healthcare life safety compliance - hcpro · the type that nfpa 80 (standard for fire doors and...
TRANSCRIPT
Assessing fire door maintenance
With the increased scrutiny that Joint Commission
surveyors and CMS state agency inspectors are providing
to fire doors, it is a sure bet that they will find a prob-
lem or two in facilities that have older door assemblies
in fire-rated barriers. Self-assessments for life safety
compliance often suffer from tunnel vision on the as-
sessor’s part, and fire doors in particular are frequently
overlooked.
One of the more common issues with older fire
doors is replacement hardware. Most (if not all) swing-
ing fire-rated doors in healthcare institutions today are
the type that NFPA 80 (Standard for Fire Doors and Fire
Windows, 1999 edition) refers to as “swinging doors
with builders hardware.” This means that the individ-
ual components of the fire door assembly are listed by
an independent testing organization, such as Under-
writers Laboratories (UL) or Intertek, as opposed to the
overall assembly being listed. As such, the “builder”
may select different types of listed components to fit
his or her design parameters. Since the individual com-
ponents are listed, they can be replaced with similarly
listed components (that are not necessarily the same
make or style) as the original components wear out or
fail. As an example, if a fire door assembly is originally
installed with
a Norton door
closer, and some
time later the
door closer fails,
the organization
may replace the
Norton closer
with an LCN
closer as long as the latter is listed for fire-rated door
assemblies.
Sometimes, in fact, it’s necessary to switch component
styles when a device fails. The ori ginal-style devices may
no longer be available, meaning the only solution may
be to install a device of a diffe rent brand. However, door
closers’ mounting hole patterns do not always match
up across brands, which may result in unfilled holes on
the fire door. This scenario is actually quite common for
older facilities.
Naturally, facility managers with this problem often
wonder what to do with the remaining holes in their
fire-rated doors. Until recently, the only option was to fill
those holes with steel fasteners, or fill the screw or bolt
holes with the same material as the door. Now there is
a new product on the market that can easily solve this
problem without resorting to the use of unsightly steel
bolts and nuts.
“We discovered the most common issues with fire
door inspectors were they are finding holes in doors
where hardware was removed,” says Gene Redahan,
vice president of operations for Fire Door Solutions in
Dothan, Ala. “There were either bare holes or some were
IN THIS ISSUE
p. 4 Main drain testIs this test really required? Guest columnist Bryan Galloy, MBA, CSP, CHFM, explores the answer.
p. 6 Addressing bottom rods What should facilities managers know about bottom rods on fire-rated doors? Read more inside.
p. 10 Questions & Answers This month’s Q&A talks about soiled utility rooms, dead bolts on psych rooms, and more.
p. 12 Quick tip This month’s quick tip is a sample tool for addressing main drain testing.
December 2012 Vol. 14, No. 12
The newsletter to assist healthcare facility managers with fire protection and life safety
HealtHcare life Safety compliance
“ We discovered the most
common issues with fire
door inspectors were they
are finding holes in doors
where hardware was
removed.”
—Gene Redahan
Page 2 Healthcare Life Safety Compliance December 2012
© 2012 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978-750-8400.
filled with wood putty, firestop, or even automotive
body fillers.”
Redahan explains that fire door inspectors were citing
these situations when they found them, but the inspec-
tors had no suggestions on how to repair the doors,
other than steel bolts.
“Upon doing some research, we found there was
nothing out there that had been tested and listed to
be used in that particular application,” says Redahan.
“It certainly makes sense that firestopping sounds like
it would work, because it is able to be used in fire-rated
walls. But there was nothing that had been tested in that
application.”
Redahan saw an opportunity to solve this problem,
and worked with his associates to develop a new style of
firestop caulk for fire-rated doors.
“So what we did, we took the basic firestop and did
our own testing with it and saw that it would hold up
to the heat but would not survive the hose stream test,
which is one of the requirements of NFPA 252,” he
explains. “So we took the firestop formula and tweaked
it and made a few changes here and there, and tested
it again. Once we were able to get past our testing, we
then took it to Intertek and had them test it to be used
in those applications of wood fire doors rated up to
90 minutes.”
Intertek, which also goes by the name of Warnock
Hersey, is an approved testing laboratory, similar to UL,
and tests to the same exact standards as UL does.
“We were tested to NFPA 252 (2012 edition), UL
10C (2009 edition), UL 10B (2009 edition), and CAN
S104 (1985 edition), which is the Canadian equiva-
lent,” says Redahan. “We met all those requirements
for those applications. Our product, as it was applied
in holes up to 3/4-inch diameter in fire-rated doors,
underwent 90 minutes in the furnace with the tem-
peratures mandated by NFPA, and then withstood the
hose stream test, which is also mandated by the same
codes.”
According to product literature, Fire Door Solutions’
caulk is a commercial-quality intumescent, noncombus-
tible fire-, smoke,- and draft-stopping sealant. The caulk
is water-based, can withstand temperatures of 3,000ºF
for up to eight hours, and can be safely removed with
soap and water prior to curing.
Redahan notes that the individual applying the prod-
uct is not required to be certified or licensed.
“NFPA 80 only requires the person making repairs on
fire-rated doors to be knowledgeable,” he says. “We’re
not creating new penetrations; we’re not drilling new
raceways or anything like that. We’re simply doing the
same thing as you would if you’re putting a steel bolt
Managing Editor: Matt Phillion, CSHA [email protected]
Senior Editor: Brad Keyes, CHSPSenior Consultant
Keyes Life Safety
Compliance
www.keyeslifesafety.com
Healthcare Life Safety Compliance (ISSN: 1523-7575 [print]; 1937-741X [online]) is published monthly by HCPro, Inc., 75 Sylvan St., Suite A-101, Danvers, MA 01923. Subscription rate is $289 for one year and includes unlimited telephone assistance. Single copy price is $25. Healthcare Life Safety Compliance, P.O. Box 3049, Peabody, MA 01961-3049. Copyright © 2012 HCPro, Inc. All rights reserved. Printed in the USA. Except where explicitly encouraged, no part of this publication may be reproduced, in any form or by any means, without prior written consent of HCPro, Inc., or the Copyright Clearance Center at 978-750-8400. Please notify us immediately if you have received an unauthorized copy. For editorial comments or questions or for technical support with questions about life safety compliance, call 781-639-1872 or fax 781-639-7857. For renewal or subscrip-tion information, call customer service at 800-650-6787, fax 800-639-8511, or email [email protected]. Occasionally, we make our subscriber list available to selected companies/vendors. If you do not wish to be in cluded on this mailing list, please write to the marketing department at the address above. Opinions expressed are not necessarily those of HLSC. Mention of products and services does not constitute endorsement. Advice given is general and based on National Fire Protection As-sociation codes and not based on local building or fire codes. No warranty as to the suitability of the information is expressed or implied. Information should not be construed as engineering advice specific to your facility and should not be acted upon without consulting a licensed engineer, architect, or other suitable professional. Final acceptability of such information and interpretations will always rest with the authority having jurisdiction, which may differ from that offered in the newsletter or otherwise. Advisory board members are not responsible for information and opinions that are not their own.
Editorial Advisory Board Healthcare Life Safety Compliance
Henry KowalenkoSupervisor, Design Standards UnitOffice of Healthcare Regulation, IL Department of Public Health Chicago, Ill.
Peter LeszczakNetwork 3 Fire Protection EngineerU.S. Department of Veterans Affairs West Haven, Conn.
David MohilePresidentMedical Engineering Services, Inc. Leesburg, Va.
James MurphyConsultantThe Greeley Company Danvers, Mass.
Thomas SalamoneDirector of EC and Regulatory ComplianceGannett Fleming Yonkers, N.Y.
William Wilson, CFPS, PEMFire Safety CoordinatorBeaumont Hospitals Royal Oak, Mich.
James R. Ambrose, PETechnical Director, HealthcareCode Consultants, Inc. St. Louis, Mo.
Frederick C. Bradley, PEPrincipalFCB Engineering Alpharetta, Ga.
Michael Crowley, PESenior Vice President, Engineering ManagerRolf Jensen & Associates, Inc. Houston, Texas
Joshua W. Elvove, PE, CSP, FSFPEFire Protection EngineerAurora, Colo.
A. Richard FasanoManager, Western OfficeRussell Phillips & Associates, LLC Elk Grove, Calif.
Burton Klein, PE PresidentBurton Klein Associates Newton, Mass.
December 2012 Healthcare Life Safety Compliance Page 3
© 2012 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978-750-8400.
through the hole. We’re just filling the hole, and there
are no tricks to it.”
Fire Door Solutions also has another product, called
the Thru-Bolt, that fills holes in wood and metal fire-
rated doors.
“The Thru-Bolt is another product that we saw a need
for,” says Redahan. “When we went through hospitals,
we would see bolts used to fill a hole where a closer was
removed. It was unsightly.”
Facility maintenance people were installing bolts,
nuts, and washers in open holes to comply with NFPA
80 requirements. “Aesthetically, it did not look good,”
says Redahan. “They would cut off the excess amount of
the bolt. We decided there needs to be a solution where
you can fill the hole and would be paintable.”
So Redahan and his associates went back to the draw-
ing board to develop a product that could be used by
maintenance staff.
“We designed a stainless steel male/female-type bolt
that screws into itself and is flat on both ends,” says
Redahan. “Once installed in the door, it screws into itself.
It is a much better-looking product.”
According to Redahan, the Thru-Bolt may be used in
steel metal rated doors and is available in diameters up
to 1/2 inch.
Frequent inspections of fire-rated doors will become
a common practice for all hospitals as soon as the 2012
edition of the Life Safety Code® (LSC) is adopted. How
facilities will track those inspections is not stated by the
new LSC, but Fire Door Solutions, along with its part-
ners, has developed a fire door assembly inspection pro-
gram that is automated and entirely cloud-based.
“We noticed a need for affordable inspection
software, not only for fire door inspection companies
but also for facilities that plan to do the inspections on
their own,” says Redahan. “The system is completely
cloud-based, meaning all of the information is stored in
servers online. As long as you have an Internet con-
nection, the program can be accessed from any com-
puter. The software is Android-based and works with a
supplied tablet. The software includes reports that are
available for the [authority having jurisdiction] at any
time. The initial cost of the software includes a tablet,
QR codes, and a year’s worth of support.”
With the pending adoption of the 2012 LSC (see the
November 2012 issue of HLSC for more on this topic),
fire door inspections will require healthcare organiza-
tions to develop a strategy for testing and inspecting their
doors. Specifically, inspections should seek answers to
the following questions:
➤ Are the door and frame free from holes and breaks in
all surfaces?
➤ Are the glazing, vision light frames, and glazing beads
intact and securely fastened?
➤ Are the doors, hinges, frame, hardware, and thresh-
old secure, aligned, and in working order with no vis-
ible signs of damage?
➤ Are there any missing or broken parts?
➤ Is the clearance from the door edge to the frame no
more than 1/8 inch?
➤ Is the door undercut no more than 3/4 inch?
➤ Does the active door leaf completely close when
operated from the full open position?
➤ Does the inactive leaf close before the active leaf
when a coordinator is used?
➤ Does the latching hardware operate and secure the
door in the closed position?
➤ Is the door assembly free from auxiliary hardware
items that could interfere with its operation?
➤ Has the door been modified since it was originally
installed?
➤ If gasketing and edge seals are installed, have they
been verified for integrity and operation? n
Contact Managing Editor Matt Phillion, CSHA
Telephone 781-639-1872, Ext. 3742
E-mail [email protected]
Questions? Comments? Ideas?
Page 4 Healthcare Life Safety Compliance December 2012
© 2012 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978-750-8400.
Editor’s note: The following article was written by guest
columnist Bryan Galloy, MBA, CSP, CHFM, fire and life safe-
ty manager for MD Anderson Cancer Center in Houston.
An understanding of the intent of NFPA codes and
standards is something a fire safety professional must
possess. In today’s world, where operational and financial
efficiencies are important factors to the E suite, fire safety
professionals must balance the effort needed to perform
required inspections, maintenance, and testing while en-
suring fire safety systems provide their designed life safety
protection without fault. This article will discuss how
main drain tests in most high-rise buildings that have
combined sprinkler/hose standpipe systems with large
supply pipes (6 inches diameter or greater) may not be as
effective of a test as the writers of the standards intended.
For systems connected to a fire pump that is fed from a
supply tank (which, in turn, is automatically refilled by a
municipal water supply), main drains provide no added
assurance of the system’s reliability.
A safety professional once told me, “NFPA codes and
standards are written with words, and words have mean-
ings.” So, to eliminate any confusion over the meaning
of critical terms discussed in this article, I will rely on the
definitions published in the 2010 edition of NFPA 13,
Standard for the Installation of Sprinkler Systems; the 2010
edition of NFPA 14, Standard for the Installation of Stand-
pipes and Hose Systems; and the 2011 edition of NFPA 25,
Standard for the Inspection, Testing, and Maintenance of Water-
Based Fire Protection Systems. A main drain is defined in
section 3.3.7.1 of NFPA 25 as the primary drain connec-
tion, which is located on the system riser and is also uti-
lized as a flow test connection. System risers are not de-
fined in NFPA 25, but NFPA 13, section 3.5.12 gives this
definition: “[t]he above ground horizontal or vertical pipe
between the water supply and the mains (cross or feed)
that contains a control valve (either directly or within its
supply pipe) and a water flow alarm device.” Finally, a
standpipe is defined by NFPA 14 as “[t]he system piping
that delivers the water supply for hose connections, and
for sprinklers on combined systems, vertically from floor
to floor.”
So where and when is a main drain test required? The
answer is found in NFPA 25, section 13.2.5, which states:
“A main drain test shall be conducted annually at each
water-based fire protection system riser to determine
whether there has been a change in the condition of the
water supply piping and control valves.”
Furthermore, section 13.3.3.4 states, “a main drain
test shall be conducted any time the control valve is
closed and reopened at system riser.”
The NFPA handbook for the 2011 edition of NFPA
25 clearly addresses the intent of a main drain test in its
commentary. The handbook states:
The two major reasons to conduct a main drain test are to
verify the following:
1. Water supply pressure is similar to the original
acceptance test or to other previous tests.
2. The system control valve is fully open after having been
closed and reopened during annual testing. Main drain
test results should not be solely relied upon to determine
whether valves are open. A main drain test may not re-
veal a partially closed valve in a large-diameter supply
pipe with relatively high pressure.
With all this being said, a fire sprinkler system and/
or a hose standpipe system connected directly to the
municipal water supply relies on municipal water pres-
sure and must adhere to the requirements of the NFPA
25 main drain test. Conducting a main drain test is not
strictly done to verify the proper operation of valves
inside of a building, but to verify the operation of valves
within the municipal water supply outside of the build-
ing’s control. Indeed, there have been numerous cases
where the supply of water from the local municipality
was impaired due to a partially closed or faulty control
valve. The main drain test will ferret out those deficien-
cies before a tragedy occurs.
Is the main drain test really required?
December 2012 Healthcare Life Safety Compliance Page 5
© 2012 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978-750-8400.
Water-based fire protection systems are usually tied into
the same city water mains that provide domestic water to a
building. If a municipal water department worker un-
knowingly leaves a valve partially closed after repairing a
leak down the street, this may result in low domestic water
pressure throughout the entire building. But without a
main drain test, low domestic water pressure alone may
not always alert the organization to a problem with water
supply to the automatic sprinkler and standpipe system.
When a main drain test indicates a water supply prob-
lem, the issue can be reported to the municipality and
typically resolved quickly. A reduction in water pressure
to a low-rise building will typically be discovered by
building occupants due to the unavailability of domestic
water long before an annual main drain test indicates a
problem. But with a high-rise building that has booster
pumps on the domestic water supply, a partially closed
valve in the street may not always be noticed.
A direct connection to the municipal water supply
is not the only configuration for water-based fire
protection systems. Depending on the size of the system
and the water supply required to operate the system
effectively, a fire pump may be required to enhance
the pressure provided by the municipal water system.
Varying local municipal codes dictate the connection of
the fire pump to the municipal water system. For exam-
ple, the city of Houston prohibits the direct connection of
a building fire pump to its water supply system. The fire
pump suction line must be connected to a water storage
tank, which is automatically refilled from the municipal
water system. Thus, the fire pump is effectively fed from
a tank, rather than from the city water mains.
In my opinion, choosing not to conduct a main drain
test in a system where the fire pump water supply is
from a tank and not a municipal water main does not
leave that system in jeopardy of performing improperly.
But remember, NFPA 25 appears to be all about “belts
and suspenders,” meaning its authors are being conser-
vative, cautious, and redundant.
The annual fire pump flow test and the analysis of
the pump curve constructed by the results of the flow
test will verify the current pressures and water flow
rates as they relate to the original acceptance report and
previous fire pump flow tests. This fire pump flow test,
like the main drain test, is a form of verifying the water
supply.
As for the second reason for conducting a main
drain test, NFPA 13 and the Life Safety Code® require
all valves in water-based fire protection systems to be
electronically supervised with tamper switches con-
nected to the building’s fire alarm system. NFPA 25
requires the tamper switches on the control valves to
be tested semiannually and visually inspected monthly.
In addition, valves within a water-based fire protec-
tion system must be of the indicating type, therefore
easily identified as open or closed during the monthly
inspections.
In conclusion, it appears to me that the main drain
test is an overly conservative and redundant approach
to water-based fire protection system maintenance,
inspection, and testing. The two reasons identified in
the NFPA 25 handbook for conducting a main drain
test are valid: The test identifies a failed or inefficient
supply of water for a water-based fire protection sys-
tem directly fed from a municipal water supply. How-
ever, as previously discussed, annual fire pump flow
tests, monthly visual control valve inspections, semi-
annual control valve tamper switch testing, quarterly
fire department connection inspections, water sup-
ply tank level inspections and monitoring, pressure
gauge calibration or replacement, and annual sprinkler
inspections all ensure that the water-based fire protec-
tion system as a whole operates as designed. By testing
and inspecting all of these components at a frequency
similar to or greater than a main drain test, a reason-
able conclusion can be drawn that the main drain test
is unnecessary and redundant. n
Editor’s note: Readers are reminded that current NFPA
codes and standards, which are enforced by all of the national
accreditation organizations, still require annual main drain
tests. See page 12 for a sample test form.
Page 6 Healthcare Life Safety Compliance December 2012
© 2012 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978-750-8400.
Fire-rated doors in healthcare organizations come
with different configurations of fire-rated hardware. One
of the more common configurations is latching hardware
that is mounted on the surface of the door, rather than
inside the door. While this configuration is popular be-
cause it is considered easier to adjust and maintain than
concealed rods, it leaves the rods exposed between the
horizontal panic hardware and the latching device at the
top and/or bottom of the door. Facility managers quickly
learn that the bottom rod extending to the lower part
of the door is a frequent target of carts, beds, and other
items that are pushed through the opening.
“Vertical rod fire exit hardware is available with top
and bottom rods and latches, or with the top rod and
latch only, known as ‘less bottom rod’ or LBR devices,”
says Lori Greene, manager of codes and resources at
Ingersoll Rand Security Technologies.
Eliminating the bottom rods and latches can help
to meet accessibility requirements and also allows the
floor strikes to be omitted; however, if the fire door
hardware is listed for use with bottom rods and latches,
then removing them after they have been installed
may require the installation of a retrofit kit or other
modifications.
“LBR devices have been available from most panic
hardware manufacturers for many years, but I still
receive questions about them regularly—either related to
the use of the product on fire doors or their installation
in a means of egress,” says Greene. “NFPA 80, Standard
for Fire Doors and Other Opening Protectives (2010 edition),
does not specifically address LBR fire exit hardware.”
NFPA 80 requires fire doors to be equipped with an
active latch bolt to ensure that the door is positively
latched during a fire. Panic hardware used on fire doors
must be fire exit hardware, which is not equipped with
the mechanical means to hold the latch retracted (aka
“dogging”) and must bear labels from the listing agency
for compliance with both panic and fire test standards.
If dogging is desired for fire exit hardware, it must be
an electric function that automatically provides positive
latching upon a fire alarm.
LBR fire exit hardware has been successfully tested for
use on fire doors, and the specifics can be found in the
manufacturer’s literature or the listing agency’s directory
of certified products, according to Greene. For most
applications, an auxiliary fire pin is required in order for
the doors to maintain their fire resistance rating. This pin
typically mounts between 6 and 12 inches above the floor,
on the edge of the door; however, some manufacturers
have tested their LBR devices without an auxiliary fire pin,
or with pins mounted in the bottom edge of the door.
The pins remain retracted under normal conditions,
and are heat actuated. When the temperature of
activation is reached—usually around 400ºF at the
location of the pin—the pin projects from the edge of
one door into a hole in the edge of the other door leaf
(or into the floor if the pins are installed on the bottom
of the door). In addition to fire exit hardware, these
auxiliary fire pins are sometimes used on fire doors with
automatic flush bolts where the bottom flush bolt is
omitted.
“The auxiliary fire pin has raised concerns regarding
egress in the past, because once the bolt is projected,
the doors no longer allow free egress,” says Greene. “It’s
important to understand that the pin projects only dur-
ing a fire, and its purpose is to maintain the alignment of
the doors to prevent the spread of smoke and flames.”
According to Underwriters Laboratories (UL), an aux-
iliary fire pin with an activating temperature of 400ºF
typically projects 15–20 minutes into a fire test, when
the temperature inside the test furnace is approximately
1,400ºF. The pin is only actuated when the activation
temperature is reached, and at that point the area would
not be tenable for occupants or firefighters, according to
Greene.
The tests used for fire door assemblies (UL 10B, UL
10C, and NFPA 252) do not require the doors to be oper-
able at the conclusion of the test. Most locks and exit
‘Less bottom rod’ fire exit hardware
December 2012 Healthcare Life Safety Compliance Page 7
© 2012 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978-750-8400.
devices incorporate fusible links that render the hard-
ware inoperable during the fire test, so the doors remain
latched throughout the hose stream portion of the test.
The auxiliary fire pin associated with LBR exit devices
operates under the same principle.
“Another issue that has been raised regards firefighter
access once the auxiliary fire pin has been projected
after reaching the activating temperature,” says Greene.
“In addition to the fact that most latching hardware is
designed to become inoperable during a fire, the doors
themselves (especially steel doors) are likely to become
wedged into the frame. The intumescent material
required in some applications may also affect the opera-
tion of the door after a fire. Firefighter access will likely
require a sledgehammer and axe, even if an auxiliary
fire pin is not part of the assembly.”
While this newsletter typically deals with require-
ments involving the Life Safety Code®, many healthcare
facilities are also required to comply with their local and
state building codes, which is often the International
Building Code (IBC). A change to the 2009 edition of the
IBC helps to clear up some of the confusion about the
egress requirements when the above-mentioned prod-
ucts are used on fire doors, according to Greene. Para-
graph 1008.1.9, Door Operations, states that you must
be able to readily open egress doors from the egress side
without the use of a key or special knowledge or effort,
except as permitted by this section of the code. Paragraph
1008.1.9.3, however, lists several exceptions where locks
and latches shall be permitted to prevent operation of
doors. These exceptions include:
➤ Places of detention or restraint
➤ Certain occupancies where key-operated locks may
be used on the main entrance if certain criteria
are met
➤ Pairs with automatic flush bolts, with a requirement
for the inactive leaf to be without hardware that
would give the impression that the inactive leaf could
be operated independently
➤ Dwelling unit doors in Group R occupancies with an
occupant load of 10 or less, where a night latch, dead
bolt, or security chain may be used in addition to an-
other latching device
And Greene notes the presence of a new exception,
which was added in the 2009 edition of the IBC: “Fire
doors after the minimum elevated temperature has
disabled the unlatching mechanism in accordance with
listed fire door test procedures.”
“The purpose of this last exception is to address the
use of fusible links and heat-actuated components used
in door hardware, including the auxiliary pin used with
less bottom rod fire exit hardware,” she says.
Before removing bottom rods and latches from
existing fire exit hardware, it’s important to check
with the manufacturers of the fire exit hardware and
the fire doors, and to follow the required procedures.
Retrofit kits are available for some brands of hardware,
and the kit may include replacement top strikes that
need to be installed. Removing existing rods and
latches without following the proper procedures is
likely to result in a fire door assembly that is no longer
code-compliant.
Openings in the outer casing of the horizontal
hardware on the door and floor-mounted recesses for
latches can easily provide surveyors and inspectors a
clue as to whether a lower bottom rod was originally
specified by the manufacturer. If they notice these
clues, they may very well ask to see documentation
from the manufacturer authorizing the removal of the
lower bottom rods. Without this documentation, you
are vulnerable to a citation. n
If it’s been more than six months
since you purchased or renewed your
subscription to HLSC, be sure to check
your envelope for your renewal notice or call customer
service at 800-650-6787. Renew your subscription early
to lock in the current price.
Don’t miss your next issue!
Page 8 Healthcare Life Safety Compliance December 2012
© 2012 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978-750-8400.
Nearly every acute care hospital in the United States
has horizontal sliding doors, most of them with glass
panels. These doors can be found in various locations
around the hospital, but regardless of location they have
one basic characteristic in common: They are all installed
in a means of egress.
The Life Safety Code® (LSC) permits horizontal sliding
doors in the means of egress provided they meet certain
requirements. For example, the doors must be operable
from both sides; the force needed to operate the doors
must not exceed a certain maximum amount; the doors
must break away and swing in the direction of egress;
and if installed in a corridor, the doors must latch and
resist the passage of smoke. They also must meet fire
door requirements if located in a fire-rated barrier,
which means the door itself must be fire rated, and self-
close and latch on a fire alarm signal.
While a basic glass panel sliding door does not qualify
as a fire-rated door, there is at least one manufacturer
that makes horizontal sliding doors that are fire rated:
Won-Door Corporation, located in Salt Lake City. Won-
Door’s FireGuard door is the original horizontal sliding
fire door assembly and carries a fire rating of up to 90
minutes. It is universally accepted as a wide-span open-
ing protective regardless of occupancy type and with no
occupant load limit. These types of doors are frequently
found in healthcare occupancies, especially where wide
corridors are desired without the restrictions created by
swinging door assemblies.
But what is frequently found in hospitals, especially in
ICUs or ERs, are aluminum-framed, glass panel non-rat-
ed horizontal sliding doors. These sliding glass doors may
come in a two-panel or a three-panel configuration and
are very popular with designers and staff alike. It is easy
to understand why they are so useful in the healthcare
setting—the clear glass allows direct supervision from
a nurses’ station into the room even with the door in a
closed position. In addition, the larger opening allowed
by the sliding panels (or leafs, as the LSC refers to them)
permits beds to be rolled into and out of the room much
more easily.
What is not as clearly understood is why designers
actually specify a three-panel horizontal sliding door in
these applications. A three-panel sliding door has one
stationary panel and two moving leafs. While these
doors function well, they are not permitted according to
the healthcare occupancy chapters of the 2000 edition
of the LSC. Sections 18/19.2.2.2.9 specifically state that
if a horizontal sliding door is not automatic closing, it
is limited to a single leaf, not two. The typical sliding
glass doors in ICU and ER patient rooms are not usually
automatic closing, so they would be limited to just one
moving leaf.
However, this doesn’t seem to stop designers from
specifying three-panel sliding glass doors in new con-
struction or renovation applications for healthcare insti-
tutions. One explanation for this conflict may be due to a
change in the 2006 edition of the LSC, which essentially
does away with the single-leaf limitation when the door
serves an occupant load of fewer than 10 individuals.
Could the designers be using the wrong edition of the
LSC when they specify these three-panel doors? Who
knows, but that may be one explanation for this code
violation.
But more importantly, what do the major national
accreditors say about three-panel horizontal sliding doors
with two moving leafs?
“We expect our accredited organizations to comply
with all of the requirements of the 2000 edition of the
Life Safety Code,” says Joseph Cappiello, chief operat-
ing officer for the American Osteopathic Association’s
Healthcare Facilities Accreditation Program (HFAP). “We
do not single out certain sections of the code to overlook.
Manual horizontal sliding doors with more than one
moving leaf are not permitted in the means of egress.
That includes patient room doors. We have cited this
issue when we observe it, and we will continue to cite it
until the code is changed.”
Horizontal sliding door limitations
December 2012 Healthcare Life Safety Compliance Page 9
© 2012 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978-750-8400.
Cappiello makes a good point about a change in the
Code. If and when CMS decides to adopt the 2012 edi-
tion of the LSC, it will have the exception for multiple
moving leaf doors in applications with fewer than
10 occupants. As yet, though, CMS has only stated that
it will consider adopting the 2012 edition. The review
process takes years, and a formal statement announcing
the adoption of the new edition is not expected for an-
other two years or so.
CMS does not make formal statements or interpreta-
tions very often—and never in a timely fashion!—but
one indivi dual who is close to the CMS office in Balti-
more says he expects the CMS state agency surveyors
to cite any manually operated sliding doors with more
than one moving leaf since this represents a violation
of the 2000 edition of the LSC. The same individual also
says he thinks CMS would accept a waiver for any doors
cited as such, but they must first be cited before the
agency will consider a waiver.
“We try to call the plays by the book,” says Randy
Snelling, chief physical environment officer at Det
Norske Veritas (DNV) Healthcare, Inc. “We require our
surveyors to apply the 2000 edition of the Life Safety
Code. I don’t see how this issue would be any different.
The surveyor finding is just the beginning of the correc-
tive action. The real action is in the details of an appeal
or corrective action.”
Efforts to receive an official comment from The Joint
Commission’s Standards Interpretation Group went
unanswered by presstime, but an unofficial comment
from the accreditor indicates it too would cite this issue
since it is an LSC requirement.
So what do you do if you discover you have noncom-
pliant manually operated horizontal sliding doors with
more than one moving leaf? Most of the accreditation
organizations above would recommend that you do not
remove them, but either submit an equivalency for their
approval, or submit a waiver request if they are cited—in
other words, don’t spend the money to fix the problem
because in a few short years, the 2012 edition of the LSC
(assuming its adoption) will permit them.
You would need to self-identify the deficiency and im-
plement appropriate alternative life safety measures, ac-
cording to your policy. The Joint Commission will most
likely accept a traditional equivalency for the deficiency
of having more than one moving leaf in a horizontal
sliding door. The traditional equivalency is a written
statement from a registered architect, a professional fire
protection engineer, or a local authority on fire safety
stating that, in the expert’s opinion, the deficiency is
not unsafe or does not pose a threat to the safety of the
patients or staff. This written statement would normally
be based on the presence of additional life safety features
which are not required, such as smoke detectors.
HFAP and DNV would accept a Fire Safety Evaluation
System (FSES) equivalency, which is based on NFPA
101A, Guide on Alternative Approaches to Life Safety (2001
edition). This entails a bit more legwork and a review
of every smoke compartment in the facility. But once
accepted, the FSES is good for the life of the facility or
until such time the area undergoes new construction or
renovation.
If cited by an accreditor during a survey, it is recom-
mended that a waiver request be made as part of your
Plan of Correction, through the accreditation organiza-
tion to the CMS regional office. The three accreditation
organizations are not allowed to grant waivers for LSC
deficiencies; only the CMS regional office is permitted
to approve waivers. This way, the waiver is valid until
the next triannual inspection, when it should be cited
again. Unlike equivalencies, waivers have to be renewed
frequently, but it’s not that long until the 2012 edition of
the LSC will probably be adopted. n
Relocating? Taking a new job?
If you’re relocating or taking a new
job and would like to continue receiving
HLSC, you are eligible for a free trial
subscription. Contact customer serv ice
with your moving information at 800-650-6787.
Page 10 Healthcare Life Safety Compliance December 2012
© 2012 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978-750-8400.
&AnswersQuestions
Editor’s note: Each month, Senior
Editor Brad Keyes, CHSP, consultant
for Keyes Life Safety Compliance, answers
your questions about life safety compli-
ance. Our editorial advisory board also
reviews the Q&A column. Follow Keyes’ blog on life safety at
www.keyeslifesafety.com for up-to-date information.
Ambulatory care soiled utility room
Q We have an ambulatory care occupancy that has
clean supply and soiled linen rooms. Since these
rooms are considered storage with combustibles, the
Life Safety Code® (LSC) views them as hazardous areas.
These rooms are sprinklered, which means they do
not need one-hour rated barriers. Do these rooms re-
quire doors that need to latch? It does not appear so,
as I read the LSC.
A You’re right. A soiled utility room in an ambu-
latory care occupancy that is protected with
automatic sprinklers does not require fire-rated walls
and no doors are required. It sounds strange, but this
is why: Section 21.3.2 of the 2000 edition of the LSC
refers to section 39.3.2 for protection from hazards,
which identifies storage rooms as hazardous rooms
that need to comply with section 8.4. This section al-
lows the option of sprinklering the room or providing
one-hour fire-rated walls. If you choose the one-hour
fire-rated walls, then you would have to provide a
3/4-hour fire-rated door and frame that self-closes
and positive latches. But in your scenario, your clean
supply and soiled linen rooms are sprinklered, and
8.4 does not require self-closing and latching doors.
Also, section 21.3.6 says there are no requirements
for corridors, so that means there are no require-
ments for corridor doors. This is quite different from
a healthcare occupancy, which would require self-
closing and latching doors even if the rooms were
sprinklered.
Dead-bolt locks on psychiatric rooms
Q In a psychiatric hospital ER, are patient holding
rooms allowed to have dead bolts on the corridor
side with no thumb latch on the inside of the room?
Our administrator’s position is that those rooms can
be used as seclusion rooms at any given time. Is that
acceptable?
A Interesting question. I would say it depends if
the seclusion rooms would only be used for the
purpose of securing individuals who present a threat
to themselves or others. This is commonly called “clin-
ical needs” and is allowed under section 19.2.2.2.4,
exception number 1 of the 2000 edition of the LSC.
However, if the same rooms are used for non–behav-
ioral health patients, then the locks would not be per-
mitted. Section 7.2.1.5.4 does not allow more than
one action to operate a door in the path of egress,
and a dead bolt and a door latch would be more than
one operation. Can you guarantee these rooms would
never be used for anything other than seclusion? If
not, then I would think most authorities would have a
problem with the dead-bolt locks. This situation is go-
ing to end up requiring an interpretation from an au-
thority having jurisdiction (AHJ). The average hospital
has five or more AHJs, and even if four of those AHJs
don’t have a problem with the locks, if the fifth AHJ
does, you’ll have to remove them. Most hospitals deal
December 2012 Healthcare Life Safety Compliance Page 11
© 2012 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978-750-8400.
with this issue by having sitters watch the patient.
It’s not the best solution, but it does meet the code
requirements.
Closures on inactive door leafs
Q A consultant has mentioned that several of our
doors to hazardous areas are noncompliant. The
door configuration is such that there is a normal 3-by-
4-inch door paired with a small, inactive leaf about 1
by 7 inches. The inactive leaf has an automatic flush
bolt but is not provided with a self-closer. I realize
that hazardous rooms need self-closing, positively
latching doors under the new construction healthcare
occupancy requirements, but I cannot find any discus-
sions on inactive leafs. My question to you is do you
know of any requirements where the configuration I
described would be allowed?
A Section 8.2.3.2 of the 2000 edition of the LSC re-
quires fire doors to be in compliance with NF-
PA 80, Standard for Fire Doors and Fire Windows (1999
edition). Section 2-4.4.5 discusses the requirements
for an inactive leaf in a room which is not occupied
by people. The exception to this section of the code
specifically states that self-closing devices on the in-
active leaf are not required. The caveat in this excep-
tion is the phrase “where acceptable to the authority
having jurisdiction”—meaning the interpretation is
subject to the AHJ’s whim. So, if you ever get an AHJ
that does not permit it, you’re out of luck, but you
could proceed with the conditions of the exception
until such time as an AHJ says you can’t. As far as I
know, The Joint Commission and CMS are in agree-
ment with this exception.
Oxygen cylinders
Q Several of our departments have stretch-
ers with onboard E-size oxygen cylinders. Can
these be considered in use and not count against
the smoke compartment’s 300-cubic-foot limit? Also,
our nursing staff currently checks oxygen inventory
daily and documents it on a log. Is this a written code
requirement?
A Yes and no. All O2 cylinders that are mounted
on gurneys, wheelchairs, and medical equip-
ment but are not actively used by patients are con-
sidered by CMS to be in use, and therefore are not
subject to the 300-cubic-foot threshold for stored
medical gas cylinders. CMS explained its position on
this issue in a memorandum called S&C-07-10, dat-
ed January 12, 2007. The Joint Commission has en-
dorsed this position as well and has said as much on
various occasions. In regard to the nurses checking
oxygen levels on a daily basis, I am not aware of any
LSC or Joint Commission requirement for this ac-
tion. Perhaps your state has something relevant to say
about it. I do know that plant operators frequently
record the level of liquid oxygen in the bulk storage
tanks, but that is more for tracking purposes and to
ensure the oxygen does not run out.
Signs on fire-rated doors
Q Are signs permitted on fire-rated doors? We
posted a sign on a fire-rated stairwell door that
instructed our staff to temporarily not use the door,
and a surveyor said we are not allowed to do this. Is
this true?
A You may have a legitimate appeal on this issue.
Section 8.2.3.2 of the 2000 edition of the LSC re-
quires compliance with NFPA 80, Standard for Fire Doors
and Fire Windows (1999 edition). Section 1-3.5 of NFPA
80 permits you to post signs on a fire-rated door as long
as the sign does not exceed 5% of the total surface area
of the door and does not interfere with the operation of
the door. The sign must be attached with adhesives, not
nails or staples. n
Page 12 Healthcare Life Safety Compliance December 2012
© 2012 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978-750-8400.
Subscriber Services Coupon Your source code: N0001
Name
Title
Organization
Address
City State ZIP
Phone Fax
Email address(Required for electronic subscriptions)
❏ Charge my:
❏ AmEx ❏ Mastercard ❏ VISA ❏ Discover
Signature(Required for authorization)
Card # Expires(Your credit card bill will reflect a charge from HCPro, the publisher of HLSC.)
❏ Start my subscription to Healthcare Life Safety Compliance. Options No. of issues Cost Shipping Total
❏ Electronic 12 issues $289 (HLSCE) N/A
❏ Print & Electronic 12 issues of each $289 (HLSCPE) $24.00
Sales tax (see tax information below)*
Grand total
Order online at www.hcmarketplace.com.
Be sure to enter source code N0001 at checkout!
Mail to: HCPro, P.O. Box 3049, Peabody, MA 01961-3049 Tel: 800-650-6787 Fax: 800-639-8511 Email: [email protected] Web: www.hcmarketplace.com
For discount bulk rates, call toll-free at 888-209-6554.
*Tax InformationPlease include applicable sales tax. Electronic subscriptions are exempt. States that tax products and shipping and handling: CA, CO, CT, FL, GA, IL, IN, KY, LA, MA, MD, ME, MI, MN, MO, NC, NJ, NM, NV, NY, OH, OK, PA, RI, SC, TN, TX, VA, VT, WA, WI, WV. State that taxes products only: AZ. Please include $27.00 for shipping to AK, HI, or PR.
Quick tip
Main drain test
Locations of
Main Drain Test
Results of this
Main Drain Test
Results of
Previous Main Drain Test
Comparison
Acceptable?
Static Residual Time Static Residual Time Yes No*
*All ‘No’ answers must be investigated and documented with work orders.
Annual Test or After a Control Valve Has Been Closed and Reopened
Date of test: Work order #: __________________________________Signature of technician(s): _________________________________________________________________________ Date of previous main drain test that this test is compared to: __________________________________________ Name of building where main drain is being tested: ___________________________________________________ Prior to testing, has the fire alarm monitoring entity been notified of the test? _____________________________ Has the fire alarm system been programmed not to activate the alarm? __________________________________ Has the fire pump been shut off, but the jockey pump left on? _________________________________________ If the fire pump is off for more than four hours in a 24-hour period, has the local fire department been notified and a fire watch been implemented? __________________________________________________________ Directions:1. Record static pressure2. Open main drain test valve and allow water to flow3. After water flow has been stabilized, record residual pressure4. Close main drain test valve slowly 5. Record time required to restore water pressure back to static pressure6. Compare results of this test to previous main drain test results for abnormalities
Source: NFPA 25, 1998 edition
1. (T) (F) “Swinging doors with builders hardware” means the individual components of the door assembly are listed by an independent testing laboratory.
2. (T) (F) According to Gene Redahan, the most common issue with fire door inspection is malfunctioning hardware.
3. (T) (F) Intertek is an approved testing laboratory, similar to Underwriters Laboratories (UL), that tests to the same exact standards as UL does.
4. (T) (F) According to guest columnist Brian Galloy, MBA, CSP, CHFM, the NFPA 25 main drain test is an overly conservative and redundant approach to water-based fire protection system maintenance.
5. (T) (F) Removing the bottom rod and latches for surface-mounted hardware on fire-rated doors may be permitted based on the manufacturer’s instructions.
6. (T) (F) After an auxiliary fire pin is activated in a fire-rated door, it is still expected to be operable for firefighters’ use.
7. (T) (F) Automatic closing sliding glass doors are frequently found in ICU and ER patient rooms.
8. (T) (F) The formal announcement of CMS’ adoption of the 2012 edition of the Life Safety Code® is expected in two years or so.
9. (T) (F) A soiled utility room in an ambulatory care occupancy that is protected with sprinklers is required to have fire-rated walls and doors.
10. (T) (F) All oxygen cylinders mounted on gurneys and wheelchairs must be counted as being in storage.
QuizQuizHealtHcare life Safety complianceThe newsletter to assist healthcare facility managers with fire protection and life safety
Vol. 14 No. 12December 2012
Quiz questions December 2012 (Vol. 14, No. 12)
A supplement to HealthcareLifeSafetyCompliance
1. True.
2. False. The most common issue is the discovery of holes in doors where old hardware has been removed.
3. True.
4. True.
5. True.
6. False. The auxiliary fire pin will project into the other door leaf when the temperature of the pin inside the door reaches 400°F; at this point, the temperature outside the door would be around 1400°F, an unsurvivable environment for any firefighter.
7. False. Manual, not automatic, sliding glass doors are frequently found in ICU and ER patient rooms.
8. True.
9. False. Fire-rated walls and doors are not required in an ambulatory care occupancy soiled utility room that is protected with sprinklers.
10. False. Oxygen cylinders mounted on gurneys and wheelchairs are counted as being in use, not in storage.
Quiz answers December 2012 (Vol. 14, No. 12)
Copyright 2012 HCPro, Inc. Current subscribers to HealthcareLifeSafetyCompliance may copy this quiz for use at their facilities. Use by others, including those who are no longer subscribers, is a violation of applicable copyright laws. ® Registered trademark, the National Fire Protection Association, Inc.