h7012a humidity and h7012b humidity and … · h7012a humidity and h7012b humidity and temperature...

4
® U.S. Registered Trademark Copyright © 2014 Honeywell Inc. All Rights Reserved EN0B-0698GE51 R1214 H7012A Humidity and H7012B Humidity and Temperature Room Sensors PRODUCT DATA GENERAL The H7012A Room Humidity Sensor is a capacitance-type relative humidity sensor for wall mounting. The H7012B Combined Room Humidity/Temperature Sensor incorporates a capacitance-type relative humidity sensor with a Pt 1000, NTC 20k, or 0…10 V temperature sensor in one housing for the measurement of room temperature and relative humidity. These sensors are used for control, indication, and alarm monitoring in air conditioning installations. MODELS OS-No. temperature sensor type sensing ranges H7012A1010 - 5...95%rh H7012B1008 Pt 1000 5...95%rh and 0...50 °C H7012B1024 NTC 20k H7012B1030 0....10 VDC output H7012BALCO500KIT BALCO 500 exchange kit for H7012A1010 0...50 C FEATURES Pt 1000, NTC 20k, or 0…10 V temperature sensing element Wide sensing range Capacitance-type sensing element for relative humidity Two-piece plug-in design. The wiring sub-base allows installation and wiring independent of the front element, which includes the electronics and plugs-into the wiring sub-base. The H7012BALCO500KIT (ordered separately) allows you to expand the H7012A1010 wall module with a BALCO 500 Ohm temperature sensor. The H7012BALCO500KIT contains five (5) BALCO 500 sensor elements plus adhesive strips.

Upload: nguyenkhue

Post on 29-Jul-2018

247 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: H7012A Humidity and H7012B Humidity and … · H7012A Humidity and H7012B Humidity and Temperature Room Sensors ... The H7012A Room Humidity Sensor is a capacitance-type relative

® U.S. Registered Trademark Copyright © 2014 Honeywell Inc. All Rights Reserved EN0B-0698GE51 R1214

H7012A Humidity and H7012B Humidity and Temperature Room Sensors

PRODUCT DATA

GENERAL The H7012A Room Humidity Sensor is a capacitance-type relative humidity sensor for wall mounting.

The H7012B Combined Room Humidity/Temperature Sensor incorporates a capacitance-type relative humidity sensor with a Pt 1000, NTC 20k, or 0…10 V temperature sensor in one housing for the measurement of room temperature and relative humidity.

These sensors are used for control, indication, and alarm monitoring in air conditioning installations.

MODELS OS-No.

temperature sensor type

sensing ranges

H7012A1010 - 5...95%rh

H7012B1008 Pt 1000 5...95%rh

and 0...50 °C

H7012B1024 NTC 20k

H7012B1030 0....10 VDC output

H7012BALCO500KIT BALCO 500

exchange kit for H7012A1010

0...50 C

FEATURES Pt 1000, NTC 20k, or 0…10 V temperature sensing

element

Wide sensing range

Capacitance-type sensing element for relative humidity

Two-piece plug-in design. The wiring sub-base allows installation and wiring independent of the front element, which includes the electronics and plugs-into the wiring sub-base.

The H7012BALCO500KIT (ordered separately) allows you to expand the H7012A1010 wall module with a BALCO 500 Ohm temperature sensor. The H7012BALCO500KIT contains five (5) BALCO 500 sensor elements plus adhesive strips.

Page 2: H7012A Humidity and H7012B Humidity and … · H7012A Humidity and H7012B Humidity and Temperature Room Sensors ... The H7012A Room Humidity Sensor is a capacitance-type relative

H7012A,B - PRODUCT DATA

EN0B-0698GE51 R1214 2

SPECIFICATION Power supply 24 Vac, +20...-30%; 50/60Hz, 34 Vdc, +20...-30%

Current consumption 20 mA at 24 V

Ambient limits

Operating temperature 0...50 C (32...122 F)

Transport and -25...+70 C (-13...+158 F) storage temperature

Humidity 5...95%rh, non-condensing

Dustiness not suitable for dusty environments

Safety

Protection class II in acc. with EN60730-1

Protection standard IP30 in acc. with EN60529

Housing material Flame retardant V0 as per UL94

Housing Dimensions 130 x 80 x 34 mm (H x W x D) (5.12 x 3.15 x 1.34”) Weight 130 g Mounting Wall, surface, or European outlet box

Temperature Sensor

Nominal value – Pt 1000 1000 at 0 C – BALCO 500 500 at 23.3 C – NTC 20k 20k at 25 C

Accuracy – Pt 1000 T/K = (0.3 + 0.005 t) [t in C] as per DIN IEC 751 Class B – BALCO 500 0.4 K at 23.3 C – NTC 20k 0.2 K at 25 C

Sensitivity – Pt 1000 3.85 / K – BALCO 500 2 / K – NTC 20k non-linear characteristic

Characteristic Response time at air velocity 0.02...0.07m/s – 0.5 Pt 1000 50 s – 0.5 Balco 500 140 s – 0.5 NTC 134 s

0…10 V active sensor ≈ 0…50 °C

Relative Humidity Sensor

Output signal 0...10 Vdc ≈ 0...100%rh

Output impedance 10 V range 274

Outputs short-circuit protected

Sensitivity 100 mV / %rh

Accuracy at 25 C / 24 Vac 5...10%rh 10% 10...30%rh 5% 30...70%rh 3% 70...90%rh 5% 90...95%rh 10%

Response time 0.5 = 20 s

Page 3: H7012A Humidity and H7012B Humidity and … · H7012A Humidity and H7012B Humidity and Temperature Room Sensors ... The H7012A Room Humidity Sensor is a capacitance-type relative

H7012A,B - PRODUCT DATA

3 EN0B-0698GE51 R1214

DIMENSIONS 80 (3.15”)

130

(5

.12

”)

34 (1.34”)

20(0.79”)

10

7 (4

-7/3

2”)60

(2-

3/8”

)

30 (

1-3/

16”)

12(7/16”)

60 (2-23/64”)

1

1

1

2

2

2

FIVE MOUNTING HOLESWITH A DIAMETER OF4 mm (0.16”) FOR THREE(TWO) 3.5-mm (0.14”)SCREWS MOUNTEDIN POSITIONS 1(PREFERRED) OR 2.

Fig. 1. Dimensions (in mm and inches) and drilling template

Page 4: H7012A Humidity and H7012B Humidity and … · H7012A Humidity and H7012B Humidity and Temperature Room Sensors ... The H7012A Room Humidity Sensor is a capacitance-type relative

H7012A,B - PRODUCT DATA

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: Automation and Control Solutions Honeywell GmbH Böblinger Strasse 17 71101 Schönaich, Germany Phone +49 (0) 7031 637 01 Fax +49 (0) 7031 637 740 http://ecc.emea.honeywell.com EN0B-0698GE51 R1214 Subject to change without notice

INSTALLATION

230 VAC 230 VAC24 VAC

1 5 / 6 rh INPUT0...10 V

COMMONCOMMON

SENSOR CONTROLLER

TRANSFORMER FORCONTROLLER

TRANSFORMER FORSENSOR

2 7

24 VAC

! !

Fig. 2. Installation example

Mounting and Installation Advice – Mount these units at the inside wall of the room to be

heated or air conditioned, away from doors, windows and heat sources.

– It should be located approx. 1.5 m above the floor and at minimum 50 cm away from the next wall.

– Do not mount in niches, book shelves, behind cabinets or curtains or where it could be exposed to solar radiation.

– Seal the conduit opening to avoid false temperature measurement due to draught from the conduit.

– Provide sufficient air circulation.

Wiring wiring run max. length

sensor to controller 200 m (660 ft)

Offset due to wire resistance per 10 m distance from sensor to controller:

type of wire

temperature offset

Pt 1000 BALCO 500 NTC

0.5 mm2 (AWG20)

0.18 K (0.324 F)

0.3 K (0.54 F)

negligible 1.0 mm2 (AWG17)

0.09 K (0.162 F)

0.15 K (0.27 F)

1.5 mm2 (AWG15)

0.06 K (0.108 F)

0.1 K (0.1 F)

NOTE: Use shielded wiring in areas with high EMI. Keep 15 cm (5.9’’) minimum distance between sensor lines and 230Vac power lines. Use two transformers: one for sensors and actuators and one for the controller (see example).

Wiring Connection H7012A,B CONTROLLER

CO

MR

H I

NP

UT

TE

MP.

IN

PU

T

24

VA

C nc

nc

nc

RH

0..

.10V

CO

M

H7012A1010: RH SENSOR 0...10 VH7012B1008: RH SENSOR 0...10 V, TEMP. SENSOR PT1000H7012B1024: RH SENSOR 0...10 V, TEMP. SENSOR NTC20kH7012B1030: RH SENSOR 0...10 V, TEMP. SENSOR 0...10 V

LIN

E V

OLT

AG

E

LIN

E V

OLT

AG

E

OPTIONAL

24 V

AC

TE

MP.

0...

10 V

TE

MP.

- P

T1

000

or

NT

C20

k

1 2 3 4 5 6 7 8 9 10

!!

Fig. 3. Wiring connection