handbook on earthing system for power supply installations.pdf

Upload: pavan

Post on 13-Feb-2018

225 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    1/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    1

    Hkkjr ljdkj GOVERNMENT OF INDIAjsy ea=ky;s as ajsy ea=ky; MINISTRY OF RAILWAYS

    egkjktiqjegkjktiqjegkjktiqjegkjktiqj,Xokfy;j &Xokfy;j &Xokfy;j &Xokfy;j & 474 005474 005474 005474 005

    Maharajpur, GWALIOR - 474 005

    dSeVsd@bZ@10&11@vfFkZax&ih,lvkbZ@1-0CAMTECH/E/10-11/EARTHING-PSI/1.0

    uoEcj 2010November 2010

    dsoy dk;Zky;hu mi;ksx gsrq(For Official Use Only)

    IkkWoj lIykbZ laLFkkiukvksadh vfFkZax .kkyhIkkWoj lIykbZ laLFkkiukvksadh vfFkZax .kkyhIkkWoj lIykbZ laLFkkiukvksadh vfFkZax .kkyhIkkWoj lIykbZ laLFkkiukvksadh vfFkZax .kkyhij gLriqfLrdkij gLriqfLrdkij gLriqfLrdkij gLriqfLrdkHandbook on

    Earthing System For Power Supply Installations

    Yk{; lewg% VhvkjMh vuqj{k.k deZpkjhYk{; lewg% VhvkjMh vuqj{k.k deZpkjhYk{; lewg% VhvkjMh vuqj{k.k deZpkjhYk{; lewg% VhvkjMh vuqj{k.k deZpkjhTARGET GROUP: TRD Maintenance Staff

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    2/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    2

    IkkWoj lIykbZ laLFkkiukvksadh vfFkZax .kkyhIkkWoj lIykbZ laLFkkiukvksa dh vfFkZax .kkyhIkkWoj lIykbZ laLFkkiukvksadh vfFkZax .kkyhIkkWoj lIykbZ laLFkkiukvksa dh vfFkZax .kkyh

    ij gLriqfLrdkij gLriqfLrdkij gLriqfLrdkij gLriqfLrdk

    Handbook on Earthing System

    For

    Power Supply Installations

    xq.koRrk uhfrxq.koRrk uhfrxq.koRrk uhfrxq.koRrk uhfrjsyksaesa;k=h vkSj eky ;krk;kr dh c

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    3/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    3

    kDdFkukDdFkukDdFkukDdFku

    VhvkjMh ds lcLVsku ,oa fLofpax LVsku ikWojlIykbZ laLFkkiukvksa dh vfFkZax]]]] midj.kksadslqpk# :Iklsdk;Z djus,oadeZpkfj;ksa,oamidj.kksa dh lqj{kk dsfy;s cgqr egRoiw.kZ gSA ;g QkYV djasV dks fuEubEihMsUl iFk nku djrk gS vkSj xzkmaM QkYV gksus ij

    lqj{kk ;a=ksadk Rofjr ,oalqfufpr ifjpkyu lqfufprdjrk gSA

    dSeVsd us **IkkWoj lIykbZ laLFkkiukvksa dh vfFkZax.kkyh** ij ;g gLriqfLrdk cukbZ gS ftlesa vfFkaZx dh

    lajpuk] d"kZ.k lcLVsku dh vfFkZax O;oLFkk] vuqj{k.k

    'kSM~;wy] vuqj{k.k eqDr vfFkZax] ,DlksFkfeZd oSfYMax] D;kdjsa vkSj D;k u djsavkfn dk fooj.k fn;k x;k gSA

    eq>svkkk gS fd ;g gLriqfLrdk VhvkjMh foHkkx esadk;Z djus okys gekjs vuqj{k.k deZpkfj;ksa ds fy,

    mi;ksxh fl) gksxh A

    dSeVsd] Xokfy;jdSeVsd] Xokfy;jdSeVsd] Xokfy;jdSeVsd] Xokfy;j ,l,l,l,l----lhlhlhlh----fla?kyfla?kyfla?kyfla?kyfnukad 24] fnlEcj] 2010fnukad 24] fnlEcj] 2010fnukad 24] fnlEcj] 2010fnukad 24] fnlEcj] 2010 dk;Zdkjh funskddk;Zdkjh funskddk;Zdkjh funskddk;Zdkjh funskd

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    4/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    4

    FOREWORD

    Earthing for substation and switching station (power

    supply installation) of TRD plays very important role in

    smooth functioning of equipment, safety of personnel and

    equipment. It provides low impedance path to fault currents

    and ensures prompt and consistent operation of protective

    devices during ground faults.

    CAMTECH has prepared this handbook on earthing

    system for power supply installation containing construction

    of earthing, earthing arrangement at traction substation,

    maintenance schedules, maintenance free earthing,

    exothermic welding and dos & dont.

    I hope this handbook will prove to be useful for themaintenance personnel working in TRD department.

    CAMTECH, Gwalior S.C. Singhal

    Date:24.12.2010 Executive Director

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    5/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    5

    HkwfedkHkwfedkHkwfedkHkwfedk

    lcLVskuksa ,oa fLofpax LVskuksa esa Ik;kZIr vfFkZax dk ko/kkuifjpkyu deZpkjh;ksa,oamidj.kksadh lqj{kk dsfy;svko;d gSA;g .kkyh ifjpkyu dk dk;Z djusdsfy;sHkh vko;d gSA vfFkZaxds}kjk fo|qr midj.kksadksi`Foh dslkekU; Hkkx lstksM+k tkrk gSftldk frjks/k dkQh de gksrk gSA

    dSeVsd }kjk **IkkWoj lIykbZ laLFkkiukvksa dh vfFkZax .kkyh**ij ;g gLriqfLrdk gekjs vuqj{k.k deZpkjh;ksa dks vuqj{k.k QzhvfFkZax ,oa,DlksFkfeZd cSfYMax ds fo"k; esavoxr djkusdsmn~ns;

    lscukbZ xbZ gSA

    ;g Li"V fd;k tkrk gS fd ;g gLriqfLrdk vkjMh,lvks]jsyos cksMZ ;k ,lh VsDku esuqvy }kjk fofuZfn"V fdlh Hkh fo/kkudks foLFkkfir ughadjrhA ;g gLriqfLrdk dsoy ekxZnkZu gsrq gS,oa ;g ,d oS/kkfud nLrkost+ughagSA

    eSa] dk;Z{ks= dsmu lHkh deZpkfj;ksadk vkHkkjh gw ftUgksusblgLriqfLrdk dkscukusesagekjh lgk;rk dh A

    rduhdh mUu;urk vkSj lh[kuk ,d lrr~ izf;k gSA vr%bl gLriqfLrdk esatksM+us@ lq/kkjusdsfy;sgesafy[kusesaLora=eglwl djsaA bl fnkk esa ge vkids;ksxnku dh ljkguk djsaxsA

    dSeVsd] Xokfy;jdSeVsd] Xokfy;jdSeVsd] Xokfy;jdSeVsd] Xokfy;j ih;w"k xqIrkih;w"k xqIrkih;w"k xqIrkih;w"k xqIrkfnukad 30] uoEcj] 2010fnukad 30] uoEcj] 2010fnukad 30] uoEcj] 2010fnukad 30] uoEcj] 2010 la la la la---- funskd fo|qrfunskd fo|qrfunskd fo|qrfunskd fo|qr

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    6/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    6

    PREFACE

    Provision of adequate earthing in substations and

    switching stations is essential for the safety of operating

    personnel as well as of equipment. It is also necessary for

    functioning of the system operation. By means of earthing,

    electrical equipment are connected to the general mass of the

    earth, which has a very low resistance.

    This handbook on earthing system for power supply

    installation has been prepared by CAMTECH with the

    objective of making our maintenance personnel aware of

    maintenance free earthing and exothermic welding.

    It is clarified that this handbook does not supersede any

    existing provisions laid down by RDSO, Railway Board or AC

    traction manual. This handbook is for guidance only and it isnot a statutory document.

    I am sincerely thankful to all field personnel who helped

    us in preparing this handbook.

    Technological up-gradation & learning is a continuous

    process. Please feel free to write to us for any addition/

    modification in this handbook. We shall highly appreciate your

    contribution in this direction.

    CAMTECH, Gwalior ( Peeyoosh Gupta)

    Date: 30 thNovember 2010 Jt. Director Electrical

    e - mail id : [email protected]

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    7/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    7

    fo"k; lwphfo"k; lwphfo"k; lwphfo"k; lwph

    ---- lalalala---- fooj.kfooj.kfooj.kfooj.k i`"B lai`"B lai`"B lai`"B la----kDdFku iiiHkwfedk vfo"k; lwph vii

    lakks/ku ifpZ;ksadk izdkku xi1-0 Lrkouk 01

    1-1 lcLVsku dh vfFkZax dsmn~ns; 01

    1-2 vfFkZax .kkyh 021-3 ifjHkkf"kd 'kCnkoyh 021-4 xzkfUMax rFkk vfFkZax esa vUrj 061-5 mPpre vuqKs; vFkZ frjks/k 071-6 vfFkZax dh lkekU; vko;drk;sa 071-7 feV~Vh dh frjks/kdrk fu/kkZfjr

    djusokys dkjd 092-0 lcLVsku ij vfFkZax O;oLFkk 15

    2-1 vFkZ bYkSDVksM 152-2 vfFkZax eSV fMt+kbu dksHkkfor

    djusokys dkjd 17

    2-3 fMt+k;u f;k 172-4 vfFkZax eSV 182-5 xM+h gqbZ jsy 202-6 flLVe vfFkZax 212-7 midj.k vfFkZax 222-8 vfFkZax pkyd dk lkbZt 292-9 fLofpax LVskuksaij vfFkZax O;oLFkk 29

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    8/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    8

    CONTENTS

    Sr.No. Description Page No.

    Foreword ivPreface viContents viiiCorrection Slip xii

    1.0 INTRODUCTION 01

    1.1 PURPOSE OF SUBSTATION EARTHING 01

    1.2 EARTHING SYSTEM 02

    1.3 TERMINOLOGY 02

    1.4 DISTINCTION BETWEEN GROUNDING AND

    EARTHING 06

    1.5 MAXIMUM PERMISSIBLE EARTH RESISTANCE 07

    1.6 GENERAL REQUIREMENT FOR EARTHING 07

    1.7 FACTORS WHICH DETERMINE RESISTIVITYOF SOIL 09

    2.0 EARTHING ARRANGEMENTS AT SUBSTATION 15

    2.1 EARTH ELECTRODES 15

    2.2 PARAMETERS AFFECTING THE DESIGN OFEARTHING MAT 17

    2.3 DESIGN PROCEDURE 172.4 EARTHINGMAT 18

    2.5 BURRIED RAIL 20

    2.6 SYSTEM EARTHING 21

    2.7 EQUIPMENT EARTHING 22

    2.8 SIZE OF EARTHING CONDUCTOR 29

    2.9 EARTHING ARRANGEMENT AT SWITCHING 29STATION

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    9/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    9

    ---- lalalala---- fooj.kfooj.kfooj.kfooj.k i`"B lai`"B lai`"B lai`"B la----

    3-0 ijEijkxr vFkZ bysDVksM dk vuqj{k.k 32

    3-1 =Sekfld vuqj{k.k 323-2 v)Z okf"kZd vuqj{k.k 333-3 okf"kZd vuqj{k.k 343-4 vFkZ bySDVksM dsfrjks/k dk ekiu 343-5 gLr pkfyr vFkZ VsLVj dk fooj.k 36

    4-0 vuqj{k.k eqDr vfFkZax 38

    4-1 vFkZ frjks/k 384-2 mi;ksx 394-3 vuqj{k.k eqDr vfFkZax .kkyh 39

    5-0 ckWfUMax] xzkmfUMax@ vfFkZax dsfy, 49,DlksFkfeZd oSfYMax la;kstu5-1 lkekU; vko;drk;sa 505-2 osfYaMx lkexzh 515-3 osfYaMx VwYl dh fofk"Vrk;sa 525-4 osfYaMx vkSt+kj 54

    6-0 D;k djsavkSj D;k u djsa 576-1 D;k djsa 576-2 D;k u djsa 58ifjfk"V&1 59

    ,SDlksFkfeZd osfYaMx f;k dsNk;kfp=ifjfk"V&2 62jsy esa fNnz djusdh f;k dsNk;kfp=ifjfk"V&3 63jsy esa fMfyax djusdh ekhu dh fofk"Vrk;salalalalanHkZnHkZnHkZnHkZ 68686868

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    10/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    10

    Sr. No. Description Page No.

    3.0 MAINTENANCE SCHEDULE OF

    CONVENTIONAL EARTH ELECTRODE 323.1 QUARETLY SCHEDULE 323.2 HALF YEARLY SCHEDULE 33

    3.3 YEARLY SCHEDULE 34

    3.4 MEASUREMENT OF EARTH ELECTRODERESISTANCE 34

    3.5 DETAILS OF EARTH TESTER(HAND DRIVEN) 36

    4.0 MAINTENANCE FREE EARTHING 384.1 EARTH RESISTANCE 38

    4.2 APPLICATION 39

    4.3 MAINTENANCE FREE EARTHING SYSTEM 39

    5.0 EXOTHERMIC WELDING CONNECTION FORBONDING, GROUNDING/ EARTHING 49

    5.1 GENERAL REQUIREMENTS 50

    5.2 WELDING MATERIAL 51

    5.3 SPECIFICATION OF WELDING TOOLS 52

    5.4 WELDING TOOLS 54

    6.0 DOS & DONTS 57

    6.1 DO S 57

    6.2 DONT 58

    ANNEXURE-1

    Photographs of Exothermic Welding Procedure 59ANNEXURE-2

    Photographs of Process of Hole Drilling in Rail 62

    ANNEXURE-3 63

    Specification of Rail Drilling Machine

    REFERENCES 68

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    11/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    11

    lakks/ku ifpZ;ksadk izdkkulakks/ku ifpZ;ksadk izdkkulakks/ku ifpZ;ksadk izdkkulakks/ku ifpZ;ksadk izdkku

    bl gLriqfLrdk ds fy;s Hkfo"; esa izdkfkr gksus okyh lakks/kuifpZ;ksadks fuEukuqlkj la[;kafdr fd;k tk;sxkA

    dSeVsd@bZ@10dSeVsd@bZ@10dSeVsd@bZ@10dSeVsd@bZ@10-11111111@@@@vfFkZaxvfFkZaxvfFkZaxvfFkZax-ih,lvkbZih,lvkbZih,lvkbZih,lvkbZ@1@1@1@1----0000@@@@lh,llh,llh,llh,l # XXfnukadfnukadfnukadfnukad-------

    tgkWaXXlEcfU/kr lakks/ku iphZ dh dze la[;k gS 01 ls izkjEHkgksdj vkxsdh vksj

    izdkfkr lakks/ku ifpZ;kizdkfkr lakks/ku ifpZ;kizdkfkr lakks/ku ifpZ;kizdkfkr lakks/ku ifpZ;k

    dzdzdzdz----lalalala---- izdkku dh rkjh[kizdkku dh rkjh[kizdkku dh rkjh[kizdkku dh rkjh[k lakksf/kr Ik"B la[;k rFkk enlakksf/kr Ik`"B la[;k rFkk enlakksf/kr Ik"B la[;k rFkk enlakksf/kr Ik`"B la[;k rFkk enla[;kla[;kla[;kla[;k

    fVIi.khfVIi.khfVIi.khfVIi.kh

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    12/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    12

    ISSUE OF CORRECTION SLIP

    The correction slips to be issued in future for this

    handbook will be numbered as follows:

    CAMTECH/E/10-11/Earthing-PSI/1.0/ C.S. # XX date---

    Where XX is the serial number of the concerned

    correction slip (starting from 01 onwards).

    CORRECTION SLIPS ISSUED

    Sr. No. Date of

    issue

    Page no. and Item

    no. modified

    Remarks

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    13/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    1

    1.0 LrkoukLrkoukLrkoukLrkouk@@@@INTRODUCTION

    Provision of adequate earthing in substations and

    switching stations is essential for the safety of operating

    personnel as well as of equipment. It is also necessary

    for functioning of the system. By means of earthing

    electrical equipment are connected to the general mass

    of the earth, which has a very low resistance.

    1.1 lcLVsku dh vfFklcLVsku dh vfFklcLVsku dh vfFklcLVsku dh vfFkZax ds mn~ns;Zax ds mn~ns;Zax ds mn~ns;Zax ds mn~ns;@@@@PURPOSE OFSUBSTATION EARTHING

    The object of an earthing system in a substation

    is to provide, under and around the substation a surface

    that shall be at a uniform potential and as near to zero

    or absolute earth potential as possible. The provision of

    such a surface of uniform potential under and around

    the substation ensures human safety from electric shock

    in case of short circuit or development of any abnormalcondition in the equipment installed.

    The primary requirements of a good earthing

    system in a substation are:

    a. It stabilizes circuit potential with respect to groundand limits the overall potential rise.

    b. It protects life and property from over voltage.c. It provides low impedance path to fault currents

    to ensure prompt and consistent operation of

    protective devices during ground faults.

    d. It keeps the maximum voltage gradient along the

    surface inside and around the substation within

    safe limits during ground fault.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    14/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    2

    1.2 vfFkZax .kkyhvfFkZax .kkyhvfFkZax .kkyhvfFkZax .kkyh@@@@EARTHING SYSTEM

    All the non current carrying parts of the

    electrical equipment in the substation are connectedto the earthing mat. Under normal conditions the

    ground rods contribute a little towards lowering the

    ground resistance. It maintains a low value of

    resistance under all weather conditions.

    The mat is connected to the following

    equipment in sub station:a. The neutral point of system through its own

    independent earth.

    b. Equipment frame work and other non current

    carrying parts.

    c. All extraneous metallic frameworks not

    associated with equipment.

    d. Lightning arrestors through their independent

    earths.

    e. Handles of operating pipes.

    f. Fence if it is within 2m from earth mat.

    1.3 ifjHkkf"kd 'kCnkoyh@ifjHkkf"kd 'kCnkoyh@ifjHkkf"kd 'kCnkoyh@ifjHkkf"kd 'kCnkoyh@TERMINOLOGY

    The following terms are commonly used in

    earthing system:

    1.3.1 Hkw@Hkw@Hkw@Hkw@Earth

    The conductive mass of the earth, whose

    electrical potential at any point is conventionally taken

    as zero.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    15/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    3

    1.3.2 vFkZ bYvFkZ bYvFkZ bYvFkZ bYkSDkSDkSDkSDVksMVksMVksMVksM@@@@Earth electrode

    A galvanized iron (GI) pipe or group of pipes in

    intimate contact with and providing an electricalconnection to earth.

    1.3.3 vFkvFkvFkvFkZ fxzM@Z fxzM@Z fxzM@Z fxzM@Earth grid

    A system of grounding electrodes consisting of

    inter-connected connectors buried in the earth to

    provide a common ground for electrical devices and

    metallic structures.

    1.3.4 vFkvFkvFkvFkZZZZeSV@eSV@eSV@eSV@Earth Mat

    A grounding system formed by a grid of

    horizontally buried conductors and which serves to

    dissipate the earth fault current to earth and also as an

    equi-potential bonding conductor system.

    1.3.5 vfFkZax midj.kvfFkZax midj.kvfFkZax midj.kvfFkZax midj.k@@@@Equipment EarthingIt comprises earthing of all metal work of electrical

    equipment other than parts which are normally live or

    current carrying. This is done to ensure effective

    operation of the protective gear in the event of leakage

    through such metal work, the potential of which with

    respect to neighboring objects may attain a value which

    would cause danger to life or risk of fire.1.3.6 flLVeflLVeflLVeflLVe vfFkZaxvfFkZaxvfFkZaxvfFkZax@@@@ System Earthing

    Earthing done to limit the potential of live

    conductors with respect to earth to values which the

    insulation of the system is designed to withstand and

    this to ensure the security of the system.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    16/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    4

    1.3.7 LVsi ,oaVp oksYVrkLVsi ,oaVp oksYVrkLVsi ,oaVp oksYVrkLVsi ,oaVp oksYVrk@@@@Step & Touch Potential

    Step & touch potential refer to the potential

    experienced by a person standing on a surface whenearth mat buried up to 750 mm below, surface has risen

    to ground potential rise (GPR).

    Touch potential is the difference between GPR &

    the surface potential at the point where person is

    standing, while his hand is in contact with grounded

    structure.

    Step potential is the difference in surface potentialexperienced by a person bridging a distance of one

    meter with his feet without contacting any other

    grounded object as shown in figure - 1

    If resistance offered by each foot is R, then for

    step potential the resistance is 2R while for touch

    potential is R/2.

    Figure 1

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    17/82

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    18/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    6

    1.4 xzxzxzxzkkkkfUMax rFkk vfFkZaxfUMax rFkk vfFkZaxfUMax rFkk vfFkZaxfUMax rFkk vfFkZax esaesaesaesa vUrj@vUrj@vUrj@vUrj@DISTINCTIONBETWEEN GROUNDING AND EARTHING

    1.4.1 xzkfUMaxxzkfUMaxxzkfUMaxxzkfUMax@@@@GroundingGrounding implies connection of current

    carrying parts to ground. It is mostly either generator or

    transformer neutral. Hence it is generally called neutral

    grounding. Grounding is for equipment safety.

    There are three requirements for grounding:

    a. Shall provide a low impedance path for the return

    of fault current, so that an over current protection

    device can act quickly to clear the circuit.

    b. Shall maintain a low potential difference between

    exposed metal parts to avoid personnel hazards.

    c. Shall control over voltage.

    1.4.2 vfFkZaxvfFkZaxvfFkZaxvfFkZax@@@@Earthing

    Earthing implies connection of non currentcarrying parts to ground like metallic enclosures.

    Earthing is for human safety.

    Under balanced operating conditions of power

    systems, earthing system does not play any role. But

    under any ground fault condition, it enables the ground

    fault current to return back to the source without

    endangering human safety as shown in figure - 2

    Figure 2

    EARTHING

    GENERATOR TRANSFORMER

    NEUTRAL GROUNDINGNEUTRAL GROUNDING

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    19/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    7

    1.5 mPpremPpremPpremPpre vuqKs; vFkZ frjks/k@vuqKs; vFkZ frjks/k@vuqKs; vFkZ frjks/k@vuqKs; vFkZ frjks/k@MAXIMUMPERMISSIBLE EARTH RESISTANCE

    At each power supply installation the combinedresistance of the earthing system shall not be more than

    the following values:-

    i) Traction Sub Station - 0.5 Ohms

    ii) Switching Station - 2.0 Ohms

    iii) BT and AT station - 10 Ohms

    1.6 vfFkZaxvfFkZaxvfFkZaxvfFkZaxdh lkekU;dh lkekU;dh lkekU;dh lkekU; vko;drk;savko;drk;savko;drk;savko;drk;saGENERAL REQUIREMENTS FOR EARTHING Earthing shall generally be carried out in

    accordance with the requirement of I.E. rules,

    1956, as amended from time to time and the

    relevant regulation of the electricity supply.

    Codes /Standard given below may also be

    referred :

    i) IS:3043-1987 - Code of practice for

    earthing (latest)

    ii) National Electricity Code - 1985 of Bureau

    of Indian Standards

    iii) IEEE guide for safety in a.c. substation

    grounding No. ANSI/IEEE standard 80-

    1986.

    iv) Indian Electricity Rule 1956 (Latestedition)

    In cases where direct earthing may prove harmfulrather than providing safety, relaxation may be

    obtained from the competent authority.

    Earth electrodes shall be provided at substations,switching stations and consumer premises in

    accordance with the requirements.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    20/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    8

    As far as possible all earth connections shall bevisible for inspection.

    All connections shall be carefully made. If theyare not properly made or are inadequate for the

    purpose for which they are intended, loss of life

    or serious personnel injury may result.

    Each earth system shall be so devised that thetesting of individual earth electrode is possible. It

    is recommended that the value of any earth

    system resistance shall not be more than specified

    value.

    The minimum size of earthing lead (discharge rodcable) used on installations shall have a nominal

    cross-section area not less than 40 mm2 multi

    stranded copper to be able to withstand short

    circuit current.

    It is recommended drawing showing the main

    earth connection and earth electrode be preparedfor each installation.

    No addition to the existing load whethertemporary or permanent shall be made, which

    may exceed the assessed earth fault or its duration

    until it is ascertained that the existing

    arrangement of earthing is capable of carrying the

    new value of earth fault current resulting due tosuch addition.

    All materials, fittings etc. used in earthing shallconfirm to Indian Standard specification

    wherever these exist. In the case of material for

    which Indian Standard specifications does not

    exists, the material shall be approved by the

    competent authority.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    21/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    9

    1.7 feVfeVfeVfeV~~~~VhVhVhVh dh frjks/kdrk fu/kkZfjr djus odh frjks/kdrk fu/kkZfjr djus odh frjks/kdrk fu/kkZfjr djus odh frjks/kdrk fu/kkZfjr djus okys dkjdkys dkjdkys dkjdkys dkjd@@@@FACTORS WHICH DETERMINE RESISTIVITY OFSOIL

    The resistivity of soil for earthing system

    depends upon the following factors:

    Type of soil

    Moisture content

    Chemical composition of salt dissolved in thecontained water

    Concentration of salt

    Temperature of material

    Grain size and distribution of grain size

    Size and spacing of earth electrodes

    1.7.1 feVfeVfeVfeV~~~~VhVhVhVh dh frjks/kdrkdh frjks/kdrkdh frjks/kdrkdh frjks/kdrk de djus dhde djus dhde djus dhde djus dh

    fof/k;k@fof/k;k@fof/k;k@fof/k;k@Methods of Reducing Resistivity of SoilfeVfeVfeVfeV~~~~Vh dh frjks/kdrk ds dkj@Vh dh frjks/kdrk ds dkj@Vh dh frjks/kdrk ds dkj@Vh dh frjks/kdrk ds dkj@Types of soilresistivity

    S.No Type of soil Resistivity in

    Ohm-cm

    1 Loamy garden soil 500 - 5000

    2 Clay 800 - 5000

    3 Clay, Sans and Gravel mix 4000 - 25000

    4 Sand and Gravel 6000 - 10000

    5 Slates, Slab sand stone 1000 - 50000

    6 Crystalline Rock 20000 - 100000

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    22/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    10

    1.7.2 feV~Vh mipkj@feV~Vh mipkj@feV~Vh mipkj@feV~Vh mipkj@Soil Treatment

    a. When the soil resistance is high, even the

    multiple electrodes in large number may also failto produce low resistance to earth. To reduce the

    resistivity of soil immediately surrounding the

    electrode some salt substances are made available

    as a solution with water. The substances are used

    salt sodium chloride (NaCl), Calcium chloride

    (CaCl2) Sodium carbonate (Na2CO3), copper

    sulphate (CuSO4) and soft cock and charcoal in

    suitable proportion.

    b. Nearly 90% of resistance between electrode andsoil is with in a radius of two meters from

    electrode/ rod. Treating this soil will result in

    required reduction in earth resistance by

    excavation of one meter diameter around top of

    the electrode/ rod to 30 cm deep and applying

    artificial soil treatment agency and watering

    sufficiently.

    c. General practice to treat the soil surrounding theground electrode with common salt, charcoal and

    soft cock in order to bring down the earth

    resistance. These conventional methods are

    effective in soils of moderately high resistivity upto 300 ohm-meter. When the soil resistivity

    exceeds this value, these conventional methods of

    chemical treatment will be inadequate to get

    desired value of earth resistance.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    23/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    11

    1.7.3 feV~Vh mipkjfeV~Vh mipkjfeV~Vh mipkjfeV~Vh mipkj esaesaesaesa ccccsUVksukbZV dk mi;ksxsUVksukbZV dk mi;ksxsUVksukbZV dk mi;ksxsUVksukbZV dk mi;ksx@@@@Use ofBentonite in Soil Treatment

    Bentonite is clay with excellent electricalproperties. It swells to several times its originalvolume when suspended in water. It binds the water

    of crystallization and the water absorbed during the

    mixing process is retained over a long period.

    Bentonite suspension in water when used to

    surround the earth electrode virtually increases the

    electrode surface area.

    Use of bentonite around the earth electrode resultsin reduction of ground resistance by about 25- 30

    %.

    Bentonite has a tremendous capacity to absorbwater and retain it over along period.

    Even during the summer months, bentonite

    suspension retains the moisture where as the naturalsoil dries up.

    Bentonite may be used to advantage in rockyterrain.

    1.7.4 feV~Vh mipkjfeV~Vh mipkjfeV~Vh mipkjfeV~Vh mipkjesaeghu jk[k dk mi;kesaeghu jk[k dk mi;kesaeghu jk[k dk mi;kesaeghu jk[k dk mi;ksxsxsxsx@@@@Use of fly ashin soil treatment

    As per CPRI studies reveals that fly ash from

    thermal stations has equivalent chemical composition

    and hence can be used for the electrical installations in

    areas of high ground resistivity. Fly ash can also be

    used as a chemical treatment material to reduce soil

    resistivity.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    24/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    12

    1.7.5 vFkZ frjks/kdrk ij vknzrkvFkZ frjks/kdrk ij vknzrkvFkZ frjks/kdrk ij vknzrkvFkZ frjks/kdrk ij vknzrk dk Hkkodk Hkkodk Hkkodk Hkko@@@@Effect ofMoisture Content on Earth Resistivity

    Moisture content is expressed in percentage byweight of dry soil. Dry earth weights about 1440 kg/m

    3.

    Therefore about 144 kg (10%) of water is required per

    cubic meter of soil to have 10% of moisture content.

    About 20% moisture the resistivity is very little

    affected below 20% moisture the resistivity increases

    very abruptly with decrease in moisture. Moisture

    content of about 17% to 18% by weight of dry soil is

    the optimum requirement. Availability of moistureassists formation of electrolyte by dissolving salt

    content in soils and there by enhance the conductivity

    of soil. More water content can not improve soil

    resistivity.

    Resistivity(Ohm-cm)Moisture content(% by

    weight) Top Soil Sandy Loam

    0 1000x106 1000x10

    6

    2.5 250000 150000

    5 165000 43000

    10 53000 18500

    20 12000 6300

    30 6400 4200

    1.7.6 rki dk Hkko@rki dk Hkko@rki dk Hkko@rki dk Hkko@Effect of TemperatureThe temperature coefficient of resistivity for soil

    is negative, but is negligible for temperatures above

    freezing point. At about 200

    C the water in the soil

    begins to freeze and introduce a tremendous increase in

    the temperature coefficient. The resistivity changes 9%

    per degree C. Below 0 degree C resistivity raises

    abnormally.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    25/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    13

    Effect of Temperature on Resistivity

    0C 0F Resistivity(Ohm-cm)20 68 7,200

    10 50 9,900

    0 32(Water) 13,000

    0 32(Ice) 30,000

    -5 23 79,000

    -15 14 330,000

    1.7.7 vFkZ frjks/kdrk dk taxvFkZ frjks/kdrk dk taxvFkZ frjks/kdrk dk taxvFkZ frjks/kdrk dk tax ij Hkko@ij Hkko@ij Hkko@ij Hkko@Effect of SoilResistivity on Corrosion

    Resistivity plays an important role in so far as

    the corrosion performance of earthing rods is

    concerned. It is observed that soils having resistivity of

    less than 25 ohm-meter are severely corrosive in nature

    while corrosion rate is of less importance in soils ofresistivity over 200 ohm- meter. The methods adopted

    to safe guard earthing conductors against corrosion

    depends upon

    a. Material of the conductor

    b. Corrosivity of the soil

    c. Size of the grounding system

    Range of soil resistivity

    (Ohm-metre)

    Class of soil

    Less than 25 Severely corrosive

    25 50 Moderately corrosive

    50 -100 Mildly

    Above 100 Very mildly corrosive

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    26/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    14

    1.7.8 lrg ij iRFkj pwjk dh irZ dsQk;ns@lrg ij iRFkj pwjk dh irZ ds Qk;ns@lrg ij iRFkj pwjk dh irZ dsQk;ns@lrg ij iRFkj pwjk dh irZ ds Qk;ns@Advantagesof Crushed Rock Used as a Surface Layer

    It provides high resistivity surface layer

    It serves as impediment to the movement of reptilesand there by help in minimizing the hazards

    which can be caused by them

    It prevents the formation of pools of oil from oilinsulated and oil cooled electrical equipment

    It discourages the growth of weeds

    It helps retention of moisture on the underlying soiland thus helps in maintaining the resistivity of thesubsoil at lower value.

    It discourages running of persons in the switchyardand saves them from the risk of being subjected

    to possible high step potentials.

    1.7.9 iRFkj pwjk dh eghu irZ dk Hkko@iRFkj pwjk dh eghu irZ dk Hkko@iRFkj pwjk dh eghu irZ dk Hkko@iRFkj pwjk dh eghu irZ dk Hkko@Effect of Thin

    Layer of Crushed RockIn outdoor switchyard, a thin layer of crushed

    rock is spread on the surface.

    The resistivity of gravel () is 2000 ohm-meter

    while that of soil is 100 ohm-meter. Since of gravel is

    high, only a high voltage can force the current through

    the body to cause injuries. The gravel act like insulator

    & throws the electric field generated by GPR back tosoil.

    1.7.10 vFkZ bYkSDVksM yxkusdk LFkkvFkZ bYkSDVksM yxkusdk LFkkvFkZ bYkSDVksM yxkusdk LFkkvFkZ bYkSDVksM yxkusdk LFkku@u@u@u@Location of EarthElectrode

    The location of earth electrode should be chosen

    in one of the following types of soil in the order of

    preference given on next page:

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    27/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    15

    a. Wet marshy ground.

    b. Clay, loamy soil and arable land

    c. Clay and loam mixed with varying proportions of

    sand, gravel and stones.d. Damp and wet sand, peat.

    Dry sand,gravel chalk limestone, granite, verystone ground and all locations where virgin rock is very

    close to the surface should be avoided.

    2.0 lcLVskulcLVskulcLVskulcLVsku ijijijij vfFkZaxvfFkZaxvfFkZaxvfFkZax O;oLFkk@O;oLFkk@O;oLFkk@O;oLFkk@EARTHING

    ARRANGEMENTS AT SUB STATION

    2.1 vFkZ bYvFkZ bYvFkZ bYvFkZ bYkSDkSDkSDkSDVksMVksMVksMVksM@@@@Earth Electrodes

    The earth electrodes are made of mild steel

    galvanized perforated pipe of not less than 40 mm

    nominal bore, of about 4 m length provided with a

    spike at one end and welded lug suitable for taking

    directly MS flat of required size at the other end. The

    pipe is embedded as far as possible vertically into the

    ground, except when hard rock is encountered, where it

    may be buried inclined to the vertical, the inclination

    being limited to 300

    from the vertical. The connection

    of MS flat to each electrode is made through MS links

    by bolted joints to enable isolation of the electrode for

    testing purpose.

    Earth electrodes shall be embedded as apart aspossible from each other. Mutual separation between

    two electrodes shall not be less than 6.0 m i.e. twice the

    length of the electrode as shown in figure- 3

    In high embankments, it may be difficult to

    achieve earth resistance even after chemical treatment

    of electrodes. In these locations, use electrodes longer

    than 4 m so as to reach the parent soil is recommended.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    28/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    16

    As far as possible, earth electrodes for traction

    substation/ switching stations shall be installed within

    and adjacent to perimeter fence.

    75

    150

    3000

    150 150

    75 75

    48.4

    75

    150mmLONG

    75mmX8mm

    M.S.FLATWELDED

    12mmDIAHOLES

    ATSIM

    ILAR

    SPACIN

    GFOR

    ENTIRE

    LENGTH

    200

    200

    500

    50

    50

    GROU

    NDLEVEL

    LAYEROFSAND

    LID

    FOREARTHBOX200

    80X(RCC)

    50mmTHIC

    K200

    EARTHBOX

    (RCC)

    AREATOBEWELL

    RAMMED

    2X75mm

    X8mm

    100mmX

    10mm

    80mmX12mm

    Alternateequal

    Layersofsalt,

    charcoalorcock

    350

    150

    150

    EARTH

    ELECTRODE

    12mmDIA

    HOLES

    Pipetomedriven

    thesoilforbetter

    holding

    50

    175 3

    500

    Figure -3

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    29/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    17

    2.2 vfFvfFvfFvfFkZax eSVkZax eSVkZax eSVkZax eSV fMt+kbufMt+kbufMt+kbufMt+kbu dks Hkkfor djusokys dkjd@dksHkkfor djusokysdkjd@dks Hkkfor djusokys dkjd@dksHkkfor djusokysdkjd@PARAMETERS AFFECTING THE DESIGN OFEARTHING MAT

    Several variable factors are involved in the

    design of earthing mat conductor. Earthing mat for each

    substation has to be designed individually. The earthing

    mat has to be designed as per the site conditions to have

    low overall impedance and a current carrying capacity

    consistent with the fault current magnitude. The

    following parameters influence the design of earthing

    mat:1. Magnitude of fault current

    2. Duration of fault

    3. Soil resistivity

    4. Resistivity of surface material

    5. Shock duration

    6. Material of earthing mat conductor

    7. Earthing mat geometry

    2.3 fMtfMtfMtfMt++++k;u f;k@k;u f;k@k;u f;k@k;u f;k@DESIGN PROCEDUREThe following steps are involved in the design

    of earthing mat:

    i. The layout of the sub station, determine the area tobe covered by the earthing mat.

    ii. Determine the soil resistivity at the sub station site.The resistivity of the earth varies within

    extremely wide limits, between 1 and 10,000

    ohm-meter. The resistivity of the soil at many

    station sites has been found to be non- uniform.

    Variation of the resistivity of the soil with

    depth is more predominant as compared to the

    variation with horizontal distances. To design

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    30/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    18

    the most economical and technically sound

    grounding system for large stations, it is

    necessary to obtain accurate data on the soil

    resistivity and on its variation at the station site.Resistivity measurements at the site will reveal

    whether the soil is homogeneous or non-

    uniform. In case the soil is found uniform,

    conventional methods are applicable for the

    computation of earth resistivity. When the soil

    is found non- uniform, either a gradual

    variation or a two-layer model may be adopted

    for the computation of earth resistivity.

    2.4 vvvvffffFkFkFkFkZaxZaxZaxZaxeSVeSVeSVeSV@@@@EARTHING MATAn earthing mat is formed by means of bare mild

    steel rod of appropriate size buried at a depth of about

    600 mm below the ground level and connected to earth

    electrodes. The connection between the earth electrodes

    and the mat shall be by means of two separate and

    distinct connections made with 75 mm x 8 mm MS flat.

    The connection between the MS flat and the MS rod

    shall be made by welding, while that between the earth

    electrode and the MS flats through MS links by bolted

    joints. The earth electrodes are provided at the outer

    periphery of the mat. As far as possible the earthing

    mat conductors shall not pass through the foundationblock of the equipment.

    All crossings between longitudinal conductors

    and transverse conductors are jointed by welding. The

    longitudinal and transverse conductors of the earthing

    grid shall be suitably spaced so as to keep the step and

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    31/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    19

    touch voltage within the acceptable limit. However the

    overall length of the earthing grid conductors shall not

    be less than the calculated length as shown in figure 4.

    BURIEDGRIDCONDUCTORWITHIN1METREOFFENCE

    MS ROD

    M S FLAT

    EARTH

    TRACTIONSUB.-STN.FENCIG

    ELECTRODE

    CROSSING

    WELDED AT

    75 mm X 8mm MS FLATS

    FROM POWERTRANSFORMER

    SECONDARY WINDINGTERMINAL

    BURIES RAIL

    75 mm X 8mm MS FLATS TO

    NON TRACK CIRCUITED RAILNEUTRAL POINT OF

    IMPEDANCE BOND

    Figure - 4

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    32/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    20

    The size of the earthing grid conductors are decided

    based on the incoming system voltage and fault level.

    The fault level considered is taking into account the

    anticipated increase in fault current during the life spanof the station. The system voltage, fault level and

    conductor size are given below:

    Sr.No

    System

    voltage

    (KV)

    Fault level (MVA) Diameter of

    grid conductor

    (GI rod) in mm

    1 66

    upto 4000

    above 4000 upto 5000above 5000 upto 6000

    32

    3640

    2 110

    upto 6000

    above 6000 upto 8000

    above 8000 upto 10000

    32

    36

    40

    3 132upto 7000

    above 7000 upto 10000

    32

    36

    4 220

    upto 12000

    above 12000 upto 16000

    above 16000 upto 20000

    32

    36

    40

    2.5 xMxMxMxM+h gqbZ+h gqbZ+h gqbZ+h gqbZ jsy@jsy@jsy@jsy@BURIED RAIL

    A steel rail of section 52 kg/m (the one used for

    the railways track) and length about 13 m is buried nearthe track at the traction substation at a depth of about

    one meter to form part of the earthing system. Two

    separate and distinct connections are made by means of

    75 mm x 8 mm MS flat between the earthing mat and

    the buried rail. The buried rail are connected by means

    of two separate and distinct connections made with 75

    mm x 8 mm MS flat to the traction rail(s) in a single-

    rail track circulated section and to the neutral points(s)

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    33/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    21

    of the impedance bond(s) in a double-rail track

    circuited section.

    In case where the feeding post is locatedseparately away from the traction substation, the buried

    rail is provided at the feeding post (where one terminal

    of the secondary winding of the traction transformer of

    the substation is grounded).

    2.6 flLVeflLVeflLVeflLVe vvvvffffFkFkFkFkZaxZaxZaxZax@@@@SYSTEM EARTHING

    One terminal of thesecondary winding (25 kV

    winding) of each traction power

    transformer are earthed directly by

    connecting it to the earthing grid

    by means of one 75 mm x 8 mm

    MS flat , and to the buried rail by

    means of another 75 mm x 8 mm

    GI flat as shown figure in - 5

    One designated terminal of the secondary of

    each potential, current and auxiliary transformer are

    connected to the earthing grid by means of two separate

    and distinct earth connection made with 50 mm x 6 mm

    MS flat as shown in figure in 6,7& 8.

    Figure - 6 Figure - 7 Figure - 8

    Figure- 5

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    34/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    22

    2.7 midj.kmidj.kmidj.kmidj.k vvvvffffFkFkFkFkZax@Zax@Zax@Zax@EQUIPMENT EARTHING

    2.7.1 ikWoj VkUlQkeZj dhikWoj VkUlQkeZj dhikWoj VkUlQkeZj dhikWoj VkUlQkeZj dh vvvvffffFkFkFkFkZax@Zax@Zax@Zax@ Earthing of Power

    Transformer

    The metallic frame work (tank) of each

    power transformer is directly connected to

    the main earthing mat by means of two

    separate distinct connections made with 50

    mm x 6 mm MS flat for the 25 kV side and

    75 mm x 8 mm MS flat for the primary

    side. One connection is made with the

    nearest longitudinal conductor, while theother is made to the nearest transverse

    conductor of the mat.

    In addition there is a direct connection from the

    tank to the earth side of lightning arrestors. The

    transformer tank rails are earthed either separately or by

    bonding at each end of the track as shown in figure- 9.

    2.7.2 lfdZVlfdZVlfdZVlfdZV cszdj rFkk buVIVjcszdj rFkk buVIVjcszdj rFkk buVIVjcszdj rFkk buVIVj dh vfFkZaxdh vfFkZaxdh vfFkZaxdh vfFkZax@@@@ Earthing ofCircuit Breakers and Interrupter

    The supporting structures of each circuit

    breaker unit are connected to the

    earthing mat by means of two separate

    distinct connections made with 50 mm

    x 6 mm MS flat for the 25 kV side and

    75 mm x 8 mm MS flat for the primaryside. One connection is made with the

    nearest longitudinal conductor, while

    the other is made to the nearest

    transverse conductor of the mat.

    Cubicles, doors and cable glands

    are also connected to the earthing mat

    as shown in figure 10 & 11.

    Figure - 9

    Figure -10 & 11.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    35/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    23

    Fi ure -14

    2.7.3 vkblksysVj dhvkblksysVj dhvkblksysVj dhvkblksysVj dh vvvvffffFkFkFkFkZax@Zax@Zax@Zax@Earthing ofIsolators

    A flexible earth conductor is

    provided between the handle andearthing conductor attached to the

    mounting bracket and the handle of

    switches is connected to earthing

    mat by means of two separate

    distinct connections made with 50

    mm x 6 mm MS flat for the 25 kV

    side and 75 mm x 8 mm MS flat for

    the primary side .One connection ismade with the nearest longitudinal

    conductor, while the other is made to the nearest

    transverse conductor of the mat as shown in figure 12

    & 13

    2.7.4 ykbfVaxykbfVaxykbfVaxykbfVax vvvvjsLVj dhjsLVj dhjsLVj dhjsLVj dh vvvvffffFkFkFkFkZaxZaxZaxZax@@@@Earthing of LightningArrestor

    In addition to the earth

    electrodes provided for the main

    earthing mat, an independent earth

    electrode is provided for each

    lightning arrester. This earth

    electrode is connected to the ground

    terminal of the lightning arrester, as

    well as to the main earthing mat bymeans of two separate distinct

    connections made with 50 mm x 6

    mm MS flat for the 25 kV side lightning arresters, and

    with 75 mm x 8 mm MS flat for the primary side

    lighting arresters. The earth electrode is provided as

    close as possible to the lightning arrester and the

    Figure -13

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    36/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    24

    connection shall be as short and straight as possible

    avoiding unnecessary bends.

    For lightning arresters provided for the traction

    power transformers, there is also be a connection as

    direct as possible from the ground terminal of the

    lighting arrester to the frame of the transformer of the

    being protected. This connection is also be made by

    two separate and distinct connections made with 50

    mm x 6 mm MS flat for the 25 kV side lightning

    arresters, and with 75 mm x 8 mm MS flat for the

    primary side lighting arresters as shown in figure- 14

    2.7.5 djsaV ,oadjsaV ,oadjsaV ,oadjsaV ,oa iksVsfUk;y VkUlQiksVsfUk;y VkUlQiksVsfUk;y VkUlQiksVsfUk;y VkUlQWWWWkeZj dhkeZj dhkeZj dhkeZj dhvvvvffffFkFkFkFkZax@Zax@Zax@Zax@Earthing of Current Transformer andPotential Transformer

    The supporting structures of

    Current Transformer and PotentialTransformer unit of bases, all bolted

    cover plates to which the bushings

    are attached connected to the earthing

    mat by means of two separate distinct

    connections made with 50 mm x 6

    mm MS flat for the 25 kV side and

    75 mm x 8 mm MS flat for the

    primary side. One connection is madewith the nearest longitudinal

    conductor, while the other is made to

    the nearest transverse conductor of

    the mat as shown in figure 15 & 16

    Figure -15& 16

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    37/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    25

    2.7.6 daVksy :e dsvUnj dhdaVksy :e ds vUnj dhdaVksy :e dsvUnj dhdaVksy :e ds vUnj dh vvvvffffFkFkFkFkZax@Zax@Zax@Zax@ Earthing insideControl Room

    An earthing ring shall beprovided inside the control

    room by means of 50 mm x 6

    mm MS flat which shall be run

    along the wall on teak wood

    blocks fixed to the wall at a

    height of about 300 mm from

    the floor level as shown in

    figure- 17.

    The earthing ring is

    connected to the main earthing

    grid by means of two separate

    and distinct connections made

    with 50 mm x 6 mm MS flat.

    The earthing ring is also be

    connected to independent earth

    electrode by means of two

    separate and distinct

    connections made with 50 mm

    x 6 mm MS flat as shown in

    figure 18.

    The metallic framework of control and relay

    panels, LT AC and DC distribution boards, battery

    chargers, remote control equipment cabinets and such

    other equipment are connected to the earthing ring by

    means of two separate and distinct connection made

    with 8 SWG galvanized iron wire. The connections are

    being taken along the wall and in the floor. All recesses

    shall be covered with cement plaster after finishing the

    work.

    Figure- 18

    Figure - 17

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    38/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    26

    Connection between the MS flats is made by welding as

    shown in figure 19, 20, 21& 22.

    Figure- 19 Figure - 20

    Figure- 21 Figure- 22

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    39/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    27

    2.7.7 vU; midj.kksadhvU; midj.kksadhvU; midj.kksadhvU; midj.kksadh vvvvffffFkFkFkFkZax@Zax@Zax@Zax@Earthing of otherEquipment

    a. vFkZ Lhu dh vfFkZaxvFkZ Lhu dh vfFkZaxvFkZ Lhu dh vfFkZaxvFkZ Lhu dh vfFkZax@@@@Earthing of Earth Screen

    The area covered

    by outdoor substation are

    shielded against direct

    strokes of lightning by an

    overhead earth screen

    comprising 19/2.5 mm

    galvanized steel standardwire strung across the

    pinnacles of the metallic

    structures. The earth

    screen wires are strung at a height as indicated

    in the approved traction substation layouts (not

    less than 2.5 m above the live conductor) and

    shall be solidly connected to the traction

    substation earthing grid at each termination by

    means of 50 m x 6 mm GI flat as shown in

    figure 23.

    b. QsfUlax LraHkksa vkSj isuyksa dhQsfUlax LraHkksa vkSj isuyksa dhQsfUlax LraHkksa vkSj isuyksa dhQsfUlax LraHkksa vkSj isuyksa dh vvvvffffFkFkFkFkZaxZaxZ a xZax@@@@Earthing of fencing uprights and panels

    Each metallic fencingupright is connected to the

    traction substation main

    earthing grid by means of

    two separate and distinct

    connections made with 50

    mm x 6 mm MS flat. In

    addition, all the metallic

    fencing panels shall be connected to the uprights

    Fi ure- 24

    Figure- 23

    Fi ure- 24

    Figure- 24

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    40/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    28

    by means of two separate and distinct

    connections made with

    6 SWG G I wire. The

    entire metallic doorpanels are also be

    connected to the

    supporting uprights by

    means of two distinct

    connections made with

    6 SWG I wire as shown

    in figure- 24 & 25

    All metallic part

    of structures, masts and

    metallic frames is

    connected to the

    traction substation

    main earthing mat by

    means of two separate

    and distinct connections

    made with 50 mm x 6 mm MS flats shown in

    figure- 26.

    2.7.8 vkW;y fQYVjsku IykaVvkW;y fQYVjsku IykaVvkW;y fQYVjsku IykaVvkW;y fQYVjsku IykaVds fy,ds fy,ds fy,ds fy, 240oksYV ,lh 50oksYV ,lh 50oksYV ,lh 50oksYV ,lh 50gVZt dsikWbaV dhgVZt dsikWbaV dhgVZt dsikWbaV dhgVZt dsikWbaV dh vvvvffffFkFkFkFkZax@Zax@Zax@Zax@Earthing at the pointof 240 V ac 50 Hz supply for oil filtration plant

    The 240 V ac 50 Hz

    distribution board for power

    supply to oil filtration plant is

    connected to the main earthing

    grid by means of two distinct

    connections made with 50 mm

    x 6 mm MS flat as shown in

    figure - 27

    Figure- 26

    Figure- 25

    Figure- 27

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    41/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    29

    2.8 vvvvffffFkFkFkFkZax pkyd dk lkbZax pkyd dk lkbZax pkyd dk lkbZax pkyd dk lkbZt@Zt@Zt@Zt@SIZE OF EARTHINGCONDUCTOR

    Size of earthing conductor depends on systemvoltage and fault level as given below:

    Sr.

    No

    Equipment

    (KV)

    System voltage and

    fault level

    Ground

    conductor size

    1 Equipment

    on the

    primary

    side of

    tractionpower

    transformer

    66 KV, upto 3000 MVA

    110 KV, upto 5000 MVA

    132 KV, upto 6000 MVA

    220 KV, upto 10000 MVA

    66 KV, above 3000 upto

    6000 MVA

    110 KV, above 5000 upto

    10000 MVA

    132 KV, above 6000 upto

    12000 MVA

    220 KV, above 10000

    pto 20000 MVA

    50mm x 6mm

    75mm x 8mm

    2 Equipment on the secondary side of

    traction power transformer

    50mm x 6mm

    3 Fencing uprights/steel structures 50mm x 6mm

    4 Doors/fencing panels 6 SWG G I wire

    2.9 ffffLofpax LVskuksa ijLofpax LVskuksa ijLofpax LVskuksa ijLofpax LVskuksa ij vvvvffffFkFkFkFkZax O;oLFkk@Zax O;oLFkk@Zax O;oLFkk@Zax O;oLFkk@EARTHINGARRANGEMENT AT SWITCHING STATION

    A minimum number of three earth electrodes

    (excluding the one to be provided separately for the

    remote control cubicle earthing) are provided at each

    switching station, and they are interconnected by means

    of 50 mm x 6 mm MS flat forming a closed loop main

    earthing ring. This ring is connected by two separate

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    42/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    30

    and distinct connections made with 50 mm x 6 mm MS

    flat, to the non-track circuited rail in a single rail track

    circuited section and to the neutral point of the

    impedance bond in a double rail track circuited sectionof the nearest track, so as to limit the potential gradient

    developing in the vicinity of the switching station in the

    event of a fault.

    2.9.1 flLVeflLVeflLVeflLVe vvvvffffFkFkFkFkZax@Zax@Zax@Zax@System Earthing

    One designated terminal of the secondary of

    each potential transformer, current transformer andauxiliary transformer are connected to the main

    earthing ring by means of two separate and distinct

    connections made with 50 mm x 6mm MS flat as

    shown in figure -28 &29.

    2.9.2midj.kmidj.kmidj.kmidj.k vvvvffffFkFkFkFkZax@Zax@Zax@Zax@Equipment earthingAll masts,

    structures, fencing

    uprights and all

    outdoor equipment

    pedestals including

    auxiliary transformer

    tank is connected to

    the earthing ring by

    means of two

    separate and distinct

    Figure- 28 Figure- 29

    Figure- 30 Figure- 31

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    43/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    31

    connections made with 50mm x 6mm MS flat. All

    fencing panels are connected to the supporting uprights

    by means of two separate and distinct connections made

    with 6 SWG G.I. wire. All the metallic door panels areconnected to the supporting uprights by means of two

    separate and distinct connections made with 6 SWG

    G.I. wire as shown in figure- 30&31

    The metal casing of potential and current

    transformers are connected to the mast/ structures by

    means of two separate and distinct connections made

    with 50mm x 6mm MS flat as shown in figure 32&33.

    The ground terminal of

    lightning arrester shall be

    connected directly to the earth

    electrodes by means of twoseparate and distinct connections

    made with 50mm x 6mm MS flat.

    The earth electrode shall be so

    placed that the earthing leads from

    the lightning arrester may be

    brought to the earth electrodes by as short and straight a

    path as possible as shown in figure 34.

    Figure- 32 Figure- 33

    Fi ure- 34

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    44/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    32

    3.0 ijEijkxrijEijkxrijEijkxrijEijkxr vFkvFkvFkvFkZ byZ byZ byZ byssssDVksM dk vuqj{k.kDVksM dk vuqj{k.kDVksM dk vuqj{k.kDVksM dk vuqj{k.kMAINTENANCE SCHEDULE FOR CONVENTIONALEARTH ELECTRODE

    3.1 ====SSSSekfld vuqj{k.k@ekfld vuqj{k.k@ekfld vuqj{k.k@ekfld vuqj{k.k@QUARTERLY SCHEDULE

    Sr. Items Inspection Action to be taken

    1 Earth flat

    connections to

    structures,equipment, rail

    and earth

    electrodes with nut

    and check nuts

    Check for

    proper

    continuityand

    tightness

    If found broken or

    loose, it should be

    immediatelyreplaced /tightened

    2 Bolts and nuts of

    the connections

    Check for

    rust and

    dirt

    Rust and dirt should

    be cleaned and apply

    grease

    3 MS links by bolted

    joints between

    earth electrode and

    75mmx 8mm MS

    flat

    Check for

    tightness

    If found broken or

    loose, it should be

    immediately

    replaced/ tightened

    4 Projection of theearth electrode

    Check forground

    level and

    proper soil

    It should be 175 10mm above the

    ground level

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    45/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    33

    3.2 v)Zv)Zv)Zv)Z okf"kZd vuqj{k.k@okf"kZd vuqj{k.k@okf"kZd vuqj{k.k@okf"kZd vuqj{k.k@HALF YEARLY SCHEDULE

    Carry out following work in addition to quarterly

    schedule:

    Sr. Items Inspection Action to be taken

    1. Measure

    earth

    resistance

    Individual earth

    electrode and

    record the value

    By earth resistance

    meter. It should be

    permissible limit

    2. Measure

    earthresistance

    combined

    Combined earth

    resistance withearthing flats,

    connected to the

    equipment,

    structures and

    earth electrode

    TSS 0.5

    Switching station 2.0

    AT Station 10.0

    3. Sump Check up general

    condition

    including dryness.

    If the surrounding area

    is too dry, water

    should be poured intothe sump to keep the

    soil moist.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    46/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    34

    3.3 okf"kZd vuqj{k.k@okf"kZd vuqj{k.k@okf"kZd vuqj{k.k@okf"kZd vuqj{k.k@YEARLY SCHEDULE

    Carry out following work in addition to

    quarterly and half yearly schedule:

    Sr. Item Inspection Action to be taken

    1. Earth

    pits

    Check up

    the

    electrode

    for proper

    earthcontinuity.

    Remove the hardened top

    layer of the earth pit for a

    depth of 1 meter, mix with

    coke and loamy soil (non-

    sandy) and ram the earth.Repair the earth. Repair

    sides and top cover of the

    earth pits. Avoid use of salt

    as far as possible to avoid

    rusting of earth pipe.

    3.4 vFkZvFkZvFkZvFkZ bybybybySSSSDVksM dsfrjks/k dk ekiu@DVksM dsfrjks/k dk ekiu@DVksM dsfrjks/k dk ekiu@DVksM dsfrjks/k dk ekiu@MEASUREMENT OF EARTH ELECTRODERESISTANCE

    Fall of potential method

    In this method two auxiliary earth electrodes,

    besides the test electrode, are placed at suitable

    distances from the test electrode as shown in figure35.

    A measured current is passed between the electrode A

    to be tested and an auxiliary current electrode C andthe potential difference between the electrode A and

    the auxiliary potential electrode B is measured. The

    resistance of the test electrode A is then given by:

    R = V/I

    Where, R = Resistance of the test electrode in

    ohms,

    V = Reading of the voltmeter in volts,

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    47/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    35

    I = Reading of the ammeter in amperes

    In most cases, there will be stray currents flowing in

    the soil and unless some steps are taken to eliminate their

    effect, they may produce serious errors in the measuredvalue. If the testing current is of the same frequency as the

    stray current, this elimination becomes very difficult. It is

    better to use an earth tester incorporating a hand driven

    generator. These earth testers usually generate direct

    current, and have rotary current reverser and synchronous

    rectifier mounted on the generator shaft so that alternating

    current is applied to the test circuit and the resulting

    potentials are rectified for measurement by a direct reading

    moving coil ohm meter. The presence of stray currents in

    the soil is indicated by a wandering of the instrument

    pointer, but an increase or decrease of generator handle

    speed will cause this to disappear.

    At the time of test, where possible, the test electrode

    shall be separated from the earthing system. The auxiliaryelectrode consists of 12.5 mm diameter mild steel rod

    driven up to one meter into the ground.

    AMMETER

    VOLTMETER

    A

    V

    CURRENT

    SOURCE

    A B C

    TESTELECTRODE

    POTENTIAL

    ELECTRODECURRENT

    ELECTRODE

    X = 1m

    Figure 35

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    48/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    36

    3.5 gLr pkfyr vFkZ VsLVj dk fooj.k@gLr pkfyr vFkZ VsLVj dk fooj.k@gLr pkfyr vFkZ VsLVj dk fooj.k@gLr pkfyr vFkZ VsLVj dk fooj.k@DETAILS OFEARTH TESTER (Hand Driven)

    Earth resistance meter are employed formeasurements of earth resistance in Traction sub

    station, switching stations and other electrical

    installations. An Earth resistance meter comprises a

    hand driven magneto type D.C. Generator, a current

    reverser, rotary rectifier and ohm meter.

    The current reverser and rotary rectifier are

    driven along with D.C. Generator by driving systems

    which incorporate a clutch mechanism for

    unidirectional rotation and a governor for speed control.

    The function of current reverser is to change the

    direction of flow of current in the soil and that of rotary

    rectifier is to maintain unidirectional current in the

    potential coils of the ohm meter.

    The ohm meter consists of a current coil and a

    potential coil mounted on a common spindle and placed

    in the magnetic field of a permanent magnet. The

    current coil is connected in series with the earth

    electrodes and current electrodes. The potential coil is

    connected across the earth electrode and the potential

    electrode through the rotary rectifier. While measuring

    the earth resistance the terminals C1, P1 are connected

    to the main earth electrode P2 to the potential electrodeand C2 to the current electrode. The potential and

    current electrodes are temporary electrodes placed in

    the ground 50 to 75 feet apart and 50 to 75 feet & from

    the earth electrode as shown in below figure- 35 A

    When the megger is operated an ac current is

    produced in the coil. The voltage drop produced in the

    earth electrode is applied across the potential coil. The

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    49/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    37

    current coil produces a torque in the clock wise

    direction, and the potential coil produces a torque in

    anti-clock wise direction. The current applied to the

    current coil is inversely proportional to the earthresistance and the voltage drop applied across the

    potential coil is directly proportional to the earth

    resistance the torque opposes each other and brings the

    moving system to rest when they are equal. The pointer

    indicates the earth resistance values on a calibrated

    scale.

    Figure 35 A

    Cu rrent Term inal: or C2Poten tial Terminal: P1 or P2

    Test EarthElectrode

    PotentialElectrode

    CurrentElectrode

    C1

    P1

    C2

    P2

    50 - 70 feet 50 - 70 feet

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    50/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    38

    4.0 vuqj{k.k eqDr vfFkZax@vuqj{k.k eqDr vfFkZax@vuqj{k.k eqDr vfFkZax@vuqj{k.k eqDr vfFkZax@MAINTENANCE FREEEARTHING

    In conventional earthing system GI pipe is usedas earth electrode. It is provided with charcoal and salt

    as conducting media, which provides a reasonable

    earth. Corrosion of metallic parts is comparatively fast.

    It also requires maintenance by way of watering of

    earth pits and chiseling of corrosion prone parts and

    their replacement. Required monitoring may not always

    be feasible in certain crowded and inaccessible areas.

    With technological developments in this field,

    modern maintenance free and durable earthing system

    employs steel conductors as electrode which are copper

    claded and utilize graphitic compounds and non

    corrosive salts as Ground Enhancing Material which

    do not lead to corrosion. Such earth pits also do not

    require the usual watering schedules to maintain the

    earth resistance with in limits. Maintenance free earthsare to be constructed as per RDSOs specification

    no.RDSO/ PE/ SPEC/ 0109-2008 (REV0).

    Where the earth pits are not easily accessible for

    schedule maintenance, maintenance free earth pits shall

    be provided. In areas where clusters of earth pits are

    required to keep the earth resistance low, provision of

    maintenance free earth pits should be made duringinitial installation.

    4.1 vFkZ frjks/kvFkZ frjks/kvFkZ frjks/kvFkZ frjks/k@@@@EARTH RESISTANCE

    The earth resistance value at earth bus bar

    should be less than 0.5 ohms for major electrical

    equipment & installation.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    51/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    39

    4.2 mi;ksx@mi;ksx@mi;ksx@mi;ksx@APPLICATIONS

    This earthing system may be used in following

    locations. Sub stations & switching stations Remote Terminal Units Transformer & Generator neutral earths Lightning arrester earths Equipment earths including panels

    4.3 vuqj{k.k eqDr vfFkZax .kkyh@vuqj{k.k eqDr vfFkZax .kkyh@vuqj{k.k eqDr vfFkZax .kkyh@vuqj{k.k eqDr vfFkZax .kkyh@MAINTENANCE

    FREE EARTHING SYSTEM

    This earthing system includes earth electrode

    installation in suitable pit, construction of earth pit with

    cover for the installation, connection of earth electrode

    with equi-potential earth bus and connection of

    equipment to equi- potential earth bus.

    4.3.1 vFkZvFkZvFkZvFkZ bySDVksM@bySDVksM@bySDVksM@bySDVksM@Earth ElectrodeThe material for earth electrode used in this type

    of earthing, has a good electrical conductivity and it

    does not corrode in a wide range of soil conditions.

    There are basic two types of earth electrodes

    used in this earthing system.

    i. jkWM Vkbi vjkWM Vkbi vjkWM Vkbi vjkWM Vkbi vFkZFkZFkZFkZbySDVksM@bySDVksM@bySDVksM@bySDVksM@Rod type earthelectrode

    The copper bonded stainless steel rod

    (low carbon high tensile steel alloy) earth

    electrode shall conform to the standard BS 4360

    Grade 43A or EN10025:2-004 S275IR

    molecularly bonded by 99.99% pure high

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    52/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    40

    conductivity copper on outer surface with

    copper coating thickness 250 micron or more.

    The earth rod shall have following

    characteristics/ specifications.

    a.The minimum length of earth electrode shallbe 3.0 meters long. The length of electrode

    may be increased in multiple of 1.0 meter to

    reduce earth resistance.

    b.To increase the length, pieces of similar rodshall be either exothermally welded to basic

    3.0 meter electrode or connected using

    socket of suitable size. These sockets shall

    be molecularly bonded by 99.99% pure

    high conductivity copper on inner & outer

    surface with copper coating thickness 250

    micron or more.

    c.The diameter of earth electrode shall not beless than 17 mm.

    d.The copper bonding thickness on stainlesssteel rod shall be 250 microns or more, hot

    dipped or electroplated.

    e.Copper bus bar of size 250 mm x 50 mm x 6mm having electrical conductivity of 101%

    IACS minimum 99.9% copper content shallbe exothermically welded to rod with 4

    holes of 12 mm dia. (2 on each side) for

    connecting earthing conductor.

    f.Current carrying capacity of earth electrodeshould be such as to have more than 15kA

    for one second.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    53/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    41

    ii. llllaaaadsfUnzr ikbi vFkZ bySDVksM@dsfUnzr ikbi vFkZ bySDVksM@dsfUnzr ikbi vFkZ bySDVksM@dsfUnzr ikbi vFkZ bySDVksM@Concentricpipe earth electrode

    MS pipe with 25 - 50 mm diameter, class B,ISI mark as per IS: 1239, length 2000 mmor 3000 mm is used as primary conductor

    as shown in table -1

    MS pipe with 40 - 100 mm diameter, class B,ISI mark as per IS: 1239, length 2000 mm

    or 3000 mm is used as secondary conductor

    (electrode) as shown in table -1

    Table - 1Sr. Current

    capacity

    Primary

    conductor

    diameter

    Secondary conductor

    (Electrode) dimensions

    (dia x length)

    1 3kA 25 mm 40 mm x 2000 mm

    2 5kA 25 mm 40 mm x 3000 mm

    3 15kA 25 mm 50 mm x 3000 mm

    4 40kA 40 mm 60 mm x 3000 mm5 50kA 50 mm 100 mm x 3000 mm

    NOTE For more than 50kA applications, multiple

    electrodes of 50kA capacity are installed and

    connected.

    For hermetically filling inside the cavity betweensecondary conductor and primary conductor,

    crystalline compound is to be injected in theelectrode assembly. It is a combination of high

    conductivity metal alloys, copper & aluminium

    powder, conductive carbon/cement and bonding

    material etc. mixed in different proportion. The

    mixture is forced (pressurized) filled inside the

    earth electrode in the paste form and after

    solidification of the same, the end caps are welded.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    54/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    42

    The metal alloys shall help in conducting the

    current and conductive carbon gives anti corrosive

    property. Bonding material provides strength to the

    mixture. Resistivity of the mixture shall be lessthan 0.2 ohm - meter. Resistivity shall be tested by

    making a 20 cm cube of the material and checking

    resistance across the opposite face of the cube.

    Complete electrodes shall be molecularly bondedby 99.99% pure, high conductivity copper on outer

    surface with copper coating thickness 300 micron

    or more.

    Its surface shall be cleaned and free from anyvisible oxide layer or foreign material.

    Copper bus bar of size 250 mm x 50 mm x 6 mmhaving electrical conductivity 101% , minimum

    99.9% copper content shall be preferable to

    exothermically welded to earth electrode or

    connected with the help of two number stainless

    steel nut bolts of appropriate size having 4 holes of12 mm dia ( 2 on each side) for connecting earthing

    conductor as shown in figure - 36

    EarthEhancement

    Earth Electrode

    (Dimension as perdesign)

    ExothermicWelding

    25 x 3mm Copper Strip (To be duplicated)

    300 x 25 x 6mm Copper bus

    ExothermicWelding

    ExothermicWelding

    Ground Level

    5 ft x 5ft x 10ft pit or 300mm bore

    (Earth Electrode Installation)

    To Equipment

    Figure - 36

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    55/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    43

    4.3.2 vFkZ bugsUlesaV lkexzhvFkZ bugsUlesaV lkexzhvFkZ bugsUlesaV lkexzhvFkZ bugsUlesaV lkexzh@@@@Earth Enhancement Material

    Earth enhancement material is a superior

    conductive material that improves earthing

    effectiveness especially in area of poor conductivity asshown in figure 36A. It improves conductivity of the

    earth electrode and ground contact area. It has

    following characteristics:

    a. It should low resistivity bellow 0.2 ohm- meters.

    b. It shall not depend on the continuous presence ofwater to maintain its conductivity.

    c. It should be a little alkaline in nature with pHvalue >7 but

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    56/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    44

    e. It has a capacity to retain >10% moisture at105

    0C.

    f. It should have water solubility

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    57/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    45

    4.3.3 cSdfQy lkexzh@cSdfQy lkexzh@cSdfQy lkexzh@cSdfQy lkexzh@Backfill material

    The excavated soil can be used if it is free from

    sand, gravel and stones. Small proportion of sand inthe soil may be permissible. Material like sand, salt,

    coke breeze, cinders and ash are not used because of

    its acidic and corrosive nature.

    While backfilling the soil shall be thoroughly

    compacted with at least 5 kg compactor, in case the

    soil is dry small quantity of water may be sprinkled

    only to make it moist enough suitable for

    compacting. Large quantity of water may make thesoil muddy which is not suitable for compacting and

    after drying the soil may contain voids which may

    permanently increase earth resistance.

    4.3.4 le foHko cl ,oavFkZ pkyd@le foHko cl ,oavFkZ pkyd@le foHko cl ,oavFkZ pkyd@le foHko cl ,oavFkZ pkyd@Equi- Potential Bus& Earth Conductor

    A copper bus bar of size 300 mm x 25 mm x 6 mmto be installed in this equipment room as equi

    potential bus connected with copper strip of size

    25 mm x 3 mm (suitable length) from instrument

    to the bus bar. The connecting terminal of the

    earth electrodes to the bus bar must be connected

    by copper strip of 25 mm x 3 mm (suitable

    length) buried inside a trench of 300 mm width x

    600 mm (depth from the nearest wall). It is

    duplicate earth conductor.

    The maximum specific resistance of the copperstrip earthing conductor shall be 17.241 x 10

    -7

    ohm cm at 200C and having electrical

    conductivity of 101% IACS i.e. minimum 99.9%

    copper content.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    58/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    46

    At a temperature of 200C, its density shall be 8.89gm/cm

    3.

    A single length of copper strip shall be used foreach duplicate earthing conductor and no joint

    shall be permitted. The joint shall be made by

    exothermic welding of at least 10 mm

    overlapping portion of the strips.

    It shall be connected to earth electrode and earthbus bar with the help of exothermic welding or at

    least two number stainless steel nut bolts of

    appropriate size.

    4.3.5 vFkZvFkZvFkZvFkZ bdkbZbdkbZbdkbZbdkbZ dk fuekZ.k@dk fuekZ.k@dk fuekZ.k@dk fuekZ.k@Construction of unit Earth

    Make 5ft x 5ft x 10ft earth pit. If it not possible to

    make such a pit due to non availability of clearspace a minimum 300 mm bore up to 10ft deep

    can be made using earth auger or any other

    method. Each pit larger than specified size can be

    made, if required.

    Sleeve the soil digged and remove the gravels andstones. If soil quality is good then add some

    quantity of earth enhancement material in the soilfor using as backfill.

    If the soil seems unusable (containing largequantity of gravel, stones, murum, sand etc) then

    replace the soil with black cotton soil.

    Insert the electrode at the center of the earth pit andarrange to keep it vertical in the pit

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    59/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    47

    Arrange for adequate quantity of water supply forthe earth pit (600 liters).

    Fill the pit with the backfill and keep on adding theearth enhancement material surrounding the

    electrode and simultaneously watering the pit

    with a steel bar or pipe, keep on poking the soil

    gel and stirring intermittently for removing the air

    pockets and proper settlement of the pit. The

    procedure to be repeated till completion of the

    filling of the earth pit along with the packing

    material and sufficient watering adequateramming.

    The pit should be very compactly rammed andwatering for 2-3 days and addition of soil if

    required be done.

    Construct inspection chamber with cover for theinstallation.

    Measure the earth resistance as per IS 3043:1987code of practice.

    4.3.6 cgq vFkZ fiVksa}kjk vFkZ fjax dk fuekZ.k@cgq vFkZ fiVksa}kjk vFkZ fjax dk fuekZ.k@cgq vFkZ fiVksa}kjk vFkZ fjax dk fuekZ.k@cgq vFkZ fiVksa}kjk vFkZ fjax dk fuekZ.k@Construction of Ring Earth by providing multiple

    earth pits

    Wherever it is not possible to achieve requiredearth resistance with one earth electrode/ pit due todifficult/ rocky soil conditions, provision of ring

    earth consisting of more than one earth pit is

    required. The number of pits required can be

    decided based on the resistance achieved for the

    earth pits already installed.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    60/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    48

    The distance between two successive earthelectrodes shall be min. 3.0 mtrs/length of electrode

    which ever is higher, and max. up to twice the

    length of the earth electrode.

    These earth pits shall inter linked using 25 x 3 mmcopper strip to from a loop preferably using

    exothermic welding or with the help of at least two

    numbers of stainless steel nut bolts of appropriate

    size.

    The interconnecting strips shall be buried not less

    than 800 mm (0.8 m) below the ground level. Thisinterconnecting strip shall also be covered with

    earth enhancing compound.

    4.3.7 fujh{k.k d{k@fujh{k.k d{k@fujh{k.k d{k@fujh{k.k d{k@Inspection chamber

    A 300 mm x 300 mm x 300 mm (inside dimension)concrete box (wall thickness min. 50 mm) with

    smooth cement plaster finish shall be provided on

    the top of pit. A concrete lid of 25 to 50 mm thick,

    with pulling hooks, painted black shall be provided

    to cover the earth pit. PVC sleeve of appropriate

    size shall be provided in concrete wall to take out

    earthing connections.

    The masonry work shall be white washed inside

    and outside.

    Care shall be taken regarding level of the floorsurrounding the earth so that the connector is not

    too deep in the masonry or projecting out of it.

    On backside of the cover, date of test and averageresistance value shall also be written with yellow

    paint on black background with date.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    61/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    49

    5.0 ckWfUMax] xzkmfUMax@ vfFkckWfUMax] xzkmfUMax@ vfFkckWfUMax] xzkmfUMax@ vfFkckWfUMax] xzkmfUMax@ vfFkZax dsfy, ,DlksFkfeZdZax dsfy, ,DlksFkfeZdZax dsfy, ,DlksFkfeZdZax dsfy, ,DlksFkfeZdoSoSoSoSfYMax la;kstufYMax la;kstufYMax la;kstufYMax la;kstu@@@@EXOTHERMIC WELDINGCONNECTION FOR BONDING, GROUNDING/EARTHING

    The Exothermic welding connection process for

    grounding/ earthing covers the requirements and

    acceptance principle for weld material, welding tool

    and tool kit, bonds/ track bond wires for making

    permanent electrical bond connection between two

    conductors as per RDSO specification no. TI/ SPC/OHE/ EXOTHRM BOND/ 0100 (04/10).

    These weld materials including tool kit shall be useful

    in following railway application on 25kV electric

    traction system.

    (a) Traction bond connection to rail & OHE structures

    enroute.(b) Traction rail continuity connection.

    (c) Earthing connections like at TSS, SP/ SSPs,SCADA/ RTU and other important electrical

    installation.

    (d) Bus bar connections etc.

    (e) Copper to copper, copper to steel connection.(f) Important bonds which are not disturbed during

    track relaying.

    (g) Sections where 90UTS rails have been provided.

    (h) Theft prone areas.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    62/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    50

    5.1 lkekU; vko;drk;salkekU; vko;drk;salkekU; vko;drk;salkekU; vko;drk;sa@@@@GENERAL REQUIREMENTS

    Welding material along with tool kit shall be

    capable of providing a permanent bondingconnection involving copper or aluminium or steel.

    The final bond shall be achieved in such a way that

    homogeneous molecular bonding of two involved

    metals takes place perfectly.

    Exothermic welding process should be a steadyburn, no pops and no drastic color changes (white

    hot color during burn, turns orange as the reaction

    stops and the molten metal grows orange).

    Welding connection shall be without voids orpinhole, and no porosity should be detected. The

    process shall be consistent and continuous.

    It shall be permanent, solid metal, maintenance freeconnection and shall not be affected by high current

    surge. It shall not loosen or corrode at the point of weld.

    There shall be no additional contact surface or

    mechanical pressures involved.

    It shall be vibration proof and corrosion freeelectrical connection.

    It shall not brittle with age and shall be able tosustain physical impacts, which may be

    experienced under the field conditions.

    Electrical resistance and other properties shall notdeteriorate with ageing and under severe Indian

    climatic conditions.

    It shall have a current carrying capacity equal to or

    greater than that of the conductors

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    63/82

    CAMTECH/E/10-11/Earthing-PSI/1.0

    Handbook on Earthing System for Power Supply Installation November 2010

    51

    Life of the joints shall not be less than 10 yearsirrespective of life of conductors, equi-potential

    earth bus bars or ground rods used.

    5.2 oooossssfYfYfYfYaaaaMx lkexzh@Mx lkexzh@Mx lkexzh@Mx lkexzh@WELDING MATERIAL

    The weld material shall be designed for twospecific types of jointing applications

    Rail welding application

    Earthing & bonding application.

    It shall not contain phosphorous or any caustic,toxic or explosive substance. For rail welding

    application, the welding material shall not contain

    tin besides the above cited elements. Its

    components shall not volatile or sensitive to shock,

    nor capable of spontaneous ignition by friction.

    The reaction of the welding material shall be

    completed within 10 seconds and on completion ofjointing & bonding process. The resulting weld

    nugget shall free of dissolved gases or low boiling

    point elements, e.g., small voids or blisters on the

    surface.

    Weld materials shall provide a final bond withminimum tensile strengths of 40,000 psi tested

    using ASTM ES-94a (Test Methods for Tension

    Testing of Metallic Material).

    The weld material for traction bond and studwelding for rail application shall be free from tin.

    As presence of metallic tin allows for wetting of

    rail surface and provides for unnecessary

    penetration that can lead to metallurgical damage to

    the rail.

  • 7/23/2019 Handbook on Earthing system for power supply installations.pdf

    64/82

    CAMTECH/E/10-11/PSI/1.0

    November 2010 Handbook on Earthing System for Power Supply Installation

    52

    The weld material for earthing & bondingapplication shall be tested as provision of IEEE-837

    by NABL/ILAC Member labs.

    5.3 osfYaMxosfYaMxosfYaMxosfYaMx VwYl dh fofk"VVwYl dh fofk"VVwYl dh fofk"VVwYl dh fofk"Vrk;sa@rk;sa@rk;sa@rk;sa@SPECIFICATIONOF WELDING TOOLS

    It shall be suitable for bonding as per the sizesspecified for bonding equi-potential earth bus bars

    (EEBB) to g