hager enclosures - cat hk02 enclosures
TRANSCRIPT
Consumer Unit
1
Product Range Summary
2
enclosed distribution board
p.2 consumer unit
p.3 consumer unit & consumer unit split bar
p.4 enclosures
p.5 invicta 63 - MCB distribution boards
p.6 - 7 invicta 63 - TP & N distribution boards
p.8 - 9 U series - invicta 125 panel board system
p.10-12 U series - invicta 250 panel board system
p.13 enclosed fuse combination switches &
switch disconnectors
p.14 enclosed fuse combination switches 32-630A
p.15 switch disconnectors
p.16 IP65 switch disconnectors TP &N 20-125A
consumer unit
2
The metal clad range of consumer units are availablewith a fixed and split load 100Afully tinned busbar. The unitsfeature either a transparent ormetal cover, protecting the
devices, and can be supplied aseither a surface or flush mounted option. The 2 poleincomer options can be either aswitch disconnector, RCCB orMCB. The outgoing devices are
either MCB’s or single / doublemodules RCBO’s. Blank insertsare available to cover unusedways. All consumer units havestandard size knockouts and aredelivered with earth bar, neutral
bar, busbar shroud and label kit.The units have been fully ASTAtested and comply withBSEN60439-3 (AnnexZA).
Neutral terminal
• fully tinned
Outgoing devices
• mcb’s
• 1 module rcbo’s
• 2 modules rcbo’s
Fixed busbar
• fully tinned
Knock outs
• for standard size conduits
Earth terminal• fully tinned
• extra ways to accept
bonding conductor
Domed holes
• for ease of installation
Cover• transparent or metal
consumer unit
3
consumer unit split bar
switch disconnector Total ways pack cat (isolator) rating qty. ref.
63/100A incoming 4 ways 1 HE04SN
6 ways 1 HE06SN
8 ways 1 HE08SN
10 ways 1 HE10SN
12 ways 1 HE12SN
14 ways 1 HE14SN
16 ways 1 HE16SN
18 ways 1 HE18SN
• other models available on request
switch disconnector Total ways pack cat (isolator) rating qty. ref.
63/100A incoming 4+2 ways 1 HE42SN
& 40/63/80A incoming DP RCD 5+2 ways 1 HE52SN
6+2 ways 1 HE62SN
5+3 ways 1 HE53SN
6+3 ways 1 HE63SN
7+3 ways 1 HE73SN
8+4 ways 1 HE84SN
• other models available on request
descriptionThis range of consumer units arespecially designed for the HongKong Market. They are easy toinstall and offer the option of aswitch disconnector or RCCBincoming device or a switch dis-connector and an RCCB in thesplit bar version. They are robustand versatile and can incorpo-rate both MCB & RCBO. Unitincludes both neutral and earth.
standards: BSEN 60439-3(BS 5486 pt 13)
surface mountingenclosures w/doors
SP+N: 1 row 4 -18 ways
Split bar: 1 row (4+2 – 8+4 ways)
Enclosure and door manufactured from steel.1.2 mm thick.
delivered with earth and neutral bars
HE06SN
HE53SN
enclosures
4
designation pack cat qty. ref.
1 row / 1 way 1 VT01E
1 row / 2 ways 1 VT02E
1 row / 4 ways 1 VTO4E
1 row / 6 ways 1 VT06E
1 row / 8 ways 1 VT08E
1 row /10 ways 1 VT10E
1 row /12 ways 1 VT12E
2 row /14 ways 1 VT14E
2 row /16 ways 1 VT16E
• other models available on request
surface mountingenclosures without doorcomplete with din rail1 row 4-16 ways
Enclosure manufactured from1.2mm steel.
delivered with earth and neutral bars
VT06E
5
invicta 63 - MCB distribution boards
description:
The invicta 63 metal clad rangeof three phase and neutral distribution boards are availablewith a fixed load or split loadpan assembly. They all have afully flush fitted metal door witha "slam" type catch. All boardsare delivered with both Neutraland Earth bars fitted and the
neutral is designed to wraparound the incoming device toensure that extra wiring space isavailable for the outgoingdevices. The incoming devicemust be selected and fitted bythe installer. The top and bottomgland plates are removable andalso include knock-outs to suitstandard size conduits. The pan
assembly is fully shrouded andthe busbars are one piece indesign, this ensures that no "hotspots" can occur as there are nomechanical joints. The boardshave been designed and independently ASTA tested toBSEN 60439-1 & 3.
Removable gland plates (top / bottom)
Outgoing circuits• Fit with SP + TP MCB’s• and 1 module RCBO’s
Incoming links
Incoming devices• Switch disconnectors• MCCB’s• RCCB’s
Safety shroud
Robust powder coated sheetsteel enclosure
Totally enclosed, busbar system rated at 200A• colour coded circuit designation
6
invicta 63 TP&N distribution boards -200A incoming, 63A outgoing
designation number of pack cat.
TP ways qty. ref.
6 1 JD06P
12 1 JD12P
18 1 JD18P
24 1 JD24P
4 1 JK04PC
6 1 JK06PC
8 1 JK08PC
10 1 JK10PC
12 1 JK12PC
16 1 JK16PC
4 1 JK04FC
6 1 JK06FC
8 1 JK08FC
10 1 JK10FC
12 1 JK12FC
16 1 JK16FC
4 1 JK04GC
6 1 JK06GC
8 1 JK08GC
10 1 JK10GC
12 1 JK12GC
16 1 JK16GC
TP & N for DP (incoming 200Adirect terminal)
TP & N (incoming 200A directterminal)
TP & N (space for 63/100A TPAI Switch)
TP & N (space for 200A TP AISwitch)
JK04FC
invicta 63 TP&N distribution boards -200A incoming, 63A outgoing
7
designation number of cat.
TP ways ref.
2 + 2 ways JK22PC
4 + 2 ways JK42PC
6 + 2 ways JK62PC
8 + 2 ways JK82PC
10 + 2 ways JK92PC
4 + 4 ways JK44PC
6 + 4 ways JK64PC
8 + 4 ways JK84PC
10 + 4 ways JK94PC
12 + 4 ways JK24PC
6 + 6 ways JK66PC
8 + 6 ways JK86PC
10 + 6 ways JK96PC
2 + 2 ways JS22PC
4 + 2 ways JS42PC
6 + 2 ways JS62PC
8 + 2 ways JS82PC
10 + 2 ways JS92PC
4 + 4 ways JS44PC
6 + 4 ways JS64PC
8 + 4 ways JS84PC
10 + 4 ways JS94PC
12 + 4 ways JS14PC
6 + 6 ways JS66PC
8 + 6 ways JS86PC
10 + 6 ways JS96PC
TP & N split Bar (space for 63/100ATP AI switch & 40/63A 4P RCD)
TP & N split bar (space for 200A TPAI switch & 40/63A 4P RCD)
JK42PC
8
U series - invicta 125 panel board system -400 A incoming, 125 A outgoing
The metal clad range of Invicta125 three phase and neutralMCCB distribution boards withincoming arrangements. They allhave a fully flush fitted half metaldoor, which ensures the incomeris accessible at all times, with aquick release door catch. Theboards are delivered with bothNeutral and Earth bars fitted and
ample wiring space is providedaround both the outgoing andincoming devices to make con-nection easy. All busbars, neu-trals & earth bars are fullytinned. The incoming & outgoing devices must beselected and fitted by theinstaller. The top and bottomgland plates are removable to
help when connecting to trunking systems. The panassembly is fully shrouded andthe busbars are one piece indesign, this ensures that no "hotspots" can occur as there are nomechanical joints. The boardsare ASTA certified have beendesigned and independentlytested BSEN 60439-1 & 3.
All MCCB’s comply withBSEN60947-2 and non-automatic MCCB’s withBSEN60947-3.
Removable gland plates• top• bottom
Numbered individualtinned earth bars
Tinned neutral bar
Shrouding oflive connection
Totally enclosed,busbar systemrated at 250A
Robust powdercoated sheetsteel enclosure
Half door
Quick release catch
Colour coded circuit designation
SP & TP outgoing MCCBs
Choice of incoming kits• 250A Switch Disconnector• 250 A or 400A MCCB
9
U series - invicta 125 panel board system -400 A incoming, 125 A outgoing
no. of pack cat.
TP Ways qty. ref.
direct connection terminals (included incoming kits)
4 X 125A outgoing ways 1 JN 04UB
6 X 125A outgoing ways 1 JN 06UB
8 X 125A outgoing ways 1 JN 08UB
10 X 125A outgoing ways 1 JN 10UB
12 X 125A outgoing ways 1 JN 12UB
16 X 125A outgoing ways 1 JN 16UB
with links and shroud to accept a 250A main switch (included incoming kits)
4 X 125A outgoing ways 1 JN 04US
6 X 125A outgoing ways 1 JN 06US
8 X 125A outgoing ways 1 JN 08US
10 X 125A outgoing ways 1 JN 10US
12 X 125A outgoing ways 1 JN 12US
16 X 125A outgoing ways 1 JN 16US
with Links and Shroud to accept a 250A MCCB (included incoming kits)
4 X 125A outgoing ways 1 JN 04UC
6 X 125A outgoing ways 1 JN 06UC
8 X 125A outgoing ways 1 JN 08UC
10 X 125A outgoing ways 1 JN 10UC
12 X 125A outgoing ways 1 JN 12UC
16 X 125A outgoing ways 1 JN 16UC
with Links and Shroud to accept a 400A MCCB (included incoming kits)
4 X 125A outgoing ways 1 JN 04UM
6 X 125A outgoing ways 1 JN 06UM
8 X 125A outgoing ways 1 JN 08UM
10 X 125A outgoing ways 1 JN 10UM
12 X 125A outgoing ways 1 JN 12UM
16 X 125A outgoing ways 1 JN 16UM
extension Box for Invicta 125
extension box for cable 1 JN 01UB
extension box for din rail 1 JN 01UD
description:Three Phase and Neutral Type BMCCB Distribution Boards areavailable in 4, 6, 8, 10, 12 &16triple pole outgoing ways.Incomers can be selected fromMCCB, non-automatic MCCB orswitch disconnector. All boardsare delivered with tinned Neutral& Earth Bars, relevant link kitsand protective shrouds. Exten-sion boxes are available forinstalling current transformers,etc. These boxes can also beused for obtaining extra cable
space. Delivered with circuitidentification label & wallet.
electrical Specification:Tested and complies to the relevant parts of BSEN 60439-1 & 3:Electrical Supply: 415V ~ Maximum Continuous Rating:400AThe rating of the board is inaccord with the incoming device.Short time withstand:40kA for 1s.
devices Incoming:400A MCCB(h400frame)250A MCCB (h250frame) 250A Non Auto MCCB250A Switch Disconnector Direct Connection
Outgoing:SP MCCB’s (h125)TP MCCB’s (h125)
• for the information of dimensionsee page 21
JN04UB
JN04US
JN04UM
10
U series - invicta 250 panel board system -800A incoming, 125A/ 250A outgoing
description:The metal clad range of Invicta250 three phase and neutralMCCB distribution boards areavailable with a choice of 3P and4P incoming arrangements.They have a fully flush fitted halfmetal door, which ensures theincomer is accessible at alltimes, and quick release doorcatch. The boards are delivered
with both Neutral and Earth barsfitted and ample wiring space isprovided around both the outgoing and incoming devicesto make connection easy. Theincoming & outgoing devicesmust be selected and fitted bythe installer. The top and bottomgland plates are removable tohelp when connecting to trunking systems. The pan
assembly is fully shrouded andthe busbars are one piece indesign, this ensures that no “hotspots” can occur as there are nomechanical joints. Extensionboxes are available and shouldbe used wherever extra cablespace is needed. The boardshave been designed and independently tested to BSEN 60439-1.
Removable gland plates• top• bottom
Individual tinned earthbars for ease of cabling
Totally enclosed,tinned busbar systemrated at 800A
Robust powdercoated sheet steel
Colour coded circuitdesignation
Outgoing MCCBs
Tinned neutral bar
Choice of incoming kits• 400 A MCCB (h630 frame)• 630 A MCCB• 800 A MCCB
Quick releasedoor lock
Shrouding oflive connection
11
U series - invicta 250 panel board system max 800A incoming, 125/250A outgoing
no of pack cat.
TP Ways qty. ref.
direct connection terminals (included incoming kits)
6 X 125A outgoing Ways 1 JF 06UB
8 X 125A outgoing Ways 1 JF 08UB
10 X 125A outgoing Ways 1 JF 10UB
12 X 125A outgoing Ways 1 JF 12UB
16 X 125A outgoing Ways 1 JF 16UB
2 X 250A + 2 X 125A outgoing Ways 1 JF 24UB
2 X 250A + 4 X 125A outgoing Ways 1 JF 26UB
2 X 250A + 6 X 125A outgoing Ways 1 JF 28UB
2 X 250A + 8 X 125A outgoing Ways 1 JF 20UB
2 X 250A +10 X 125A outgoing Ways 1 JF 22UB
4 X 250A outgoing Ways 1 JF 41UB
4 X 250A + 2 X 125A outgoing Ways 1 JF 46UB
4 X 250A + 4 X 125A outgoing Ways 1 JF 48UB
4 X 250A + 6 X 125A outgoing Ways 1 JF 40UB
4 X 250A + 8 X 125A outgoing Ways 1 JF 42UB
6 X 250 outgoing Ways 1 JF 61UB
* delivered with protective shroud
no of pack cat.
TP Ways qty. ref.
with position for a 400A MCCB (included incoming kits)
6 X 125A outgoing Ways 1 JF 06UF
8 X 125A outgoing Ways 1 JF 08UF
10 X 125A outgoing Ways 1 JF 10UF
12 X 125A outgoing Ways 1 JF 12UF
16 X 125A outgoing Ways 1 JF 16UF
2 X 250A + 2 X 125A outgoing Ways 1 JF 24UF
2 X 250A + 4 X 125A outgoing Ways 1 JF 26UF
2 X 250A + 6 X 125A outgoing Ways 1 JF 28UF
2 X 250A + 8 X 125A outgoing Ways 1 JF 20UF
2 X 250A +10 X 125A outgoing Ways 1 JF 22UF
4 X 250A outgoing Ways 1 JF 41UF
4 X 250A + 2 X 125A outgoing Ways 1 JF 46UF
4 X 250A + 4 X 125A outgoing Ways 1 JF 48UF
4 X 250A + 6 X 125A outgoing Ways 1 JF 40UF
4 X 250A + 8 X 125A outgoing Ways 1 JF 42UF
6 X 250 outgoing Ways 1 JF 61UF
* delivered with protective shroud
description:
Three Phase and Neutral Type BMCCB Distribution Boards are available in 4, 6, 8, 10, 12 & 16triple pole outgoing ways.Incomers can be selected fromMCCB, non-automatic MCCB orswitch disconnector. All boardsare delivered with both fullytinned Neutral & Earth Bars, rele-vant link kits and protectiveshrouds. Extension boxes areavailable for installing currenttransformers, etc. These boxes
can also be used for obtainingextra cable space. The correct incoming connection kitmust be selected to suit theincoming device.
electrical Specification:Tested and complies to the relevant parts of BSEN 60439-1:Electrical Supply: 415V ~Maximum Continuous Rating:800A. The rating of the board isin accord with the incomingdevice.
Short time Withstand:40kA for 1s.
mechanical specification:Protection Category IP 31Material 1.5mm CR4 SteelPowder Coated RAL 9001
devicesIncoming:400A MCCB cable lug (h630 frame) 630A MCCB (cable lug) (h630frame) 630A Non Auto MCCB
(cable lug) (h630 frame) 800A MCCB (cable lug or flatbar) (h800 frame) 800A Non Auto MCCB (cable lug or flat bar) (h800 frame)
Outgoing:SP MCCB’s (h125, h250 frame)TP MCCB’s (h125, h250 frame)Extension boxes Incomer connection kit
• for the information of dimensionsee page 21
JF06UB
12
U series - invicta 250 panel board system -max 800A incoming, 125/250A outgoing
JF06UM
extension box for cable 1 JF 01UB∆ extension box for din rail 1 JF 01UD
∆ Can be used with modular devices as meter pack
incoming Kits for Invicta 250 includes mounting kit, links and shroudincoming kit for 800A 3 pole MCCB 1 JF 80UC
# incoming kit order seperately
no of pack cat.
TP Ways qty. ref.with position for a 3 pole 630A (incoming# (800A MCCB kits order separately)
6 X 125A outgoing Ways 1 JF 06UM
8 X 125A outgoing Ways 1 JF 08UM
10 X 125A outgoing Ways 1 JF 10UM
12 X 125A outgoing Ways 1 JF 12UM
16 X 125A outgoing Ways 1 JF 16UM
2 X 250A + 2 X 125A outgoing Ways 1 JF 24UM
2 X 250A + 4 X 125A outgoing Ways 1 JF 26UM
2 X 250A + 6 X 125A outgoing Ways 1 JF 28UM
2 X 250A + 8 X 125A outgoing Ways 1 JF 20UM
2 X 250A + 10 X 125A outgoing Ways 1 JF 22UM
4 X 250A outgoing Ways 1 JF 41UM
4 X 250A + 2 X 125A outgoing Ways 1 JF 46UM
4 X 250A + 4 X 125A outgoing Ways 1 JF 48UM
4 X 250A + 6 X 125A outgoing Ways 1 JF 40UM
4 X 250A + 8 X 125A outgoing Ways 1 JF 42UM
6 X 250 outgoing Ways 1 JF 61UM
• delivered with protective shroud
13
enclosed fuse combination switchesand switch disconnectors
The range of enclosed FuseCombination Switches (FCS)and Switch Disconnectors (LBS)have been designed for easyinstallation. The robust enclosureis made from 1.2mm CR steeland the switching device offersthe latest technology to ensuresafe long lasting and
maintenance free operation. The switches have 4 breakpoints to ensure that a high ACrating can be obtained. The FCShas contacts either side of thefuses which ensures that thefuse connections are totally isolated when the product isswitched off. Operation of the
product is through a rotary handle that ensures that theenclosures cannot be openedwhen the device is in theswitched on position. The 3 poledevices are delivered completewith Neutral Bar & earth pointand the 4 pole with earth pointonly. The products have been
independently tested and fullycomply with the requirements ofBSEN60947-3
Knock outsand removablegland plate
Positive action door handle. Lockable off
Neutral bar
Can be top orbottom fed
Key hole mounting slots
Accepts BS88 fuses
Plastic shrouding
Robust 1.2mm steelenclosure
14
enclosed fuse combinationswitches 32-630A
designation In pack 2 pole 3 pole 4 pole
A qty. cat. ref. cat. ref cat. ref.
32A 1 JG 02FC - -
63A 1 JG 04FC - -
100A 1 JG 06FC - -
32A 1 - JG 09FC -
63A 1 - JG 11FC -
100A 1 - JG 17FC -
160A 1 - JG 23FC -
200A 1 - JG 26FC -
315A 1 - JG 30FC -
400A 1 - JG 32FC -
630A 1 - JG 36FC -
32A 1 - - JG 10FC
63A 1 - - JG 12FC
100A 1 - - JG 18FC
160A 1 - - JG 24FC
200A 1 - - JG 27FC
315A 1 - - JG 31FC
400A 1 - - JG 33FC
630A 1 - - JG 37FC
200A 1 - JG 37EF JG 38EF
315A 1 - JG 39EF JG 40EF
400A 1 - JG 41EF JG 42EF
630A 1 - JG 43EF JG 44EF
descriptionThe range of enclosed FCShave been designed to matchthe TP & N range of distribution boards. The numberof enclosure sizes have beenoptimized, to ensure that theinstallation is easy and uniform.The FCS products are designedto protect & isolate individual circuits. All handles can be padlocked in the off position.
Extension boxes are available forextra cabling space. Operation isthrough a door operated rotaryhandle.
electrical specification: Tested and complies to BSEN60947-3: LBS Sequence 1 & 3FCS Sequence 1 & 4Electrical Supply: 415V ~ AC Rating AC23A (630AAC22A)
mechanical specification:Protection Category IP 41Material 1.5mm CR4 SteelPowder Coated RAL 9001
devices & accessoriesSPSN 32 - 100A (3 ratings)TP & N 32 - 630A (8 ratings)TP & sw N 32 - 630A (8 ratings)
• for the information of dimensionsee page 22-23
JG11FC
enclosed FCS single pole switched neutral
triple pole & neutral
triple pole switched neutral
cable extension boxes
switch disconnector
15
designation In pack 3 pole 4 pole
A qty. cat. ref. cat. ref
20A 1 JG 07SC -
32A 1 JG 09SC -
63A 1 JG 11SC -
100A 1 JG 17SC -
160A 1 JG 23SC -
200A 1 JG 26SC -
250A 1 JG 28SC -
315A 1 JG 30SC -
400A 1 JG 32SC -
630A 1 JG 36SC -
20A 1 - JG08SC
32A 1 - JG10SC
63A 1 - JG12SC
100A 1 - JG18SC
160A 1 - JG24SC
200A 1 - JG27SC
250A 1 - JG29SC
315A 1 - JG31SC
400A 1 - JG33SC
630A 1 - JG37SC
250A 1 JG 37ES JG 38ES
315A 1 JG 39ES JG 40ES
400A 1 JG 41ES JG 42ES
630A 1 JG 43ES JG 44ES
triple pole & switch neutral
enclosed LBStriple pole & neutral
descriptionThe range of enclosed LBS havebeen designed to match the TP& N range of distribution boards.The number of enclosure sizeshave been optimized, to ensurethat the installation is easy anduniform. Products are designedto isolate individual circuits. Allhandles can be padlocked in theoff position. Extension boxes areavailable for extra cabling space.Operation is through a dooroperated rotary handle.
electrical specification:Tested and complies to the relevant parts of BSEN 60947-3:LBS Sequence 1 & 3Electrical Supply: 415V ~ AC Rating AC23A (630A AC22A)
mechanical specification:Protection Category IP 41Material 1.5mm CR4 SteelPowder Coated RAL 9001
devices & accessoriesTP & N 20-630A (10 ratings)TP & sw N 20-630A (10 ratings)
• for the information of dimensionsee page 22-23
JG17SC
cable extension boxes
16
IP65 switch disconnectors TP&N 20-125A
designation In cat.
A ref.
single pole & switched neutral 20A JG 220S
32A JG 232S
40A JG 240S
63A JG 263S
80A JG 280S
125A JG 225S
triple pole & neutral 20A JG 320S
32A JG 332S
40A JG 340S
63A JG 363S
80A JG 380S
125A JG 325S
descriptionThe range of IP65 switch dis-connectors are designed to beused in outdoor applications.They are rated at AC22A andoffer options of 2 pole with earthterminal or 3 pole with neutral &earth terminal. They are com-pact and easy to install. Theproduct can be locked in the offposition.
electrical specification:Tested and complies to BSEN60947-3: Electrical Supply: 240/ 415V ~ AC Rating AC22A
Mechanical Specification:Protection Category IP 65Material ABS
devices & accessories1P + N 20 - 125A (6 ratings)3P + N 20 - 125A (6 ratings)
• for the information of dimensionsee page 24
JG232S
technical information
p.18 consumer units, split bar and enclosures
p.19-20 invicta 63 - TP & N distribution boards
p.21 invicta 125, max 250A incoming, 125A outgoing
- invicta 250, max 800A incoming, 250A outgoing
p.22 enclosed fuse combination switch
- cable extension boxes ( tpn / tpsn )
p.23 enclosed load break switch
- technical information fuse combination units
p.24 IP 65 enclosed switch disconnector
18
consumer unit
consumer unit split bar
dimensions
cat. ref. H W D
HE04SN 230 210 75
HE06SN 230 246 75
HE08SN 230 282 75
HE10SN 230 322 75
HE12SN 230 354 75
HE14SN 230 394 75
HE16SN 230 426 75
HE18SN 230 466 75
• All dimensions are in mm
dimensions
cat. ref. H W D
HE42SN 230 300 75
HE52SN 230 318 75
HE62SN 230 336 75
HE53SN 230 336 75
HE63SN 230 354 75
HE73SN 230 372 75
HE84SN 230 408 75
• All dimensions are in mm
enclosures
dimensions
cat. ref. H W D
VT01E 205 142 65
VT02E 205 178 65
VT04E 205 250 65
VT06E 205 322 65
VT08E 205 394 65
VT10E 205 466 65
VT12E 205 538 65
VT14E 485 361 85
VT16E 485 397 85
• All dimensions are in mm
dimensions
cat. ref. A B C D
JD06P 485 385 125 277
JD12P 585 385 125 277
JD18P 705 385 125 277
JD24P 805 385 125 277
• All dimensions are in mm
19
invicta 63 - TP & N distribution boards
dimensions
cat. ref. no of ways A B C D
JK04PC 4 way 495 385 115 277
JK06PC 6 way 555 385 115 277
JK08PC 8 way 605 385 115 277
JK10PC 10 way 660 385 115 277
JK12PC 12 way 715 385 115 277
JK14PC 14 way 770 385 115 277
JK16PC 16 way 820 385 115 277
JK18PC 18 way 875 385 115 277
JK04FC 4 way 495 385 115 277
JK06FC 6 way 555 385 115 277
JK08FC 8 way 605 385 115 277
JK10FC 10 way 660 385 115 277
JK12FC 12 way 715 385 115 277
JK14FC 14 way 770 385 115 277
JK16FC 16 way 820 385 115 277
JK18FC 18 way 875 385 115 277
JK04GC 4 way 495 385 115 277
JK06GC 6 way 555 385 115 277
JK08GC 8 way 605 385 115 277
JK10GC 10 way 660 385 115 277
JK12GC 12 way 715 385 115 277
JK14GC 14 way 770 385 115 277
JK16GC 16 way 820 385 115 277
JK18GC 18 way 875 385 115 277
• All dimensions are in mm
20
TP & N Split bar
cat. ref. no of ways A B C D
JK22PC 2 + 2 way 595 385 125 277
JK42PC 4 + 2 way 650 385 125 277
JK62PC 6 + 2 way 705 385 125 277
JK82PC 8 + 2 way 760 385 125 277
JK92PC 10 + 2 way 815 385 125 277
JK44PC 4 + 4 way 705 385 125 277
JK64PC 6 + 4 way 760 385 125 277
JK84PC 8 + 4 way 815 385 125 277
JK94PC 10 + 4 way 870 385 125 277
JK24PC 12 + 4 way 925 385 125 277
JK66PC 6 + 6 way 815 385 125 277
JK86PC 8 + 6 way 870 385 125 277
JK96PC 10 + 6 way 925 385 125 277
JS22PC 2 + 2 way 595 385 125 277
JS42PC 4 + 2 way 650 385 125 277
JS62PC 6 + 2 way 705 385 125 277
JS82PC 8 + 2 way 760 385 125 277
JS92PC 10 + 2 way 815 385 125 277
JS44PC 4 + 4 way 705 385 125 277
JS64PC 6 + 4 way 760 385 125 277
JS84PC 8 + 4 way 815 385 125 277
JS94PC 10 + 4 way 870 385 125 277
JS24PC 12 + 4 way 925 385 125 277
JS66PC 6 + 6 way 815 385 125 277
JS86PC 8 + 6 way 870 385 125 277
JS96PC 10 + 6 way 925 385 125 277
• All dimensions are in mm
invicta 63 - TP & N distribution boards
dimensions
cat. ref. A B C
surface mounted
JN04UB /US /UM /UC 862 666 135
JN06UB /US /UM /UC 937 666 135
JN08UB /US /UM /UC 1017 666 135
JN10UB /US /UM /UC 1097 666 135
JN12UB /US /UM /UC 1172 666 135
JN16UB /US /UM /UC 1327 666 135
• All dimensions are in mm
21
invicta 125, max 400A incoming,125A outgoing
dimensions
cat. ref. A B C
surface mounted
JF06UB /UF /UM 1127 846 165
JF08UB /UF /UM 1207 846 165
JF10UB /UF /UM 1277 846 165
JF12UB /UF /UM 1357 846 165
JF16UB /UF /UM 1507 846 165
JF24UB /UF /UM 1077 846 165
JF28UB /UF /UM 1227 846 165
JF20UB /UF /UM 1307 846 165
JF22UB /UF /UM 1382 846 165
JF41UB /UF /UM 1107 846 165
JF46UB /UF /UM 1177 846 165
JF42UB /UF /UM 1407 846 165
JF61UB /UF /UM 1207 846 165
• All dimensions are in mm
invicta 250, max 800A incoming,250A outgoing
cat. ref. description height width depth
JG37EF/ JG38EF 200A 228 380 206
JG39EF/ JG40EF 315A 253 450 256
JG41EF/ JG42EF 400A 253 450 256
JG43EF/ JG44EF 630A 353 600 356
JG37ES/ JG38ES 200A 203 300 206
JG39ES/ JG40ES 315A 303 400 256
JG41ES/ JG42ES 400A 303 400 256
JG43ES/ JG44ES 630A 303 450 256
cable extension boxes (tpn/tpsn)
cat. ref. description height width depth
JG02FC 32A SPSN 353 300 135
JG04FC 63A SPSN 353 300 135
JG06FC 100A SPSN 353 300 135
JG09FC 32A TPN 353 300 135
JG10FC 32A TPSN 353 300 135
JG11FC 63A TPN 353 300 135
JG12FC 63A TPSN 353 300 135
JG17FC 100A TPN 353 300 135
JG18FC 100A TPSN 353 300 135
JG23FC 160A TPN 453 380 206
JG24FC 160A TPSN 453 380 206
JG26FC 200A TPN 453 380 206
JG30FC 315A TPN 503 450 256
JG31FC 315A TPSN 503 450 256
JG32FC 400A TPN 503 450 256
JG33FC 400A TPSN 503 450 256
JG36FC 630A TPN 703 600 356
JG37FC 630A TPSN 703 600 356
All dimensions are in mm and exclude the handle.Add 70mm to the depth to allow for the handle.
22
enclosed fuse combination switch
fused combination switch
cat. ref. description height width depth
JG07SC 20A TPN 203 150 104
JG08SC 20A TPSN 203 150 104
JG09SC 32A TPN 203 150 104
JG10SC 32A TPSN 203 150 104
JG11SC 63A TPN 203 150 104
JG12SC 63A TPSN 203 150 104
JG17SC 100A TPN 303 250 135
JG18SC 100A TPSN 303 250 135
JG23SC 160A TPN 303 250 135
JG24SC 160A TPSN 303 250 135
JG26SC 200A TPN 403 300 206
JG27SC 200A TPSN 403 300 206
JG28SC 250A TPN 403 300 206
JG29SC 250A TPSN 403 300 206
JG30SC 315A TPN 603 400 256
JG31SC 315A TPSN 603 400 256
JG32SC 400A TPN 603 400 256
JG33SC 400A TPSN 603 400 256
JG36SC 630A TPN 603 450 256
JG37SC 630A TPSN 603 450 256
• All dimensions are in mm
thermal current Ith (40oC) 32A 63A 100A 125A 60A 200A 315A 400A 630Afuse size: BS A1 A2-A3 A4 A4 B2 B2 B3 B4 C1-C2rated insulated voltage Ui (V) 690 750 750 750 750 750 1000 1000 1000impulse voltages Uimp 8000 8000 8000 8000 8000 8000 8000 8000 1200operational current Ie (A) A B A B A B A B A B A B A B A B A B400V ac AC-23A/AC-23B 32 32 63 63 100 100 125 125 160 160 200 200 315 315 400 400 630 630Motor power (kW)400V ac 9 30 51 63 80 100 160 160 220 220 355 355reactive power 400V ac (kVAR) 15 25 45 55 60 75 125 150 2x125overload capacityshort-circuit with fuses (kA Rms) 50 50 50 50 50 50 50 50 50fuse rating (A) 32 63 100 125 160 200 315 400 630BS88making & breaking characteristicsbreaking capacity 320 500 800 1000 1280 1600 2520 3200 5040400V AC-23B (A Rms)making capacity 256 630 1000 1250 1600 2000 3150 4000 6300400V AC-23B (A Rms)withstandmechanical 20000 10000 10000 10000 10000 10000 10000 10000 5000(number of operationselectrical 1500 1500 1500 1000 1000 1000 500 500 1000(number of operations)operating force (mN) 2.5 7 10 10 10 10 12 15 42connectionminimum Cu cable section (mm2) 2.5 10 25 35 50 70 185 185 2x150maximum Cu cable section (mm2) 16 25 95 95 95 95 240 240 2x300
23
technical information fusecombination units
enclosed load break switch
24
IP 65 enclosed switch disconnector
1 pole + switched neutral
ref. current H W D
JG220S 20 A 136 100 101
JG232S 32 A 136 100 101
JG240S 40 A 136 100 101
JG263S 63 A 136 100 105
JG280S 80 A 201 136 118
JG225S 125 A 201 136 118
3 pole + fixed neutral
JG320S 20 A 136 100 101
JG332S 32 A 136 100 101
JG340S 40 A 136 100 101
JG363S 63 A 136 100 105
JG380S 80 A 201 136 118
JG325S 125 A 201 136 118
• All dimensions are in mm