hands on relay school - ieeeewh.ieee.org/soc/pes/newyork/newsite/pdfs/protection related... ·...

63
Hands On Relay School Transformer Protection Open Lecture

Upload: dinhduong

Post on 13-Feb-2018

235 views

Category:

Documents


6 download

TRANSCRIPT

Hands On Relay SchoolTransformer Protection Open Lecture

Hands On Relay SchoolTransformer Protection Open Lecture

Class Outline• Transformer protection overview• Review transformer connections• Discuss challenges and methods of current 

differential Protection• Discuss other protective elements used in 

transformer protection

Scott CooperEastern Regional ManagerManta Test Systems

[email protected](727)415-5843

204 37th Avenue North #281Saint Petersburg, FL 33704

Transformer Protection Overview Transformer Protection Zones

Types of ProtectionMechanical Protection

• Analysis of Accumulated Gases– Looks for arcing by‐products

• Sudden Pressure Relays– Orifice allows for normal thermal expansion/contraction.  Arcing 

causing pressure waves in oil or gas space overwhelming the orifice and actuating the relay.

• Thermal– Caused by overload, over excitation, harmonics and geo magnetically 

induced currents• Hot spot temperature• Top Oil• LTC Overheating

Types of ProtectionRelay Protection

• Internal Short Circuit– Phase:  87HS, 87T– Ground:  87HS, 87T, 87GD

• System Short Circuit Back Up Protection– Phase and Ground Faults

• Buses:  50, 50N, 51, 51N, 46• Lines:  50, 50N, 51, 51N, 46

Types of ProtectionRelay Protection

• Abnormal Operating Conditions– Open Circuits: 46– Overexcitation: 24– Undervoltage: 27– Abnormal Frequency:  81U– Breaker Failure:  50BF, 50BF‐N

Phase DifferentialOverview

• What goes into a “unit” comes out of a “unit”

• Kirchoff’s Law: The sum of the currents entering and leaving a junction is (should be) zero

• Straight forward concept, but not that simple in practice with transformers

UNITI1 I2

I3

I1 + I2 + I3 = 0

Phase DifferentialOverview

A host of issues presents itself to decrease security and reliability of transformer differential protection

• CT ratio caused current mismatch• Transformation ratio caused current mismatch (fixed taps)• LTC induced current mismatch• Delta‐wye transformation of currents

– Vector group and current derivation issues• Zero‐sequence current elimination for external ground faults on wye windings• Inrush phenomena and its resultant current mismatch• Harmonic content availability during inrush period due to point‐on‐wave 

switching (especially with newer transformers)• Over‐excitation phenomena and its resultant current mismatch• Internal ground fault sensitivity concerns• Switch onto fault concerns• CT saturation, remnance and tolerance

Compensation (2)Change in CT Ratio 1:1, Y-Y

1:1, 3Y4:1, 3Y

IA, IB, IC Ia, Ib, Ic

IA'*4 = Ia'IB' * 4 = Ib'IC' * 4 = Ic'

IA', IB', IC' Ia', Ib', Ic'

Phase DifferentialOverview‐Transformer Basics

Transformer Tap Calculation‐Per Unit Concept

Compensation (3)Transformer Ratio 2:1, Y-Y

1:1, 3Y1:1, 3Y

IA, IB, IC Ia, Ib, Ic

IA' = Ia' / 2IB' = Ib' / 2IC' = Ic' / 2

IA', IB', IC' Ia', Ib', Ic'

Phase DifferentialOverview‐Transformer Basics

Transformer Tap Calculation‐Per Unit Concept

Compensation (2)Change in CT Ratio

IA, IB, IC Ia, Ib, Ic

IA', IB', IC' Ia', Ib', Ic'

Phase DifferentialOverview‐Transformer Basics

Transformer Tap Calculation‐Per Unit Concept

There must be an easier way…..

Transformer Tap Calculation‐Per Unit Concept

Phase DifferentialOverview‐Transformer Basics

100MVAIN

100MVAOUT

Transformer Tap Calculation‐Per Unit Concept

Phase DifferentialOverview‐Transformer Basics

3∗∗=

− CTRVrVATransformeWindingTap

LL CTRVrVATransformeWindingTap

LL ∗=

Tap Calculation with Delta CTsTap Calculation with Wye CTs

Transformer Tap Calculation‐Per Unit Concept

Phase DifferentialOverview‐Transformer Basics

Each measured current is divided by the winding Tap. The result is a percent of rating. These percent of ratings can be compared directly.

AB connected delta‐wye transformer

Phase DifferentialOverview‐Transformer Basics

a

b

c -b

• Subtracting Vectors: Subtract from reference phase vector the connected non-polarity vector…in our example Ia-Ib

• Can be repeated for B & C, or you can assume –120 and –240 displacement from A for B&C respectively

• Ib – Ic and Ic – Ia would be the vectors

Phase DifferentialOverview‐Transformer Basics

AC connected delta‐wye transformer

Ia Ia

Ib Ib

IcIc

Ia

Ib

Ic

Ia-Ic

Ib-Ia

Ic-Ib

Ia

Ia-IcIb

Ic

Ib-Ia

Ic-Ib

Phase DifferentialOverview‐Transformer Basics

• Subtracting vectors: Subtract from reference phase vector the connected non-polarity vector…in our example Ia-Ic

• Can be repeated for B & C, or you can assume –120 and –240 displacement from A for B&C respectively

• Ib – Ia and Ic – Ib would be the vectors

a

b

c

-c

Phase DifferentialOverview‐Transformer Basics

Angular Displacement Conventions:• ANSI Y‐Y, Δ‐Δ@ 0°; Y‐Δ , Δ‐Y @ X1 lags H1 by 30°

– ANSI makes life easy

• Euro‐designations use 30° increments of LAG from the X1 bushing to the H1 bushings

– Dy11=X1 lags H1 by 11*30°=330°or, H1 leads X1 by 30°

– Think of a clock – each hour is 30 degrees

0

6

39

8

7

10

11 12

5

4

Dy1 = X1 lags H1 by 1*30 = 30, or H1 leads X1 by 30 (ANSI std.)

Phase DifferentialOverview‐Transformer Basics

US Standard Dy Example:• H1 (A) leads X1 (a) by 30• Currents on “H” bushings are delta quantities

a

b

c A

B

C

Assume 1:1 transformer

Phase DifferentialOverview‐Transformer Basics

Assume 1:1 transformer

a

b

c

AB

C

Phase DifferentialOverview‐Transformer Basics

US Standard Yd Example:•H1 (a) leads X1 (A) by 30•Currents on “X” bushings are delta quantities

Phase DifferentialOverview

• Applied with variable percentage slopes to accommodate CT saturation and CT ratio errors

• Applied with inrush and over excitation restraints

• Set with at least a 20% pick up to accommodate CT performance– Class “C” CT; +/‐ 10% at 20X 

rated• If unit is LTC, add another +/‐

10%• May not be sensitive enough 

for all faults (low level, ground faults near neutral)

• CT ratios and tap settings are selected to account for:

– Transformer ratios– If delta or wye connected CTs are 

applied– Delta increases ratio by 1.73

• Delta CTs must be used to filter zero‐sequence current on all wye transformer windings

• Dy transformer connections compensated by yd CT connections to make the currents “apples to apples”.

Phase DifferentialE‐M Relay Application 

Zero‐sequence elimination:  In E‐M relays with wye connected transformers, delta connected CTs are used to remove the ground current. 

Phase DifferentialE‐M Relay Application 

Settings compensate for the following:• Transformer ratio• CT ratio• Vector quantities

– Which vectors are used– Where the 1.73 factor (√3) is applied

• When examining line to line quantities on delta connected transformer windings and CT windings

• Zero‐sequence current filtering for wye windings so the differential quantities do not occur from external ground faults

Phase DifferentialDigital Relay Application 

Angular displacement (IEC and SEL)• IEC (Euro) practice does not 

have a standard like ANSI• Most common connection is 

Dy11 (low lead high by 30!)• Obviously observation of 

angular displacement is extremely important when paralleling transformers!

*1

*1

*2

*2

*1 = ANSI std. @ 0°

*2 = ANSI std. @ X1 lag H1 by 30°, or “high lead low by 30 ° “

Phase DifferentialDigital Relay Application 

Digital Relay Application

All wye CTs shown, most can retrofit legacy delta CT applications

Benefits of Wye CTs

• Phase segregated line currents– Individual line current oscillography– Currents may be easily used for overcurrent protection and metering

– Easier to commission and troubleshoot– Zero sequence elimination performed by calculation 

Zero‐sequence elimination:  In digital relays with wye connected transformers and wye connected CTs, ground current must be removed from the differential calculation. 

•3I0 = [Ia + Ib + Ic]I0 = 1/3 *[Ia + Ib + Ic]

•Used where filtering is required, such as wyewinding with wye CTs

Phase DifferentialDigital Relay Application 

Typical Transformer Inrush Waveform

2nd and 4thHarmonicsDuringInrush

Phase DifferentialDigital Relay Application 

Harmonically Restrained Differential Element• Inrush Detection and Restraint

– Inrush occurs on transformer energizing as the core magnetizes– Sympathy inrush occurs from adjacent transformer(s) energizing, fault 

removal, allowing the transformer to undergo a low level inrush– Characterized by current into one winding of transformer, and not out 

of the other winding(s)– This causes the differential element to pickup– Use inrush restraint to block differential element during inrush period

Phase DifferentialDigital Relay Application 

• Inrush Detection and Restraint– 2nd harmonic restraint has been employed for years– “Gap” detection has also been employed– As transformers are designed to closer tolerances, both 2nd harmonic 

and low current gaps in waveform have decreased– If 2nd harmonic restraint level is set too low, differential element may 

be blocked for internal faults with CT saturation (with associated harmonics generated)

Phase DifferentialDigital Relay Application 

• Inrush Detection and Restraint– 4th harmonic is also generated during inrush– Odd harmonics are not as prevalent as Even harmonics during inrush– Odd harmonics more prevalent during CT saturation– Use 4th harmonic and 2nd harmonic together– M‐3310/M‐3311 relays use RMS sum of the 2nd and 4th harmonic as 

inrush restraint– Result:  Improved security while not sacrificing reliability

Phase DifferentialDigital Relay Application 

• Overexcitation Restraint– Overexcitation occurs when volts per hertz level rises (V/Hz)

– This typically occurs from load rejection and malfunctioning generation AVRs

– The voltage rise at nominal frequency causes the V/Hz to rise

– This causes 5th harmonics to be generated in the transformer as it begins to go into saturation

– The current entering the transformer is more than the current leaving due to this increase in magnetizing current

– This causes the differential element to pick‐up– Use 5th harmonic level to detect overexcitation

Phase DifferentialDigital Relay Application 

0.5

1.0

1.5

2.0

0.5 1.0 1.5 2.0

87T Pick Up

87T Pick Upwith 5th Harmonic Restraint

Slope 1

Slope 2

Slope 2Breakpoint

TRIP

RESTRAIN

Phase DifferentialDigital Relay Application 

• 87T Pick Up– Class C CTs, use 20%– LTC, add 10%– Magnetizing losses, add 1%– 0.3 to 0.4 pu typically setting

• Slope 1– Used for low level currents– Typically set for 25%

• Slope 2 “breakpoint”– Typically set at 2X rated current– This setting assumes that any current over 2X rated is a 

through fault or internal fault, and is used to desensitize the element against unfaithful replication

Phase DifferentialDigital Relay Application 

• Slope 2– Typically set at 70%

• Inrush Restraint (2nd and 4th harmonic)– Typically set from 15‐20%– Employ cross phase averaging blocking for security

• Over‐excitation Restraint (5th harmonic)– Typically set at  30%– Raise 87T pick up to 0.60 pu during overexcitation– No cross phase averaging needed, as overexcitation is 

symmetric on the phases

Phase DifferentialDigital Relay Application 

• Unrestrained 87H Pick Up– Typically set at 8‐10pu rated current– This value should be above maximum possible inrush current 

and lower than the CT saturation current– C37.91, section 5.2.3, states 10pu an acceptable value– Can use data captured from energizations to fine tune the 

setting

Phase DifferentialDigital Relay Application 

CT Issues:• Remnance:  Residual magnetism that causes dc saturation of the 

CTs• Saturation:  Error signal resulting from too high a primary current 

combined with a large burden• Tolerance:  Class “C” CTs are rated +/‐ 10% for currents x20 of 

nominal – Thru‐faults and internal faults may reach those levels depending on ratio 

selected

Phase DifferentialDigital Relay Application 

CT Issues (cont.)• Best defense is to use high “Class C” voltage levels

– C400, C800– These have superior characteristics against saturation and  relay/wiring 

burden• Use low burden relays

– Digital systems are typically 0.020 ohms• Use a variable percentage slope characteristic to desensitize 

the differential element when challenged by high currents that may cause replication errors

Phase DifferentialDigital Relay Application 

“Point‐on‐Wave” Considerations During Energization• As most circuit breakers are ganged three‐pole, each phase is closed at a 

different angle resulting in less harmonics on one phase and more on the others

• Low levels of harmonics may not provide inrush restraint for affected phase –security risk!

• Most modern relays employ some kind of cross‐phase averaging scheme to compensate for this issue

– Provides security if any phase has low harmonic content during inrush or overexcitation– This can occur depending on the voltage point‐on‐wave when the transformer is energized for a 

given phase– Cross phase averaging uses the average of harmonics on all three phases to determine level

Phase DifferentialDigital Relay Application 

Improved Ground Fault Sensitivity:• 87T element is typically set with 20‐40% pick up• This is to accommodate Class “C” CT accuracy 

during a fault plus the effects of LTCs• That leaves 20‐40% of the winding not covered for 

a ground fault• Employ a ground differential element to improve 

sensitivity (87GD)

Phase DifferentialDigital Relay Application 

Switch‐onto‐Fault:• Transformer is faulted on energizing• Harmonic restraint on unfaulted phases may work against trip decision if cross phase averaging is used– Un‐faulted phase will have no harmonics, other phases may have high value

• Employ 87HS to protect winding that is being energized

• Employ 87GD on coupled winding if it is wye

Phase DifferentialDigital Relay Application 

Switch‐onto‐Fault (cont):• Employ 87HS to protect winding that is first energized• 87HS is set above inrush current• If fault is near the bushing end of the winding, the current will be higher 

than inrush– Typically 9‐12 pu thru current

• 87HS does not employ harmonic restraint– Fast tripping on high current faults

Phase DifferentialDigital Relay Application 

• Use 87GD• IA + IB + IC = 3I0

• If fault is internal, opposite polarity

• If fault is external, same polarity

IG

IA

IB

IC

Ground DifferentialDigital Relay Application 

IG

IA

IB

IC

IG

IA

IB

IC

Internal External

Ground DifferentialDigital Relay Application 

Restricted Earth Fault Trip Characteristic

• 87GD Pick Up– Element normally uses directional comparison between phase 

residual current (3I0) and measured ground current (IG)• No user setting

– Pick up only applicable when 3I0 current is below 140mA (5A nom.)

• Pick up = 3I0 - IG

– If 3I0 greater than 140mA, element uses:• –3I0 * IG * cosθ.  It will trip only when the directions of the 

currents is opposite, indicating an internal fault• Using direction comparison mitigates the effects of saturation on 

the phase and ground CTs

Ground DifferentialDigital Relay Application 

IG

IA

IB

IC

3I0IG

Residual currentcalculated fromindividual phasecurrents. ParalleledCTs shown toillustrate principle.

0

90

180

270

IG

-3IO

Ground DifferentialDigital Relay Application 

0

90

180

270

IG

-3IO

Ground DifferentialDigital Relay Application 

• Fuses– Small transformers ( <10 MVA)– Short circuit protection only

• Over current protection– H‐side

• Through fault protection• Differential back‐up protection for high side faults

– X‐side• System back up protection• Unbalanced load protection

Other Transformer ProtectionOver current Elements

H‐side over current elements:• Protection against heavy prolonged through faults• Transformer Category by nameplate capacity

– IEEE Std. C57.109‐1985 Curves

Other Transformer ProtectionOver current Elements

Cat. 2 & 3 Fault Frequency 

Zones

Through Fault Category 1

Through Fault Category 2

Through Fault Category 3

Through Fault Category 4

X‐side Over Current Elements

• Used to protect against un‐cleared faults downstream of the transformer

• May consist of phase and ground elements

• Coordinated with line protection off the bus Failed Breaker

5151G

Other Transformer ProtectionOver current Elements

X‐side Over Current Elements:• Negative sequence over 

current used to protect against unbalanced loads & open conductors

• Easy to coordinate46

Other Transformer ProtectionOver current Elements

• Overexcitation:– Responds to overfluxing; excessive v/Hz– Continuous operational limits

• ANSI C37.106 & C57.12– 1.05 loaded, 1.10 unloaded

• Inverse curves typically available for values over the continuous allowable maximum

Other Transformer ProtectionOver current Elements

Causes:• Generating Plants

– Excitation system runaway – Sudden loss of load– Operational issues (reduced frequency)

• Static starts• Pumped hydro starting• Rotor warming

• Transmission Systems– Voltage and Reactive Support Control Failures

• Capacitor banks ‘ON’ when they should be ‘OFF’• Shunt reactors ‘OFF’ when they should be ‘ON’• Generator unit transformer connected to long line with no‐load (Ferranti effect)

• Runaway LTCs

Other Transformer ProtectionOver current Elements

Overexcitation Curve

This is typically how the apparatus manufacturer specs it

Overexcitation Curve

This is how protection engineers enter the v/Hz curve into a protective device

References:‐ANSI / IEEEC37.91, “Guide for Protective Relay Applications for Power Transformers”‐ANSI/IEEE C57.12,  “Standard General Requirements for Liquid Immersed Distribution,  Power and Regulating Transformers”Protective Relaying:  Principals and applications, Third Edition By J. Lewis Blackburn and Thomas J. Domin‐Digital Transformer Protection from Power Plants to Distribution Substations,  CJ MozinaGeneral Electric “Transformer Connections including Autotransformer Connections”  GET‐2J, Dec, 1970

87T

50

51 51G

High Side Low Side