Guideline for Sunshades – Spec, Design Requirements & Std Drawings Version 1.0 GU-631 Page 7 Dec 2009 2.2.1 General As Sunshades are specifically designed to protect equipment from solar radiation, their sizes are directly related to the angle of the sun during the most intense period of this solar radiation. Accordingly, the equipment that needs to be shaded shall be within the boundaries and angles shown in Figure 1 below:- North Side 85° from the horizontal South Side 70° from the horizontal East & West Sides 50° from the horizontal SUNSHADE ROOF SUNSHADE ROOF 50 O 50 O 70 O 85 O NORTH SOUTH EAST WEST GL EQUIPMENT TO BE SHADED SUN Figure 1 It should be noted that the angle shall be taken from the underside and around the perimeter of equipment to be protected and not ground level. Also, shading can be increased by installing side cladding; however a design check against the extra wind forces need to be made. 2.2.2 Materials All materials required for Sunshades shall comply with the relevant Standards listed in Section 1.4.2 of this specification Guideline. 2.2.3 Design All Sunshades designs shall be in accordance with the relevant Standards listed in Section 1.4.1.of this specification Guideline. 2.2.3.1 Steel Structure The steel structures, both with and without integral lifting facilities shall be designed in accordance with EN 1993 (or Eurocode 3).

Upload: barouniamine

Post on 03-Oct-2015

231 views

Category:

Documents


3 download

DESCRIPTION

sunshade guideline

TRANSCRIPT

  • Guideline for Sunshades Spec, Design Requirements & Std Drawings Version 1.0

    GU-631 Page 7 Dec 2009

    2.2.1 General

    As Sunshades are specifically designed to protect equipment from solar radiation, their sizes are directly related to the angle of the sun during the most intense period of this solar radiation. Accordingly, the equipment that needs to be shaded shall be within the boundaries and angles shown in Figure 1 below:-

    North Side 85 from the horizontal

    South Side 70 from the horizontal

    East & West Sides 50 from the horizontal

    SUNSHADE ROOF SUNSHADE ROOF

    50O50O70O85ONORTH SOUTH EAST WEST

    GL

    EQUIPMENT TO BE SHADED

    SUN

    Figure 1

    It should be noted that the angle shall be taken from the underside and around the perimeter of equipment to be protected and not ground level. Also, shading can be increased by installing side cladding; however a design check against the extra wind forces need to be made.

    2.2.2 Materials

    All materials required for Sunshades shall comply with the relevant Standards listed in Section 1.4.2 of this specification Guideline.

    2.2.3 Design

    All Sunshades designs shall be in accordance with the relevant Standards listed in Section 1.4.1.of this specification Guideline.

    2.2.3.1 Steel Structure

    The steel structures, both with and without integral lifting facilities shall be designed in accordance with EN 1993 (or Eurocode 3).