2.2.1 General
As Sunshades are specifically designed to protect equipment from solar radiation, their sizes are directly related to the angle of the sun during the most intense period of this solar radiation. Accordingly, the equipment that needs to be shaded shall be within the boundaries and angles shown in Figure 1 below:-
North Side 85 from the horizontal
South Side 70 from the horizontal
East & West Sides 50 from the horizontal
SUNSHADE ROOF SUNSHADE ROOF
50O50O70O85ONORTH SOUTH EAST WEST
GL
EQUIPMENT TO BE SHADED
SUN
Figure 1
It should be noted that the angle shall be taken from the underside and around the perimeter of equipment to be protected and not ground level. Also, shading can be increased by installing side cladding; however a design check against the extra wind forces need to be made.
2.2.2 Materials
All materials required for Sunshades shall comply with the relevant Standards listed in Section 1.4.2 of this specification Guideline.
2.2.3 Design
All Sunshades designs shall be in accordance with the relevant Standards listed in Section 1.4.1.of this specification Guideline.
2.2.3.1 Steel Structure
The steel structures, both with and without integral lifting facilities shall be designed in accordance with EN 1993 (or Eurocode 3).