation (nom) (min.)

0.80.91.01.01.01.01.21.21.41.41.61.61.82.02.22.42.6

Min. Thick-ness of Innersheath (mm)0.30.30.30.30.30.30.30.30.30.40.40.40.50.50.60.60.7

Thick-ness of PVC Insulation (Nom.) (Mm)0.800.901.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60

Nominal Dimensions of Armour (mm)

Strip-----4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Min. Thick-ness of PVC Inner-sheath (mm)0.300.300.300.300.300.300.300.300.300.400.400.400.500.500.600.600.70

Wire1.401.401.401.401.401.601.601.601.602.002.002.002.002.502.502.503.15

Min. Thickness of PVC Outer Sheath (mm)

Strip Armour-----1.401.401.401.561.561.561.721.881.882.202.362.52

Nom. Thick-ness of Outer Sheath (mm)1.801.801.801.801.801.802.002.002.002.202.202.202.402.602.803.003.40

Wire Armour1.241.241.241.241.401.401.401.401.561.561.721.721.882.042.202.362.68

Overall Diameter (Approx.)

11.0012.0013.5014.4015.6016.8020.2021.7024.8028.5031.6034.7038.9044.5049.0053.5062.00

Overall Diameter (Approx.) (mm)

Strip Armour-----19.522.524.027.530.534.538.041.545.552.056.564.5

Wire Armour14.015.016.517.519.521.024.025.529.033.037.040.044.049.055.060.069.5

Net Wt. of Cable (Approx.)

19023030035043543560073092012151545183022502760351542755400

Approx. Net. Wet of Cable

Strip Armour (Kg/Km)-----6808801025131016301990237528253365425051406270

Max. D.C. Resis-tance

0at 20 C (Ohm/Km)

18.1012.107.414.613.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778

Wire Armour (Kg/Km)42050059568583089011201305160521602645305035604590562066508720

Max. D.C. Resistance

0at 20 C (Ohms/Km)

18.1012.107.414.613.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778

Max. A.C. Resis-tance

0at 70 C (Ohms/Km)21.7214.528.895.533.702.291.441.040.770.530.380.300.250.200.150.120.09

Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Max. A.C. Resistance

0at 70 C (Ohms/Km)

21.7214.528.895.533.702.291.441.040.770.530.380.300.250.200.150.120.09

Approx. Capa-citance (mFd/Km)

0.1400.1500.4100.4700.5600.7600.8600.9801.0201.1801.2001.3101.3101.3101.3401.4101.450

Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Approx.Capaci-tance (mFd/Km)

0.140.150.410.470.560.760.860.981.021.181.201.311.311.311.341.411.45

Direct in GroundAmps

1621283546607692110135165185210235275305335

CURRENT RATINGS

Direct in GroundAmps1621283546607692110135165185210235275305335

CURRENT RATINGS

In duct

Amps

141823303950637795115140155175200235260290

In duct

Amps141823303950637795115140155175200235280290

In Air

Amps1318233040517086105130155180205240280315375

In AirAmps

1318233040517086105130155180205240280315375

Page 19: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

3 Core Copper pvc Unarmoured Power Cables

Min. Thick-ness of PVC Inner-sheath (mm)0.30.30.30.30.30.30.30.30.30.40.40.40.50.50.60.60.7

Nom. Thick-ness of Outer Sheath (mm)1.801.801.801.801.801.802.002.002.002.202.202.202.402.602.803.003.40

Overall Diameter (Approx.)

11.0012.0013.5014.4015.6016.8020.2021.7024.8028.5031.6034.7038.9044.5049.0053.5062.00

Net Wt. of Cable (Approx.)

218284372470629723106313671783245832764009493961147928981712540

Max. A.C. Resis-tance

0at 20 C

(Ohm/Km)14.508.875.523.692.191.380.870.6270.4630.3210.2310.1840.1490.1200.09120.07390.0592

Max. D.C. Resis-tance

0at 70 C (Ohms/Km)12.107.414.613.081.831.150.730.5240.3870.2680.1930.1530.1240.0990.0750.0600.0470

Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.090.090.0870.0870.0870.0870.0860.086

Approx. Capa-citance (mFd/Km)

0.1400.1500.4100.4700.5600.7600.8600.9801.0201.1801.2001.3101.3101.3101.3401.4101.450

Direct in GroundAmps

21273645607799120145175210240270300345385425

In duct

Amps

1724303850648199125150175195225255295335360

In AirAmps

17243039576690110135165200230265305355400455

Thick-ness of PVC Insulation (Nom.) (Mm)0.80.91.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60

Min. No.Of wires

1111666661215181830343453

No. of cores and cross sectional area

3C x 1.53C x 2.53C x 43C x 63C x 103C x 163C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400

CURRENT RATINGS

Thickness of PVC Insulation (Nom.) (Mm)

0.80.91.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60

Nominal Dimensions of Armour (mm)

Strip0.30.30.30.30.30.30.30.30.30.40.40.40.50.50.60.60.7

Min. Thickness of PVC Outer Sheath (mm)

Strip Armour-----1.41.41.41.561.561.561.721.881.882.202.362.52

Overall Diameter (Approx.) (mm)

Strip Armour-----19.522.524.027.530.534.538.041.545.552.056.564.5

Approx. Net. Wet of Cable

Strip Armour (Kg/Km)-----9491339168721702863375345685556676387191066513490

Max. D.C. Resistance

0at 20 C(Ohms/Km)

12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

Max. A.C. Resistance

0at 70 C (Ohms/Km)

14.58.875.523.692.191.380.870.6270.4630.3210.2310.1840.1490.1200.09120.07390.0592

Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Approx.Capaci-tance (mFd/Km)

0.140.150.410.470.560.760.860.981.021.181.201.311.311.311.341.411.45

Direct in GroundAmps21273645607799120145175210240270300345385425

In Air

Amps17243039576690110135165200230265305355400455

Min. No. of wires

1111666661215181830343453

Min. Thickness of PVC Inner-sheath (mm)0.30.30.30.30.30.30.30.30.30.40.40.40.50.50.60.60.7

No. of cores and cross sectional area3C x 1.53C x 2.53C x 43C x 63C x 103C x 163C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400

CURRENT RATINGS

Wire1.41.41.41.41.41.61.61.61.62.02.02.02.02.52.52.53.2

Wire Armour1.241.241.241.241.401.401.401.401.561.561.721.721.882.042.202.362.68

Wire Armour14.015.016.517.519.521.024.025.529.033.037.540.544.049.055.560.069.5

Wire Armour (Kg/Km)4425426637891017115315531915243033554362522162617948100621213215954

3 Core Copper ovc Armoured Power Cables

3 Core Copper pvc Armoured Power Cables

3 Core Copper pvc Unarmoured Power Cables

Page 20: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

3 Core Aluminium XLPE Armoured Power Cables

3 Core Aluminium XLPE Armoured Power Cables

3 Core Aluminium XLPE Unarmoured Power Cables

No. ofcores andcross sectional area

3C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400

3 Core Aluminium XLPE Unarmoured Power Cables

No. of cores and cross sectional area

3C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400

Min. No.ofwires

6661215151530303053

Min. No. of wires

6661215151530303053

Thicknessof Insul-ation (Nom.) (mm)

0.90.911.11.11.21.41.61.71.82

Thickness of Insulation (Nom.) (mm)

0.900.901.001.101.101.201.401.601.701.802.00

Min. Thickness of Innersheath (mm)

0.30.30.30.40.40.40.50.50.60.60.7

Nominal Dimensions of Armour (mm)

Strip

1.61.61.62.02.02.02.02.52.52.53.15

Min. Thickness of inner sheath (mm)

0.300.300.300.400.400.400.500.500.600.600.70

Wire

4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Min. Thickness of Outer Sheath (mm)

Strip Armour1.41.41.561.561.561.721.882.042.22.362.68

Nom. Thickness of Outer Sheath (mm)

2222.22.22.22.42.62.833.2

Wire Armour1.41.41.41.561.561.561.721.882.042.22.52

Overall Diameter (Approx.)

2123252932353943485359

Overall Diameter (Approx.) (mm)

Strip Armour2325283235394247535865

Wire Armour21.323263032363944495460

Net Wt. of Cable (Approx.)

52064070010801350164020202490315038904840

Approx. Net. Wet of Cable

Strip Armour (Kg/Km)9801160132019502320277032604220511060308010

Max. D.C. Resistance

0at 20 C(Ohms/Km)

1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778

Wire Armour (Kg/Km)770900100014501750210025203050377045405640

Max. D.C. Resis-tance at

020 C (Ohms/Km)1.20.8680.6410.4430.3200.2530.2060.1640.1250.10.0778

Max. A.C. Resistance

0at 90 C(Ohms/Km)

1.54001.11000.82000.56700.41000.32500.26500.21100.16200.13000.1023

Max. A.C. Resistance

0at 90 C (Ohms/Km)

1.541.110.820.5670.410.3250.2650.2110.1620.130.1023

Approx. Reactance at 50 Hz (Ohm/Km)

0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

Approx. Reactance at 50 Hz (Ohm/Km)

0.080.080.0780.0770.0740.0720.0720.0720.0720.0710.07

Approx. Capacitance (mFd/Km)

0.200.230.240.260.290.290.290.290.310.330.33

Approx. Capaci-tance (mFd/Km)

0.20.230.240.260.290.290.290.290.310.330.33

CURRENT RATINGS

In duct

Amps94113133164196223249282326367418

Direct in Ground

Amps94113133164196223249282326367418

CURRENT RATINGS

In Air

Amps96117142179221257292337399455530

In Air

Amps96117142179221257292337399455530

Page 21: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

Direct in GroundAmps119144174210252288324360414462510

In Air

Amps108132162198240276318366426480546

Wire1.601.601.602.002.002.002.002.502.502.503.15

Wire Armour1.401.401.401.561.561.561.721.882.042.202.52

Wire Armour1.401.401.401.561.561.561.721.882.042.202.52

Wire Armour (Kg/Km)21.323.026.030.032.036.039.044.049.054.060.0

Wire Armour (Kg/Km)117714691872257033334085498861377838966712190

3 Core Copper XLPE Armoured Power Cables

Min.Thick-ness of PVC Innersheath(mm)

0.30.30.30.40.40.40.50.50.60.60.7

Nominal Dimensions of Armour (mm)

Strip4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Min. Thickness of PVC Outer Sheath (mm)

Strip Armour1.401.401.561.561.561.721.882.042.202.362.68

Overall Diameter (Approx.) (mm)

Strip Armour23.025.028.032.035.039.042.047.053.058.065.0

Overall Diameter (Approx.) (mm)

Strip Armour23.025.028.032.035.039.042.047.053.058.065.0

Approx. Net. Wet of Cable

Strip Armour (Kg/Km)1373171321713052386847255691724591121108714437

Max. D.C.Resis-tance

0 at 20 C (Ohms/Km)0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

Max. A.C.Resistance at

090 C (Ohms/Km)0.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602

Approx. Reac-tance at 50 Hz (Ohm/Km)0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

Approx. Capacitance (mFd/Km)

0.200.230.240.260.290.290.290.290.310.330.33

Thickness of XLPE Insulation (Nom.) (mm)

0.900.901.001.101.101.201.401.601.701.802.00

Min. No. of wires

6661215181830343453

No. of cores and cross sectional area

3C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400

CURRENT RATINGS

Thickness of XLPE Insulation (Nom.) (mm)

0.900.901.001.101.101.201.401.601.701.802.00

Min. Thickness of inner sheath (mm)

0.30.30.30.40.40.40.50.50.60.60.7

Overall Diameter (Approx.)

21.023.025.029.032.035.039.043.048.053.059.0

Net Wt. of Cable (Approx.)

93512191578222229483659451156007249900111429

Direct in Ground

Amps119144174210252288324360414462510

In Air

Amps108132162198240276318366426480546

Max. D.C. Resistance

0at 20 C (Ohms/Km)

0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

Max. A.C. Resistance

0at 90 C (Ohms/Km)

0.9300.6710.4950.3430.2470.1960.1560.1270.09650.07690.0602

Approx. Reactance at 50 Hz (Ohm/Km)

0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

Approx. Capacitance (mFd/Km)

0.200.230.240.260.290.290.290.290.310.330.33

CURRENT RATINGSNom. Thickness of PVC Outer Sheath (mm)2.002.002.002.202.202.202.402.602.803.003.20

Min. No. of wires

6661215181830343453

No. of cores and cross sectional area

3C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400

3 Core Copper XLPE Unarmoured Power Cables

3 Core Copper XLPE Armoured Power Cables

3 Core Copper XLPE Unarmoured Power Cables

Page 22: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

3.5 Core Aluminium PVC Armoured Power Cables

No. ofcores andcross sectional area

3.5C x 25/163.5C x 35/163.5C x 50/253.5C x 70/353.5C x 95/503.5C x 120/703.5C x 150/703.5C x 185/953.5C x 240/1203.5C x 300/1503.5C x 400/185

No. of cores and cross sectional area3.5C x 25/163.5C x 35/163.5C x 50/253.5C x 70/353.5C x 95/503.5C x 120/703.5C x 150/703.5C x 185/953.5C x 240/1203.5C x 300/1503.5C x 400/185

3.5 Core Aluminium PVC Unarmoured Power Cables

Min. No.ofwires

6/6.6/6.6/6.12/6.15/6.15/12.15/12.30/15.30/15.30/15.53/30.

Min. No. of wires

6/6.6/6.6/6.12/6.15/6.15/12.15/12.30/15.30/15.30/15.53/30.

Thick-nessof Insul-ation (Nom.) (Mm)1.2/1.01.2/1.01.4/1.21.4/1.21.6/1.41.6/1.41.8/1.42.0/1.62.2/1.62.4/1.82.6/2.0

Thickness of PVC Insulation (Nom.) (mm)1.2/1.01.2/1.01.4/1.21.4/1.21.6/1.41.6/1.41.8/1.42.0/1.62.2/1.62.4/1.82.6/2.0

Min. Thick-ness of Innersheath (mm)0.300.300.300.400.400.500.500.500.600.600.70

Nominal Dimensions of Armour (mm)

Strip

4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Min. Thickness of PVC Innersheath (mm)0.300.300.300.400.400.500.500.500.600.600.70

Wire

1.601.601.602.002.002.002.002.502.503.153.15

Nom. Thickness of Outer Sheath (mm)2.002.002.002.202.202.402.402.603.003.203.40

Min. Thickness of Outer Sheath (mm)

Strip Armour1.401.401.561.561.561.721.882.042.202.362.68

Wire Armour1.401.401.561.561.721.881.882.042.362.522.68

Overall Diameter (Approx.)

22.7024.0027.0031.0035.0040.0042.3046.8054.5059.0067.00

Overall Diameter (Approx.) (mm)

Strip Armour25.026.029.533.537.541.045.550.057.061.570.0

Net Wt. of Cable (Approx.)

700830106013951795220025753150406049706210

Wire Armour26.527.531.036.040.043.048.053.560.066.075.0

Max. D.C. Resistance

0at 20 C (Ohm/Km)

1.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778

Approx. Net. Wet of Cable

Strip Armour (Kg/Km)10001170147018102305276032153900484058357250

Wire Armour (Kg/Km)12601450180524053015354540305300639082109900

Max. A.C. Resistance

0at 70 C (Ohms/Km)

1.441.040.770.530.380.300.250.200.150.120.09

Max. D.C. Resis-tance at

020 C (Ohms/Km)1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778

Approx. Reactance at 50 Hz (Ohm/Km)

0.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Max. A.C. Resis-tance

0at 70 C (Ohms/Km)1.441.040.770.530.380.300.250.200.150.120.09

Approx. Capacitance (mFd/Km)

0.860.981.021.181.201.311.311.311.341.411.45

Approx. React-anceat 50 Hz (Ohm/Km)0.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Approx. Capaci-tance (mFd/Km)

0.860.981.021.181.201.311.311.311.341.411.45

Direct inGroundAmps7692110135165185210235275305335

CURRENT RATINGS

Direct in GroundAmps7692100135165185210235275305335

CURRENT RATINGS

In duct

Amps637795115140155175200235260290

In duct

Amps637795115140155175200235260290

In Air

Amps7086105130155180205240280315375

In Air

Amps7086105130155180205240280315375

3.5 Core Aluminium PVC Unarmoured Power Cables

3.5 Core Aluminium PVC Armoured Power Cables

Page 23: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

Min. Thickness of PVC Innersheath (mm)0.300.300.300.400.400.500.500.500.600.600.70

Nom. Thickness of Outer Sheath (mm)2.002.002.002.202.202.402.402.603.003.203.40

Overall Diameter (Approx.)

22.7024.0027.0031.0035.0040.0042.3046.8054.5059.0067.00

Net Wt. of Cable (Approx.)

1255156120712845380447885673708091941140014395

Max. D.C. Resistance

0at 20 C (Approx.) (Ohm/Km)0.730.5240.3870.2680.1930.1530.1240.0990.0750.0600.0470

Max. D.C. Resistance

0at 70 C (Ohms/Km)

0.870.6270.4630.3210.2310.1840.1490.12000.09120.07390.0592

Approx. Reactance at 50 Hz (Ohm/Km)

0.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Approx. Capacitance (mFd/Km)

0.860.981.021.181.201.311.311.311.341.411.45

Direct inGroundAmps99120145175210240270300345385425

In duct

Amps8199125150175195225255295335360

In Air

Amps90110135165200230265305355400455

Thickness of PVC Insulation (Nom.) (mm)1.2/1.01.2/1.01.4/1.21.4/1.21.6/1.41.6/1.41.8/1.42.0/1.62.2/1.62.4/1.82.6/2.0

Min. No. of wires

6/6.6/6.6/6.12/6.15/6.18/12.18/12.30/15.34/18.34/18.53/30.

No. of cores and cross sectional area

3.5C x 25/163.5C x 35/163.5C x 50/253.5C x 70/353.5C x 95/503.5C x 120/703.5C x 150/703.5C x 185/953.5C x 240/1203.5C x 300/1503.5C x 400/185

CURRENT RATINGS

3.5 Core Copper PVC Unarmoured Power Cables

Thickness of PVC Insulation (Nom.) (mm)

1.2/1.01.2/1.01.4/1.21.4/1.21.6/1.41.6/1.41.8/1.42.0/1.62.2/1.62.4/1.82.6/2.0

Min. Thickness of PVC Inner-sheath(mm)0.30.30.30.40.40.50.50.50.60.60.7

Nominal Dimensions of Armour (mm)

Strip4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Min. Thickness of PVC Outer Sheath (mm)

Strip Armour1.401.401.561.561.561.721.882.042.202.362.68

Overall Diameter (Approx.) (mm)

Strip Armour25.026.029.533.537.541.045.550.057.061.570.0

Approx. Net. Wet of Cable Strip

Armour(Kg/Km)15841896248033024349533563597821100271227715402

Max. A.CResista-nce at

070 C (Ohms/Km)0.870.6270.4630.3210.2310.1840.1490.1200.09120.07390.0592

Approx. React-ance at 50 Hz (Ohm/Km)0.0970.0970.0940.0900.090.0870.0870.0870.0870.0860.086

Approx. Capac-itance (mFd/Km)

0.860.981.021.181.201.311.311.311.341.411.45

Direct inGroundAmps99120145175210240270300345385425

In Air

Amps90110135165200230265305355400455

Min. No. of wires

6/6.6/6.6/6.12/6.15/6.18/12.18/12.30/15.34/18.34/18.53/30.

No. of cores and cross sectional area

3.5C x 25/163.5C x 35/163.5C x 50/253.5C x 70/353.5C x 95/503.5C x 120/703.5C x 150/703.5C x 185/953.5C x 240/1203.5C x 300/1503.5C x 400/185

CURRENT RATINGS

Wire1.601.601.602.002.002.002.002.502.503.153.15

Wire Armour1.401.401.561.561.721.881.882.042.362.522.68

Wire Armour26.527.531.036.040.043.048.053.560.066.075.0

Wire Armour(Kg/Km)18282146276338764976601171169105114641460018083

Max. D.C. Resistance

0at 20 C (Ohms/Km)

0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

3.5 Core Copper PVC Armoured Power Cables

3.5 Core Copper PVC Armoured Power Cables

3.5 Core Copper PVC Unarmoured Power Cables

Page 24: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

3.5 Core Aluminium XLPE Armoured Power Cables

No. of cores and cross sectional area3.5C x 253.5C x 353.5C x 503.5C x 703.5C x 953.5C x 1203.5C x 1503.5C x 1853.5C x 2403.5C x 3003.5C x 400

3.5 Core Aluminium XLPE Unarmoured Power Cables

No. of cores and cross sectional area

3.5C x 253.5C x 353.5C x 503.5C x 703.5C x 953.5C x 1203.5C x 1503.5C x 1853.5C x 2403.5C x 3003.5C x 400

Min. No. of wires

6/6.6/6.6/6.12/6.15/6.15/12.15/12.30/15.30/15.30/15.53/30.

Min. No. of wires

6/6.6/6.6/6.12/6.15/6.15/12.15/12.30/15.30/15.30/15.53/30.

Thickness of Insulation

(min.)

0.90.91.01.11.11.21.41.61.71.82.0

Thickness of Insulation

(nom.)

0.900.901.001.101.101.201.401.601.701.802.00

(nom)

0.70.70.90.91.01.11.11.11.21.41.6

(mm)

0.700.700.900.901.001.101.101.101.201.401.60

Min. Thick-ness of Innersheath (mm)0.30.30.30.40.40.40.50.50.60.60.7

Min. Thickness of inner sheath (mm)

0.30.30.30.40.40.40.50.50.60.60.7

Nominal Dimensions of Armour (mm)

Strip1.601.601.602.002.002.002.002.502.502.503.15

Wire4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Nom. Thickness of Outer Sheath (mm)

2.002.002.002.202.202.202.402.602.803.003.40

Min. Thickness of Outer Sheath (mm)

Strip Armour1.401.401.561.561.561.721.882.042.202.362.68

Overall Diameter (Approx.)

2225273135384247525766

Wire Armour1.401.401.401.561.561.721.721.882.042.202.52

Overall Diameter (Approx.) (mm)

Strip Armour2527303438424651576171

Net Wt. of Cable (Approx.)

60072091012301550205023002860361044105650

Wire Armour2325283235394347535766

Max. D.C. Resistance

0at 20 C (Ohms/Km)

1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778

Approx. Net. Wet of Cable

Strip Armour (Kg/Km)11101290158021702620316036704780576067909040

Wire Armour (Kg/Km)8701030123016102000246028403480429051706480

Max. A.C. Resistance

0at 90 C(Ohms/Km)

1.54001.11000.82000.56700.41000.32500.26500.21100.16200.13000.1023

Max. D.C. Resis-tance at

0 20 C (Ohms/Km)1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778

Approx. Reactance at 50 Hz (Ohm/Km)

0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

Max. A.C. Resis-tance at

090 C (Ohms/Km)1.54001.11000.82000.56700.41000.32500.26500.21100.16200.13000.1023

Approx. React-ance at 50 Hz (Ohm/Km)0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

Approx. Capacitance (mFd/Km)

0.200.230.240.260.290.290.290.290.310.330.33

Approx.Capaci-tance (mFd/Km)

0.200.230.240.260.290.290.290.290.310.330.33

Direct in Ground

Amps94113133164196223249282326367418

CURRENT RATINGS

CURRENT RATINGS

Direct in GroundAmps94113133164196223249282326367418

In Air

Amps96117142179221257292337399455530

In Air

Amps96117142179221257292337399455530

3.5 Core Copper PVC Armoured Power Cables

3.5 Core Copper PVC Unarmoured Power Cables

Page 25: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

3.5 Core Copper XLPE Unarmoured Power CablesMin. No. of wires

6/6.6/6.6/6.12/6.15/6.18/12.18/15.30/15.34/18.34/18.53/30.

Thickness of XLPE Insulation (Nom.) (mm)

0.9/0.70.9/0.71.0/0.91.1/0.91.1/1.01.2/1.11.4/1.11.6/1.11.7/1.21.8/1.42.0/1.6

Nom. Thickness of PVC Outer Sheath (mm)2.002.002.002.202.202.202.402.602.803.003.40

Overall Diameter (Approx.)

22.025.027.031.035.038.042.047.052.057.066.0

Direct in Ground

Amps119144174210252288324360414462510

In Air

Amps108132162198240276318366426480546

Net Wt. of Cable (Approx.)

1102138918362567341643175178650883891040113271

Max. D.C. Resistance

0 at 20 C (Ohms/Km)

0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

Max. A.C. Resistance

0 at 90 C (Ohms/Km)

0.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602

Approx. Capacitance (mFd/Km)

0.200.230.240.260.290.290.290.290.310.330.33

Approx. Reactance at 50 Hz (Ohm/Km)

0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

CURRENT RATINGSMin. Thickness of PVC Inner-sheath (mm)0.30.30.30.40.40.40.50.50.60.60.7

No. of cores and cross sectional area

3.5C x 25/163.5C x 35/163.5C x 50/253.5C x 70/353.5C x 95/503.5C x 120/703.5C x 150/703.5C x 185/953.5C x 240/1203.5C x 300/1503.5C x 400/185

3.5 Core Copper XLPE Armoured Power CablesNominal Dimensions of Armour (mm)

Strip4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Min. Thickness of PVC Outer Sheath (mm)

Strip Armour1.401.401.561.561.561.721.882.042.202.362.68

Overall Diameter (Approx.) (mm)

Strip Armour2527303438424651576171

Approx. Net. Wet of Cable

Strip Armour (Kg/Km)15831925246834654426549864738333104351267116498

Max. D.C. Resist-ance at

020 C (Ohms/Km)0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

Max. A.C. Resis-tance at

090 C (Ohms/Km)0.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602

Approx. React-ance at 50 Hz (Ohm/Km)0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

Approx. Capac-itance (mFd/Km)

0.200.230.240.260.290.290.290.290.310.330.33

Direct in GroundAmps119144174210252288324360414462510

In Air

Amps108132162198240276318366426480546

Min. No. of wires

6/6.6/6.6/6.12/6.15/6.18/12.18/15.30/15.34/18.34/18.53/30.

Min. Thickness of PVC Innersheath (mm)0.30.30.30.40.40.40.50.50.60.60.7

Thick-ness of XLPE Insulation (Nom.) (mm)0.9/0.70.9/0.71.0/0.91.1/0.91.1/1.01.2/1.11.4/1.11.6/1.11.7/1.21.8/1.42.0/1.6

No. of cores and cross sectional area

3.5C x 25/163.5C x 35/163.5C x 50/253.5C x 70/353.5C x 95/503.5C x 120/703.5C x 150/703.5C x 185/953.5C x 240/1203.5C x 300/1503.5C x 400/185

CURRENT RATINGS

Wire1.601.601.602.002.002.002.002.502.502.503.15

Wire Armour1.401.401.401.561.561.721.721.882.042.202.52

Wire Armour2325283235394347535766

Wire Armour (Kg/Km)1354168021432931383148315691710090351112614059

3.5 Core Copper XLPE Armoured Power Cables

3.5 Core Copper XLPE Unarmoured Power Cables

Page 26: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

4 Core Aluminium PVC Armoured Power Cables

4 Core Aluminium PVC Armoured Power Cables

No. of cores and cross sectional area

4C x 1.54C x 2.54C x 44C x 64C x 104C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400

4 Core Aluminium PVC Unarmoured Power Cables

4 Core Aluminium PVC Unarmoured Power Cables

No. of cores and cross sectional area

4C x 1.54C x 2.54C x 44C x 64C x 104C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400

Min. No. of wires

1111166661215151530303053

Min. No. of wires

1111166661215151530303053

Thick-nessof PVC Insulation(Nom.) (mm)0.80.91.01.01.01.01.21.21.41.41.61.61.82.02.22.42.6

Thickness of PVC Insulation (Nom.) (Mm)

0.800.901.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60

Min. Thickness of PVC Inner-sheath (mm)0.30.30.30.30.30.30.30.30.40.40.40.50.50.60.60.70.7

Min. Thickness of PVC Innersheath (mm)0.300.300.300.300.300.300.300.300.400.400.400.500.500.600.600.700.70

Nominal Dimensions of Armour (mm)

Strip----4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Wire1.401.401.401.401.601.601.601.602.002.002.002.002.502.502.503.153.15

Nom. Thickness of Outer Sheath (mm)

1.801.801.801.801.802.002.002.002.202.202.402.402.602.803.003.403.60

Min. Thickness of PVC Outer Sheath (mm)

Strip Armour----1.401.401.401.401.561.561.721.881.882.042.362.522.84

Wire Armour1.241.241.241.241.401.401.401.561.561.561.721.882.042.202.362.682.84

Overall Diameter (Approx.)

11.7013.2015.0016.0019.0021.5023.0025.0029.5034.0037.5041.5045.5050.0057.0063.2070.00

Overall Diameter

(Approx.) (mm)

Strip Armour----21.1523.0025.0027.5032.0036.5040.0044.5048.0053.0060.0065.5073.00

Net Wt. of Cable (Approx.)

210270340420510550750900120015202000238029003580453056807040

Wire Armour14.516.017.519.023.025.027.030.034.538.042.547.051.557.064.071.078.0

Max. D.C. Resistance

0at 20 C (Approx.) (Ohm/Km)

18.1012.107.414.613.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778

Approx. Net. Wet of Cable

Strip Armour (Kg/Km)----80083010751280162020102550304035804340546066308185

Wire Armour(Kg/Km)47056067580010301050135016202175266032803840488058107050926011020

Max. A.C. Resistance

0at70 C (Ohms/Km)

21.7214.528.895.533.702.291.441.040.770.530.380.300.250.200.150.120.09

Max. D.C. Resis-tance

0at 20 C(Ohms/Km)18.100012.10007.41004.61003.08001.91001.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778

Approx. Reactance at 50 Hz (Ohm/Km)

0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Max. A.C. Resis-tance

0 at 70 C (Ohms/Km)21.7214.528.895.533.702.291.441.040.770.530.380.300.250.200.150.120.09

Approx. Capacitance (mFd/Km)

0.1400.1500.4100.4700.5600.7600.8600.9801.0201.1801.2001.3101.3101.3101.3401.4101.450

Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Approx. Capac-itance (mFd/Km)

0.140.150.410.470.560.760.860.981.021.181.201.311.311.311.341.411.45

Direct in Ground

Amps1621283546607692110135165185210235275305335

CURRENT RATINGS

Direct in Ground

Amps1621283546607692110135165185210235275305335

CURRENT RATINGS

In duct

Amps141823303950637795115140155175200235260290

In duct

Amps141823303950637795115140155175200235260290

In Air

Amps1318233040517086105130155180205240280315375

In Air

Amps1318233040517086105130155180205240280315375

Page 27: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

4 Core Copper PVC Unarmoured Power Cables

4 Core Copper PVC Unarmoured Power Cables

In Air

Amps17243039576690110135165200230265305355400455

Direct in Ground

Amps21273645607799120145175210240270300345385425

Approx. Capac-itance (mFd/Km)

0.140.150.410.470.560.760.860.981.021.181.201.311.311.311.341.411.45

Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Max. A.C. Resis-tance

0 at 70 C (Ohms/Km)14.58.875.523.692.191.380.870.6270.4630.3210.2310.1840.1490.1200.09120.07390.0592

Max. D.C. Resis-tance

0at 20 C (Ohms/Km)12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

Wire Armour(Kg/Km)50361677194712731421193624363288426255256660836910183128071648820254

Approx. Net. Wet of Cable

Strip Armour (Kg/Km)----21.523.025.027.532.036.540.044.048.053.060.065.573.0

CURRENT RATINGS

4 Core Copper PVC Armoured Power Cables

4 Core Copper PVC Armoured Power Cables

Wire Armour14.516.017.519.023.025.027.030.034.538.042.547.051.557.064.071.078.0

Overall Diameter

(Approx.) (mm)

Strip Armour----21.1523.0025.0027.5032.0036.5040.0044.5048.0053.0060.0065.5073.00

Max. D.C. Resistance

0at20 C (Approx.) (Ohm/Km)

12.107.414.613.081.831.150.730.5240.3870.2680.1930.1530.1240.0990.0750.0600.0470

In duct

Amps1724303850648199125150175195225255295335360

In Air

Amps17243039576690110135165200230265305355400455

Max. A.C. Resistance

0at 70 C(Ohms/Km)

14.508.875.523.692.191.380.870.630.460.320.230.180.150.120.090.070.05

Approx. Reac-tance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086

Approx. Capac-itance (mFd/Km)

0.1400.1500.4100.4700.5600.7600.8600.9801.0201.1801.2001.3101.3101.3101.3401.4101.450

Direct in Ground

Amps21273645607799120145175210240270300345385425

CURRENT RATINGSNet Wt. of Cable (Approx.)

25633544657677393513651764235431874308528864728056104151307016477

Min. Thickness of PVC Outer Sheath (mm)

Strip Armour----1.401.401.401.401.561.561.721.881.882.042.362.522.84

Wire Armour1.241.241.241.241.401.401.401.561.561.561.721.882.042.202.362.682.84

Overall Diameter (Approx.)

11.7013.2015.0016.0019.0021.5023.0025.0029.5034.0037.5041.5045.5050.0057.0063.2070.00

Nom. Thickness of Outer Sheath (mm)

1.801.801.801.801.802.002.002.002.202.202.402.402.602.803.003.403.60

Wire1.401.401.401.401.601.601.601.602.002.002.002.002.502.502.503.153.15

Nominal Dimensions of Armour (mm)

Strip----4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Min. Thickness of PVC Innersheath (mm)0.300.300.300.300.300.300.300.300.400.400.400.500.500.600.600.700.70

Min. Thickness of PVC Inner-sheath (mm)0.30.30.30.30.30.30.30.30.40.40.40.50.50.60.60.70.7

Thickness of PVC Insulation (Nom.) (mm)

0.800.901.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60

Thick-nessof PVC Insulation(Nom.) (Mm)0.80.91.01.01.01.01.21.21.41.41.61.61.82.02.22.42.6

Min. No .ofwires

1111666661215181830343453

Min. No. of wires

1111666661215181830343453

No. of cores and cross sectional area

4C x 1.54C x 2.54C x 44C x 64C x 104C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400

No. of cores and cross sectional area

4C x 1.54C x 2.54C x 44C x 64C x 104C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400

Page 28: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

4 Core Aluminium XLPE Unarmoured Power Cables

4 Core Aluminium XLPE Unarmoured Power Cables

No. of cores and cross sectional area

4C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400

4 Core Aluminium XLPE Armoured Power Cables

4 Core Aluminium XLPE Armoured Power Cables

No. of cores and cross sectional area

4C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400

Min. No. of wires

66661215151530303053

Min. No. of wires

66661215151530303053

Thick-ness of Insu-lation (Nom.) (mm)0.70.90.91.01.11.11.21.41.61.71.82.0

Thickness of Insulation (Nom.) (Mm)

0.70.90.91.01.11.11.21.41.61.71.82.0

Min.Thickness of Inner Sheath (mm) 0.30.30.30.30.40.40.50.50.50.60.70.7

Min.Thickness of Inner Sheath (mm) 0.30.30.30.30.40.40.50.50.50.60.70.7

Nominal Dimensions of Armour (mm)

Strip1.601.601.601.602.002.002.002.502.502.503.153.15

Wire4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Nom. Thickness of Outer Sheath (mm)

1.802.002.002.002.202.202.402.602.803.003.203.60

Min.Thickness of Outer Sheath (mm)

Strip Armour1.401.401.401.561.561.721.882.042.202.362.522.84

Wire Armour1.401.401.401.561.561.561.721.882.042.202.362.68

Overall Diameter (Approx.)

202326293336414550566371

Overall Diameter (Approx.) (mm)

Strip Armour222628313640445055616876

Wire Armour212426303437424651576371

Net Wt. of Cable (Approx.)

-650800100013701740217026303250411050706420

Approx. Net. Wet of Cable

Strip Armour (Kg/Km) -118014101720241029003480448053306420836010070

Max. D.C. Resistance

0at 20 C(Ohms/Km)

1.91001.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778

Wire Armour (Kg/Km) - 9401130140018002190269032203920485059007310

Max. A.C. Resis-tance at

0 90 C (Ohms/Km)

2.45001.54001.11000.82000.56700.41000.32500.26500.21100.16200.13000.1023

Max. D.C. Resistance

0at 20 C (Ohms/Km)

1.911.20.8680.6410.4430.320.2530.2060.1640.1250.10.0778

Max. A.C. Resis-tance at

0 90 C(Ohms/Km)

2.451.541.110.820.5670.410.3250.2650.2110.1620.130.1023

Approx. React-ance at 50 Hz (Ohm/Km)

0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

Approx. React-ance at 50 Hz (Ohm/Km)

0.080.080.0780.0770.0740.0720.0720.0720.0720.0710.07

Approx. Capaci-tance (mFd/Km)

0.200.230.240.260.290.290.290.290.310.330.33

Approx. Capaci-tance (mFd/Km)

0.20.230.240.260.290.290.290.290.310.330.33

Direct in GroundAmps7394113133164196223249282326367418

CURRENT RATINGS

Direct in GroundAmps7394113133164196223249282326367418

CURRENT RATINGS

In Air

Amps7096117142179221257292337399455530

In Air

Amps7096117142179221257292337399455530

Page 29: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

4 Core Copper XLPE Armoured Power Cables

4 Core Copper XLPE Armoured Power Cables

Thickness of XLPE Insulation (Nom.) (mm)

0.700.900.901.001.101.101.201.401.601.701.802.00

Nominal Dimensions of Armour (mm)Strip

4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Min. Thickness of PVC Outer Sheath (mm)

Strip Armour1.401.401.401.561.561.721.882.042.202.362.522.84

Overall Diameter (Approx.) (mm)

Strip Armour22.026.028.031.036.040.044.050.055.061.068.076.0

Approx. Net. Wet of Cable

Strip Armour (Kg/Km)121017092154273238874970658377029377117761507218669

Max. D.C. Resistance

0 at 20 C (Ohms/Km)

1.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

Max. A.C. Resistance

0 at 90 C (Ohms/Km)

1.470.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602

Approx. React-ance at 50 Hz (Ohm/Km)0.0800.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

Approx. Capacit-ance (mFd/Km)

0.360.200.230.240.260.290.290.290.290.310.330.33

Min. No. of wires

66661215181830343453

No. of cores and cross sectional area

4C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400

Min. Thickness of PVC Inner-sheath (mm)0.30.30.30.30.40.40.50.50.50.60.70.7

CURRENT RATINGS

Direct in GroundAmps92119144174210252288324360414462510

In Air

Amps79108132162198240276318366426480546

Wire Armour (Kg/Km)99814731886243133014299582765008031102861198815872

Wire Armour1.601.601.601.602.002.002.002.502.502.503.153.15

Wire Armour1.401.401.401.561.561.561.721.882.042.202.362.68

Wire Armour 21.024.026.030.034.037.042.046.051.057.063.071.0

Nom. Thickness of PVC Outer Sheath (mm)1.802.002.002.002.202.202.402.602.803.003.203.60

Overall Diameter (Approx.)

20.023.026.029.033.036.041.045.050.056.063.071.0

Approx. Net Wt. of Cable (Approx.)

7131193156620572898385853245947740095841194815207

Max. D.C. Resistance

0 at 20 C (Ohms/Km)

1.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

Approx. Reactance at 50 Hz (Ohm/Km)

0.0800.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070

Max. ACResistance

0 at 90 C (Ohms/Km)

1.470.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602

Approx. Capacitance (mFd/Km)

0.360.200.230.240.260.290.290.290.290.310.330.33

CURRENT RATINGSMin. Thickness of PVC Inner-sheath (mm)0.30.30.30.30.40.40.50.50.50.60.70.7

Thickness of XLPE Insulation (Nom.) (mm)

0.700.900.901.001.101.101.201.401.601.701.802.00

Min. No. of wires

66661215181830343453

No. of cores and cross sectional area

4C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400

Direct in Ground

Amps92119144174210252288324360414462510

In Air

Amps79108132162198240276318366426480546

4 Core Copper XLPE Unarmoured Power Cables

4 Core Copper XLPE Unarmoured Power Cables

Page 30: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

LT Control Cables

www.gridcables.com

Page 31: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

Core colours:-

Sheath colour:-

Conductor:-

PVC Insulation:-

PVC Sheath:-

Rated voltage:-

Test Voltage:-

Min. bending radius:-

Tensile strength:-

Max. working temperature :-

Max short circuit temperature :-

Minimum Laying Temperature:-

Use :-

CONTROL CABLESPVC Insulated and Sheathed Flexible Cables

Technical Specifications

Black / grey with reverse colour numbering+ yellow / green, Grey, Black and white

Annealed Bare Copper as per IS : 8130

Type A conforming to IS:5831

Type ST-1 conforming to IS :5831

HR, FR & FRLS sheathing as per requirement

650/1100V

2000 V.A.C.

4 time overall diameter of cable

12.50 N per sq.mm of PVC insulation and sheath

70°C, also available for 85°C as per requirement

160°C

15°C

These cables are used for flexible use for medium mechanical stredded with free movement without tensile stress in dry and moist condition for measuring and control in tool machines, conveyor belts, production lines in machinery production, steel production and electrical substations.

Page 32: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

CONSTRUCTION

1. Solid / Stranded annealed Copper Conductor & Tinned / Bare2. General Purpose / HR PVC insulation3. Cores Laid up ( filled if needed )4. FRLS / General purpose PVC inner sheath5. Armoring round galvanized steel wires / strips6. FRLS / General purpose PVC outer sheath

MAX. CONDUCTOR D.C. RESISTANCE AT 20°C – CONDUCTOR SIZE

1.5 SQ.MM – 12.1 Ohm / km (Bare) , 12.2 Ohm / km (Tinned)2.5 sq.mm – 7.41 Ohm / km (Bare), 7.56 Ohm / km (Tinned)*Dimensions specified are with stranded conductor.

Armoured PVC Control Cable IS:1554(Pt-I)-1988

Thickness of Inner sheath (min.) extruded mm0.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.4

Strip size mm

-------4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8------4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8

Thickness of PVC Outer sheath (Min.) mm-------1.241.401.401.401.401.401.401.40 1.401.401.401.401.401.401.401.561.56

Approx. OD mm

-------19.520.821.723.126.426.927.829.7 21.822.823.824.926.130.030.632.034.7

Approx. net weight of cable Kg/km

-------76083092010401250135514301670 90010201130121013551655177019402300

Round Wire Dia mm

1.41.41.41.41.41.41.41.61.61.61.61.61.61.61.61.41.41.41.41.41.41.61.61.61.61.61.61.61.62.0

Thickness of PVC Outer sheath (Min.) mm1.241.241.241.241.241.241.401.401.401.401.401.401.401.401.401.241.241.241.241.241.241.401.401.401.401.401.561.561.561.56

Approx. OD mm

13.614.115.015.916.916.920.621.522.423.324.728.028.529.431.314.815.416.417.518.718.723.424.425.426.527.732.032.633.637.1

Approx. Net weightof cable Kg/Km

4154304905456056308359501040113012651510161017001960500520590660745780111012401340145516051970210022502900

Standard Delivery Length in Mtrs.

100010001000100010001000100010001000100010001000100010001000100010001000100010001000100010001000100010001000100010001000

Direct in Ground

Amps23212116151413121111109998322727232120181716151413121211

In Air / Duct.

Amps20171714131311101099887727242419181715141313121110109

Thickness of PVC Insulation (Nom.) mm

0.80.80.80.80.80.80.80.80.80.80.80.80.80.80.80.90.90.90.90.90.90.90.90.90.90.90.90.90.90.9

No. of Cores & Cross Secitonal Area No. x mm22C x 1.53C x 1.54C x 1.55C x 1.56C x 1.57C x 1.510C x 1.512C x 1.514C x 1.516C x 1.519C x 1.524C x 1.527C x 1.530C x 1.537C x 1.52C x 2.53C x 2.54C x 2.55C x 2.56C x 2.57C x 2.510C x 2.512C x 2.514C x 2.516C x 2.519C x 2.524C x 2.527C x 2.530C x 2.537C x 2.5

Strip Armoured Cable Wire Armoured Cable Current Rating

Page 33: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

Unarmoured PVC Control Cable IS:1554(Pt-I)-1988

CONSTRUCTION

1. Solid / Stranded annealed Copper Conductor & Tinned / Bare2.General Purpose / HR PVC insulation3.Cores Laid up ( filled if needed )4.FRLS / General purpose PVC inner sheath5.FRLS / General purpose PVC Outersheath

MAX. CONDUCTOR D.C. RESISTANCE AT 20°C – CONDUCTOR SIZE

1.5 SQ.MM – 12.1 Ohm / km (Bare) , 12.2 Ohm / km (Tinned)2.5 sq.mm – 7.41 Ohm / km (Bare), 7.56 Ohm / km (Tinned)*Dimensions specified are with stranded conductor.

No. of Cores & Cross Secitonal Area No. x mm2

2C x 1.53C x 1.54C x 1.55C x 1.56C x 1.57C x 1.510C x 1.512C x 1.514C x 1.516C x 1.519C x 1.524C x 1.527C x 1.530C x 1.537C x 1.52C x 2.53C x 2.54C x 2.55C x 2.56C x 2.57C x 2.510C x 2.512C x 2.514C x 2.516C x 2.519C x 2.524C x 2.527C x 2.530C x 2.537C x 2.5

Thickness of PVC Insulation (Nom.) mm

0.80.80.80.80.80.80.80.80.80.80.80.80.80.80.80.90.90.90.90.90.90.90.90.90.90.90.90.90.90.9

Thickness of Inner sheath (min.) extruded mm

0.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.4

Thickness of Outersheath (nom.)mm

1.81.81.81.81.81.81.81.81.81.82.02.02.02.02.01.81.81.81.81.81.81.82.02.02.02.02.02.02.02.2

Approx. O.D. Mm

11.812.313.214.115.115.118.418.919.820.722.525.826.327.229.113.013.614.615.716.916.920.822.223.224.325.529.4303134.1

Approx. Net Weight of Cable Kg/Km

185190225260295315425480535595720880960104012302302402903353854205706907758609851215133014501790

Standard Delivery Length in Mtrs.

100010001000100010001000100010001000100010001000100010001000100010001000100010001000100010001000100010001000100010001000

Direct in Ground

Amps23212116151413121111109998322727232120181716151413121211

Current Rating

In Air / Duct.

Amps20171714131311101099887727242419181715141313121110109

Page 34: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

www.gridcables.com

SingleMulticore Flexible Cables

Page 35: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

Single-core flexible cables – for Electrical Panels and Switch Boards

Features

• Higher Safety Factors

• Compact construction

• Choice of superior insulation systems for meeting IEC classification Temp. rise, protection etc.

Technical Specification

Conductor : Bunched electrolytic grade, annealed with superb flexibility according to harmonized grades H05V-K and H07-K available in various sizes from 0.5 sq.mm to 300 sq.mm

Insulation : PVC insulation upto 4 sq.mm 6 sq.mm and above generally available with HRPVC insulation or as per customer orders.

Standard colors : Grey, Red, Blue, Black, other colours as per order.

Standard packing : upto 10 sq.mm – 100 mtr. Coils , 16-130 sq.mm – longer lengths supplied on order.

SINGLE / MULTICORE FLEXIBLE CABLES

Applications and Standards

Type of insulation

70°C Heat Resistant PVC

Flame Retardant Low Smoke (FRLS)

Halogen Free Flame Retardant (HFFR) from 1.0 to 4.0 sq.mm

Typical applicationsWiring of panels for use in high ambient temperature

Wiring in high density critical installations in public places and fire prone areas

Wiring in high density critical installations in public places andfire prone areas and vicinity of electronics systems

Applicable standardsIS-694, BS 6004, IEC 60227, DIN VDE 0281-3

IEC 60332-1BS 4066-1IEC 60754-1ASTMD-2843ASTMD-2863

IEC 60322-1&3BS 4066-1&3IEC 60754-1&2ASTMD-2863BS 7211DIN VDE 0282-9

Page 36: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

Multicore Flexible Cables - For appliances & Machine Tools

Features

• Compact construction reduces weight per meter

• Rugged yet flexible for industrial use

• High temperature insulation

Technical Specifications

Conductor : High purity bright, electrolytic grade, pain annealed copper properly bunched having superb flexibility according to harmonized grades H05V-H07V-K and BS 6360 Class 5 available in various sizes. ‘Unilay’ conductor on the core will be provided on special order from 1 to 4 sq.mm

Insulation : Generally available with general purpose PVC insulation and PVC sheathing or as per customer.

Standard colours : Grey and Black

Standard Packing : 100 mtrs. Coils longer lengths supplied on order.

Cross Section Area (sq.mm)

0.50.751.01.52.54.06.010.016.0

25.035.050.070.095.0120.0150.0185.0240.0300.0

Physical and Electrical Properties

Approx. AWG

2119181614121086

4212/03/04/0---

Overall Dia Max. (mm)

2.62.83.03.804.04.84.68.09.6

11.513.015.015.017.519.021.023.526.529.5

Insulation Thickness Nom. (mm)0.600.600.600.600.700.800.801.001.00

1.21.21.41.41.61.61.82.02.202.40

Conductor NO. of wires / Max. Dia16/0.224/0.232/0.230/0.2550/0.2556/0.384/0.3140/0.3126/0.4 or 226/0.3196/0.4276/0.4396/0.4356/0.5480/0.5610/0.5750/0.5940/0.51200/0.51500/0.50

Conductor Resist. Ohm/Km at 20°C Max392619.513.37.984.953.301.911.21

0.7800.5540.3860.2720.2060.1610.1290.1060.08010.0641

Max current rating, Amp

6914243243547290

115150180240275310350400475500

Approx. Voltagedrop per amp per meter, mv46.031.022.015.09.15.73.82.21.4

0.890.640.450.320.240.190.150.120.100.08

Page 37: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

Physical and Electrical Properties

Flat submersible cable

Type of insulationStandard PVC

Heat resistant PVC upto 105°C

Standard PVC of FRLS

No. of coresCircularly Laid Up Cores

2 Cores Red, Black

3 Cores Red, Black And Green

4 Cores Red, Yellow, Blue And Green

No. core

3 CORE FLAT LAID CORES

Typical applicationsStandard PVC, HRPVC

Standard PVC, HRPVC

FRLS(Flame Retardant Low Smoke)

PropertiesConductorIns. Thickness (nom), mmSingle Core OD (max.), mmCond. Resist. (max.) ohm/kmSheath thickness (nom.), mmOverall dia. (max.) mmCurrent rating DC or single phase AC, amo voltage drop DC or phase AC, mV / A/m

Sheath thickness, (nom), mmOverall dia (max), mmCurrent rating DC or single phase AC, Amp. Voltage drop DC or single phase AC, mV / A/mSheath thickness, (nom.), mm

Overall dia (max), mmCurrent rating DC or single phase AC, AmpCurrent rating three phase ACVoltage drop DC or single phase AC, mV / A/m Voltage Drop, three phase AC

Properties

Sheath thickness , (nom), mm ConfigurationOverall dia (avg.)mmCurrent rating DC or single phase AC, Amp.Current rating, three phase ACVoltage drop DC or single phase Ac, mV / A/m Voltage drop, three phase AC

0516/0.20.62.6039.00.97.20693

0.97.606102

0.98.206610288

1.50

0.922/0.35.8x11818162925

0.7524/020.62.8026.00.97.80962

0.98.20962

0.98.80996254

2.50

0.936/0.36.75x14.124201815

1.032/0.20.63.019.50.98.01446

0.98.601446

0.99.4014144640

4.0

1.056/0.37.5x16.43225119.5

1.530/0250.63.830.30.98.601832

0.99.201832

1.010.5018183227

6.0

1.156/0.38.3x18.1042357.36.4

10.0

1.2140/0.39.5x22.5055454.43.8

2.550/0.250.74.07.981.010.502419

1.011.02419

1.01224201916

4.056/0.30.84.84.951.012.03212

1.012.503212

1.014.032251210

Applicable standardsIS 694, BS 6500, IEC 60227, DIN VDE-0281

IS 694, BS 6500, IEC 60227, DIN VDE-0281

IS 694/BS-6500, IEC 60227, DIN VDE-0281, IEC 60754-1, IEC 60332-1, BS-4066-1, ASTMD 2843, ASTMD-2863

Typical applicationsPower cords for applications, temporary power supplies, 3 core flat cables are suitable for submersible pump applications

Hi-power appliances, Ovens, Temporary Power supply in higher temp. areas

Power cords for appliances used to fire prone areas. Flame proof equipments, machine tools used in critical locations and heat zones.

Applications and standards

Page 38: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

www.gridcables.com

Aerial Bunched Cables

Page 39: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

FeaturesGRID make Aerial Bunched Cables (ABC) is a novel concept for overhead power distribution system.

GRID make Aerial Bunched Cable are designed, manufactured and tested conforming to IS:14255, IS :7098(Pt-I) and other international specifications like IEC, NFC etc.

ApplicationsABC can conveniently be used :-

a) In theft prone areasb) As replacement of bare conductors in rural areas, in forest and in other localities like narrow street

where the space is limitedc) As replacement of bare conducts where reliability of supply is of prime importanced) As replacement of bare lines where high degree of stability of supply voltage is of importance.e) As hilly terrains where cost of erection of overhead lines or under ground cable becomes very high.f) As reinforcement of existing system without increasing voltage.g) For temporary suppliesh) Reduces burning of transformers and maintenance

AdvantagesIn comparison to bare overhead distribution lines, AB cables have very high reliability during the services. As the power and neutral conductors are insulated with the best dielectric material, resulting in the following advantages :

1. Less fault rate on account of good protection against line and ground fault by high winds or falling trees or birds especially in hilly areas and forests as encountered in rural distribution networks.

2. High insulation resistance to earth in al polluted atmosphere. Negligible currents and low losses.3. Multiple circuits of power and telephone cables could be strung in the same set of poles or any other

supports like walls etc.4. Better adaptability to run concurrently with existing over-head bare conductor system without any

interference. 5. High capacitance and low inductance leading to low impedance of lines.6. Lower voltage drop, higher current carrying capacities, vis-à-vis better voltage regulation.7. Longer spans and longer distance lines are possible with better systems stability.8. AB cables are much safer then bare conductors.9. It can be overhung in dense vegetation and forests.10. Additional connections can be easily and quickly made with hot-line connectors.11. Total lines costs are deduced. 12. Maintenance costs are reduced.13. Very difficult to tap the AB cables, thus reducing theft which leads to lower distribution loses.

AERIAL BUNCHED CABLES

Page 40: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

GRID INDIA POWER CABLES PVT. LTD. Manufactures a wide variety of cables suitable for process instrumentation. In the projects related to power generation and distribution, chemical and fertilizer industries and various other types of engineering industries, the process instrumentation plays a vita role in measurement, supervision ad control of the process. Introduction of microprocessor based / computerized instrumentation has demanded stringent quality requirements alongwith special electrical parameters for instrumentation cables. Very low level electrical signals pass between measuring end and display units / controllers which are situated far off. These low level signals are prone to external noise pickups and heavy silenuation during transmission.

All this means that the cables to be used for instrumentation should be designed and manufactured very carefully, GRID CABLES with its meticulous efforts in maintaining quality, stringent in process control during manufacture and the knowledge of cable designing, is proud to say that it is capable of supplying instrumentation cables meeting any Indian / International standard or a specific requirement desired by project authority. The efforts done by GRID CABLES are reqarded by acceptance of our quality by the country's prime organizations.

INSTRUMENTATION CABLES

Conductor:-

Insulation :-

Elements:-

Shields :-

Element laying:-

Armouring:-

Sheathing:-

Specification:-

0.4mm dia (0.126 sq.mm) to 2.5 sq.mm or higher sizes of electrolytic copper wire, Tinned / untinned, solid / stranded copper conductors.

70 Deg. C/ 85 Deg. C Grade PVC, Polyethylene, Halogen free FRLS Polymeric compounds

Pairs / Triples / Quads, colour coded / number printed ring marked / dual colour extruded.

Aluminium Polyester tape screen with copper drain wire or alternately with Copper wire braiding, individual element or overall shielding as specified.

Concentric formation or unit & ground formation as per applicable specification.

Galvanized steel wire / strip armour.

PVC 70/90 Deg. C grade, PVC FRLS, Halogen free FRLS Polymeric Compounds.

BS:5308 (1&2) IEC-189 (1&2)VDE 0815, ENI -181.00 and customer specifications

Range of Instrumentation Cables :-

OUTER SHEATH1) PVC (ST-1 ST-2)2) FRLS VPC3) Halogen Free FRLSARMOUR WIRE/STRIPGavalnised Steel

INNER SHEATH1) PVC (ST-1/ ST-2)2) FRLS VPC3) Halogen Free FRLS

INSULATION1) PVC (Type A.C)2) Polyethylene3) Halogen Free FRLS

COPPER CONDUCTOR1) Bare (ABC)2) Tinned (ATC)3) Solid4) Stranded

OVERALL SCREEN1) Copper Wire Braid2) AI-Polyester tape with copper drain wire

Cabling element

Pair Triad Unit

Element Pair

Typical Instrumentation Cable Constructions

Page 41: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

Basic Code

GPC-2420GPC-1430GPC-2230GPC-3630GPC-5630GPC-8430

Feature

Insulation material Insulation propertyTemperature ratingThermal stability Flame retardancy Safety during burning Requirement of Oxygen to Catch Fire (% in air)Temperature required to catch fire (with 21% oxygen)Visibility during cable burning(%)Release of halogen Gas during burning (% by weight)Abrasion Resistance during installation

COMPARATIVE PROPERTIES OF GRID WIRES

Single Core PVC/HR PVC / FRLS / ZHFR Insulated Copper Conductor (Unsheathed). House Wires in Voltage Grade upto and including 1100 Volts as per IS:694-1990.

Nominal Cross Section Area of Conductor Sq.mm0.751.001.502.504.006.00

Number / Nom. Dia of wires * (Nom.) Number / mm24/0.2014/0.3022/0.3036/0.3056/0.3084/0.30

Normal PVC WirePVCNormal70°CNormalGoodAverage

>21Room temp.

<20

<20

Good

Thickness of insulation (Nom.) mm

0.600.700.700.800.800.80

Heat Resistant HR PVCPVCGood85°CVery goodGoodAverage

>21Room temp.

<20

<20

Good

Overall diameter Max. mm

2.83.23.44.24.85.6

Fire Retardant FR-PVCSpl. PVCGood70°CGoodVery goodGood

>30>250°C

<35

<20

Good

Current carrying capacity in conduit / trunking (Amps)PVC

71113182431

Fire Retardant Low Smoke FRLSSpl. PVCGood70°CGoodVery goodGood

>30>250°C

>40

<20

Good

HR PVC81316202636

FRLS

71113182431

Zero Halogen Low SmokeSpl. PolymerVery good85°CVery goodExcellentExcellent

>35>300°C

>80

Zero

Good

ZHFR

81316202636

Resistance (Max.) at 20°C Ohm / Km26.0018.1012.107.414.953.30

An ISO: 9001-2008 Certified Company

www.gridcables.com

Page 42: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

Concentric Cables

www.gridcables.com

Page 43: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

APPLICATIONS

Power cables for energy supply are used for industry and distribution boards, power stations, house connecting boxes and street lighting and as control cables for the transmission of control impulses and test data.Overall, where increased electrical and also mechanical protection are required. These cables are installed in open air, in underground, in water, indoors and in cable ducts.

The concentric conductor (C) is allowed use as PE-, PEN-Conductor as shield.

Due to the typical construction of concentric conductor it is possible to obtain many more cables joints, without cutting any conductor. In that way the operating reliability is guaranteed.

The product conforms to the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.

PROPERTIESl PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/EN 50265-

2/1 /IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B)l The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers.l Highest permissible voltage.l Direct current systems 1.8kV.l Alternating current systems, single-phase systems 1.4kV both conductors insulated, single-phase

Systems 0.7kV one conductor grounded, three-phase systems 1.2kV with concentric conductor And a cross-section of 240 sq. mm and above 3.6kV.

TECHNICAL DATAl Power and Control cable as per DIN VDE0276 part 603, HD 603 S1 & IEC 60502.l Temperature range flexing -5°C to +50°C, fixed installation 40°C to +70°C.l Nominal voltage U0/U0,6/1 kVl Test Voltage 4kVl Max. Permissible tensile stress with cable grip for Cu-conductor = 50 N/sq.mml Minimum bending radius for single conductor approx. 15xcable ø; for multi conductor approx.

12xcable øl Power ratings see Technical informationl Caloric load values see Technical Information

CONCENTRIC CONDUCTOR CABLES upto 1100 V (NYCWY/NYY)

Page 44: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

Description and No.

Conductors x cross-sec. sq.mm

NYCWY 2X10 re/10

NYCWY 0.6 / 1KV 2x16 re /16

NYCWY 0.6 / 1KV 2x25 rm/25

NYCWY 0.6 / 1KV 3x10 re/10

NYCWY 0.6 / 1KV 3x16 re/16

NYCWY 0.6 / 1KV 3x25 rm/16

NYCWY 0.6 / 1KV 3x25 rm/25

NYCWY 0.6 / 1KV 3x35 sm/35

NYCWY 0.6 / 1KV 3x35 sm/16

NYCWY 0.6 / 1KV 3x50 sm/50

NYCWY 0.6 / 1KV 3x50 sm/25

NYCWY 0.6 / 1KV 3x70 sm/70

NYCWY 0.6 / 1KV 3x70 sm/35

NYCWY 0.6 / 1KV 3x95 sm/95

NYCWY 0.6 / 1KV 3x95 sm/50

NYCWY 0.6 / 1KV 3x120 sm/70

NYCWY 0.6 / 1KV 3x120 sm/120

NYCWY 0.6 / 1KV 3x150 sm/70

NYCWY 0.6 / 1KV 3x140 sm/150

NYCWY 0.6 / 1KV 3x185 sm/95

NYCWY 0.6 / 1KV 3x185 sm/185

NYCWY 0.6 / 1KV 3x240 sm/120

NYCWY 0.6 / 1KV 4x10 re/10

NYCWY 0.6 / 1KV 4x16 re/16

NYCWY 0.6 / 1KV 4x25 rm/16

NYCWY 0.6 / 1KV 4x35 sm/16

NYCWY 0.6 / 1KV 4x50 sm/25

NYCWY 0.6 / 1KV 4x70 sm/35

Outer Dia

19.0

21.0

24.0

19.5

22.0

26.0

26.0

27.5

27.0

29.5

29.0

34.0

33.0

38.5

38.0

41.0

42.0

45.0

46.0

50.0

51.0

57.0

20.5

23.5

28.0

29.0

33.0

37.0

Copper Weight

kg/km

312.0

489.0

763.0

408.0

643.0

902.0

1003.0

1402.0

1190.0

2000.0

1723.0

2796.0

2410.0

3791.0

3296.0

4263.0

4786.0

5100.0

5970.0

6383.0

7363.0

8242.0

504.0

796.0

1142.0

1526.0

2203.0

3082.0

Weight ca.

kg/km

650.0

850.0

1210.0

730.0

1000.0

1550.0

1600.0

1850.0

1750.0

2450.0

2250.0

3350.0

2950.0

4550.0

4100.0

5050.0

5550.0

6000.0

6900.0

7550.0

8500.0

9950.0

890.0

1250.0

1800.0

2050.0

2700.0

3750.0

AWG

8

6

4

8

6

4

4

2

2

1

1

2/0 kcmil

2/0 kcmil

3/0 kcmil

3/0 kcmil

4/0 kcmil

4/0 kcmil

300 kcmil

300 kcmil

350 kcmil

350 kcmil

500 kcmil

8

6

4

2

1

2/0

Cable constructionPlain copper conductors, as per VDE 0295 cl.1 od. Cl.2, IEC 60228, BS 6360 cl. 1 and HD 383, solid or stranded versions, conductor types.10-16 sq.mm round, solid conductors (re) alt. 10-25 sq.mm, stranded conductor (rm), 35-240 sq.mm, sector shaped conductor, stranded (sm)PVC conductor insulation, DIV4 to HD 603.1Color coded to DIN VDE 0293-308 and HD 186Conductors stranded concentricallyFilling compoundConcentric conductor (Ceander), inner layer of corrugated copper wires, outer layer with copper tapePVC outer jacket, DMV5 to HD 603.1Jacket color black

Page 45: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

Any Type of Special Cables

www.gridcables.com

Page 46: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

Thermocouple Extension / Compensating Cables

Range of Thermo-couple extension / compensation cables

COLOUR CODES as per various Standard Specifications

These cables can also be termed as instrumentation cables, since they are used for process temperature measurement. The construction is similar to pair instrumentation cable but the conductor material is different. Thermocouples are used in processes to sense temperature and is connected to the pyrometers for indication and control. The thermocouple and pyrometer are electrically conducted by thermocouple extension / compensating cables. The conductors used for these cables are required to have similar thermo-electric (emf) properties as that of the thermocouple used for sensing the temperature. The cables are manufactured as per IS:8784, ANSI-MC 96, 1, B.S., ENI, DIN and customers specification.

ANY TYPE OF SPECIAL CABLES

Extension cables

KX (NiCr/Nia)JX (Fe/CuNi)EX (NiCr/CuNi)TX (Cu/CuNi)Compensating Cables KX(A)/VX(NiCr/NiaL)SX/RX (PtRh-Pt)

KXJXTXEX

KX(A)/VXSX/RXGreen

COMPENSATING CABLES

+ve

Yellow WhiteBluePurple

-

EXTENSION CABLES-ve

RedRedRedRed

-Black

Overall

YellowBlackBluePurple -Red

+ve

RedRedRedRed

RedRed

STANDARDS REFERRED

PositiveChromelIronChromelCopper

CopperCopper

-ve

GreenBlueBlackViolet

GreenWhite

Conductor material

Overall

GreenBlueBlackViolet

GreenWhite

+ve

BrownYellow WhiteBrown

WhiteWhite

-ve

BlueBlueBlueBlue

BlueBlue

NegativeAlumelConstantanConstantanConstantan

Constantanconstantan

Overall

RedBlackBlueBrown

RedGreen

Page 47: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

Test

Critical Oxygen Index

Temperature Index

Smoke Density Rating(Light Transmission )

Acid Gas Gas Generation

Function

To determine Percentage of Oxygen required for supporting combustion of insulating material at room temperature

To determine at what temperature normal oxygen content of 21% in air will support combustion of insulating material To determine the visibility (Light Transmission) under Fire of Insulating Material

To ascertain the amount of Hydrochloric Acid Gas evolved from insulation of Cables under fire.

Following additional test is offered on these cables :-

1)Flammability Testa) IEEE383b) IEC 332(Part-I)c) IEC-332 (Part-III)

2)Swedish Chimney Testa) SS 4241475

Specification

ASTM-d-2863

ASTM-D-2863 & BICC Handbook Chapter No. 6

ASTM-D-2843

IEC-754-I

Typical values of FRLS compound

More than 29%

More than 250°C

More than 40%

Less than 20%

Typical values of Halogen free compoundMore than 29%

More than 250°C

More than 80%

Less than 0.5%

Typical values of ordinary PVC Compound23%

0150 C

10-15%

450-50%

GRID FRLS and Halogen Free Cables

Page 48: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

www.gridcables.comwww.gridcables.com

Conductor

Page 49: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

1. Corrosion resistance : AAAC exhibits excellent corrosion resistance especially in sea coast areas and in polluted industrial areas due to Absence of steel core

2. Lower power losses : since AAC is homogeneous (with all strands of Aluminium Alloy) with no steel component, the resistance of AAAC is lower as compared to that of ACSR.

3. Higher ampacity :AAAC can carry atleast 15-20% extra current as compared to ACSR of equal size.4. Longer life : Experience in foreign countries shows that all Aluminium Alloy Conductors are in service for over 60 years, which is

about double the life of ACSR conductors.5. Surface hardness : The surface hardness of AAAC is 80 BHN as compared to 35BHN of ACSR. This reduces damage to surface

during handling and therefore leading to lesser corona losses and radio interference at EHV.6. Thermal stability : AAA Conductors are stable upto 90°C against ACSR conductors which are stable upto 75°C.7. Higher strength to weight ratio : Since AAAC has higher strength to weight ratio, span car be increased from 2 to 15% resulting in

Overall reduction of cost in tower / supports and other accessories in transmission lines system.

CONDUCTORSADVANTAGES OF AAAC

All Aluminium Alloy Conductors

(Clauses 7.2.1 & 7.2.2) as per IS-398 (Part 4) 1994

Actual area

mm2

15

22

34

55

80

100

125

148

173

200

232

288

346

400

465

525

570

604

642

695

767

Stranding &

wire dia mm

3/2.50

7/2.00

7/2.50

7/3.15

7/3.81

7/4.26

19/2.89

19/3.15

19/3.40

19/3.66

19/3.94

37/3.15

37/3.45

37/3.71

37/4.00

61/3.31

61/3.45

61/3.55

61/3.66

61/3.81

61/4.00

Approx. Overall

Dia mm

5.39

6

7.5

9.45

11.43

12.78

14.45

15.75

17

18.3

19.7

22.05

24.15

25.97

28

29.79

31.05

31.95

32.94

34.29

36

Approx Mass

kg/km

40.15

60.16

94.00

149.20

218.26

272.86

342.51

406.91

474.02

549.40

636.67

794.05

952.56

1101.63

1280.50

1448.39

1573.71

1666.00

1771.36

1919.13

2115.54

Calculated maximum

resistance at 20°C

Ohms/km

2.3040

1.5410

0.9900

0.6210

0.4250

0.3390

0.2735

0.2298

0.1969

0.1710

0.1471

0.1182

0.0984

0.0855

0.0734

0.0651

0.0598

0.0568

0.0534

0.0492

0.0446

Approx calculated

breaking load

(kN)

4.33

6.45

10.11

16.03

23.41

29.26

36.64

43.50

50.54

58.66

68.05

84.71

101.58

117.40

136.38

146.03

158.66

167.99

178.43

193.25

213.01

Page 50: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

An ISO: 9001-2008 Certified Company

www.gridcables.com

AAAC HS Aluminium Alloy Stranded Conductor

Aluminium Conductors, Galvanized Steel-reinforced for extra high voltages IS 398(Part 5) : 1992(Clause 8.2.2)

Stranded Aluminium Conductor Steel Reinforced (ACSR)IS-398 (Part-2) 1996Clauses 8.21 8.2.2 and 4.3.2

AAAC size equivalent to ACSR

SquirrelWeaselRabbit RacoonDog

ACSR Code word

Moie…SquirrelWeaselRabbitRaccoonDogWolfPantherKundahZebraMooseMorkulla

Conductor size sq.mm

101820305080100150200400420520560

Overall diameter mm

4.505.886.337.7710.0512.2714.1518.1321.0026.8828.6231.7731.68

Ultimate strength kN

3.976.747.6111.1218.2526.9132.4167.3489.6788.79130.32159.60120.16

Calculated Electrical resistance at 20°C Ohm/km 2.7801.6181.3940.92890.55240.37120.27920.18710.13900.073110.068680.055950.05231

Copper equivalent

611121932486496129246261322343

Nominal Aluminium (1)mm

520560690

Nominal Al-Area

mm21420305080100

Calculated Resistance at 20°C maximum Ohm/km2.3041.5410.9900.6210.4250.399

Approx. calculated breaking load kN4.3316.46710.10616.04423.47329.344

Approx. Mass

Kg/km40.1560.1394.00149.20218.26272.86

Stranding and wire dia

mm3/2.507/2.007/2.507/3.157/3.817/4.26

Stranding Nos/mm

Al.6/1.506/1.966/2.116/2.596/3.356/4.096/4.7230/2.5930/3.0042/3.5054/3.1854/3.5342/4.13

Calculated sectional area sq.mm

Al. 10.6018.1020.9831.6152.8878.83105.00158.10212.10404.10428.90528.50562.70

Calculated sectional area sq.mm

ACSR4373851282143193947269741281162119981781

Steel 1/1.501/1.961/2.111/2.591/3.351/4..097/1.577/2.597/3.004/1.967/3.187/3.537/2.30

ACSR12.3721.1224.4836.8861.7091.97118.50194.90261.50425.20484.50597.00591.70

Al.295058871452162884375861116118614611553

Steel1423274169103106289388165435537228

Stranding and wire diameterAl. (2)mm54/3.5342/4.1342/4.57

Steel (3)7/3.53528.57/2.13562.77/2.54688.9

Sectional Area

mm214.7321.9934.3654.5579.8199.77

Sectional area of Aluminium

528.5562.7688.9

Approx. overall Dia

mm5.386.007.509.4511.4312.78

Total sectional area

597.0591.7724.4

Approx overall diameter

31.7731.6835.04

Approx mass

2 0041 7872 187

Calculated resistance at 20°C

0.055 520.051 990.042 42

Approx breaking load min.

161.20120.16146.87

REC Specification No. 33/1984.

Note: (1) kN = 100,000,000 dyne = 102 kgNote: The standard length of the conductor manufactured as per specific requirement of the customer and being supplied in non-returnable wooden drums or steel drum, quite strong, to withstand any kind of transit handlings in the erection field.

Page 51: GRID INDIA POWER CABLES PVT. LTD. · Tehri Hydro Development Corporation Ltd. ABB Limited Angelique International Ltd. Annapurna Construction & Transmission Avadh Transformers Pvt

On receipt of the cable drums visual inspection of drums should be made. White unloading the drums from the lorry / trailer, a crane or suitable derrick system with chain pully arrangement should be used and the drums carefully lifted and deposited on the ground. When lifting the drums with the crane, it is recommended the lagging should be kept in place to prevent the flanges from crushing on to the cable. If the crane is not available, a ramp should be prepared with approximate inclination of 1:3 or 1:4. The cable drum should be rolled over the ramp by means of ropes and winches. Under no circumstances should the drums be dropped to the ground as the shock may cause serious damage to the inner layer of the cables.

Cables should not be dragged along the earth surface.

Cable ends should always be sealed by means of suitable end sealing material to prevent miniaturization of cores and armour.

Drums should be rolled in direction of arrow marked on the drums.

Storage

The site chosen for the storage of cable drums should be dry and covered place to prevent exposure to climatic conditions and wear and tear of wooden drums and it should be preferably on a concrete / consolidated surface which will not cause the drums to sink and thus lead to flange rot and extremely difficult in moving the drums.

The drums should be stored in such a manner as to leave sufficient space between them for air circulation. It is desirable for the drums to stand on battens placed directly under the flanges.

In no case shall the drums be stored flag i.e. with flanges horizontal.

Minimum permissible bending radius

While installing the cables, the following minimum bending raidus should be observed in order so that the cable, especially insulation, may not undergo damage. Wherever possible larger bending radium should be used.

Voltage rating KVUpto 1.1 Above 1.1 to 11

Where D is outer diameter of cable.

PVC & XLPE CablesSingle Core Multicore15 D 12 D 15 D 12 D

An ISO: 9001-2008 Certified Company

www.gridcables.com

Handling & Storage