“grounding, from the ground up” - ieee entity web ... · pdf filepurposes of...
TRANSCRIPT
![Page 1: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/1.jpg)
“Lightning Protection”
1MCPQG/IEEE, May 3, 2011
![Page 2: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/2.jpg)
“Lightning Protection”
Presented by,
Mike Puckett, P.E., Puckett Engineering, PLLC
May 3, 2011
Joint meeting of the Music City Power Quality Group and the IEEE Central TN Section
2MCPQG/IEEE, May 3, 2011
![Page 3: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/3.jpg)
3
OverviewPurposes of Lightning ProtectionLightning StatisticsPhysics of LightningHow does Lightning Damage EquipmentLightning Protection • Grounding and Bonding• Isolation• Surge Protection• Building Envelope
Personal Safety from Lightning
MCPQG/IEEE, May 3, 2011
![Page 4: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/4.jpg)
4
Purposes of Lightning Protection
Protect PeopleProtect EquipmentProtect Power LinesProtect Structures (Buildings)Protect Storage of Explosive MaterialsProtect Towers and TanksProtect WatercraftProtect Livestock
MCPQG/IEEE, May 3, 2011
![Page 5: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/5.jpg)
5
Lightning Statistics
30 to 100 Lightning Flashes per Second around the World (Cloud & Cloud-to-Ground)Up to 9 Million Flashes per Day worldwideCloud Discharges account for more Flashes than Cloud-to-Ground Flashes (Intracloud most common)
MCPQG/IEEE, May 3, 2011
![Page 6: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/6.jpg)
6
Lightning Statistics, cont.Insurance payouts in U.S. 1/3 to 1 Billion/yr.Cost of U.S. Lightning Damage ~ 1 Billion/yr.NFPA reports ~ 30,000 Lightning Caused House Fires each year with cost of $175 Mil.About 30% of all Church Fires are Lightning RelatedLightning is Primary Cause of Fires on Farms and for more than 80% of Livestock LossesIn 1999, Lightning Ignited more than 2000 Forest Fires in Florida alone.
MCPQG/IEEE, May 3, 2011
![Page 7: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/7.jpg)
7
Physics of LightningTypical 1st Return Stroke near 30,000 Amps but can be as high as 300kA.Subsequent strokes 10,000 to 15,000 Amps.1st Return Stroke Rise Times of 1.8µs to 18µs with 5.5µs being typical for. Equates to 14kHz to 139kHz with 45kHz being typical.Subsequent Return Stroke Rise Times of 0.22µs to 4.5µs with 1.1µs being typical for 1st Return Stroke. Equates to 56kHz to 1.1MHz with 227kHz being typical.Leader Potential of 1,000,000 to 10,000,000 Volts with respect to earth.
MCPQG/IEEE, May 3, 2011
![Page 8: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/8.jpg)
Lightning Stroke
MCPQG/IEEE, May 3, 2011 8
![Page 9: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/9.jpg)
9
Lightning Stroke
MCPQG/IEEE, May 3, 2011
The shape Represents a
Downward Leader
Leader/Streamer Connection
![Page 10: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/10.jpg)
10
How does Lightning Damage Equipment
Direct Lightning Strikes.Resistive Coupling.Inductive Coupling.Capacitive Coupling.
MCPQG/IEEE, May 3, 2011
![Page 11: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/11.jpg)
11
Direct Lightning Strikes
• Strike will cause extensive damage and can also cause damage to equipment inside the building
MCPQG/IEEE, May 3, 2011
![Page 12: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/12.jpg)
12
Resistive & Inductive Coupling
• Inductive coupling can also induce voltages into nearby equipment.
MCPQG/IEEE, May 3, 2011
![Page 13: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/13.jpg)
13
Capacitive Coupling
• Transients travelling along circuit conductors will induce voltages into adjacent conductors through mutual capacitance and inductance.
• Similar for cables near objects carrying lightning current.
MCPQG/IEEE, May 3, 2011
![Page 14: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/14.jpg)
14
Lightning Protection
Grounding and BondingIsolationSurge ProtectionBuilding Envelope
MCPQG/IEEE, May 3, 2011
![Page 15: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/15.jpg)
15
Grounding and Bonding
Relatively Low Earth ResistanceEquipotential Ground Plane
MCPQG/IEEE, May 3, 2011
![Page 16: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/16.jpg)
16
Earth Grounding
MCPQG/IEEE, May 3, 2011
![Page 17: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/17.jpg)
17
Ground Field ConsiderationsThe Ground Rod’s Earth Connection:
“Interfacing Hemisphere”
MCPQG/IEEE, May 3, 2011
![Page 18: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/18.jpg)
18
Ground Field ConsiderationsInterfacing Hemisphere• The rod’s interfacing hemisphere (IH) has a
radius of approximately 1.0 times the rod’s length. Therefore, it is best to space rods at least twice their length.
• The interfacing hemisphere makes up approximately 94% of the rod’s earth connection (i.e. resistance)
• 25% of the rod’s earth resistance is within the first 1.2 inches of the rod’s IH. Therefore, the first few inches away from the rod are the most important for reducing the earth resistance.
MCPQG/IEEE, May 3, 2011
![Page 19: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/19.jpg)
19
Ground Field Considerations
Rod, Pipe, and Plate Electrodes with ground resistance greater than 25 ohms must be augmented by one of the following:
» Building steel structure where it is effectively grounded» Concrete encased electrode in foundation or footing» Ground ring encircling the building» Rod or pipe electrode» Plate electrode» Other local underground systems or structures, such as piping
systems and underground tanks• Earth resistivity must be 60 ohm-meters or less for one 8’
rod to achieve 25 ohms (Average soil resistivity in Middle TN is 250 ohm-meters according to Soil Resistivity Map)
• Few areas in U.S. have average soil resistivity less than 60 ohm-meters
MCPQG/IEEE, May 3, 2011
![Page 20: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/20.jpg)
20
Ground Field Considerations
Ufer Grounds (Encased Electrodes)» Average Soil Resistivity for Middle TN = 250
Ohm-Meters Vs 0.12 Ohm-Meters for Erico’s “GEM”
» Concrete Resistivity is 30 ohm-meters.» Moisture Retention.
Can use Erico’s Calculator for Calculating Earth Resistance with and without GEM or do it manually using the Dwight formulas in the IEEE Green book or other reference. Can calculator download from their website.
MCPQG/IEEE, May 3, 2011
![Page 21: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/21.jpg)
21
Ground Field ConsiderationsEarth Resistance Guidelines:• Residence – 25 Ohms• Small Commercial – 20 Ohms• Industrial, Large Commercial – 10 Ohms Max.• Substations – 5 Ohms Maximum• With regards to the power system, in general, the
larger the electrical system the lower the earth resistance should be due to the higher fault currents.
• Another reason for lower resistance is for lightning protection. To give lightning the best path possible to earth.
MCPQG/IEEE, May 3, 2011
![Page 22: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/22.jpg)
22
Ground Field ConsiderationsGrounding Electrode Conductors• Minimize Lengths and sharp bends• Use minimum bending radius of 8 inches• Minimizing length is more important than bends• Conductor Z predominantly inductive reactance at HF
» Z~X=2πfL» L (in µH) =.508l[2.303Log(4l/d) -.75] x 0.01
– l=Length in inches– d=Diameter in inches
» f=Frequency is 45kHz to 227kHz typical (based on 5.5µs and 1.1µs rise times). For IEEE C62.41, 8 x 20µs Waveform, f=32.5 kHz. Lightning can also be in the 1 MHz range or higher.
» VD=Z x I = 163 V/FT. (each way) for 3kA, 8 x 20 µs impulse, using 2 AWG conductor.
» VD=Z x I = 5002 V/FT. (each way) for 3kA, 1 MHz impulse, using 2 AWG conductor.
MCPQG/IEEE, May 3, 2011
![Page 23: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/23.jpg)
23
Electrical Service Grounding
• With few exceptions, it is imperative to bond everything together to create a virtual “Grounding Grid”
MCPQG/IEEE, May 3, 2011
![Page 24: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/24.jpg)
24
Ideal Signal (Grounding) Reference Grid
SRG provides equipotential plane between equipment, which minimizes or eliminates potential differences between equipment.The SRG could include a grid of conductors, solid sheet of copper or sheet metal, and/or a building’s steel structure.
MCPQG/IEEE, May 3, 2011
![Page 25: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/25.jpg)
25
Grounding Grid Considerations
Take a comprehensive approach to grounding/bonding.
MCPQG/IEEE, May 3, 2011
![Page 26: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/26.jpg)
26
Radio Cable Grounding
Ground Bus
MCPQG/IEEE, May 3, 2011
![Page 27: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/27.jpg)
27
Radio Cable Bulkhead
MCPQG/IEEE, May 3, 2011
![Page 28: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/28.jpg)
28
Grounding Grid Considerations, cont.
For steel buildings, take advantage of the building’s structure.• The massive grid of steel can make for a nice
“Grounding Grid” if it is bonded and grounded.• Confirm all bolted connections are continuous. If
not, add jumpers.» The Lightning Protection standards allow using the
steel columns for down conductors but do not require bonding across bolted connections.
• For bar joist construction, confirm whether the metal deck pan is welded to the joists and if the joists are welded together via cross members.
MCPQG/IEEE, May 3, 2011
![Page 29: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/29.jpg)
29
Grounding Grid Considerations, cont.When bonding to steel, remove primer/paint to ensure a good connection (even if the lug is fastened using a tapped hole).• Advise installer to take necessary precautions if
primer/paint includes lead.• Use lock-washers.• Reapply primer/paint to exposed bare metal.• Apply an antioxidant compound around connection.• Where grounding conductors are installed in metal
conduit, be sure to bond each end of metal conduit to the same grounding point as the ground wire. Otherwise, the conductor and conduit act like a single turn coil.
• Use lugs with two bolt holes to minimize twisting lug where wire or lug could be hit.
MCPQG/IEEE, May 3, 2011
![Page 30: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/30.jpg)
30
Grounding Grid Considerations, cont.
Bonding Jumper across column and beam connection.Same for the steel purlins that were screwed to beams.
MCPQG/IEEE, May 3, 2011
![Page 31: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/31.jpg)
31
“Isolation”Minimizing or Eliminating the Adverse Effects of
Potential Differences on the Grounding System
Equipotential Ground Plane (Grounding Grid) (discussed earlier)Ethernet NetworksSignal IsolatorsOptical IsolatorsFiber Optic Cables
MCPQG/IEEE, May 3, 2011
![Page 32: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/32.jpg)
32
Ethernet Networks
Ethernet networks are more immune to ground loops due to internal isolation on data portsIsolated ground usually not be necessary
MCPQG/IEEE, May 3, 2011
![Page 33: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/33.jpg)
33
Signal Isolator
This is normally used in process controlsIsolated ground may not be necessary
MCPQG/IEEE, May 3, 2011
![Page 34: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/34.jpg)
34
Optical Isolator
Optical isolators can provide 2.0kV or more of isolationFor 100% isolation use fiber optic cable between equipment
MCPQG/IEEE, May 3, 2011
![Page 35: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/35.jpg)
35
Optical Isolator
B&B Electronics offers models for various applicationsFor Ethernet, use Fiber Optic Media Converters.
MCPQG/IEEE, May 3, 2011
![Page 36: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/36.jpg)
36
Surge ProtectionLocations• Each Electrical Service Entrance• Sub-Panels supplied from transformers, and/or
supplying critical/sensitive equipment.• Each Communications Service (Telephone, Cable
TV, Satellite, etc.)• Each power or communications or data circuit that
extends beyond the building for outdoor equipment or remote buildings.
• Critical/Sensitive utilization equipment. Consider combination units where the equipment is connected to both power and communications/data.
MCPQG/IEEE, May 3, 2011
![Page 37: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/37.jpg)
37
Surge Protection, cont.SPD Conductor Connections• SPD let-through voltage is insignificant compared to the effect of
conductor lengths• Conductor Z predominantly inductive reactance at high frequency
» L (in µH) =.508l[2.303Log(4l/d) -.75] x 0.01– l=Length in inches– d=Diameter in inches
» f=Frequency is 45kHz to 227kHz typical (based on 5.5µs and 1.1µs rise times). For IEEE C62.41, 8 x 20µs Waveform, f=32.5 kHz. Lightning can also be in the 1 MHz range or higher.
» VD=Z x I = 163 V/FT. (each way) for 3kA, 8 x 20 µs impulse, using 2 AWG conductor.
» VD=Z x I = 5002 V/FT. (each way) for 3kA, 1 MHz impulse, using 2 AWG conductor.
• Consider SPD units integrally-mounted in panels. Be aware if it fails destructively, the panel could also fail.
MCPQG/IEEE, May 3, 2011
![Page 38: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/38.jpg)
38
Church Case Study
Built in 3 Phases between 1956 and 2008
Wood & ConcreteStructures
1956 & 1992
Steel RoofStructure & Rubber
Roof2001
SteelStructure & Metal
Roof2008
Five Modular Buildings with Steel Floor Joists & Metal
Roof
MCPQG/IEEE, May 3, 2011
Steeple ~110’ above grade
![Page 39: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/39.jpg)
39
Church Case Study, cont.
Built in 3 Phases between 1956 and 2008
Five Modular Buildings with
Steel Floor Joists & Metal Roof
Wood & ConcreteStructures
1956 & 1992
Steel RoofStructure &
Rubber Roof2001Steel
Structure & Metal Roof
2008
Service #3
Service #2 Service #1
MCPQG/IEEE, May 3, 2011
Annex I Building
![Page 40: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/40.jpg)
40
Church Case Study, Cont.
MCPQG/IEEE, May 3, 2011
![Page 41: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/41.jpg)
41
Church Case Study, Systems49 HVAC Units with 26 roof-mounted on 2001 section roof.HVAC DDC Control System.
» This system includes a data cable (RS-485 protocol) that daisy-chains through all HVAC unit controllers.
LAN that originates in 1992 section with fiber optic cables between 1992 section and 2008 section.A/V Control Room in 2008 section for Sanctuary.Video Transmitter in 2008 A/V Control Room with video Receiver in 2001 Café and in 2008 Library. Intercom at main front entrance for communicating with receptionist in front lobby.Access Control System with three card readers.
MCPQG/IEEE, May 3, 2011
![Page 42: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/42.jpg)
42
Church Case Study, Analysis
Access Control System with three card readers.
MCPQG/IEEE, May 3, 2011
![Page 43: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/43.jpg)
43
Church Case Study, Lightning Damage
HVAC DDC Control System.» This was the main damage that occurred repeatedly. » It occurred occasionally before the 2008 section but
escalated after the 2008 section.» This system includes a data cable (RS-485 protocol)
that daisy-chains through all HVAC unit controllers.Video Transmitter in 2008 A/V Control Room and video Receiver in 2001 Café. The café receiver had been damaged 2 to 3 times prior to 2010.Intercom and Card reader at main front entrance.
MCPQG/IEEE, May 3, 2011
![Page 44: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/44.jpg)
Church Case Study, Grounding Before
MCPQG/IEEE, May 3, 2011 44
![Page 45: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/45.jpg)
Church Case Study, Grounding After
MCPQG/IEEE, May 3, 2011 45
![Page 46: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/46.jpg)
Church Case Study, Typical Ground Field
MCPQG/IEEE, May 3, 2011 46
Both 8’ rods together yield 21Ω in 150Ω-m soil.
The encased conductor yields 16Ω in 150Ω-m soil.
Each 8’ rod alone yields 38Ω in 150Ω-m soil.
![Page 47: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/47.jpg)
Church Case Study, Ground Field Details
MCPQG/IEEE, May 3, 2011 47
Can download Erico’s Ground Resistance calculator from their
website or calculate manually per IEEE Green book.
![Page 48: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/48.jpg)
Church Case Study, DDC Controls Before
MCPQG/IEEE, May 3, 2011 48
![Page 49: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/49.jpg)
Church Case Study, Ground Differential
MCPQG/IEEE, May 3, 2011 49
![Page 50: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/50.jpg)
Church Case Study, Ground Differential
MCPQG/IEEE, May 3, 2011 50
![Page 51: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/51.jpg)
Church Case Study, DDC Controls After
MCPQG/IEEE, May 3, 2011 51
![Page 52: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/52.jpg)
52
Optical Isolator
Optical isolators can provide 2.0kV or more of isolationFor 100% isolation use fiber optic cable between equipment
MCPQG/IEEE, May 3, 2011
![Page 53: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/53.jpg)
53
Optical Isolator
B&B Electronics offers models for various applicationsFor Ethernet, use Fiber Optic Media Converters.
MCPQG/IEEE, May 3, 2011
![Page 54: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/54.jpg)
54
Church Case Study, Other Improvements
SPD for all Electrical Services.SPD for all sub-panels that supply rooftop equipment.Bonded the same sub-panels to the building steel.Monitoring system for SPDs to send alarms via the LAN.Improved installation of ac supply SPDs for fire alarm control panels and for low-voltage SPD for fire alarm outdoor circuit to PIV.Installed outdoor exposed DDC data cables in steel conduit.Intercom and Card reader at main front entrance.
MCPQG/IEEE, May 3, 2011
![Page 55: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/55.jpg)
55
Church Case Study, Lightning Events Since Improvements
As of December 2010, bonding of steel and water pipes were completed.2/24/11 thunderstorm, no damage.2/28/11 thunderstorm, three DDC controllers failed. Several had to be reset.3/23/11 and 4/4/11, Thunderstorms, no damage.Earth Grounding work completed 4/4/11.Optical Isolators installed 4/5/11. Most other work completed by 4/22/11.No problems in recent severe thunderstorms.
MCPQG/IEEE, May 3, 2011
![Page 56: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/56.jpg)
56
Case Study: “Too Much” Grounding
Metro Emergency Communications CenterMCPQG/IEEE, May 3, 2011
![Page 57: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/57.jpg)
57
Case Study: “Too Much” Grounding
MCPQG/IEEE, May 3, 2011
UP
STAIR125
CO
RR
IDO
R12
6
911 ROOM
E.O.C.
COORIDOR107
WATCH108
TAP
ES
TOR
.1
12
109
TOIL.
STO.109
CONFEREN
CE10
1
COFFEE
102
MEN
S12
8
TELE
.
TRAN
SMIT
TER
MAI
NT.1
13
UPS
102
LOUNGE1 16
MENS LOCKER RM.
WOMENSLOCKER RM.120
BATT
ERY
GENER
ATOR R
M.
EQUIP.124
SECRETARY106
MENS
WOMENS
ELEVATOR STOR. CORRIDOR
STOR.
MENS WOMEN
JANIT
OR
ELEVATORLOBBY
TRAN
SMIT
TER R
M.
TOIL
.
PASS
AGE
STOR.
STAI
RS
105
ENTRY
110
TVSS
TVSS
TVSS
MANAGER
110911 SUPERVISOR
SECURITYOFFICE
RECEPTION
LOAD
ING
DOCK
117
155
![Page 58: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/58.jpg)
58
Case Study: “Too Much” Grounding
MCPQG/IEEE, May 3, 2011
![Page 59: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/59.jpg)
59
Case Study: “Too Much” Grounding
MCPQG/IEEE, May 3, 2011
![Page 60: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/60.jpg)
60
Personal Safety from Lightning
Safer places include:• Buildings that are protected against lightning.• Large metal frame buildings.• Enclosed automobiles or other vehicles with metal
top and bodies.• Enclosed metal boats or ships.• City streets shielded by nearby buildings.
However, be aware of possible voltage gradients should lightning hit a nearby building.
MCPQG/IEEE, May 3, 2011
![Page 61: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/61.jpg)
61
Personal Safety from Lightning, cont.If caught in an open area:• Crouch as low as possible,• Keep feet together,• Put hands on knees,• To minimize risk of a direct strike, keep as low as
possible.• To minimize risk of step potential, minimize the
area of the body in contact with the ground. Do not lie flat.
Refer to NFPA 780 and/or other lightning publications for more safety information.
MCPQG/IEEE, May 3, 2011
![Page 62: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/62.jpg)
62
Personal Safety from Lightning, cont.
Car Protection (Faraday Cage)
MCPQG/IEEE, May 3, 2011
![Page 63: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/63.jpg)
63
Personal Safety from Lightning, cont.
The Shower Jolt!
MCPQG/IEEE, May 3, 2011
![Page 64: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/64.jpg)
64
For Effective Lightning Protection
Look at THE BIG PICTURE.Consider all Systems and Equipment Involved.For Personal Safety, Respect Lightning
MCPQG/IEEE, May 3, 2011
![Page 65: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures](https://reader031.vdocuments.net/reader031/viewer/2022021818/5aa718417f8b9a50528be204/html5/thumbnails/65.jpg)
65
God Bless Americaand Our Troops
MCPQG/IEEE, May 3, 2011