gsm communication the future of alarm communication

71
GSM Communication The Future of Alarm Communication

Upload: tamber

Post on 26-Jan-2016

52 views

Category:

Documents


1 download

DESCRIPTION

GSM Communication The Future of Alarm Communication. What is GSM?. Global System for Mobile Communications Developed in 1990s One of the leading digital cellular networks AT&T network in the U.S. Rogers network in Canada Most popular standard for mobile phones in the world. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: GSM  Communication The Future of Alarm Communication

GSM Communication

The Future of Alarm Communication

Page 2: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

2

GSM Communication

What is GSM?

• Global System for Mobile Communications– Developed in 1990s

– One of the leading digital cellular networks

– AT&T network in the U.S.

– Rogers network in Canada

• Most popular standard for mobile phones in the world.– Approximately 70% of the world’s market

– Open standard with roaming capability

Page 3: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

3

GSM Communication

Two communication paths: GPRS and SMS

GPRS• General Packet Radio Service

– Always On connection• Typically faster than SMS

– Real-time confirmation

• Higher bandwidth capacity– Supports downloading

SMS• Short Message Service

– Store and forward communication• Sent via SMS Center

• Less bandwidth capacity– No downloading support

Both signaling and speech channels are digital.Higher digital voice quality and text messaging

Page 4: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

4

GSM Communication

Honeywell GSM Radio Offering

• Uses GPRS for reliable transmission of alarm signals

• Back-up reporting with SMS

• Contact ID or ADEMCO Hi Speed

• Power Supply and battery included

• Panel downloading supported

• 6 HW zone inputs (seven zones)

• Tampered enclosure

• Fault Relay output

Future Proof Design Protects Your Business

Page 5: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

5

GSM Communication

Honeywell i-GSM Radio Offering

• Uses an existing internet connection for reliable transmission of alarm signals

• Back-up reporting with GPRS or SMS

• Contact ID or ADEMCO Hi Speed

• Power Supply and battery included

• Panel downloading supported

• 6 HW zone inputs (seven zones)

• Tampered enclosure

• Fault Relay output

Page 6: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

6

GSM Communication

Honeywell GSMCF/iGSMCF Radio Offering

GSMCF• Will replace the 7835CF, 7845CF and 7845CZF; but does not replace the 7720ULF or 7720ULFPLUS.

• This device cannot be a stand-alone communicator, although it can be a primary communicator if you have another form of communication.

• It is designed to replace one phone line to a fire panel.

IGSMCF• This radio has been ETL approved for primary commercial fire use.

• This radio will replace the 7835CF, 7845CF, 7845CZF, 7720ULF and 7720ULFPLUS.

• This device is a stand-alone communicator, designed to replace both phone lines to a fire panel.

The GSMCF and IGSMCF both come in a red fire resistant can and includes an

externally mounted antenna (3dB gain).

Page 7: GSM  Communication The Future of Alarm Communication

GSM Communication

Installation Procedures

Page 8: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

8

GSM Communication

Installation Procedures

Installation of a GSM radio will consist of a few steps:

1. Activating the SIM card.

2. Finding a suitable mounting location with adequate signal strength.

3. Wiring to control panel.

4. Programming and Registration

Page 9: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

9

GSM Communication

Activating the SIM Card

• The SIM card on the GSM device you are installing must be activated prior to completing the registration process.

• You will not have any signal strength indication on your GSM radio prior to SIM activation.

• The SIM card can be activated up to thirty days prior to registration.

• You may set up registration at the time of activation.

• If the radio is not registered to an account within thirty days, the SIM will be automatically deactivated by Alarmnet.

Page 10: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

10

GSM Communication

Activating the SIM Card

There are three ways to activate a SIM card:

1) Log on to Alarmnet Direct website and enter MAC ID and CRC information

https://services.alarmnet.com/alarmnetdirect/

2) Contact your Central Station

3) Call Alarmnet SIM activation at 800-222-6525 Select option 1 for Technical Support, then press 1 for Alarmnet

GSM device activation.

You must have the MAC ID and CRC to activate the SIM.

It will take from several minutes to a few hours to activate the SIM.

Page 11: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

11

GSM Communication

Where can I get the Mac ID and CRC?

Page 12: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

12

GSM Communication

Check Signal Strength

9VAC

15VA

NOTE: It is extremely important that you select a suitable mounting location that allows for adequate signal strength!!!

Page 13: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

13

GSM Communication

Wiring for ECP and 4204 modes

9VAC

15VA

NOTE: AC Power must be applied on 1 and 2.

Page 14: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

14

GSM Communication

Wiring for ECP on a LynxR-i

NOTE: DC Power is supplied from LynxR-i panel.

The LynxR-I series panels provide the primary and backup power for the GSM radio.

Do Not Connect the 7845GSM internal battery or the GSM power transformer.

Page 15: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

15

GSM Communication

Wiring Zone 1 input to a LynxR trigger output

9VAC

15VA

NOTE: AC Power must be applied to terminals 1 and 2 on 7845GSM.

Program Trigger as V- and enable Lynx Panic

Page 16: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

16

GSM Communication

Wiring Zone Input for Bell (or positive voltage) output

Page 17: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

17

GSM Communication

Zone input using NO/NC contact with EOLR Supervision

Page 18: GSM  Communication The Future of Alarm Communication

GSM Communication

Programming and Registration

Page 19: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

19

GSM Communication

Programming and Registration

• There are several options to program and register the GSM radio:

1. Log on to Alarmnet Direct website and enter the appropriate radio and account information• https://services.alarmnet.com/alarmnetdirect/

2. Program and register using the 7720p program tool.

3. Contact your Central Station

4. Call Alarmnet Registration at 800-222-6525• Select option 1 for Technical Support, then press 1 for Alarmnet GSM device

registration.

You must have an account number (provided by your Central Station) and be able to provide radio MAC and CRC to proceed with registration.

Page 20: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

20

GSM Communication

Programming: Using the 7720p

You must have AC power on terminals 1 and 2 for 7720p to work.

Page 21: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

21

GSM Communication

Programming Basics: Using the 7720p

Plug in 7720P programmer and press Enter key– Press Enter to accept entries

Use the up/down arrow keys to scroll through the programming questions without changing any values.

Perform a Shift function by pressing Shift key and then the appropriate key.

Strt Prog Mode?Y/N_

Press Shift & Y

Page 22: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

22

GSM Communication

Programming Options

Enter Password

Program 7845?Y/N

Press Shift & Y

Create Password?Y/N

Page 23: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

23

GSM Communication

Programming Options

Device Mode?ECP

Options:ECPZone Triggers4204 EMU2 4204s

(Use the space key to scroll through options)

Primary City ID?(??)

Primary CS ID?(??)

Primary Sub ID?(????)

Acct info provided by your Central Station

Page 24: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

24

GSM Communication

Programming Options

2ND City ID?(??)

2ND CS ID?(??)

2ND Sub ID?(????)

2ND CS Y/N?

Option to use 2nd CS reporting only available on High-End panels (polling loop panels)

Page 25: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

25

GSM Communication

Programming Options

Device Address(03)

Enable DW Y/N(N)

Direct Wire Address(28)

If YesHigh-endPanels Only

(polling loop)

Page 26: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

26

GSM Communication

Programming Mode

Supervision24 hours

Old Alarm Time(10 Minutes)

GSM Flt Time(60 mins)

Flt Rel On Y/N(N)

Options are:•None

•24 Hours

•30 days

Note: This feature does NOT enable a test report to be sent to the Central Station

Page 27: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

27

GSM Communication

Programming Mode

Pwr Loss Rpt (Y/N)(Y)

Low Bat Rpt (Y/N)(Y)

Tamper Rpt (Y/N)(Y)

1-3 hours of loss

Disable these reports if installing on the LynxR-I (ECP)

Page 28: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

28

GSM Communication

Programming Mode

Enable Zn 6 (Y/N)(N)

Zn 6 Trigger Type(V+)

Invert Zn 6 (Y/N)(N)

Restore Zn 6 (Y/N)(N)

Delay Zn 6 (secs)(00)

Zones 6 & 7 are available in ECP mode

Repeat for zone 7 if required

Page 29: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

29

GSM Communication

Zone Mode

• When the GSM is programmed for zone mode, there are six input zones available.

• The first zone input (TB1, pin 5) can detect a pulsed signal (reported as zone 1) or a steady signal (reported as zone 2).

• When using zone trigger mode, messages are sent in ADEMCO high-speed format.

Page 30: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

30

GSM Communication

Zone Mode Programming Options

Trip Inputs 1or2 w/Bell out (N)

Enable this option when wiring zone 1/2 input (terminal 5) to control panel positive bell output.

This will help prevent false alarms caused by supervision voltage on the bell circuit.

This will also prevent the radio from causing bell circuit faults on the control panel.

►Note: Enabling this feature will raise the trip voltage on zones 1, 2, and 3 from 2VDC to 5VDC.

This option should not be enabled with negative trigger inputs on zones 1, 2, or 3.

Page 31: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

31

GSM Communication

Zone Mode Programming Options

Zn1 Trigger Type (V+)

This selects the triggering method for this zone input.

Options are: (V+), (V-), or (EOLR)

If zone is set for (V+), the zone will report an alarm when voltage input is 2VDC-14VDC.

Trigger levels above 14VDC may damage the unit and trigger levels below 2VDC may not trigger the zone.

Remember: Enabling “Trip Inputs w/Bell out” increases minimum

trigger requirement for zones 1, 2, and 3 to 5VDC.

Page 32: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

32

GSM Communication

Zone Mode Programming Options

Zn1 Trigger Type (V+)

This selects the triggering method for this zone input.

Options are: (V+), (V-), or (EOLR)

•If the zone is set to (V-), the negative triggering voltage must be less than 1.0VDC.

•If the zone is set to (EOLR), the zone will report an alarm when the EOLR is removed from the zone.

Recommended EOLR is 2K ohms.

Page 33: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

33

GSM Communication

Zone Mode Programming Options

Restore Zn1 Y/N

(Y)

This enables the zone to report when it is restored.

Delay Zn1 (secs)

(00)

This option defines any delay in reporting for this zone input (from 0 to 15 seconds).

Rpt Zn1 ONLY if

Armed (N)

This option will disable this zone from reporting unless the conditional zone is triggered. (The conditional zone is zone 7 when radio is in zone mode.)

Page 34: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

34

GSM Communication

Zone Mode Programming Options

Invert Zn2 Y/N

(N)

This option inverts the alarm and normal states of the zone trigger.

Lynx Panic Y/N

(N)

This option is enabled only when radio is connected to a Lynx, LynxR, or LynxR-EN. This enables a silent panic alarm to be sent when a single pulse is detected on zone 1.

Page 35: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

35

GSM Communication

7845I-GSM Programming Options

IP Flt Time

(60 mins)

Notify Panel Of

(Neither Fault)_

• Basically the same as the previously discussed “GSM flt time.” In the event there is loss of contact with the network over the Ethernet connection, enter the time delay before the 7845i-GSM notifies the Central Station of the problem.

• IP failure will always be reported as “Primary Communication Path Failure”

• Programming options are: “Neither Fault” or “Both IP and GSM Faults.”

• If “Both IP and GSM Faults” is selected, the device will notify the control panel (via ECP bus or GSM fault relay) if both communication paths fail.

Page 36: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

36

GSM Communication

7845I-GSM Programming Options

GSM Rollover Y/N

(Y)_

GSM 24Hr Tst Y/N

(N)_

• If enabled, all messages (including AlarmNet network supervisory messages) are sent over GSM network in

the event of an internet failure. • If disabled, all messages (except AlarmNet network supervisory messages) are sent over GSM network in the event of an internet failure.

• If enabled, the 7845i-GSM sends a supervision ping over the GSM network once a day to verify backup communication path.

• A “secondary communication path loss” message is generated if the message is not successfully delivered.

Page 37: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

37

GSM Communication

7845I-GSM Programming Options

Use DHCP Y/N (Y)_

NIC IP Address:255.255.255.255_

Subnet Mask:255.255.255.255_

Gateway IP Addr:255.255.255.255_

DNS Server IP Addr:255.255.255.255_

DHCP dynamically allocates the IP addresses (recommended). If you select “No,” then you must program the following fixed (static) IP addresses:

Page 38: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

38

GSM Communication

7845I-GSM Programming Options

Enable Pwr Save

(Y)_

For 24 UL battery backup requirement, this feature must be enabled, or the unit must be powered by an appropriate UL

listed UPS.

What does it do?

If the feature is enabled, the communicator’s NIC card will power down and will power up every 20 seconds to send a test ping (to

test internet path) then power down again. The NIC will also power up anytime the unit needs to transmit information over the

internet. If connectivity problems occur with certain routers or switches, disable this option.

Page 39: GSM  Communication The Future of Alarm Communication

GSM Communication

Registering the GSM New and Replacement

Page 40: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

40

GSM Communication

New Registration (Radio on New Account)

Shift

Registration Success

Registering…

After exiting programming mode on the 7720p, you may register the radio by hitting the Shift key, then the “up” arrow.

Page 41: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

41

GSM Communication

Replacement Registration

• When registering a replacement radio on an active account, a pin number must be entered. After exiting programming mode, select the “down” arrow key. You will be prompted to enter a pin.

– Enter PIN and hit the Enter key to proceed with registration.• If replacing a C radio, enter the last four digits of the min number.• If replacing a GSM with another GSM, a PIN must be generated by your

Central Station.

Enter PIN#

Registering…

RegistrationSUCCESS

Page 42: GSM  Communication The Future of Alarm Communication

GSM Communication

Programmerless Registration:Using Alarmnet Direct

Page 43: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

43

GSM Communication

Programmerless Registration

Preliminary Steps Required Before Registration

• Before registering, you must have the following information available: a. CITY numberb. CS numberc. RADIO SUBSCRIBER numberd. DEVICE MODEe. Daily or Monthly Supervisionf. MAC Address from 7845GSM Radiog. MAC CRC number from the 7845GSM Radio

• City number, CS number, and Radio Subscriber number is assigned by your Central Station

Page 44: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

44

GSM Communication

Programmerless Registration

Steps Required to Enter Data

• Log into AlarmNet Direct using your user name and password. https://services.alarmnet.com/AlarmNetDirect

• To program a radio on a NEW account, select “Program New Device GSM/I”

• To replace a “C” radio with a GSM, select “Replace C Device”

• To replace a GSM with another GSM, select “Replace Other Device”

Page 45: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

45

GSM Communication

Programmerless RegistrationProgrammerless Registration• Enter the radio’s information

a) CITY number

b) CS number

c) SUBSCRIBER number

d) Supervision Rate

e) MAC number

f) CRC number

• Confirm the Device Mode, and if using ECP with device address 03 click Done.

Page 46: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

46

GSM Communication

Programmerless RegistrationAlarmNet C Replacement

Enter 10 digit MIN number from old C Radio

Page 47: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

47

GSM Communication

Programmerless RegistrationAlarmNet GSM Replacement

Enter PIN number generated by your Central Station

Page 48: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

48

GSM Communication

Programmerless Registration

Important Note AboutProgrammerless Replacements!

• The PIN is only transferred to the 7845GSM device on the first data transfer attempt.

• If your device fails to register, take the following steps using AlarmNet Direct.

a) Delete the account from “Show Programmed Devices”.b) Add the account back using “Replace C” or “Replace Other Device”.c) From the “Show Programmed Devices” page, execute the SEND

DATA command and get confirmation of the data transfer by refreshing the page.

d) After current date and time are showing in the “Transferred” column, execute the “Register” command.

• Following these steps will ensure the PIN is transferred to the device. Remember, If the device fails to register the first time, the PIN will be reset to FFFF and will not be accepted by the AlarmNet servers.

Page 49: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

49

GSM Communication

Programmerless Registration

Selecting “Done” sets programming to default values, which is ECP Mode, Device Address 03.

• If the installation requires you to change any programming option from the default value, select “Advanced Programming”.

Page 50: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

50

GSM Communication

Programmerless RegistrationScreenshot of “Advanced Programming” screen

Page 51: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

51

GSM Communication

Programmerless RegistrationScreenshot of “Advanced Programming” screen

Page 52: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

52

GSM Communication

Programmerless RegistrationScreenshot of “Advanced Programming” screen

Page 53: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

53

GSM Communication

Programmerless Registration

Page 54: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

54

GSM Communication

Programmerless Registration• On site click the Tamper Switch 3 times. The green (status) and yellow

(message) LED’s on the top left should start flashing together.

Page 55: GSM  Communication The Future of Alarm Communication

GSM Communication

IP Downloading

Page 56: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

56

GSM Communication

IP Downloading Support

Panels that can be downloaded via GSM

Page 57: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

57

GSM Communication

IP Downloading Support

Panels that can be downloaded via GSM

Page 58: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

58

GSM Communication

Vista-20P and LynxR-i

• The Vista-20P and LynxR-I communicates with the 7845GSM over the ECP (keypad) bus.

• To setup the control panel, do the following:1. Connect the 7845GSM module to the control panel’s ECP (keypad)

terminals as you would a keypad.

2. Enable the 7845GSM as a Long Range Radio in the control panel to enable alarm reporting and module supervision.

- Vista - *29 = 1- LynxR-I - *55 = 1

3. Program the 7845GSM and set the ECP address to 3.

4. Register the 7845GSM with AlarmNet. The module must be registered before downloading or alarm reporting can take place.

Page 59: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

59

GSM Communication

Vista-128/250BP and Vista-128/250FBP

• To set up the control panel, do the following:1. Connect the 7845GSM module to the control panel’s ECP (keypad)

terminals as you would a keypad.2. Program the 7845GSM as required using the 7720P programmer. (To

do this, temporarily disconnect the RJ11 from the 7845GSM and plug in the programmer). Remember to program:

• Question 13 (ANI ECP Address) with the same address programmed in Step 4. Two additional programming questions have been added for direct wire downloading over IP:

• Question 14 (Enable DW) to enable direct wire downloading; and • Question 15 (Direct Wire Address), to tell the 7845GSM what keypad

address the 7845GSM is going to use for direct wire downloading (same address as entered in Step 5).

3. Connect the trigger cable between the control panel trigger connector and the 7845GSM (RJ11 connection).

4. Enable an address for the 7845GSM as a Long Range Radio (LRR) in the control panel’s Device Programming Mode (*93). This enables the 7845GSM on the control panel.

Page 60: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

60

GSM Communication

Vista-128/250BP and Vista-128/250FBP

6. Enable a second address for the 7845GSM as a keypad in the control panel’s Device Programming Mode (*93). This enables the control panel to perform downloading over IP. Do not connect an actual keypad or any other device at this address.

7. Register the 7845GSM with AlarmNet. The module must be registered before downloading or alarm reporting can take place.

Page 61: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

61

GSM Communication

Direct Wire Connections

Page 62: GSM  Communication The Future of Alarm Communication

GSM Communication

Diagnostics

Page 63: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

63

GSM Communication

Exterior L.E.D. Status

Page 64: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

64

GSM Communication

Mode and Status Indicator Switch

LED 4 not used on 7845GSM

Page 65: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

65

GSM Communication

Mode and Status Indicator Switch

Connected To Web

Remember: LED 4 not used on 7845GSM

Page 66: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

66

GSM Communication

7845i-GSM Network Connectivity Display

Page 67: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

67

GSM Communication

7845GSM ECP Keypad Display Status Codes

Note: You can only display Status Codes on an alpha keypad.

Page 68: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

68

GSM Communication

7845i-GSM ECP Keypad Display Status Codes

Note: You can only display Status Codes on an alpha keypad.

Page 69: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

69

GSM Communication

7845GSM Central Station Messages

Page 70: GSM  Communication The Future of Alarm Communication

Honeywell Proprietary

Honeywell.com

70

GSM Communication

7845i-GSM Central Station Messages

Page 71: GSM  Communication The Future of Alarm Communication

http://www.security.honeywell.com/hsce/

and click on MyWebTech

User name: honeywell

Password: support99

Honeywell Security support e-mail: [email protected]