hgt-el om - 1 - florida building · (ffpc, nfpa 220, 4.3.1) means of fire protection portable fire...

1
LI FE SAFETY DATA APPLICABLE CODES FLORIDA BUILDING CODE (FBC) - 2014 EDITION FLORIDA FIRE PREVENTION CODE (FFPC) - 5TH EDITION OCCUPANCY CLASSIFICATION FBC: RESIDENTIAL GROUP R-1, TRANSIENT. (FBC 602.3, TABLES 503 AND 601) FFPC: RESIDENTIAL - HOTEL. (FFPC 6.1.8.1.3) CONSTRUCTION TYPE FBC: TYPE 111-8. (FBC 602.3, TABLES 503 AND 601) FFPC: TYPE 11(111). (FFPC, NFPA 220, 4.3.1) MEANS OF FIRE PROTECTION PORTABLE FIRE EXTINGUISHERS (EXISTING) NO FIRE SPRINKLERS SYSTEM IN EXISTING COMPLEX (NON-SPRINKLERED) BUILDING HEIGHTANDAREAS (FBC, TABLE 503) DESCRIPTION BUILDING HEIGHT NUMBER OF STORIES BUILDING AREA PER STORY MAXIMUM ALLOWED 4 16,000 SQFT PROVIDED 25'-6" (EXISTING) 3 (EXISTING) 10,408 SQFT (EXISTING) FIRE CLASSIFICATION OF INTERIOR FINISHES INTERIOR FINISH CLASSIFICATION LIMITATIONS (NON-SPRINKLERED BUILDING) FBC: TABLE 803.9 FFPC: CHAPTER 20.8 R-1(FBC) 55 FEET OCCUNPANCY HOTEL (FFPC) EXITS A I or 11 A I or 11 EXITS ACCESS CORRIDOR A or B A or B OTHER SPACES A, B, or C A, B, or C NOTES: 1. Cioss A interior woll and ceiling finish - flame spread 0-25, (new) smoke developed 0-450 2. Class B interior wall and ceiling finish - flame spread 26-75, (new) smoke developed 0-450 3. Class C interior wall and ceiling finish - flame spread 76-200,(new) smoke developed 0-450 4. Class I interior floor finish - critical r{]diont flux, not less than 0.45 W/cm2 5. Class 11 interior fkor finish - cfiticol radiont flux, not less tholl 0.22 W/cm2 but less than 0.45 W/'cm2 MEANS OF EGRESS CRITERIA FFPC 1. MAXIMUM TRAVEL DISTANCE OCCUPANCY: EXISTING HOTELS (FFPC, NFPA 101, 29.2) MAXIMUM ALLOWED: 75 FT. WITHIN A GUEST ROOM TO A CORRIDOR DOOR (FFPC, NFPA 101, 29.2.6.1) 100 FT. FROM CORRIDOR DOOR OF GUEST ROOM TO THE NEAREST EXIT (FFPC, NFPA 101, 29.2.6.3.1) 200 FT. FROM CORRIDOR DOOR OF GUEST ROOM TO THE NEAREST EXIT FOR EXTERIOR WAYS OF EXIT ACCESS (FFPC, NFPA 101, 29.2,6.3.2) 2. COMMON PATH OF EGRESS TRAVEL OCCUPANCY: MAXIMUM ALLOWED: EXISTING HOTELS 35 FT. FROM CORRIDOR DOOR OF GUEST ROOM (FFPC, NFPA 101, 29.2) TO THE NEAREST EXIT (FFPC, NFPA 101, 29.2.5.3) 3. DEAD ENDS: OCCUPANCY: EXISTING HOTELS (FFPC, NFPA 101, 29.2) 4. CORRIDORS: OCCUPANCY: HOTELS MAXIMUM ALLOWED: 50 FL (FFPC, NFPA 101, 29.2.5.5) MIN. ALLOWED: 36 IN. (FFPC, 14.8.3.4.1) FIRE-RESISTANCE RATING REQUIREMENTS (HOURS) BUILDING ELEMENT PRIMARY STRUCTURAL FRAME BEARING WALLS EXTERIOR INTERIOR NONBEARING WALLS AND PARTITIONS EXTERIOR (FIRE SEPARATION DISTANCE=X) INTERIOR FLOOR CONSTRUCTION AND SECONDARY MEMBERS ROOF CONSTRUCTION AND SECONDARY MEMBERS 0 CONST. TYPE: 111-B (FBC, TABLE 601) 0 (X>30') 1 (20'<X<30') 0 0 0 2 0 CONST. TYPE: 11(111) (FFPC, NFPA 220 TABLE 4.1.1) 1 0 0 1 1 FBC 1. MAXIMUM TRAVEL DISTANCE OCCUPANCY: RESIDENTIAL R-1 1 THIRD FLOOR LIFE SAFETY PLAN MAXIMUM ALLOWED: 200 FL (FBC, TABLE 1016.2) 2. COMMON PATH OF EGRESS TRAVEL OCCUPANCY: MAXIMUM ALLOWED: RESIDENTIAL R-1 75 FT. (FBC, TABLE 1014.3) 3. DEAD ENDS: OCCUPANCY: RESIDENTIAL R-1 4. CORRIDORS: OCCUPANCY RESIDENTIAL R-1 FIRE SEPARATION MAXIMUM ALLOWED: 20 FT. (FBC, 1018.4) MINIMUM WIDTH ALLOWED: WALLS SEPARATING DWELLING OR SLEEPING UNITS (FBC 420.2, 708.1) 44 IN. (FBC, 1018.2) HORIZONTAL ASSEMBLIES SEPARATING DWELLING OR SLEEPING UNITS (FBC 420.3, 711.3) ---------- 1HR 1 HR SCALE: 1/8" = 1 '-0" FIRST FLOOR OCCUPANT LOAD CALCULATION CHART (FFPC TABLE 14.8.1.1 / FBC, TABLE 1004.1.2). *STRINGENT FACTOR APPLIED SPACE / ROOM MAIN LOBBY LOBBY OFFICE, RECEPTION, LAUNDRY, POOL RESTROOM HOTEL ROOMS (1-10) (MAIN BUILDING) SUPPLY CLOSET, ELECTRICAL, UTILITY TOTAL FUNCTION OF SPACE ASSEMBLY: LESS CONCENTRATED USE WITHOUT WITHOUT FIXED SEATING BUSINESS RESIDENTIAL: HOTEL AND DORMITORIES STORAGE FLOOR AREA (SQ. FT.) 310 636 4312 225 OCCUPANTLOAD FACTOR (SQUARE FEET PER PERSON) 15 NET 100 GROSS 200 GROSS 300 GROSS OCCUPANT LOAD (PERSONS) SECOND FLOOR OCCUPANT LOAD CALCULATION CHART (FFPC TABLE 14.8.1.1 / FBC, TABLE 1004.1.2). *STRINGENT FACTOR APPLIED SPACE / ROOM HOTEL ROOMS(23-26) (EAST BUILDING) HOTEL ROOMS(11-20) (MAIN BUILDING) HOTEL ROOMS(21-22) (WEST BUILDING) OFFICE, LAUNDRY, STORAGE AREA MULTI-PURPOSE ROOM TOTAL FUNCTION OF SPACE RESIDENTIAL: HOTEL AND DORMITORIES RESIDENTIAL: HOTEL AND DORMITORIES RESIDENTIAL: HOTEL AND DORMITORIES BUSINESS ASSEMBLY: LESS CONCENTRATED USE WITHOUT WITHOUT FIXED SEATING FLOOR AREA (SQ. FT.) 1422 4312 666 554 315 OCCUPANTLOAD FACTOR (SQUARE FEET PER PERSON) 200 GROSS 200 GROSS 200 GROSS 100 GROSS 15 NET 7 22 51 OCCUPANTLOAD (PERSONS) THIRD FLOOR OCCUPANT LOAD CALCULATION CHART (FFPC TABLE 14.8.1.1 / FBC, TABLE 1004.1.2). *STRINGENT FACTOR APPLIED SPACE / ROOM HOTEL ROOMS(27-30) (EAST BUILDING) TOTAL FUNCTION OF SPACE RESIDENTIAL: HOTEL AND DORMITORIES FLOOR AREA (SQ. FT.) 1422 OCCUPANTLOAD FACTOR (SQUARE FEET PER PERSON) 200 GROSS 8 22 4 6 61 OCCUPANTLOAD (PERSONS) 8 8 21 21 TGI AT/f' 1-L_i i_L LL LL iii EXISTING OPEN STAIR No.2 AREA OF RENOVATIONS 12" VIN 7 \/ RENO ATED HgT-EL OM_- __1 No. 30 TRAA/DISTANCE TO GROUND FLOOR = 112 1, O 02 iII 3-81- 41 j / [3\/ S /\ z -8 0 Al -81 A M =FL _1 011 -251 -fi] '/;1111'=====5111111111115/ LIFE SAFETY LEGEND -- -- ---- @ j=j FTEr' _1 -- 0 0 0 0 0 ]IL{ - =T« 1Illlllllll1, 0 0 RENOVATED HOTEL ROOM No. 29 RENOVATED HOTEL ROOM No. 28 RENOVATED HOTEL ROOM No. 27 71__ '111[111111]111 1 HOUR FIRE RATING 2-HOUR FIRE RATING 3-HOUR FIRE RATING 4-HOUR FIRE RATING SMOKE BARRIER (1-HOUR RATED) SMOKE PARTITION NON-RATED) TRAVEL DISTANCE SMOKE DETECTOR, CEILING MOUNTED SMOKE DETECTOR, WALL MOUNTED EXIT SIGN, CEILING MOUNTED FIRE EXTINGUISHER CABITET 7 E 3 i ZZZZZZZZZZZZ1 E No. Perez & Partners, Inc. architecture ARCHITECT Jorge I. Perez, AIA AR 95576 Perez & Partners, Inc. AA 26002942 7720 SW 89 Ct Miami, Fl 33173 786.543.9093 [email protected] CLIENT/PROJECT NAME 0 1- 00 Ed Z 1- QO- 4 I .2) > 111 -B 003 Z 1- 00 MILI 0 - LU I LU ,_ 1- Z CONSULTANTS STRUCTURAL ENGINEER: CO (D G, (\1 0 05 0 Z _1 < LL OI 00 LU > Adolfo J. Gonzalez, PE 2050 Coral Way #502 Miami, Fl 33145 305.415.8782 [email protected] MEP ENGINEER: Treasure Coast Engineering, Inc. 492513th Lane Vero Beach, Fl 32966 772.567.1007 www.tce.eng.pro ISSUE/REVISIONS DATE 9-14-15 10/13/15 PROJECT No. DRAWN BY: CHECKED BY: SEAL SHEET No. DESCRIPTION PERMIT SUBMITTAL PERMIT COMMENTS 15-03 A2.02

Upload: lekiet

Post on 01-Sep-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: HgT-EL OM - 1 - Florida Building · (ffpc, nfpa 220, 4.3.1) means of fire protection portable fire extinguishers (existing) no fire sprinklers system in existing complex (non-sprinklered)

LI FE SAFETY DATA

APPLICABLE CODES

FLORIDA BUILDING CODE (FBC) - 2014 EDITIONFLORIDA FIRE PREVENTION CODE (FFPC) - 5TH EDITION

OCCUPANCY CLASSIFICATION

FBC: RESIDENTIAL GROUP R-1, TRANSIENT. (FBC 602.3, TABLES 503 AND 601)

FFPC: RESIDENTIAL - HOTEL. (FFPC 6.1.8.1.3)

CONSTRUCTION TYPE

FBC: TYPE 111-8. (FBC 602.3, TABLES 503 AND 601)FFPC: TYPE 11(111). (FFPC, NFPA 220, 4.3.1)

MEANS OF FIRE PROTECTION

PORTABLE FIRE EXTINGUISHERS (EXISTING)

NO FIRE SPRINKLERS SYSTEM IN EXISTING COMPLEX (NON-SPRINKLERED)

BUILDING HEIGHTANDAREAS

(FBC, TABLE 503)

DESCRIPTION

BUILDING HEIGHT

NUMBER OF STORIES

BUILDING AREA PER STORY

MAXIMUM ALLOWED

4

16,000 SQFT

PROVIDED

25'-6"

(EXISTING)

3 (EXISTING)

10,408 SQFT

(EXISTING)

FIRE CLASSIFICATION OF INTERIOR FINISHES

INTERIOR FINISH CLASSIFICATION LIMITATIONS (NON-SPRINKLERED BUILDING)

FBC: TABLE 803.9

FFPC: CHAPTER 20.8

R-1(FBC)

55 FEET

OCCUNPANCY

HOTEL (FFPC)

EXITS

A

I or 11

A

I or 11

EXITS ACCESS

CORRIDOR

A or B

A or B

OTHER SPACES

A, B, or C

A, B, or C

NOTES:

1. Cioss A interior woll and ceiling finish - flame spread 0-25, (new) smoke developed 0-4502. Class B interior wall and ceiling finish - flame spread 26-75, (new) smoke developed 0-4503. Class C interior wall and ceiling finish - flame spread 76-200,(new) smoke developed 0-4504. Class I interior floor finish - critical r{]diont flux, not less than 0.45 W/cm25. Class 11 interior fkor finish - cfiticol radiont flux, not less tholl 0.22 W/cm2 but less than 0.45 W/'cm2

MEANS OF EGRESS CRITERIA

FFPC

1. MAXIMUM TRAVEL DISTANCE

OCCUPANCY:

EXISTING HOTELS

(FFPC, NFPA 101, 29.2)

MAXIMUM ALLOWED:

75 FT. WITHIN A GUEST ROOM TO A CORRIDOR DOOR

(FFPC, NFPA 101, 29.2.6.1)

100 FT. FROM CORRIDOR DOOR OF GUEST ROOM

TO THE NEAREST EXIT (FFPC, NFPA 101, 29.2.6.3.1)

200 FT. FROM CORRIDOR DOOR OF GUEST ROOM TO

THE NEAREST EXIT FOR EXTERIOR WAYS OF EXIT ACCESS

(FFPC, NFPA 101, 29.2,6.3.2)

2. COMMON PATH OF EGRESS TRAVEL

OCCUPANCY: MAXIMUM ALLOWED:

EXISTING HOTELS 35 FT. FROM CORRIDOR DOOR OF GUEST ROOM

(FFPC, NFPA 101, 29.2) TO THE NEAREST EXIT (FFPC, NFPA 101, 29.2.5.3)

3. DEAD ENDS:

OCCUPANCY:

EXISTING HOTELS

(FFPC, NFPA 101, 29.2)

4. CORRIDORS:

OCCUPANCY:

HOTELS

MAXIMUM ALLOWED:

50 FL (FFPC, NFPA 101, 29.2.5.5)

MIN. ALLOWED:

36 IN. (FFPC, 14.8.3.4.1)

FIRE-RESISTANCE RATING REQUIREMENTS (HOURS)

BUILDING ELEMENT

PRIMARY STRUCTURAL FRAME

BEARING WALLS

EXTERIOR

INTERIOR

NONBEARING WALLS AND PARTITIONS

EXTERIOR (FIRE SEPARATION DISTANCE=X)

INTERIOR

FLOOR CONSTRUCTION AND SECONDARY MEMBERS

ROOF CONSTRUCTION AND SECONDARY MEMBERS

0

CONST. TYPE:

111-B

(FBC, TABLE 601)

0 (X>30')

1 (20'<X<30')

0

0

0

2

0

CONST. TYPE:

11(111)(FFPC, NFPA 220

TABLE 4.1.1)

1

0

0

1

1

FBC

1. MAXIMUM TRAVEL DISTANCE

OCCUPANCY:

RESIDENTIAL R-1

1THIRD FLOORLIFE SAFETY PLAN

MAXIMUM ALLOWED:

200 FL (FBC, TABLE 1016.2)

2. COMMON PATH OF EGRESS TRAVEL

OCCUPANCY: MAXIMUM ALLOWED:

RESIDENTIAL R-1 75 FT. (FBC, TABLE 1014.3)

3. DEAD ENDS:

OCCUPANCY:

RESIDENTIAL R-1

4. CORRIDORS:

OCCUPANCY

RESIDENTIAL R-1

FIRE SEPARATION

MAXIMUM ALLOWED:

20 FT. (FBC, 1018.4)

MINIMUM WIDTH ALLOWED:

WALLS SEPARATING DWELLING OR

SLEEPING UNITS (FBC 420.2, 708.1)

44 IN. (FBC, 1018.2)

HORIZONTAL ASSEMBLIES SEPARATING DWELLING OR

SLEEPING UNITS (FBC 420.3, 711.3) ---------- 1HR

1 HR

SCALE: 1/8" = 1 '-0"

FIRST FLOOR OCCUPANT LOAD CALCULATION CHART

(FFPC TABLE 14.8.1.1 / FBC, TABLE 1004.1.2). *STRINGENT FACTOR APPLIED

SPACE / ROOM

MAIN LOBBY

LOBBY OFFICE,

RECEPTION, LAUNDRY,POOL RESTROOM

HOTEL ROOMS (1-10)(MAIN BUILDING)

SUPPLY CLOSET,

ELECTRICAL, UTILITY

TOTAL

FUNCTION OF SPACE

ASSEMBLY: LESS CONCENTRATED USE

WITHOUT WITHOUT FIXED SEATING

BUSINESS

RESIDENTIAL:

HOTEL AND DORMITORIES

STORAGE

FLOOR AREA

(SQ. FT.)

310

636

4312

225

OCCUPANTLOAD

FACTOR (SQUAREFEET PER PERSON)

15 NET

100 GROSS

200 GROSS

300 GROSS

OCCUPANT LOAD

(PERSONS)

SECOND FLOOR OCCUPANT LOAD CALCULATION CHART

(FFPC TABLE 14.8.1.1 / FBC, TABLE 1004.1.2). *STRINGENT FACTOR APPLIED

SPACE / ROOM

HOTEL ROOMS(23-26)(EAST BUILDING)

HOTEL ROOMS(11-20)(MAIN BUILDING)

HOTEL ROOMS(21-22)(WEST BUILDING)

OFFICE, LAUNDRY,STORAGE AREA

MULTI-PURPOSE

ROOM

TOTAL

FUNCTION OF SPACE

RESIDENTIAL:

HOTEL AND DORMITORIES

RESIDENTIAL:

HOTEL AND DORMITORIES

RESIDENTIAL:

HOTEL AND DORMITORIES

BUSINESS

ASSEMBLY: LESS CONCENTRATED USE

WITHOUT WITHOUT FIXED SEATING

FLOOR AREA

(SQ. FT.)

1422

4312

666

554

315

OCCUPANTLOAD

FACTOR (SQUAREFEET PER PERSON)

200 GROSS

200 GROSS

200 GROSS

100 GROSS

15 NET

7

22

51

OCCUPANTLOAD

(PERSONS)

THIRD FLOOR OCCUPANT LOAD CALCULATION CHART

(FFPC TABLE 14.8.1.1 / FBC, TABLE 1004.1.2). *STRINGENT FACTOR APPLIED

SPACE / ROOM

HOTEL ROOMS(27-30)(EAST BUILDING)

TOTAL

FUNCTION OF SPACE

RESIDENTIAL:

HOTEL AND DORMITORIES

FLOOR AREA

(SQ. FT.)

1422

OCCUPANTLOAD

FACTOR (SQUAREFEET PER PERSON)

200 GROSS

8

22

4

6

61

OCCUPANTLOAD

(PERSONS)

8

8

21

21

TGI

AT/f'

1-L_i i_L LL LL iiiEXISTING

OPEN STAIR No.2

AREA OF RENOVATIONS

12"

VIN

7 \/

RENO ATEDHgT-EL OM_- __1 No. 30

TRAA/DISTANCE TO GROUND FLOOR = 1121,

O 02

iII 3-81-41 j

/

[3\/S /\

z -8

0Al

-81

AM =FL _1 011

-251

-fi]

'/;1111'=====5111111111115/

LIFE SAFETY LEGEND

--

--

----

@

j=j

FTEr'

_1

--

0

0

0

0

0

]IL{ -

=T«1Illlllllll1,

0

0

RENOVATED

HOTEL ROOM

No. 29

RENOVATED

HOTEL ROOM

No. 28

RENOVATED

HOTEL ROOM

No. 27

71__'111[111111]111

1 HOUR FIRE RATING

2-HOUR FIRE RATING

3-HOUR FIRE RATING

4-HOUR FIRE RATING

SMOKE BARRIER

(1-HOUR RATED)

SMOKE PARTITION

NON-RATED)

TRAVEL DISTANCE

SMOKE DETECTOR,CEILING MOUNTED

SMOKE DETECTOR,WALL MOUNTED

EXIT SIGN, CEILING MOUNTED

FIRE EXTINGUISHER CABITET

7

E

3 i

ZZZZZZZZZZZZ1

E

No.

Perez & Partners, Inc.architecture

ARCHITECT

Jorge I. Perez, AIAAR 95576

Perez & Partners, Inc.

AA 26002942

7720 SW 89 Ct

Miami, Fl 33173786.543.9093

[email protected]

CLIENT/PROJECT NAME

01-

00 EdZ 1-QO-

4 I .2)> 111 -B003Z 1- 00

MILI 0

- LU

ILU ,_1-Z

CONSULTANTS

STRUCTURAL ENGINEER:

CO

(D

G,

(\1

0 050

Z _1< LL

OI00

LU

>

Adolfo J. Gonzalez, PE

2050 Coral Way #502Miami, Fl 33145

305.415.8782

[email protected]

MEP ENGINEER:

Treasure Coast

Engineering, Inc.

492513th Lane

Vero Beach, Fl 32966

772.567.1007

www.tce.eng.pro

ISSUE/REVISIONS

DATE

9-14-15

10/13/15

PROJECT No.

DRAWN BY:

CHECKED BY:

SEAL

SHEET No.

DESCRIPTION

PERMIT SUBMITTAL

PERMIT COMMENTS

15-03

A2.02