h27e direct vent gas stove

9
H27E-11 Gas Stove | 1 H27E Direct Vent Gas Stove Model H27E-NG11 H27E-LP11 Fuel Type Natural Gas Propane Minimum Supply Pressure 5” W.C. (1.25 kPa) 11” W.C. (2.74 kPa) Manifold Pressure - High 3.5” W.C. (0.87 kPa) 10” W.C. (2.49 kPa) Manifold Pressure - Low 1.6” W.C. (0.40 kPa) 6.4” W.C. (1.59 kPa) Orifice Size #42 DMS #54 DMS Minimum Input 18,000 BTU/h (5.28 kW) 17,500 BTU/h (5.13 kW) Maximum Input 25,000 BTU/h (7.32 kW) 22,000 BTU/h (6.45 kW) Vent Sizing (Rear Vent) 4” Inner / 6-5/8” Outer 4” Inner / 6-5/8” Outer Vent Sizing (Top Vent) 4” Inner / 6-5/8” Outer 4” Inner / 6-5/8” Outer CSA P.4.1 61.22% 63.07% Approved Venting Systems Flex Vent Systems: FPI AstroCap™ Flex Vent Rigid Pipe Vent Systems: Simpson Direct Vent Pro® Selkirk Direct-Temp™ Metal-Fab® Sure Seal American Metal Products® Amerivent Direct Security Secure-Vent™ ICC Excel Direct 17 13/16” (452 mm) 17 13/16” (452 mm) CLEARANCES TO COMBUSTIBLES The clearances listed are MINIMUM distances. Measure the clearance to both the appliance and the chimney connector. The farthest distance is correct if the two clearances do not coincide. For example, if the appliance is set as indicated in one of the figures but the connector is too close, move the stove until the correct clearance to the connector is obtained. This appliance may be installed only with the clearances as shown in the situations pictured. Do not combine clearances from one type of installation with another in order to achieve closer clearances. This unit can be installed on a solid combustible surface like a wood floor. This unit can also be installed directly on carpeting or vinyl. Use the minimum clearances shown in the diagrams below: H27E-NG11 & H27E-LP11 Clearances A Left Side Wall to Unit* 6" / 150 mm B Back Wall to Unit 3" / 75 mm C Vertical Vent Pipe to Back Wall 2" / 50 mm E Unit Corner to Wall 2" /50 mm Unit Top to Alcove Ceiling 24" / 610 mm Minimum ceiling height is 24" /610 mm from top of unit.

Upload: others

Post on 25-Mar-2022

4 views

Category:

Documents


0 download

TRANSCRIPT

H27E-11GasStove |1

H27E Direct Vent Gas StoveModel H27E-NG11 H27E-LP11

FuelType NaturalGas Propane

MinimumSupplyPressure

5”W.C.(1.25kPa)

11”W.C.(2.74kPa)

ManifoldPressure-High

3.5”W.C.(0.87kPa)

10”W.C.(2.49kPa)

ManifoldPressure-Low

1.6”W.C.(0.40kPa)

6.4”W.C.(1.59kPa)

OrificeSize #42DMS #54DMS

MinimumInput 18,000BTU/h(5.28kW) 17,500BTU/h(5.13kW)

MaximumInput 25,000BTU/h(7.32kW) 22,000BTU/h(6.45kW)

VentSizing(RearVent)

4”Inner/6-5/8”Outer 4”Inner/6-5/8”Outer

VentSizing(TopVent) 4”Inner/6-5/8”Outer 4”Inner/6-5/8”Outer

CSAP.4.1 61.22% 63.07%

Approved Venting Systems

Flex Vent Systems: FPI AstroCap™ Flex Vent

Rigid Pipe Vent Systems: Simpson Direct Vent Pro®Selkirk Direct-Temp™Metal-Fab® Sure SealAmerican Metal Products® Amerivent DirectSecurity Secure-Vent™ICC Excel Direct

17 13/16”(452 mm)

17 13/16”(452 mm)

CLEARANCES TO COMBUSTIBLES

TheclearanceslistedareMINIMUMdistances.Measuretheclearancetoboththeapplianceandthechimneyconnector.The farthest distance is correct if the two clearances do not coincide.

Forexample,iftheapplianceissetasindicatedinoneofthefiguresbuttheconnectoristooclose,movethestoveuntilthecorrectclearancetotheconnectorisobtained.

Thisappliancemaybeinstalledonlywiththeclearancesasshowninthesituationspictured.Do not combine clearances from one type of installation with another in order to achieve closer clearances.

Thisunitcanbeinstalledonasolidcombustiblesurfacelikeawoodfloor.Thisunitcanalsobeinstalleddirectlyoncarpetingorvinyl.

Usetheminimumclearancesshowninthediagramsbelow:

H27E-NG11 & H27E-LP11 Clearances

A LeftSideWalltoUnit* 6"/150mm

B BackWalltoUnit 3"/75mm

CVerticalVentPipetoBackWall

2"/50mm

E UnitCornertoWall 2" /50mm

UnitToptoAlcoveCeiling 24" /610mm

Minimumceilingheightis24"/610mmfromtopofunit.

2| H27E-11GasStove

H27E-11 Gas Stove

Pipe Length

VerticalTermination

Cap

Storm Collar

Flashing

Ceiling Firestop

PipeLength

Adj.Pipe Length

90 Elbowo

HorizontalTermination

Cap

Wall Thimble

Vinyl SidingStandoff (Optional)

RIGID PIPE VENTING SYSTEMSHorizontal or Vertical Terminations

Alternate HorizontalTermination Caps

When using Rigid Vent other thanSimpson Dura-Vent, 3 screws must be used to secure rigid pipe to adaptor.

TheFPIAstroCapTMandFPIRiserVentterminalarecertifiedfor installationsusingFPIventingsystemsaswellasSimpsonDura-Vent®DirectVent,AmericanMetalProductsAmeriVentDirectVent,SecuritySecureVent®,SelkirkDirect-TempandICCExcel.AstroCapTMisaproprietarytrademarkofFPIFireplaceProductsInternationalLtd.Dura-Vent®andDirectVentProareregisteredand/orproprietarytrademarksofSimpsonDura-VentCo.Inc.

ThisproducthasbeenevaluatedbyIntertekforusingaRigidPipeAdaptorinconjunctionwithDuraventDirect-VentPro,SelkirkDirect-Temp,AmeriVentDirect, ICCExcel ventingand Security Secure Vent systems. Use ofthesesystemswiththeRigidPipeadaptorisdeemedacceptableanddoesnot affect theIntertekWHIlistingofcomponents.

WARNING:

Do not combine venting components fromdifferentventingsystems.

Howeveruseof thetheAstroCapTMandFPIRiserisacceptablewithallsystems.

H27E-11GasStove |3

H27E-11 Gas Stove

Offset to Vertical Terminations

Venting Arrangements - Horizontal Terminations using Dura-Vent Venting Systemand/or Riser Vent Termination

Snorkel Termination Riser Vent Termination

VENTING ARRANGEMENTS

Vertical Terminations Systems for Residential Manufactured and Mobile Homes

The shaded area in the diagram below shows all allowable combinations of straight vertical and offset to vertical runs with vertical terminations.Maximum two 45o elbows.

IftheventisENCLOSEDinachase(min.size9"x9")maintaina1-1/4"clearancetocombustibles.

May be installed in Manufactured (Mobile) Homes after first sale.

Horizontal Terminations for All Venting Systems

The shaded areas in the diagram below show allallowablecombinationsofverticalrunswithhorizontalterminations.Maximumone90Oelbow(two45oelbowsequalone90oelbow).

Propane and Natural Gas: Residential, Manufactured and Mobile Homes Installations

May be installed in Manufactured (Mobile) Homes after first sale.

The two diagrams show all allowable combinations of straight horizontal termination with one 45o elbow off the unit with Snorkels or FPI Riser Vent. Restrictor position "A".

4| H27E-11GasStove

H27E-11 Gas StoveHorizontal Venting with Two (2) 90o Elbows

Horizontal Venting with Two (2) 90o Elbows

H

H1

V

One 90o elbow = Two 45o elbow

Option V H + H1 With these opt ions,maximumtotalpipelengthis 30 feet with minimumof 6 feet total verticalandmaximum8feettotalhorizontal.Please note minimum 1 foot between 90o elbows is required.

A) 2'Min. 4'Max.

B) 3'Min. 5'Max.

C) 4'Min. 6'Max.

D) 5'Min. 7'Max.

E) 6'Min. 8'Max.

Lengthsdonotincludeelbowindicated.

VentrestrictorpositionA(fullyopen),refertothe"VentRestrictorPosition"section.

One 90o elbow = Two 45o elbow

Option H V H + H1 With these opt ions,maximumtotalpipelengthis 30 feet with minimumof 8 feet total verticalandmaximum8feettotalhorizontal.Please note minimum 1 foot between 90o elbows is required.

A) 1'Max. 1'Min. 3'Max.

B) 2'Max. 2'Min. 5'Max.

C) 3'Max. 4'Min. 6'Max.

D) 4'Max. 6'Min. 7'Max.

E) 5'Max. 8'Min. 8'Max.

Lengthsdonotincludeelbowindicated.

VentrestrictorpositionA(fullyopen),refertothe"VentRestrictorPosition"section.

H27E-11GasStove |5

H27E-11 Gas StoveVertical Venting with Two (2) 90o Elbows

Vertical Venting with Two (2) 90o Elbows

One 90o elbow = Two 45o elbows.

V1

VH

Option V H V + V1 A) 1'Min. 4'Max. 2'Min. B) 2'Min. 5'Max. 3'Min. C) 3'Min. 6'Max. 4'Min. D) 4'Min. 7'Max. 5'Min. E) 5'Min. 8'Max. 6'Min.

Withtheseoptions,max.totalpipelengthis30feetwithmin.of6feettotalverticalandmax.8feettotalhorizontal.Please note min. 1 foot between 90o elbows is required.

Vent restrictor position A (fully open), refer to the "Vent Restrictor Position" section.

Lengthsdonotincludeelbowindicated

Option H + H1 V A) 2'Max. 2'Min. B) 3'Max. 3'Min. C) 4'Max. 4'Min. D) 5'Max. 5'Min. E) 6'Max. 6'Min.

Withtheseoptions,max.totalpipelengthis30feetwithmin.of6feettotalverticalandmax.6feettotalhorizontal.Please note min. 1 foot between 90o elbows is required.

One 90o elbow = Two 45o elbows.

VentrestrictorpositionA(fullyopen),refertothe"VentRestrictorPosition"section.

Lengthsdonotincludeelbowindicated

6| H27E-11GasStove

H27E-11 Gas Stove

Flex Liner

ExhaustFlue

A maximumof two certified

joiner kitsmay be used

per length.#948-305 (35 ft)

Air Intake

Co-linear DVVertical Termination

Cap # 946-529

Co-LinearFlex

Adapterwith Kit#946-563

OuterPipe

with Kit#946-563

Inner PipeAdapterwith Kit#946-563

Venting Arrangements - Vertical Terminations with Co-linear Flex System for bothResidential & Manufactured Homes into Masonry Fireplaces

The shaded area in the diagram shows the allowable vertical terminations. Note: Must remove 4 screws from stove collar and rotate 180o to have collar facing straight back. Secure into place with 4 screws.

VERTICAL TERMINATION WITH CO-LINEAR FLEX SYSTEM

This appliance is designed to be attached totwo3"(76mm)co-linearaluminiumflexrunningthefulllengthofthechimney.SeetheVentingArrangements chart below for minimum andmaximum flue lengths. See chart below forminimumdistancesfromroof.Periodicallycheckthattheventisunrestricted.

Masonry chimneys may take various contours which the flexible liner will accommodate.However,keep the flexible liner as straight as possible,avoidunnecessarybending.

TheAirIntakepipemustbeattachedtotheinletaircollaroftheterminationcap.

Straight Vertical Terminations

Required Parts:Part # Description946-529 Co-linearDVVertical TerminationCap948-305 3"Flex-35ft.946-563 Co-AxialtoCo-LinearAdapterKit whichcontainsthefollowing: Co-linearFlexAdapter OuterPipe InnerPipeAdapter

Vent Restrictors set at fully open, Posiiton "A"

THE APPLIANCE MUST NOT BE CONNECTED TO A CHIMNEY FLUE

SERVING A SEPARATE SOLID FUELBURNING APPLIANCE.

Alternate Approved Caps46DVA-VC VerticalTerminationCap46DVA-VCH HighWindCap46DVA-GK 3''Co-linearAdapterwith flashing

H27E-11GasStove |7

H27E-11 Gas Stove

AdapterTrim Collar

4" ID Liner

SpacerSpring

ThimbleCover Termination Cap

(Part# 946-523/P)

AstroCap

Wall Thimble(required for

combustible walls)

Adjustable PipeLength 13-1/2" - 24",

2 pieces

4 ft. Pipe Lengthwith Kit # 946-216or 2 ft. Pipe Length withKit # 946-116

TrimCollar

DV STOVE HORIZONTAL VENT KIT

DV2ft.StoveVentKit(Part#946-116)andDV4ft.StoveVentKit(946-216)includesallthepartsneededtoinstalltheH27DirectVentunitwithminimumhorizontalandverticalventdimensions.Forinstallationsthatrequirelongerverticaland/orhorizontalventsusetheDura-Ventsystemasshowninthe"Dura-VentTerminationKit"and"Dura-VentVentingComponents"sections.

Qty. Description1) 1 RigidPipeSection(Kit#946-116:2ft.(1.2m)length, Kit#946-216:4ft.(1.2m)length,6-1/2"(165mm) insidediameter2) 1 FlexLiner,compressedaluminium2plyliner,4"(102mm) insidediameter3) 4 springspacers4) 1 90deg.Elbow5) 1 Adjustablepipesection13-1/2"to24"(343mmx610mm),2pcs.6) 1 ThimbleCover7) 1 WallThimble(2pcs.)8) 1 Adapter9) 1 AstroCapTerminationCap10)2 TrimCollars11)1 TubeofMill-Pac,hightemperaturesealant12)12 Screws,#8x1/2"Selftapping,StainlessSteel13)14 Screws,#8x1/2"Selftapping,Black14)4 Screws#8x1-1/2"DrillPoint,Black15)4 Screws#8x1-1/2"DrillPoint,StainlessSteel16)8 Woodscrews#8x1"

Note: a) Liner sections should be

continuous without any joints or seams.

b) This is an approved system, therefore components in this system must not be substituted for any other manufacturer's products.

8| H27E-11GasStove

H27E-11 Gas Stove

Pipe Length (max. 18")Part (6-5/8" Dia)

(4" Dia.)

DecorativeWall Trim

HorizontalTerminalPart# 640-530/P

Wall Thimble(required for

combustible walls)

Vinyl SidingStandoff (Optional)Part #946-205

Adapter(required)

RESIDENTIAL AND MANUFACTURED HOMES / MOBILE HOMES Minimum Horizontal Termination InstallationsPlanning Your Venting Installation

You will require the following components with your new Hampton® RearVent DirectVentFreestandingGasStove.Pleasereviewyourproducttomakesureyouhaveeverythingyouneed. In theevent that youaremissinganypart, contact yourdealer.Decorativebrassorchrometrimkitsareavailable fromSimpsonDura-Vent for theirwall thimbles,aswellasasquarewallthimblecover.

Note: These are the minimum pieces required. Other parts may be required for your particular installation.

See the "Exterior Vent Terminal Locations" section for requirements. Thegasstove isapprovedforaminimumhorizontalterminationwiththeFPIRiserVentKit.Seethediagramforminimumandmaximumpipelengths.

When planning your installation, it will benecessarytoselecttheproper lengthofventpipeforyourparticularrequirements.Determinetheminimumclearancetocombustiblesfromtherearoftheunittothewall.Itisalsoimportanttonotethewallthickness.BeforecuttingtheventholethroughthewallensurethatALLventandterminationclearances(seethe"ExteriorVentTerminallocations"section)willbemet.

*Ifthisisanoutsidecorner,theminimumdistancebetweentheventandtheoutsidecorneris6"(15cm).See"F"onthediagraminthe"ExteriorVentTerminalLocations"section.

NOTE:Ensurecompliancewith theoutsideventterminal location before cutting hole as bothdimensionsmustbemet.

Minimum components for a Horizontal Installation:

946-544 HorizontalTerminationKitwhichincludes: 1 6-5/8"Dia.x18"BlackPipe 1 4"Dia.x18"AluminumVent 1 WallPenetrationHeatShield(WallThimble)(2pcs) 1 640-530/P RiserVentTerminal 1 DecorativeWallTrim(Black) 1 948-128 TubeMill-Pac Screws

Optional Components:946-204 45oElbow-6-5/8"Blackpipe and4"AluminumVent946-205 VinylSidingShieldforRiserVent Terminal946-208/P VentGuard

FPI Riser Vent#640-530/P

Max. 15-1/2"(394mm)

Min. 2" (51mm)If outside corner see note * above.

*

**Min.6-1/2"

(165mm)

Max. 23-1/2"(597mm)

Min. 3"(76mm)

FPIRiserVent#640-530/P

Riser Vent Termination

Max 24" (610 mm)

H27E-11GasStove |9

H27E-11 Gas Stove

Pipe Length

Round SupportBox/Wall Thimble

VerticalTerminal

Storm Collar

Flashing(0-12/6-12)

CeilingFirestop

Pipe Length(included in 46DVA-KHA)

Dura-Vent Horizontal

Termination Installation

Dura-Vent Vertical

Termination Installation

*Adj.Pipe Length(included in #46DVA-KHA)

*90 Elbow(included in 46DVA-KHA)

o

*Round SupportBox/Wall Thimble(included in 46DVA-KHA)

*HorizontalTermination Cap(included in 46DVA-KHA)

Wall Thimble(B) Part # 46DVA-WT

Vinyl SidingStandoff (Optional)

Part #46DVA-VSS

CathedralCeiling

Support Box

(D)

Vertical Termination Kit

Part # 46DVA-KVA (A)

*Horizontal Termination Kit

Part # 46DVA-KHA

Basic Horizontal Kit

1 90oElbow1 WallThimbleCover1 Horiz.Sq.Term.Cap

DURA-VENT TERMINATION KIT

Planning Your Dura-Vent Installation

TherearetwobasictypesofDura-VentDirectVentSysteminstallations:horizontalterminationandverticaltermination.Confirmthemaximumhorizontalrunandmaximumverticalrisefromthediagramsinthe"VentingArrangement"section.

When planning your installation, it will benecessary toselect theproper lengthofventpipe for your particular requirements. Forhorizontalinstallations,determinetheminimumclearancefromtherearoftheunittothewall.It isalso important tonotethewall thickness.(Thewallthimbleissuitablefor2x4or2x6wallconstruction.)Selecttheamountofvertical

rise desired for "vertical-to-horizontal" typeinstallations.

Warning: Always maintain required clearances (air spaces) to nearby combustibles to prevent a fire hazard. Do not fill air spaces with insulation.

Theminimumclearancerequirementsbetweenthe outer wall of the vent pipe and nearbycombustible surfaces is 1-1/2", except whenpassing through a wall, ceiling, or at thetermination where the use of a firestop orwall thimble reduces the required clearanceto 1". Be sure to check the vent termination

clearancerequirementsfromdecks,windows,soffits, gas regulators, air supply inlets andpublicwalkwaysasspecified in the "ExteriorVentTerminalLocations"sectionand inyourlocalbuildingcodes.

Todeterminethelengthofventpiperequiredforverticalinstallations,measurethedistancefromtheunitflueoutlettotheceiling,theceilingthickness,theverticalriseinanatticorsecondstorey,andallow for sufficient verticalheightabovetheroofline.

For multi-storey applications, fire stops arerequired at each floor level. If an offset isneeded,additionalpipe,elbowsandsupportswillberequired.

Donotexceedthemaximumnumberofelbows.One90oforhorizontalterminationsandtwo45oforverticaltermination.

AstroCapPart#946-523/P

Alternate Horizontal Termination Caps

Alternate Horizontal Riser Vent Terminal Part# 640-530/P

TheFPIAstroCapTMiscertifiedforinstallationsusingFPIventingsystemsaswellasSimpsonDura-Vent®andDirectVentPro.TheFPIAstroCapTMistheproprietarytrademarkofFPIFireplaceProductsInternationalLtd.Dura-Vent®andDirectVentProareregisteredand/orproprietarytrademarksofSimpsonDura-VentCo.Inc.