hart principle & application
TRANSCRIPT
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
1
Topic
HART Multiplexer&
Application
HART Multiplexer
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
2
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
3
What is HART HART Multiplexer
Highway Addressable Remote Transducer
HART is the acronym for
HART is a fully open and de-factocommunication protocol for process industriesAlmost 75%+ field transmitters are HART capable
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
4
Communication Modes HART Multiplexer
HART is a MASTER-SLAVE Communication Protocol
SLAVE device communication isinitiated by MASTER device
SLAVE can be a Field Device andMASTER can be a DCS/PLC/PC/HHT
2 MASTERS is allow in the HART loop
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
5
Communication Modes HART Multiplexer
HART also allow Burst Mode communication
Burst Mode allow faster communication(3-4 data update per second)
SLAVE continuously send reply messageuntil MASTER instruct SLAVE to stopbursting
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
6
HART Physical Layer HART Multiplexer
HART communication protocoluse BELL 202 telephonecommunication standardBELL 202 is a FSK technology
Super-impose sine wave on conventional4/20 mA signal
LOGIC 1 1,200 HzLOGIC 0 2,200 Hz
Communicationspeed (baud rate)= 1.2 kbps(1,200 baud)
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
7
HART Physical Layer HART Multiplexer
-0,5 mA
+0,5 mA
TimeFSK 1,200 Hz 2,200 HzLOGIC “0”“1”
4/20 mADC current
1/1,200 sec
HART uses Frequency Shift Keying to encodedigital information on top of the 4/20 mA analog signal
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
8
HART Physical Layer HART Multiplexer
-0,5 mA
+0,5 mA
Time
4/20 mADC current
1/1,200 sec
AB
The current modulation for “A” is positive cycleand “B” is negative cycle. The resultant current or average current is zero. This meaning the FSK current modulation will not disturb the 4/20 mA DC current.
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
9
HART Load Requirement HART Multiplexer
HART protocol has a min. sensitivity of 200 mV p-p.This also means that for 1 mA p-p (+0.5 mA to –0.5 mA) FSK current modulation, min. load is 200 according to Ohm’s Law.
HART specified load requirement for the loop
230 … 1,100
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
10
HART Network: HART Multiplexer
HART Multiplexer
AI device PLC/DCS
orAO device
HART Multiplexermax. 7,905 channelsfor 1 PC
PC running maintenance software
KFD2-HMM-16ON
13 14 1519 20 2116 17 18
ON
OptionalIS barrier
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
11
HART Commands HART Multiplexer
HART Commands
Universal Common Practice Device-Specific
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
12
HART Benefits HART Multiplexer
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
13
HART Product Overview HART Multiplexer
P+F HART Multiplexer Oil & Gas
Petrochemical
Pharmaceutical
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
14
HART Product Overview HART Multiplexer
P+F HART Multiplexer
Max. baud rate at RS-485 com line: 38.4 kbps
Master-slave design for cost effectiveness
Max. 7,905 channels for 1 PC(255x31=7,905 channel)
Stand alone or retrofit using FI- interfaceboard solution
Customized solution using motherboardwith IS barrier
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
15
HART Product Overview HART Multiplexer
DIN Rail
KFD0-HMS-16 KFD0-HMS-16
KFD2-EB2
4 AT
789 10 1112 13 14 15
1 23 4 5 6
!
KFD2-HMM-16
ON
13 14 1519 20 21
16 17 18
ON
24 Vdc
14 way ribbon cable
Up to 15 HART Mux Slaves per Master
26 way ribbon cable
HART signals from HART Field device -16 HART field devices per Slave and Master
RS 485 connection Up to 31 HART Mux Masters
RS-232RS 485 Converter
AMSCornerstone
Valve Manager
Master Slave
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
16
Ex
Safe Area
or
KFD0
-HM
S-16
SlaveMaster
KFD2
-HM
M-1
6
ON
13
14
1519
20
21
16
17
18
ON
KFD2-STC4-Ex2
PWR
7 8 9 10 111213 14 15
1 23 4 5 6
KFD2-STC4-Ex2
PWR
7 8 9 10 111213 14 15
1 23 4 5 6
KFD2-STC4-Ex2
PWR
7 8 9 10 111213 14 15
1 23 4 5 6
KFD2-STC4-Ex2
PWR
7 8 9 10 111213 14 15
1 23 4 5 6
KFD2-STC4-Ex2
PWR
7 8 9 10 111213 14 15
1 23 4 5 6
KFD2-STC4-Ex2
PWR
7 8 9 10 111213 14 15
1 23 4 5 6
KFD2-STC4-Ex2
PWR
7 8 9 10 111213 14 15
1 23 4 5 6
KFD2-STC4-Ex2
PWR
7 8 9 10 111213 14 15
1 23 4 5 6
Motherboardwith Barriers
Motherboard Solutions:
• single or dual channel barriers
• 4, 8, 12 and 16 barriers/motherboard
• customized system connectors
• redundant power supply
System Connector to DCS/PLC
PC
24 Vdc
Redundant 24 Vdc
Motherboard HART Multiplexer
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
17
Overview of P+F HART Multiplexer
31 HART Multiplexers Master
465 HART Multiplexers Slave
7,905 HART transmitters
PC
HART
Maintenance software supported :‘AMS’, ‘Valve Manager’, ‘Cornerstone’, ‘PACTware’ etc
Legends :-HMM -HART Multiplexer masterHMS -HART Multiplexer slaveHART Tx -HART TransmitterPC -IBM compatible Personal ComputerHART -Highway Addressable Remote Transducer developed by Rosemount in mid 1980’s using FSK ( Frequency-Shift-Keying,
Bell 202 standard ) technology superimposed on conventional 4 - 20 mA signal
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
18
Overview of P+F HART Multiplexer
1. One FI-PFH-XXXXXX connector can be connected up to 16 HART transmitters/positioners.
2. One HART Multiplexer Slave KFD0-HMS-16 can be connected to one FI-PFH-XXXXXX connector through 26 way ribbon cable.
3. One HART Multiplexer Master KFD2-HMM-16 can also be connected to one FI-PFH-XXXXXX connector through 26 way ribbon cable.
4. One HART Multiplexer Master KFD2-HMM-16 can be connected to 15 HART Multiplexers Slave KFD0-HMS-16 through 14 way ribbon cable.
5. One HART Multiplexer Master KFD2-HMM-16 with 15 HART Multiplexers Slave KFD0-HMS-16 can be
connected up to 255 HART transmitters. {( 1+15 ) x 16 } -1= 255.
6. Up to 31 HART Multiplexers Master KFD2-HMM-16 can be connected through RS-485 physical layer. Using RS-485/RS-232 converter, it can communicate through Personal Computer.
7. One Personal Computer can communicate to 7,905 HART transmitters/positioners [ {( 1+15 ) x 16 } -1 ] x 31 = 7,905 using 31 HART Multiplexers Master KFD2-HMM-16 and 465 HART Multiplexers Slave KFD0-HMS-16.
8. Three most popular maintenance software supported are, ‘AMS’, ‘Valve Manager’ & ‘Cornerstone’.
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
19
Overview of P+F HART Multiplexer
16x HART Tx
16x HART Tx
SMART AIN
26 wayribbon cable
SMART AIN
26 wayribbon cable
PC Serialcom port
RS-232( max. 16 m )
HART
HMM
HMS# 1
# 1
14 way ribbon cable
HMM
HMS# 1
# 0
14 way ribbon cable
2 corecable
RS-485
RS-232
2 corecable
RS-485/RS-232converter
2-wire RS-485 ( max. 1 km )
24Vdc PS 24Vdc PS
Patch Board
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
20
ON
13 14 1519 20 21
ON
1 2 3
4 5 6
7 8 910 11 1213 14 15
RS - 232
RS - 485
KFD2-EB2
!
4 AT
24 Vdc
Converter
KFD0-HMS-16
Power Rail Insert
14 wayribbon cable
KFD0-HMS-16
HART ® connector to Patch Board / Flexible Interface Board
DIN Rail
26 way ribbon cable
Up to 15 HART ® Mux Slaves per Master
CornerstonePACTware
AMS
26 way IDC 26 way IDC 26 way IDC
KFD2-HMM-16
16 17 18
P+ F HART Multiplexer System Components
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
21
P+F HART Multiplexer Master type KFD2-HMM-16Communication Baud Rate & Address Setting
KFD2-HMM-16
ON
13 14 1519 20 21
16 17 18
ON
RS485 baud rate setting(3 bits)
RS485 address setting(5 bits)
ON
1 2 3 4 5 6 7 8
9.6 kbps 19.2 kbps
(recommended)
38.4 kbpsON
1 2 3
ON
1 2 3
ON
1 2 3
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8 ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
ON
4 5 6 7 8
Addr 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Addr 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
HART Multiplexer MasterKFD2-HMM-16(.1S)
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
22
P+F HART Multiplexer Slave type KFD0-HMS-16Address Setting
SLAVE ID.
Rotary switch for slave address
HART Multiplexer SlaveKFD0-HMS-16
KFD0-HMS-16
Addr 0 = not usedAddr 1 = 1Addr 2 = 2
Addr 14 = EAddr 15 = F
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
23
Wiring Diagram for P+F HART MultiplexerUsing FI-PFH-NS0137 for Intrinsically Safe Application
Case # 1Wiring for 2-wire HART transmitter
+
-
+
-
Channel 1
Channel 16
16x
Patch BoardAnalog Input modulefrom PLC/DCS
In 1 250 B1A1
C1D1
4-20mA+HART
In 16com
com
250 B16A16
C16D16
4-20mA+HART
16x 16x
14+ 15-
8+7-
1+3-
Supply 24 Vdc
KFD2-STC3-Ex1
4-20mA+HART
14+ 15-
8+7-
1+3-
Supply 24 Vdc
KFD2-STC3-Ex1
4-20mA+HART
Hazardous Area Safe Area
HART Positionereg. Rosemount 3044
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
24
Wiring Diagram for P+F HART MultiplexerUsing FI-PFH-NS0137 for Intrinsically Safe Application
Patch BoardAnalog Output modulefrom PLC/DCS
Out 1++
- 4-20mA+HART
B1A1
C1
D14-20mA+HART
Out 16+Out 16-
Out 1-
+
- 4-20mA+HART
B16
A16
C16
D164-20mA+HART
Channel 1
Channel 16
16x16x 16x
+
-
+
-
11+ 12-
8+7-
1+2-
Supply 24 Vdc
KFD2-SCD-Ex1.LK
11+ 12-
8+7-
1+2-
Supply 24 Vdc
KFD2-SCD-Ex1.LK
HART Positionereg. Fisher DVC 5000
Hazardous Area Safe Area
Case # 2Wiring for HART Positioner
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
25
Wiring Diagram for P+F HART MultiplexerUsing FI-PFH-NS0137 for Non Intrinsically Safe Application
Case # 3Wiring for 2-wire HART transmitter
FI-PFH-NS0137Analog Input modulefrom PLC/DCS
+24 VdcIn 1
250
+
- 4-20mA+HART
A1B1
D1
C14-20mA+HART
+24 VdcIn 16
com
com
250
+
- 4-20mA+HART
A16B16
D16C16
4-20mA+HART
Channel 1
Channel 16
16x
16x16x
26-wayIDC connectorto HART multiplexermaster/slave
126 mm
110
mm
1
16
1
PEPPERL+FUCHSFI-PFH-NS0137
11
AB C
D
1616 16
AB C D
Note:-FI-PFH-NS0137 with de-couplingCapacitor on terminal A1~ A16.
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
26
Wiring Diagram for P+F HART MultiplexerUsing FI-PFH-NS0137 for Non Intrinsically Safe Application
Case # 4Wiring for HART current source
+
- 4-20mA+HART
+
- 4-20mA+HART
Channel 1
Channel 16
16x
FI-PFH-NS0137Analog Input modulefrom PLC/DCS
In 1 250 B1A1
C1D1
4-20mA+HART
In 16com
com
250 B16A16
C16D16
4-20mA+HART
16x 16x
+
-
+
-
26-wayIDC connectorto HART Multiplexermaster/slave
126 mm
110
mm
1
16
1
16
1 1
16 16
PEPPERL+FUCHSFI-PFH-NS0137
AB C
D
Note:-FI-PFH-NS0137 with de-couplingCapacitor on terminal A1~ A16.
AB C D
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
27
Wiring Diagram for P+F HART MultiplexerUsing FI-PFH-NS0137 for Non Intrinsically Safe Application
Case # 5Wiring for HART Positioner
FI-PFH-NS0137Analog Output modulefrom PLC/DCS
Out 1++
- 4-20mA+HART
B1A1
C1
D14-20mA+HART
Out 16+Out 16-
Out 1-
+
-4-20mA+HART
B16A16
C16D16
4-20mA+HART
Channel 1
Channel 16
16x16x 16x
+
-
+
-
26-wayIDC connectorto HART Multiplexermaster/slave
126 mm
110
mm
1
16
1
16
1 1
16 16
PEPPERL+FUCHSFI-PFH-NS0137
AB C
D
Note:-FI-PFH-NS0137 with de-couplingCapacitor on terminal A1~ A16.
A B C D
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
28
HART Software HART Multiplexer
Fisher-Rosemount Applied Systems Technology
Pepperl+Fuchs
P+F and ELCON HART Multiplexerare compatible with major software package
supplier
Neles Automation
?Yokogawa
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
29
AMS Display Panel HART Multiplexer
Directory-like HART device list
Table-like detail parameters
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
30
Cornerstone Display Panel HART Multiplexer
HART device list
Detail parameters
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
31
Valve Manager Display Panel
HART Multiplexer
HART device list
Detail parameters
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
32
PRM Display Panel
HART Multiplexer
Detail parameters
HART device list
PEPPERL+FUCHS P
RO
CES
S A
UTO
MA
TIO
N
33