  • GU611A Controller Operation Manual

    1

    The clarification of notation used within this manual:

    WARNING: A WARNING indicates a potentially hazardous situation which, if not avoided, could result in death, serious personal injury or property damage.

    CAUTION: A CAUTION indicates a potentially hazardous situation which, if not avoided, could result in damage to equipment or property.

    NOTE: A NOTE provides other helpful information that does not fall under the warning or caution categories.

  • GU611A Controller Operation Manual

    2

    WARNING: Read this entire manual pertaining to the work to be performed before installing, operating, or servicing this controller. Practice all plant and safety instructions and precautions. Failure to follow instructions can cause personal injury and/or property damage. The engine or other type of prime mover should be equipped with an overspeed shutdown device to protect against runaway or damage to the prime mover with possible personal injury, loss of life, or property damage. The overspeed shutdown device must be totally independent of the prime mover control system. An overtemperature or overpressure shutdown device may also be needed for safety, as appropriate.

    CAUTIONBATTERY CHARGING To prevent damage to a controller that uses an alternator or battery-charging device, make sure the charging device is turned off before disconnecting the battery from the system. Controllers contain static-sensitive parts. Observe the following precautions to prevent damage to these parts: Do not disassemble the rear back of controller and touch the components or conductors on a printed circuit board.

  • GU611A Controller Operation Manual

    3

    Contents

    1. Description ...........................................................................................4

    2. The Outline Dimensional Drawings and Wirings of Controller ............5

    3. Operation Panel ..........................................................................................8

    4. Installation Guide ........................................................................................10

    5. Control and Operation Instruction ............................................................11

    6. Measure and Display Data ......................................................................18

    7. Warning and Shutdown Alarm ...................................................18

    8. Parameters Setting ..........................................................................23

    9. LCD Display and Menu System....................................................31

    10. Preparation before Start the Controller..................................................34

    11. Technical Parameters.................................................................................34

  • GU611A Controller Operation Manual

    4

    1. Description GU611A is an auto start controller of Mains failure. Mains monitored by controller under auto control mode, when Mains occurs failure, generator auto start and Gen supply; Mains supply when Mains recover and generator stop delay. The control procedure and protection parameters of generator can be modified, completely meet requirements of Genset on auto start, and stop control and basic protection. z Controller through LCD on panel displays control status, running status and

    related measuring data for Genset. z LCD has background-light function that operator can clearly read the

    operating parameters even at night. z Controller has two running modes: AUTO/MAN, they are selected by buttons on

    panel. z Controller measures and displays output voltage, current, oil pressure, coolant

    temperature, frequency, and DC source voltage for generator. z Voltage and current are measured by true RMS to make sure data accuracy. z It can control the output switches both of Gen and Mains making or breaking. z Optional internal communication interface can be used to configure parameters

    via PC. z All connections of controller are connected by pin-like and locked up terminal,

    easier and more convenient to connect, move, maintain and replace the device. This manual only suitable for GU611A generator automatic controller, user must

    carefully see this manual first.

  • GU611A Controller Operation Manual

    5

    2. The Outline Dimensional Drawings and Wirings of Controller 2.1 Following Details:

    Operation Panel W120mmH102mm Install Cutout W110mm H92mm Thickness D48mmunconnected

  • GU611A Controller Operation Manual

    6

    2.2 Connecting Terminals: Pin no. Function Description Signal Dim

    1 L1 Mains phase voltage input 0-300Vac 1mm

    2 L2 Mains phase voltage input 0-300Vac 1mm

    3 L3 Mains phase voltage input 0-300Vac 1mm

    4 Mains neutral 1mm

    5 L1 Gen phase voltage input 0-300Vac 1mm

    6 Gen neutral 1mm

    7 I1 Gen current input 0-5A 2.5mm

    8 I2 Gen current input 0-5A 2.5mm

    9 I3 Gen current input 0-5A 2.5mm

    10 common for current input 0-5A 2.5mm

    11 P-sensor or switch signal P-sensor (

  • GU611A Controller Operation Manual

    7

    2.3 Typical Wiring Diagram

    (OR TEMP. SWITCH)

    (OR OIL SWITCH)

    LOAD

    (3P&N)

    M2M1

    MAINS

    GU61

    1A

    CONFIG

    . OU

    TPUT

    FUEL

    CRANK

    DC POWER

    CLOSE

    CLOSE

    GEN.

    MAIN

    S

    (12/24V)

    OIL PRESSURE

    COOLANT TEMP.

    CONFIG

    . INPU

    T

    A fuse with the rating of 10A shall be provided external to the equipment.

  • GU611A Controller Operation Manual

    8

    3. Operation Panel

    The whole operation panel includes 3 sections: LCD displays measuring parameters, indicator light for common failure, and control buttons and select buttons for control modes.

    LCD cycle displays different measuring parameters. When failure occurs LCD displays corresponding sign. LCD has background-light function so that operator can clearly read information whenever at day or night. After pressing any buttons the background-light will auto turn off in a certain time.

    LCD display and its control buttons provide a friendly operation interface for operator, which makes operator conveniently read information and set running parameter.

    3.1 Control buttons and LED

    Function Description Tag

    Enter into submenu/modify/confirm modification/scroll menu MUTE button When controller failure occurs, alarm buzzer sounding, press mute button, sound stop, LCD displays mute icon. Continuously press this button 2s, all LEDs lights up simultaneously.

    AUTO button/ LED The button is used for setting auto-operation mode. When controller is running in AUTO mode, LED above the button lights up. According to the remote start signal is active or not, to control generator start or stop.

    MAN button /LED The button is used for setting manual-operation mode. When controller is running in MAN mode, LED above the button lights up. The controller controls generator start and stop by pressing START and STOP buttons.

    START/ VALUE ASCEND + The button is used for MAN start Genset. When controller is setting in MAN-operation mode, press this button can start generator. When enter in parameters setting operation, this button is used for value ascend.

  • GU611A Controller Operation Manual

    9

    STOP/ RESET/ VALUE DESCEND - The button is used for MAN stop Genset. When controller is setting in MAN-operation mode, continuously press this button more than 2s can stop generator. If occur failure output, light press this button, the shutdown lockout can be cleared by controller. When enter in parameters setting operation, this button is used for value descend.

    FAILURE LED When controller occur warning, failure LED flash. When controller occur shutdown alarm, failure LED lights up.

  • GU611A Controller Operation Manual

    10

    4. Installation Guide 4.1 The dimensional drawing of install cutout on panel, shown as above

    attached. The controller is fixed by 2 special mounting fittings. The shock-proof equipment must be installed, if the enclosure that installed on controller is directly installed on Genset body or other heavy vibrant device. A readily accessible disconnect device shall be incorporated external to the equipment;

    4.2 Please see above 2.3 Typical Wiring Diagram for wiring connecting. 4.3 The installations of P-sensor and T-sensor for engine:

    1211GU611A CONTROLLER

    Port No.

    12Battery negative (unit enclosure)

    11Purpose

    Sensor Com. PortT-sensor/ temp switchP-sensor/ low oil pressure switch

    CAUTION z Pin no. 11 and 12 respectively for P-sensor or switch

    signal and T-sensor or switch signal input, either switch or sensor can be chosen. When sensor is used, can increase the cross section area of cable base on the practical condition, so that to reduce the cable resistance that from controller to engine, to make sure the accuracy of measured values both for oil pressure and temperature.

    z If the control system is simultaneously required for switches and sensors for both oil pressure and temperature, the Pin no. 11 and 12 can be respectively connected to P-sensor and T-sensor, and use another 2 configurable input ports to connect to oil pressure switch and temperature switch, and then matching parameters by setting.

  • GU611A Controller Operation Manual

    11

    5. Control and Operation Instruction The controller has 2 kinds of control mode: AUTO mode and MAN mode. 5.1 Operation Mode Setting:

    Operation Description

    Press AUTO button (continue 2s), LED above the button lights up; controller is running in AUTO mode.

    Press MAN button (continue 2s), LED above the button lights up; controller is running in MAN mode.

    NOTE: Only can select 1 mode from above 2 modes. 5.2 AUTO Control Process: The controller is running in AUTO mode. Mains normal, Mains supply: When Mains normal, means Mains voltage is under the range of the setting high and low limits, LED for Mains normal lights up, the timer for Mains Supply Delay begins count, when delay time out, the Mains closing relay making output, the transfer switch switches on Mains, power supply by Mains, the switch Aux. contact at Mains side closing, LED for Mains supply lights up.

    WARNING: LED for Mains normal lights up, means Mains voltage is under the range of the setting high and low limits; When LED for Mains normal do not light up, means Mains voltage is beyond the range of the setting high and low limits. Do not judge no Mains voltage by LED not lights up.

    NOTE: z The realization of above control procedure, is defines one of

    configurable input ports as Mains Switch Close, and connects the switch N. O. Aux. contract to this port.

    z In practical application, maybe none of the configurable input ports is defined for Mains Switch Close, here, LED for Mains supply lights on only expresses the Mains closing relay of controller making output. Under the condition, the alarm for Fail to Mains Supply is inactive, and the along function of start Genset also disable.

  • GU611A Controller Operation Manual

    12

    If Mains closing relay making output, the delay timer for fail to Mains supply begins, if controller does not detect that the switch auxiliary contact on Mains side is close, that is Fail to Mains Supply. The process of generator start supply: When Mains voltage failure, means detects that Mains voltage is exceeds the range of the setting high and low limits, or occur Fail to Mains Supply and the remote start signal is active, the controller implements following procedure: Start-delay timer begins count, when delay time out, if preset preheat function, preheat relay making output, the timer for preheat time begins count, when time expired, fuel relay takes action, the fuel solenoid of engine opened, after 300ms delay, the start relay making output, the start motor of engine switches on power, begin crank, when the running speed of engine is reach to the crank disconnect speed, controller stop start-output, the safety-on delay time begin count, before time out, if controller detects that parameters of Genset such as voltage, frequency, oil pressure, coolant temperature are normal, and no other failure, means Genset successfully start and running normal, LCD displays corresponding measuring parameters. After Gen voltage frequency resuming to normal, LED for voltage normal lights up, the timer for Gen supply-delay begins count, when time expired, Gen closing relay making output, transfer switch switches on Gen, power supply by Gen, the switch Aux. contact at Gen side closing, LED for Gen supply lights up.

    NOTE: z The start procedure carried out by Fail to Mains Supply, the

    timer for start-delay is inactive, directly enter into preheat procedure or fuel relay takes action.

    z When Mains voltage failure or remote signal is active, the timer for start-relay begins count. During counting, if remote start signal is inactive, or Mains voltage resume to normal, the start-relay stop counting immediately, controller stop start procedure and related output, recover to original standby status.

    z During the period of crank or idle, if remote start signal is inactive, or Mains voltage resume to normal, controller stop start procedure and related output, recover to original standby status.

    NOTE: z During crank, engine ignition, when the output frequency of

    alternator is reaches to preset frequency, start motor disconnect power. Or the start motor is disconnected power by one of the following reasons: the output voltage of alternator is reaches to 80% rating voltage; start time over. After the low oil pressure switch of engine opening, delay counting time out.

    z Controller can not implement idle procedure, when it detects that the frequency of generator is reached the preset level, or the oil pressure switch of engine is open.

  • GU611A Controller Operation Manual

    13

    CAUTION Since the crank disconnect signal of engine is from the output voltage frequency of generator, must make sure the output voltage is greater than controller measurable voltage during the period of generator crank attempt, to avoid the possible damage on start motor.

    NOTE: The realization of above control procedure, is defines one of configurable input ports as Gen Switch Close, and connects the switch N. O. Aux. contract to this port. In practical application, maybe none of the configurable input ports is defined as Gen Switch Close; LED for Gen supply lights on only expresses the Gen closing relay of controller making output at the time.

    If preset idle function, simultaneously the start relay making output, the relay which is defined for idle function making output, the timers for idle delay and safety-on time delay begins count together, the shorter delay will be displayed first, the following procedure as above. During crank counting time, engine can not igniting, and controller will not output start signal during crank intermission, and the Fail to Start Sign in LCD flashing at that time. Once crank intermission time out, controller will attempt to restart engine again. Above start phenomena repeat again and again until engine successful ignition and or reach the preset crank times. If any stop failures occur during start process, controller stops control output immediately, until failure eliminated and reset, then it can be operated again. Fail to start: When above start phenomena repeat again and again and over the preset crank times, controller will stop control output, failure LED for Fail to stop lights up, LCD displays Fail to stop icon.

    CAUTION If occur start failure, operator must check the whole Genset system to make sure failure reason, only after eliminating the failure can press STOP/RESET button to unlock fault-locked status, and restart the Genset.

    The processes of Mains resume, Mains supply and generator shutdown: When Mains voltage resume to normal, means detects that Mains voltage is under the range of the setting high and low limits, LED for Mains normal lights up, the timer for Mains supply delay begins counting, Gen closing relay breaking after time expired, Mains Closing relay making output, transfer switch switches on Mains, power supply by Mains, the switch Aux. contact at Mains side close, LED for Mains supply lights up. Simultaneously the Mains closing relay making output, the timer for cooling delay begins counting, when time expired, the fuel relay of controller takes action, breaking fuel solenoid immediately, generator stop and enter into standby status.

  • GU611A Controller Operation Manual

    14

    Fail to stop: When cooling-delay expired, the fuel relay of controller takes action, the timer for fail to stop delay begins counting, when time expired, if controller detects that the voltage and frequency of generator is greater than the internal setting value, or the oil pressure of engine is greater than the internal setting value, failure LED for Fail to stop lights up, LCD displays Fail to stop icon.

    NOTE: When occur fail to stop, except failures were removed and reset or can not restart generator.

    The conditions for generator auto start running: When controller under auto control mode, it will auto enter into start running procedure in the following 3 conditions: z Mails voltage failure; z Remote start signal is active; z Fail to Mails supply. When there are no configurable input ports can be defined as Remote Signal, when Mails voltage failure controller auto enter into start running procedure; When there are configurable input ports can be defined as Remote Signal, when remote start signal is active and Mains voltage failure controller auto enter into start running procedure, when Mails voltage failure but remote start signal is not active will not enter into start running procedure, but the Mains closing relay will be broken; When there are no configurable input ports can be defined as Mains Close Signal, the function of Fail to Mails Supply is not active. If generator starts running since occurs Fail to Mails Supply, when failure is removed and unlocked by pressing reset button, Gen closing relay is breaking, Mains closing relay making output, transfer switch switches on Mains, power supply by Mains. 5.3 The produce of MAN control: The controller is running in MAN mode. Mains normal, Mains supply: When Mains normal, means Mains voltage under the range of the setting high and low limits, LED for Mains normal lights up. Mains closing relay will not making output, switching transfer switch by MAN, switching on Mains, power supply by Mains, the switch Aux. contact at Mains side closing, LED for Mains supply lights up.

  • GU611A Controller Operation Manual

    15

    The process of generator start supply: Press START button, fuel relay takes action, the fuel solenoid of engine opened, after 300ms delay, the start relay making output, the start motor of engine switches on power, begin crank, when the running speed of engine is reach to the crank disconnect speed, controller stop start-output, the safety-on delay time begin count, before time out, if controller detects that parameters of Genset such as voltage, frequency, oil pressure, coolant temperature are normal, and no other failure, means Genset successfully start and running normal, LCD displays corresponding measuring parameters. After generator normal running, Gen closing relay will not making output, switching transfer switch by MAN, switching on Gen, power supply by Gen, the switch Aux. contact at Gen side closing, LED for Gen supply lights up.

    NOTE: When under MAN operation mode, to make LED indicators for Mains and Gen lights up, must define 2 configurable input port as Mains Switch Close and Gen Switch Close, and connect the N.O. Aux. contract of switch to the port, otherwise both LED indicators will not light up in any conditions.

    5.4 The start and stop processes of engine, which fuel solenoid is N. O. type: Start control process: When start running, the fuel relay of controller will not close, fuel solenoid no power, means the electromagnet of solenoid no action. Stop control process: When controller starts at stop control process, the fuel relay of controller is close, fuel solenoid on load, fuel solenoid take action, engine begins stop. After delay (same as fail to stop delay) fuel relay breaking, disconnect the power of fuel solenoid. Other control process same as engine fuel solenoid is N. C. type. 5.5 Idle function: When one of the configurable outputs is defined as Idle, controller has idle control function immediately. The idle control flow reference to the flow chart for start and stop.

  • GU611A Controller Operation Manual

    16

    5.6 Preheat function: When one of the configurable outputs is defined as Preheat, controller obtains preheat control function immediately. Controller has 3 optional preheat control modes: Mode 1 during preheat time, preheat relay making output. Mode 2 during preheat time, preheat relay making output until successfully

    ignition. Mode 3 during preheat time, preheat relay making output until safety-on

    delay expired. No matter setting at which mode, during crank attempt the preheat relay will not making output. The idle control flow reference to the flow chart for start and stop. The preheat relay making output, LCD displays the sign of preheat operating status:

  • GU611A Controller Operation Manual

    17

    5.7 Flow chart for start and stop

    T1 start delay T2 crank time T3 preheat time

    T4 safety-on time T5 idle time T6 fail to stop delay

    NOTE: When T4>T5 and engine is under the period of idle, the protection of low oil pressure will not operation; When T4

  • GU611A Controller Operation Manual

    18

    6. Measure and Display Data Mains phase voltage L1-N L2-N L3-N Mains line voltage L1-L2 L2-L3 L3-L1 Gen phase voltage L1-N Generator current I1 I2 I3 Frequency HZ Engine speed RPM (signal from generator frequency) Engine oil pressure BAR /PSI (signal from engine P-sensor) Engine coolant temperature /F (signal from engine T-sensor) Battery voltage Vdc Running hour h

    7. Warning and Shutdown Alarm 7.1 Warning (NOTE: Warns are non-critical failure conditions and do not affect the operation of the generator system, they serve to draw the operators attention to an undesirable condition and remove it to make sure system continuous running. When warns occur, the status indicator light flash, but failure will not be locked and the unit will not shutdown. Once failure removed warning indicator auto turn off.)

    Warning/ Description LCD Display Fail to Charge: if controller detects that voltage has fallen below the low battery warning value from the excitation contact of auxiliary AC charger after the safety-on timer has expired, failure indicator light flash, LCD displays Fail to Charge icon. Battery Low Voltage: if controller detects that battery voltage has fallen below the low battery warning value, failure indicator lights up. For example, low battery warning value preset as: 23.6V, when battery voltage falls below this value, LCD flashing low value icon. Battery High Voltage: if controller detects that battery voltage has exceeded the high battery warning value, failure indicator lights up. For example, high battery warning value preset as: 28.2V, when battery voltage exceeds this value, LCD flashing high value icon. Low Oil Pressure: if controller detects that the engine oil pressure has fallen below the low oil pressure warning value after the safety-on timer has expired, failure indicator light flash. For example, low oil pressure warning value preset as: 2.20BAR, when engine oil pressure falls below this value, LCD flashing low value icon.

  • GU611A Controller Operation Manual

    19

    High Temperature: if controller detects that engine coolant temperature has exceeded the high coolant temperature warning value, failure indicator lights up. For example, high coolant temperature warning value preset as: 95, when engine coolant temperature exceeds this value, LCD flashing high value icon. Overspeed: if engine speed exceeds the overspeed warning value, failure indicator lights up. For example, overspeed warning value preset as: 1600RPM, when engine speed exceeds this value, LCD flashing high value icon. Underspeed: if engine speed falls below the underspeed warning value after the safety-on timer has expired, failure indicator lights up. For example, underspeed warning value preset as: 1440RPM, when engine speed falls below this value, LCD flashing low value icon. High Current: if controller detects that the current of generator any phase output has exceeded the high current warning value after the safety-on timer has expired, failure indicator light flash. For example, high current warning value preset as: 850A, when the current of generator any phase output exceeds this value, LCD flashing high value icon for corresponding phase. High Voltage: if controller detects that the voltage of generator any phase output has exceeded the high voltage warning value after the safety-on timer has expired, failure indicator light flash. For example, rating voltage preset as: 220A, high voltage warning value preset as: 115%, when the generator output voltage exceeds this value, LCD flashing high value icon for corresponding phase. Low Voltage: if controller detects that the voltage of generator any phase output has fallen below the low voltage warning value after the safety-on timer has expired, failure indicator light flash. For example, rating voltage preset as: 220A, low voltage warning value preset as: 90%, when the generator output voltage falls below this value, LCD flashing low value icon for corresponding phase.

    Low Fuel Level: define a configurable switch as low fuel level used for warning input, when the input signal is active, failure indicator light flash. LCD flashing low fuel level icon.

    Fail to Mains Supply: define a configurable switch as Mains Close, when controller closing relay making output, if Mains close switch is inactive after fail to Mains supply delay has expired, means fail to Mains supply, the indicator for Mains Close on controller panel flash.

    Auxiliary Warning: define a configurable switch as warning input, when the input signal is active, failure indicator light flash. LCD flashing Aux. warning icon.

  • GU611A Controller Operation Manual

    20

    Note: To make warnings of low oil pressure and high coolant temperature active, must use P-sensor and T-sensor, when only use oil pressure switch and temperature switch, both warnings inactive.

    Note: z Controller continuously detects battery voltage during

    generator standby, the warnings of Battery Low Voltage/ Battery High Voltage are active.

    z During engine crank, the warning of Battery Low Voltage is inactive.

    Caution: Under the period of safety-on delay, some warnings (eg: underspeed, low voltage, low oil pressure) are inactive, the safety-on time must be carefully and properly set to make Genset has full protection.

    7.2 Shutdown Alarm (NOTE: shutdown failures immediately lock system and stop generator, it only can operate controller again after removing failures and press rest button to unlock)

    Failures/ Description LCD Display

    Fail to Start: if engine does not fire after the preset number of crank attempts has been made, means fail to start, failure LED lights up. LCD displays fail to start icon.

    Fail to Stop: if engine does not stop after the stop delay expires, failure LED lights up. LCD displays fail to stop icon.

    Emergency Stop: define a configurable switch as emergency stop input, when the input signal is active, controller immediately stop all relay control output except alarm, failure LED lights up. LCD displays emergency stop icon. Low Oil Pressure: if controller detects that the oil pressure level still falls below oil pressure alarm value or oil pressure switch is closing after the safety-on timer has expired, engine stop immediately, failure LED lights up. LCD displays low oil pressure icon.

  • GU611A Controller Operation Manual

    21

    High Temperature: if controller detects that engine coolant temperature has exceeded the high coolant temperature alarm value or temperature switch is closing, engine stop immediately, and failure LED lights up. LCD displays high temperature icon.

    Overspeed: if controller detects that engine speed exceeds the overspeed alarm value, engine stop immediately, and failure LED lights up. LCD displays overspeed icon.

    High Current: if controller detects that the current of generator any phase output has exceeded the high current warning value after the safety-on timer has expired, the engine will be shut down immediately, common failure LED illuminates, LCD alternately displays the code of the high voltage as the right side picture. High Voltage: After safety on delay times up, if the phase voltage is higher than the voltage limit, the engine will be shut down immediately, common failure LED illuminates, LCD alternately displays the code of the high voltage as the right side picture. Low VoltageAfter safety on delay times up, if the phase voltage is lower than the voltage limit, the engine will be shut down immediately, common failure LED illuminates, LCD alternately displays the code of low voltage as the right side picture.

    Low Fuel Level: define a configurable switch as low fuel level used for warning input, when the input signal is active, failure LED lights up. LCD displays low fuel level icon.

    Auxiliary Failure: define a configurable switch as failure input, when the input signal is active, failure LED lights up. LCD displays Aux. warning icon.

  • GU611A Controller Operation Manual

    22

    Note: z Engine speed signal is from generator output voltage

    frequency, is used for control and failure protection parameters, to the convenience of user, some data expressed by RPM, RPM=HZ*60/pair of poles.

    z The generator occur failure during its operating: stop immediately no delay after occurred high temperature, low oil pressure and overspeed; protection is active whatever has idle function or not when low oil pressure occurs during coolant delay.

    Caution: Under the period of safety-on delay, the protection of low oil pressure failure is inactive, to avoid non oil start engine, must make sure the oil is normal and the safety-on time shall be carefully and properly set for the first commissioning.

  • GU611A Controller Operation Manual

    23

    8. Parameters Setting 8.1 System Parameters: NO. Items Preset Value Range 1.1 CT ratio 100 1-2000

    1.2 voltage ratio 1.0 1.0-100.0

    1.3 rating voltage 220 45-9999VAC

    1.4 measure AC voltage 3 1-3 (3 3-phase 4 wires, 1 signal phase 2 wires) 1.5 begin control mode 0 0-1 / 0 (MAN) /1 (AUTO)

    1.6 oil pressure units 0 0-2 (0-BAR,1-PSI,)

    1.7 temperature units 0 0-2 (0-,1- ) 1.8 communication address 1 1-247

    1.9 resume to default

    1.10 on-line update

    1.11 page scroll time 0S 0-10S /0 (not used)

    NOTE: Begin Control Mode is used for the setting the begin control mode of controller when controller switches on power. When the parameter set at 1 and controller switches on power, controller will auto operating in AUTO control mode; When the parameter set at 0 and controller switches on power, controller will auto operating in MAN control mode.

    NOTE: Generator running speed is set by pair of poles, RPM=HZ*60/ pair of poles, when rating frequency is 50 HZ, if pole pairs set at 2, the running speed is 1500 rpm, if pole pairs set at 1 , the running speed is 3000 rpm.

  • GU611A Controller Operation Manual

    24

    8.2 Generator Parameters:

    NO. Items Preset Value Range 2.1 V low alarm 0 20-200% / 0 (not set) 2.2 V low warning 90% 20-200% / 0 (not set) 2.3 V high warning 115% 20-200% / 9999 (not set) 2.4 V high alarm 9999 20-200% / 9999 (not set) 2.5 HZ low alarm 45.0Hz 10.0-100.0Hz/ 0 (not set) 2.6 HZ high alarm 57.0Hz 10.0-100.0Hz / 999.9 (not set)2.7 I high warning 100% 20-200% / 9999 (not set) 2.8 I high alarm 150% 20-200% / 9999 (not set)

    2.9 I high failure type 0 0-1 (1-shutdown 0-electrical tripping) 2.10 Failure delay 10S 0-600S 2.11 Gen supply delay 5S 1-9999S 2.12 Gen breaking delay 5S 1-9999S

    8.3 Engine Parameters:

    NO. Items Preset Value Range 3.1 pair of poles 2 1-4 3.2 fuel mode 0 0-1 / 0(NC) /1 (NO) 3.3 T-sensor mode 3 0-10 / 0 (not use) 3.4 P-sensor mode 4 0-15 / 0 (not use) 3.5 start delay 10s 0-300 s 3.6 crank attempt 3 times 1-10 times 3.7 crank time 8S 0-30 S 3.8 crank rest 15S 0-300 S 3.9 crank disconnect 300RPM 1-9999 RPM 3.10 idle delay 0 0-9999s 3.11 preheat delay 3S 0-300 s 3.12 preheat mode 1 1-3 3.13 safety on delay 60S 0-600S 3.14 cooling delay 300S 0-600 S 3.15 fail to stop delay 20S 0-60S 3.16 underspeed alarm 0RPM 0-9999 RPM / 0 (not set)

  • GU611A Controller Operation Manual

    25

    3.17 underspeed warning 1440RPM 0-9999 RPM / 0 (not set)3.18 overspeed warning 1600 RPM 1-9999 RPM/ 9999 (not set) 3.19 overspeed alarm 1710 RPM 1-9999 RPM/ 9999 (not set) 3.20 low oil-press alarm 1.4BAR 0-45.0 BAR 3.21 low oil-press warning 2.2BAR 0-45.0 BAR 3.22 high temp warning 95 70-320/ 9999 (not set) 3.23 high temp alarm 105 70-320 / 9999 (not set) 3.24 low battery warning 8.0V 1-25.0V / 0 (not set) 3.25 high battery warning 28.0V 1-35.0V / 99.9 (not set) 3.26 charge V warning 8.0V 1-25.0V / 0 (not set)

    8.4 Input and Output Setting

    4.1 configurable input 1 8 0-12 (define code as follows) 4.2 configurable input 2 7 0-12 (define code as follows) 4.3 configurable input 3 12 0-12 (define code as follows) 4.4 input 1 delay 2S 0-60S 4.5 input 2 delay 2S 0-60S 4.6 input 3 delay 2s 0-60S 4.7 configurable relay 1 2 0-80 (define code as follows) 4.8 configurable relay 2 3 0-80 (define code as follows)

    NOTE: configurable input delay is only for 1 to 4 codes in 8.8. 8.5 Mains Parameters

    5.1 Mains V low 90% 20-200% / 0 (not set)

    5.2 Mains V high 115% 20-200% / 9999 (not set) 5.3 Mains HZ 50.0 Hz 50.0-60.0Hz

    5.4 M-supply delay 5S 1-9999S 5.5 M-failure breaking 5S 1-9999S

  • GU611A Controller Operation Manual

    26

    8.6 Calibration Menu

    6.1 Gen voltage V1 0 10.0% 6.2 Gen current I1 0 10.0% 6.3 Gen current I2 0 10.0% 6.4 Gen current I3 0 10.0% 6.5 Mains voltage V1 0 10.0% 6.6 Mains voltage V2 0 10.0% 6.7 Mains voltage V3 0 10.0% 6.8 oil pressure 0 10.0% 6.9 Coolant temp 0 10.0% 6.10 battery voltage 0 10.0%

    8.7 The optional items for PT-sensor:

    Code The brand model of P-sensor The brand model of T-sensor 0 not used not used 1 close for low oil pressure close for high temperature 2 open for low oil pressure open for high temperature 3 VDO 5 bar VDO 120 4 VDO 10 bar VDO 150 5 Datcon 7 bar Datcon 6 Murphy 7 bar Murphy 7 Define 1 Pt100 8 Define 2 Define 1 9 Define 3 Define 2 10 Define 4 Define 3 11 configurable (base on sensor data) Define 4 12 configurable (base on sensor data)

    Note: When controller leave factory, the optional model and function of P-sensor and T-sensor have been preset as above table, if the used sensor not listed in table, user can select the item of configurable, read-in sensor parameters to controller by software.

  • GU611A Controller Operation Manual

    27

    z Parameter table for P-sensor VDO 5 bar:

    VDO 10 bar

    Datcon 7 bar:

    Murphy 7 bar:

    Define 1

    Define 2

    P(Bar) 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5 P(PSI) 0 7.3 14.5 21.8 29.0 36.3 43.5 50.8 58.0 65.3 72.5R() 11 29 47 65 82 100 117 134 151 167 184

    P(Bar) 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0P(PSI) 0 14.5 29.0 43.5 58.0 72.5 87.0 101.5 116.0 130.5 145.0R() 10 31 52 71 90 106 124 140 155 170 184

    P(Bar) 0.0 0.7 1.4 2.1 2.8 3.4 4.1 4.8 5.5 6.2 6.9P(PSI) 0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0R() 240 200 165 135 115 95 78 63 48 35 25

    P(Bar) 0.0 0.7 1.4 2.1 2.8 3.4 4.1 4.8 5.5 6.2 6.9 P(PSI) 0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0R() 240 205 171 143 123 103 88 74 60 47 33

    P(Bar) 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0P(PSI) 0 14.5 29.0 43.5 58.0 72.5 87.0 101.5 116.0 130.5 145.0R() 15 31 49 66 85 101 117 132 149 164 178

    P(Bar) 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0P(PSI) 0 14.5 29.0 43.5 58.0 72.5 87.0 101.5 116.0 130.5 145.0R() 30 41 65 110 115 145 150 172 185 190

  • GU611A Controller Operation Manual

    28

    Define 3

    Define 4

    z Parameter table for T-sensor VDO 120

    VDO 150

    Datcon

    Murphy

    P(Bar) 0.0 1.7 3.4 5.2 6.9 8.6 10.3 P(PSI) 0 25 50 75 100 125 150 R() 21 36 52 72 84 100 120

    P(Bar) 0.0 1.0 2.0 3.0 4.0 5.0 6.0 6.5 7.0 8.0 9.0P(PSI) 0 14.5 29.0 43.5 58.0 72.5 87.0 94.3 101.5 116.0 130.5R() 251 195 155 127 107 88 72 65 61 54 48

    T() 40 50 60 70 80 90 100 110 120 130 140T() 104 122 140 158 176 194 212 230 248 266 284R() 291 197 134 97 70 51 38 29 22 18 15

    T() 50 60 70 80 90 100 110 120 130 140 150T() 122 140 158 176 194 212 230 248 266 284 302R() 322 221 155 112 93 62 47 37 29 23 19

    T() 40 50 60 70 80 90 100 110 120 130 140T() 104 122 140 158 176 194 212 230 248 266 284R() 900 600 400 278 200 141 104 74 50 27 4

    T() 40 50 60 70 80 90 100 110 120 130 140T() 104 122 140 158 176 194 212 230 248 266 284R() 1029 680 460 321 227 164 120 89 74 52 40

  • GU611A Controller Operation Manual

    29

    PT100

    Define 1

    Define 2

    Define 3

    Define 4

    T() -100 -50 0 20 40 60 80 100 150 200 300T() -148 -58 32 68 104 140 176 212 302 392 572R() 60 81 100 108 116 123 131 139 157 176 212

    T() 20 30 40 50 60 70 80 90 100 110 120T() 68 86 104 122 140 158 176 194 212 230 248R() 900 600 420 282 152 113 86 62 48 30

    T() 30 50 60 70 80 90 100 110 120T() 86 122 140 158 176 194 212 230 248R() 980 400 265 180 125 90 65 50 38

    T() 20 30 40 50 60 70 80 90 100 110 120T() 68 86 104 122 140 158 176 194 212 230 248R() 805 540 380 260 175 118 83 58 42 30 21

    T() 28 35 40 50 60 70 80 90 95 98 T() 82 95 104 122 140 158 176 194 203 208 R() 579 404 342 250 179 136 103 77 67 63

  • GU611A Controller Operation Manual

    30

    8.8 The optional items for configurable input: Code Optional Function NOTE

    0 not used 1 warning (active immediately) low level is active 2 alarm (active immediately) low level is active

    3 warning (active after safety-on delay) low level is active

    4 alarm (active after safety-on delay) low level is active

    5 low oil pressure low level is active 6 high temperature low level is active 7 emergency stop low level is active 8 remote start low level is active 9 Mains switch close low level is active 10 Gen switch close low level is active 11 low fuel level low level is active 12 lamp test low level is active

    8.9 The optional items for configurable output: Code Failure Type Define Code Failure Type Define

    0 Not used 1 Over current tripping 2 Alarm 3 Warning 4 Idle 0 (NC) 5 Preheat mode 6 Speed up 7 Reserved 8 Fuel pump control 9 Running 10 System in AUTO mode 11 Reserved 12 System in MAN mode 13 Reserved 14 Idle 1 (NO) 15 Fail to Mains close (within 5s) 16 Fail to Gen close (within 5s) 17 Fail to start

    Note: Define one of the configurable outputs as Speed Up, after controller detects that engine is successfully crank, speed up relay making output; if has idle function, then speed up relay making output after idle delay expired.

  • GU611A Controller Operation Manual

    31

    9. LCD Display and Menu System

    Adopt TN type LCD displays data information, and LCD has background-light

    function, after pressing any buttons the background-light will auto turn off in a

    certain time. In normal operating status, auto scroll page to cycle display each measuring data, also can press scroll to view each measuring data, when

    failure occurs, LCD displays the corresponding failure icon.

    Continuously press button 2s in any page enter into setting status, you can use or in the same grade menu to scroll page at that moment, press again enter into submenu, select the desired item to be modified, press or enter into modify, displays 0 0 0 0 when prompt key in password, you can use or to modify value at that moment, press move to modify lower value, the first value will be displayed as asterisk * after moved to right, press again for exit after the password was set to 2213, and parameters have been changed, otherwise prompted key in password again, Continuously press button 2s after modification can exit the setting status. 9.1 LCD displays measuring data: When Mains normal, Mains supply and generator standby, cycle displays each measuring data:

    When generator operating, cycle displays each measuring data:

  • GU611A Controller Operation Manual

    32

    9.2 Setting running parameters For example: (setting current transformer rate at 1000 /5, then CT should be set at 200)

    Operation Description

    Continuously press 2s, enter into parameters setting menu, then LCD display:

    press , then LCD display:

    press , prompt key in password: (2213), then LCD display:

    Press or change parameter, change at 200, then LCD display:

    After changing press to confirmthen press , then LCD display:

    Press again for quit, or continuously press more that 2s also can quitthen LCD display:

    For example: (setting controller crank attempt at 2)

    Operation Description

    Continuously press 2s, enter into parameters setting menu, then LCD display:

    Press 28 times and then press , then LCD display:

    press , prompt key in password, then LCD display:

    Key in modified password: (2213), press , then LCD display:

  • GU611A Controller Operation Manual

    33

    Press or change parameter, change at 2, Press confirm change, and then continuously press

    2s can quit parameters setting menu.

    For example: (resume all parameters of controller to factory default)

    Operation Description

    Continuously press 2s, enter into parameters setting

    menu, then LCD display:

    Press 8 times again, then LCD display:

    press , prompt enter password, key in modified password: (2213)

    Press recover default, continuous press 2s

    can quit parameters setting menu.

    For example: (set controller as online program mode)

    Operation Description

    Continuously press 2s, enter into parameters setting menu,

    then LCD display:

    Press 9 times, then LCD display:

    press , prompt enter password, key in modified password: (3132)

    Press again enter into program mode, in this mode the

    power supply must be make sure normal, after connecting to the

    communication line, using special program software correctly

    duplication, controller will auto repeat reset action, or will not quit

    this status, until switch off plant supply.

  • GU611A Controller Operation Manual

    34

    10. Preparation before Start the Controller

    10.1 Make sure controller is fixed well and its install ambient meet requirements. 10.2 Confirm all wiring connections of controller are meet electric specification and

    corresponding to 2.3 typical wiring diagram. Especially need confirm DC supply source has added fusing element to protect, and correct polarity. Otherwise, it maybe damage controller.

    10.3 We recommend mounting E- stop button in external, connecting E-stop

    signal input terminal to the N. O. contact of E- stop button, and another terminal of contact connected to the negative of battery source.

    10.4 Switch on DC plant supply, make sure the preset parameter meet practical

    condition, such as current ratio, P-sensor mode, T-sensor mode, etc. 11. Technical Parameters

    DC supply: 8.0V to 35V continuous Cranking drop outs: 0V for 100mS, assuming dc supply was at least 10V before dropout and recovers to 5V Max. operating current: @12V 180mA, @24V 90mA Standby current: TBA. AC input voltage: phase voltage15-300 Vac RMS (AC frequency 40 Hz) AC input frequency: 3-70Hz (voltage 15V) Accuracy class: 1% Aux Control relay output: 3A/30Vdc Start relay output: 3A/30Vdc Fuel relay output: 3A/30Vdc Protection: IP65 (when correctly installed) Operating ambient temperature: -20 to 70 Storage ambient temperature: -30 to 80

    Version061B090724