hi-lume 3d overview - w. w. graingerfluorescent dimming ballasts hi-lume ® 3d architectural dimming...

14
® SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume® 3D Overview Hi-lume® 3D architectural electronic dimming ballasts are designed to meet the most demanding lighting requirements. By providing industry leading performance with a full-range of 100% to less than 1% fluorescent dimming, Hi-lume® 3D ballasts enable you to provide the ideal visual environment for any application. Features • Continuous, flicker-free dimming from 100% to 0.7% for T8, 1% for T5 and T5HO, and 5% for T5 twin-tube • 100% compatible with all Lutron® 3-wire fluorescent controls and EcoSystem® digital controls for consistent fixture-to-fixture dimming performance • Compatible with Energi Savr NodeT with EcoSystemR devices, GRAFIK EyeR QS control unit, PowPakT dimming module with EcoSystemR connection, and QuantumR software, allowing for integration into an existing or planned EcoSystemR lighting control solution. • Programmed rapid start design preheats lamp cathodes before applying full arc voltage to ensure full-rated lamp life while dimming and cycling • Lamps turn on to any dimmed level without going to full brightness • Low harmonic distortion throughout the entire dimming range maintains power quality • Frequency of operation ensures that ballast does not interfere with infrared devices operating between 38 kHz and 42 kHz • Inrush current limiting circuitry eliminates circuit breaker tripping, switch arcing, and relay failure • Ballasts maintain consistent light output for different lamp lengths, ensuring fixture-to-fixture uniformity • Ultra-quiet operation • Ballast protected from miswires of any input power to control lead, or from lamp leads to each other and/or ground Hi-lume® 3D, case type C 1.18 in (30 mm) W x 1.00 in (25 mm) H x 18.00 in (457 mm) L Hi-lume® 3D, case type G 2.38 in (60 mm) W x 1.00 in (25 mm) H x 9.50 in (241 mm) L • 100% performance tested and burned in at factory • Non-volatile memory restores all ballast settings after power failure • Buy American Act (BAA) models available; see Model List for specific availability • RoHS compliant • NOM certified models available; see Model List for specific availability • Custom ballast factors available for UL or CSA listed products. Design tool and specifications can be found at www.lutron.com/ballasttool

Upload: others

Post on 09-Jul-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 1 09.04.12

Hi-lume® 3D Overview

Hi-lume® 3D architectural electronic dimming ballasts are designed to meet the most demanding lighting requirements. By providing industry leading performance with a full-range of 100% to less than 1% fluorescent dimming, Hi-lume® 3D ballasts enable you to provide the ideal visual environment for any application.

Features

•Continuous,flicker-freedimmingfrom100%to0.7%for T8, 1% for T5 and T5HO, and 5% for T5 twin-tube

•100%compatiblewithallLutron® 3-wire fluorescent controls and EcoSystem® digital controls for consistent fixture-to-fixture dimming performance

•CompatiblewithEnergiSavrNodeT with EcoSystemR devices, GRAFIK EyeRQScontrolunit,PowPakT dimming module with EcoSystemR connection, and QuantumR software, allowing for integration into an existing or planned EcoSystemR lighting control solution.

•Programmedrapidstartdesignpreheatslampcathodes before applying full arc voltage to ensure full-rated lamp life while dimming and cycling

•Lampsturnontoanydimmedlevelwithoutgoingtofull brightness

•Lowharmonicdistortionthroughouttheentiredimming range maintains power quality

•Frequencyofoperationensuresthatballastdoesnot interfere with infrared devices operating between 38 kHzand42 kHz

•Inrushcurrentlimitingcircuitryeliminatescircuitbreakertripping,switcharcing,andrelayfailure

•Ballastsmaintainconsistentlightoutputfordifferent lamp lengths, ensuring fixture-to-fixture uniformity

•Ultra-quietoperation•Ballastprotectedfrommiswiresofanyinputpowerto

control lead, or from lamp leads to each other and/or ground

Hi-lume® 3D, case type C

1.18in(30mm)Wx1.00in(25mm)Hx18.00in(457mm)L

Hi-lume® 3D, case type G

2.38in(60mm)Wx1.00in(25mm)Hx9.50in(241mm)L

•100%performancetestedandburnedinatfactory•Non-volatilememoryrestoresallballastsettingsafter

power failure•BuyAmericanAct(BAA)modelsavailable;seeModelListforspecificavailability

•RoHScompliant•NOMcertifiedmodelsavailable;seeModelListfor

specific availability•CustomballastfactorsavailableforULorCSAlisted

products. Design tool and specifications can be found at www.lutron.com/ballasttool

Page 2: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 2 09.04.12

Performance•DimmingRange:100%to0.7%measuredrelativelightoutput(RLO)forT8,100%to1%measuredRLOforT5andT5HO,and100%to5%measuredRLOforT5twin-tube.

•LampStarting:programmedrapidstart•LampCurrentCrestFactor:lessthan1.7•LampFlicker:nonevisible•LightOutputVariation:constant±2%lightoutputforlinevoltagevariationsof±10%

•LampLife:averagelamplifemeetsorexceeds rating of lamp manufacturer•PowerFactor:greaterthan0.95•TypicalTotalHarmonicDistortion(THD)lessthan10%**•MaximumInrushCurrent:7Aperballastat 120V~3Aperballastat277V~

•OperatingVoltage:Universalinput120,220/240, 277V~at50/60Hz

•FrequencyofOperation:greaterthan42KHz•BallastFactor(BF):1.0/1.17forT8lampsand1.0for

T5, T5HO, and T5 twin-tube lamps

DimmingRangeforT5andT5HOlamps:BF Dimming Range

(Max/Min [BF])Dimming Ratio

1.0 1.00 / 0.01 100:1

DimmingRangeforT8lamps:BF Dimming Range

(Max/Min [BF])Dimming Ratio

1.17 1.17/0.0085 138:11.0 1.00 / 0.0085 118:1

DimmingRangeforT5TwinTubelamps:

BF Dimming Range (Max/Min [BF])

Dimming Ratio

1.0 1.00 / 0.05 100:5

Specifications

Regulatory Approvals•CaliforniaEnergyCommissionListed* •ULListed(evaluatedtotherequirementsofUL935)•CSAcertified(evaluatedtotherequirementsofC22.2No.74)(specificmodelnumbersonly)

•ClassPthermallyprotected•MeetsANSIC82.11HighFrequencyBallastStandard•MeetsFCCPart18Non-Consumerrequirements forEMI/RFIemissions•MeetsANSIC62.41CategoryAsurgeprotection standardsuptoandincluding4kV•ManufacturingfacilitiesemployESDreduction practices that comply with the requirements ofANSI/ESDS20.20•Lutron® Quality Systems registered to ISO9001.2008

Environment•Minimumlampstartingtemperature:50°F(10°C)•Relativehumidity:lessthan90%non-condensing•SoundRating:ClassA•Maximumballastcasetemperature:75°C

Ballast Wiring & Mounting•Ballastisgroundedviaamountingscrewtothefixture•Ballastmountsusingtwoscrews(orsheetmetal

feature and one screw) within a fluorescent fixture.•Powerandlampwiringterminalsacceptone18to16 AWG(0.75to1.5 mm() solid copper wire per terminal.

Lamp Seasoning•Refertothelampmanufacturer'srequirementsforlamp

seasoning requirements prior to dimming.

Warranty•5-yearlimitedwarrantywithLutron® field service

commissioning (3-year standard warranty) from date of purchase.ForadditionalWarrantyinformation,pleasevisit: www.lutron.com/TechnicalDocumentLibrary/Ballast%20and%20Driver%20Warranty.pdf

* NotrequiredforT5twintubemodels.** TypicalTHDformodelsH3DT817CU110,H3DT514CU110andH3DT521CU110lessthan15%.

Page 3: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 3 09.04.12

Hi-lume® 3D Ballasts for Linear and U-Bent T8 Lamps For proper dimming all lamps must comply to accepted standards, 17, 25, 32 and 40 W (NEMA LL9-2009)Not for use with Reduced Wattage Lamps Lamp Type

Lamp Watts (length)

Lamps per Ballast

Case Size

Hi-lume® 3D Model Number

Input Voltage (V~)

Ballast Current (A)

Ballast Factor (BF)

Input Power (W)

System Lumens3 (lm)

System Efficacy3 (lm/W)

Ballast Efficacy Factor (BEF)

Relative System Efficacy (RSE)

T8 and U-Bent

40W (60in [1524mm])

1 C H3DT840CU110 120240277

0.380.180.16

1.001.001.00

43.843.042.8

380038003800

878889

2.282.332.34

0.910.930.94

1 C H3DT840CU117 120240277

0.420.210.18

1.171.171.17

50.649.449.6

444644464446

889090

2.312.372.36

0.920.950.92

2 C H3DT840CU210 120240277

0.760.370.32

1.001.001.00

90.988.488.9

760076007600

848686

1.101.131.13

0.900.910.94

2 C H3DT840CU217 120240277

0.850.410.36

1.171.171.17

100.397.298.2

889288928892

899291

1.171.201.19

0.930.960.95

32W (48in [1219mm])

1 C H3DT832CU1101,2 120240277

0.290.140.12

1.001.001.00

34.833.633.2

300030003000

868990

2.872.983.01

0.920.950.96

G H3DT832GU1101,2 120240277

0.130.150.30

1.001.001.00

34.835.035.1

300030003000

868685

2.872.852.85

0.920.910.91

1 C H3DT832CU1171,2 120240277

0.340.170.15

1.171.171.17

40.840.841.6

351035103510

868684

2.872.872.82

0.920.920.90

G H3DT832GU1171 120240277

0.150.170.34

1.171.171.17

39.740.040.1

351035103510

888888

2.952.922.92

0.940.940.93

2 C H3DT832CU2101,2 120240277

0.570.280.24

1.001.001.00

68.467.266.5

600060006000

888990

1.461.491.50

0.940.950.96

G H3DT832GU2101,2 120240277

0.240.280.54

1.001.001.00

65.766.366.5

600060006000

919090

1.521.511.50

0.970.970.96

2 C H3DT832CU2171,2 120240277

0.650.320.28

1.171.171.17

78.076.877.6

702070207020

909191

1.501.521.51

0.960.980.97

G H3DT832GU2171 120240277

0.280.310.67

1.171.171.17

75.476.576.9

702070207020

939291

1.551.531.52

0.990.980.97

3 G H3DT832GU3101,2 120240277

0.830.400.37

1.001.001.00

99.696.0102.5

900090009000

909488

1.001.040.98

0.961.000.94

3 G H3DT832GU3171 120240277

0.950.470.41

1.171.171.17

114.0112.8113.6

10,53010,53010,530

929393

1.031.041.03

0.991.000.99

Continued on next pageNotes: 1.BAAmodelsavailable.Adda"U"toprefixofmodelnumberwhenordering(ie:UH3DT832CU110).2.NOMapprovedmodelsavailable.Adda"N"tosuffixofmodelnumberwhenordering(ie:H3DT832CU110N).3. Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specific data.

Page 4: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 4 09.04.12

Hi-lume® 3D Ballasts for Linear and U-Bent T8 Lamps (continued) For proper dimming all lamps must comply to accepted standards, 17, 25, 32 and 40 W (NEMA LL9-2009)Not for use with Reduced Wattage Lamps Lamp Type

Lamp Watts (length)

Lamps per Ballast

Case Size

Hi-lume® 3D Model Number

Input Voltage (V~)

Ballast Current (A)

Ballast Factor (BF)

Input Power (W)

System Lumens3 (lm)

System Efficacy3 (lm/W)

Ballast Efficacy Factor (BEF)

Relative System Efficacy (RSE)

T8 and U-Bent

25W (36in [914mm])

1 C H3DT825CU1102 120240277

0.260.110.11

1.001.001.00

31.226.430.5

190019001900

617262

3.213.793.28

0.800.950.82

1 C H3DT825CU117 120240277

0.280.140.12

1.171.171.17

33.633.633.2

222322232223

666667

3.483.483.52

0.870.870.88

2 C H3DT825CU2102 120240277

0.470.230.20

1.001.001.00

56.455.255.4

380038003800

676969

1.771.811.81

0.890.910.90

2 C H3DT825CU217 120240277

0.510.250.22

1.171.171.17

61.260.060.9

444644464446

737473

1.911.951.92

0.960.980.96

17W (24in [610mm])

1 C H3DT817CU1101,2 120240277

0.180.090.08

1.001.001.00

21.621.622.2

130013001300

606059

4.634.634.51

0.790.790.77

G H3DT817GU1101,2 120240277

0.080.090.19

1.001.001.00

22.922.622.8

130013001300

575857

4.374.424.39

0.740.750.75

1 C H3DT817CU1171 120240277

0.190.100.08

1.171.171.17

22.824.022.2

152115211521

676369

5.134.885.28

0.870.830.90

G H3DT817GU1171 120240277

0.090.100.20

1.171.171.17

25.325.325.6

152115211521

606059

4.624.624.57

0.790.790.78

2 C H3DT817CU2101,2 120240277

0.350.180.15

1.001.001.00

42.043.241.6

260026002600

626063

2.382.312.41

0.810.790.82

G H3DT817GU2101,2 120240277

0.140.160.32

1.001.001.00

38.738.439.1

260026002600

676866

2.582.602.56

0.880.890.87

2 C H3DT817CU2171 120240277

0.350.170.15

1.171.171.17

42.040.841.6

304230423042

727573

2.792.872.82

0.950.980.96

G H3DT817GU2171 122240277

0.150.180.36

1.171.171.17

41.841.743.1

304230423042

737371

2.802.812.71

0.950.950.92

3 H3DT817GU3101 120240277

0.480.250.21

1.001.001.00

57.660.058.2

390039003900

686567

1.741.671.72

0.890.850.88

3 H3DT817GU3171 120240277

0.550.270.23

1.171.171.17

66.064.863.7

456345634563

697072

1.771.811.84

0.900.920.94

Notes: 1.BAAmodelsavailable.Adda"U"toprefixofmodelnumberwhenordering(ie:UH3DT832CU110).2.NOMapprovedmodelsavailable.Adda"N"tosuffixofmodelnumberwhenordering(ie:H3DT832CU110N).3. Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specific data.

Page 5: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 5 09.04.12

Lamp Type

Lamp Watts (length)

Lamps per Ballast

Case Size

Hi-lume® 3D Model Number

Input Voltage (V~)

Ballast Current (A)

Ballast Factor (BF)

Input Power (W)

System Lumens3 (lm)

System Efficacy3 (lm/W)

Ballast Efficacy Factor (BEF)

Relative System Efficacy (RSE)

T5 Linear

28W(45.2in [1148mm])

1 C H3DT528CU1101,2 120240277

0.280.130.12

1.001.001.00

33.631.233.0

290029002900

869388

2.983.213.63

0.830.900.85

2 C H3DT528CU2101,2 120240277

0.520.260.22

1.001.001.00

62.462.459.8

580058005800

939397

1.601.601.67

0.900.900.94

21W(33.4in [848mm])

1 C H3DT521CU1101,2 120240277

0.220.110.10

1.001.001.00

26.326.326.6

210021002100

808079

3.813.813.76

0.800.800.79

2 C H3DT521CU2101,2 120240277

0.410.200.18

1.001.001.00

48.748.648.5

420042004200

868687

2.052.062.06

0.860.860.87

14W(21.6in [549mm])

1 C H3DT514CU1101,2 120240277

0.160.080.07

1.001.001.00

19.219.219.4

135013501350

707070

5.215.215.16

0.730.730.72

2 C H3DT514CU2101,2 120240277

0.300.150.13

1.001.001.00

36.036.036.0

270027002700

757575

2.782.782.78

0.780.780.78

Hi-lume® 3D Ballasts for Linear T5 Lamps For proper dimming all lamps must comply to accepted standards, 14 W (60081-IEC-6520), 21 W (60081-IEC-6530) and 28 W (60081-IEC-6640)Not for use with Reduced Wattage Lamps

Notes: 1.BAAmodelsavailable.Adda"U"toprefixofmodelnumberwhenordering(ie:UH3DT832CU110).2.NOMapprovedmodelsavailable.Adda"N"tosuffixofmodelnumberwhenordering(ie:H3DT832CU110N).3. Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specific data.

Page 6: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 6 09.04.12

Lamp Type

Lamp Watts (length)

Lamps per Ballast

Case Size

Hi-lume® 3D Model Number

Input Voltage (V~)

Ballast Current (A)

Ballast Factor (BF)

Input Power (W)

System Lumens3 (lm)

System Efficacy3 (lm/W)

Ballast Efficacy Factor (BEF)

Relative System Efficacy (RSE)

T5HO 54W(45.2in [1148mm])

1 C H3DT554CU1101,2 120240277

0.540.260.23

1.001.001.00

64.862.463.7

500050005000

778078

1.541.601.57

0.830.870.85

2 C H3DT554CU2101,2 120240277

0.950.480.42

1.001.001.00

114.0115.2116.3

100001000010000

888786

0.880.870.86

0.950.940.93

39 W(33.4in [848mm])

1 C H3DT539CU1101,2 120240277

0.370.190.17

1.001.001.00

44.444.946.0

350035003500

797876

2.252.232.17

0.880.870.85

2 C H3DT539CU2101,2 120240277

0.700.350.29

1.001.001.00

84.084.081.4

700070007000

838386

1.191.191.23

0.930.930.96

24W(21.6in [549mm])

1 C H3DT524CU1101,2 120240277

0.250.120.10

1.001.001.00

30.028.827.7

200020002000

676972

3.333.473.61

0.800.830.87

2 C H3DT524CU2101,2 120240277

0.460.230.20

1.001.001.00

54.655.255.4

400040004000

737272

1.831.811.81

0.880.870.87

Hi-lume® 3D Ballasts for Linear T5HO Lamps For proper dimming all lamps must comply to accepted standards, 24W (60081-IEC-6620), 39 W (60081-IEC-6730), 54 W (60081-IEC-6840) Not for use with Reduced Wattage Lamps

Notes: 1.BAAmodelsavailable.Adda"U"toprefixofmodelnumberwhenordering(ie:UH3DT832CU110).2.NOMapprovedmodelsavailable.Adda"N"tosuffixofmodelnumberwhenordering(ie:H3DT832CU110N).3. Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specific data.

Page 7: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 7 09.04.12Hi-lume® 3D Ballasts for Twin-Tube T5 Lamps Not for use with Reduced Wattage Lamps

Lamp Type

Lamp Watts (length)

Lamps per Ballast

Case Size

Hi-lume® 3D Model Number

Input Voltage (V~)

Ballast Current (A)

Ballast Factor (BF)

Input Power (W)

System Lumens2 (lm)

System Efficacy2 (lm/W)

Ballast Efficacy Factor (BEF)

Relative System Efficacy (RSE)

T5 Twin-Tube

50 W(22.5in [572mm])

1 G H3DT550GU1101 120240277

0.450.230.20

1.001.001.00

53.554.654.8

400040004000

757373

1.871.831.82

0.930.920.91

2 G H3DT550GU2101 120240277

0.840.420.36

1.001.001.00

99.899.898.7

800080008000

808081

1.001.001.01

1.001.001.01

40W(22.5in [572mm])

1 G H3DT540GU1101 120240277

0.360.180.16

1.001.001.00

42.842.843.9

310031003100

727271

2.342.342.28

0.930.930.91

2 G H3DT540GU2101 120240277

0.640.320.27

1.001.001.00

76.076.074.0

620062006200

828284

1.321.321.35

1.051.051.08

3 G H3DT540GU3101 120240277

0.950.470.40

1.001.001.00

112.9111.7109.7

930093009300

828385

0.890.900.91

1.061.071.09

36W(15.5 in [394mm])

1 G H3DT536GU1101 120240277

0.330.170.14

1.001.001.00

39.240.438.4

285028502850

737174

2.552.482.60

1.020.991.04

2 G H3DT536GU2101 120240277

0.610.310.26

1.001.001.00

72.573.771.3

570057005700

897770

1.381.361.40

1.101.091.12

Notes: 1.NOMapprovedmodelsavailable.Adda"N"tosuffixofmodelnumberwhenordering(ie:H3DT832CU110N).2.Actualnumbermayvarywithlampmodel.Pleaseconsultlampmanufacturerforlamp-specificdata.

Page 8: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 8 09.04.12

AB

C

D

Case Dimensions

CA 18.00in(457mm)

B 17.68in(449mm) (mounting center)

C 1.0in(25mm)

D 1.18 in (30 mm)

GA 9.5in(241mm)

B 8.9in(226mm) (mounting centers)

C 7.1in(180mm)

D 1.0in(25mm)

E 2.38in(60mm)

AB

CD

E

AB

C

D

Page 9: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 9 09.04.12

Hi-lume® 3D Dimmer Wiring

3-Wire Control Wiring

WARNING: Shock hazard. May result in serious injury or death. Disconnect power before servicing or installing.

•MakesurethatthesupplybreakertotheDigital Ballast is OFF when wiring

•Wireasshown

Line input: Connects to:Hot DimmerBlackWireNeutral Dimmer White Wire

Dimmer wire: Connects to:Yellow Ballast Orange (DH)Red BallastBlack(HOT)White BallastWhite(NEU)Green Earth Ground

•Hi-lume® 3D ballast line voltage and 3-wire input terminalsacceptone18to16AWG(0.75to1.5 mm2) solid copper wire per terminal.

Emergency

•ForemergencywiringpleaseseeLutron® AppNote#106.

E1E2

NEU LINE

HOTDH

Class 2Bus

E1E2

NEU

HOTDH

Class 2Bus

LUTRON

LINEHot / Black

3-Wire Dimmer

Ground

Green

GroundRed

Yellow

Whi

te

Ora

nge

Black

White

Neutral

Ground

Page 10: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 10 09.04.12

Hi-lume® 3D Wiring Diagrams

E1E2

NEU

HOTDH

Class 2Bus

E1E2

NEU

HOTDH

Class 2Bus

LINELINE

Ballast Terminals

Ballast Terminals

EcoSystem® Digital Link Overview

•TheEcoSystem®DigitalLinkwiring(E1andE2)connects digital ballasts and drivers together to form a lighting control system.

•SensorsdonotdirectlyconnecttoHi-lume® 3D ballasts.•E1andE2(EcoSystem®digitallinkwires)arepolarity

insensitive and can be wired in any topology.•AnEnergiSavrNodeTM with EcoSystem® unit,

GRAFIK Eye® QS control unit with EcoSystem®, or Quantum® dimming module with EcoSystem® provides power for the EcoSystem®digitallinkwhichsupportsupto64digitalballastsorLEDdrivers,64 occupantsensors,16daylightsensorsand64wallstationsorIRreceivers.

•PowPakTM dimming module with EcoSystem® provides power for the EcoSystem®digitallinkwhichsupportsupto32digitalballastsorLEDdrivers, 6 occupantsensors,1 daylightsensorand9 Pico® wireless controllers.

•AllEcoSystem®DigitalLinkprogrammingiscompletedby using the Energi Savr App for an Apple iPad, iPod Touch or iPhonemobiledigitaldevice;GRAFIKEyeR QS with EcoSystem®,PowPakT dimming module with EcoSystem® ; or Quantum® System.

•Forcompleteinformation,seeEcoSystem® Design & ApplicationGuide(P/N367-1533).

•ForemergencywiringpleaseseeLutron®AppNote#106.

EcoSystem® Digital Link Wiring

•BallastEcoSystem®DigitalLinkterminalsacceptone18to16 AWG(0.75to1.5 mm() solid copper wire per terminal.

•MakesurethatthesupplybreakertotheDigitalBallastand EcoSystem®DigitalLinkSupplyisOFFwhenwiring.

•ConnectthetwoconductorstothetwoDigitalBallastterminalsE1andE2asshown.

•UsingtwodifferentcolorsforE1andE2willreduceconfusion when wiring several ballasts together.

•TheEcoSystem®DigitalLinkmaybewiredClass1orClass2.Consultapplicableelectricalcodesforproperwiring practices.

Notes

•TheEcoSystem®DigitalLinkSupplydoesnothavetobelocatedattheendoftheDigitalLink.

•EcoSystem®DigitalLinklengthislimitedbythewiregaugeusedforE1andE2asfollows:

Wire Gauge Maximum Digital Link Length

12AWG 2200ft14AWG 1400ft16AWG 900 ft18 AWG 550 ft

Wire Size Maximum Digital Link Length

4.0mm( 825m2.5mm( 515 m1.5 mm( 310 m1.0 mm( 205m0.75mm( 155 m

To the EcoSystem® DigitalLink Supply

Apple, iPad and iPhoneR aretrademarksofAppleInc.,registeredintheU.S.andothercountries.

Page 11: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 11 09.04.12

Wiring to One Lamp (C case shown)

NOTICE

•Maximumballasttolampsocketleadlengthis7ft(2m)•Wirecolorsshownarelabeledontheballast,butmayvarydependinguponfixtureconstruction

BLUBLU

REDRED

BLUBLU

REDRED

YELYEL

Blue

Red

Wiring to Two Lamps (C case shown)

Blue

Yellow

Red

Hi-lume® 3D Ballast Wiring Diagrams — T8, T5, and T5HO linear lamps

Page 12: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 12 09.04.12

NOTICE

•Maximumballasttolampsocketleadlengthis7ft(2m)•Wirecolorsshownarelabeledontheballast,butmayvarydependinguponfixtureconstruction

BLUBLU

REDRED

YELYEL

N/CN/C

BLUBLU

REDRED

YELYEL

B/WB/W

Wiring to Two Lamps (G case shown)

Wiring to Three Lamps (G case shown)

Blue

Yellow

Red

Blue

Yellow

Red

Striped

Wiring to One Lamp (G case shown)

BLUBLU

REDRED

N/CN/C

N/CN/C

Blue

Red

Hi-lume® 3D Ballast Wiring Diagrams — T8, T5, and T5HO linear lamps

Page 13: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 13 09.04.12

Hi-lume® 3D Ballast Wiring Diagrams — T5 Twin-Tube

Wiring to One Lamp

Wiring to Two Lamps

BLUBLU

REDRED

NOTICE

•Maximumballasttolampsocketleadlengthis3ft(1m)•Wirecolorsshownarelabeledontheballast,butmayvarydependinguponfixtureconstruction

BLUBLU

REDRED

YELYEL

Blue

Red

Yellow

Blue

Red

Wiring to Three Lamps

BLUBLU

REDRED

YELYEL

B/WB/W

Red

Yellow

Blue

Striped

Page 14: Hi-lume 3D Overview - W. W. GraingerFluorescent Dimming Ballasts Hi-lume ® 3D Architectural Dimming 369280h 1 09.04.12 Hi-lume ® 3D Overview Hi-lume ® 3D architectural electronic

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Fluorescent Dimming Ballasts Hi-lume® 3D Architectural Dimming

369280h 14 09.04.12

ATTENTION ELECTRICIANS AND CONTRACTORS

Ballast/Socket LeadsLeadlengthsfromballasttosocketmustnotexceed7 ft(2 m)forT8,T5,andT5HOlinearlamps.

Lamp SocketsLutronrequiresandNEMA®recommendssocketscomplyingwithIEC60400.InspectsocketsformarkstoensurethesocketcomplieswithIEC60400. Twoexamplesofthesemarksare:E and Q. Socketsmust have a Zmarkaswell.UseRapidStartsockets.DO NOTuseInstantStartsockets.SeeLutron® AppNote#122orNEMA®docLSD-34-2006.

Lamp Socket Wiring TesterUseSocketTester(FDB-LSWT-T5/T8)toverify proper lamp holder wiring.Available for purchase at www.lutronstore.com

Lamp MountingManyfluorescentlampsocketsareavailablewithmounting slots to vary the height of the lamp away from the grounded metal surface. Having a fluorescent lamp too close to the grounded metal will reduce lamp life. Having a fluorescent lamp too far awayfromthegroundedmetalwillmakethelampflickerornotturnonatall.Pleasenotethatallofthelamp heights are measured between the grounded metal surface and the glass wall of the lamp.

Mounting for T8 LampsMountlamps1/8to3/4in(3.2to19mm)awayfromthe grounded metal surface.

Mounting for T5 and T5HO LampsMountlamps1/16to3/8in(1.6to9.5mm)awayfromthe grounded metal surface.

Mounting for T5 Twin Tube LampsMountlamps1/16to1/2in(1.6to13mm)awayfromthe grounded metal surface.

Ballast Operating TemperatureBallastcasetemperaturemustnotexceed75 °Catany point on the ballast.

Cold Air FlowEnsurethatnocoldair(fromHVACsystem,etc)isblowingacrossthelamps.CoolingthelampwillcauseperformanceissuesasnotedinNEMA LSD-34.

Wiring and GroundingBallast and lighting fixture must be effectively grounded. Ballasts must be installed per national and local electrical codes.

ATTENTION FACILITIES MANAGERS

PERFORMANCE

Lamp SeasoningConsultlampmanufacturer’srecommendationsonlamp seasoning prior to dimming.

SERVICE

Replacement PartsUseLutron® replacement parts with exact model numbers.ConsultLutronifyouhaveanyquestions.

Further InformationFor further information, please visit us at www.lutron.com/ballastsorcontactour24-hourTechnicalSupportCenterat1.800.523.9466.

IMPORTANT: Lamps must never touch ground plane and should be placed without obstruction.

Lamp Lamp Socket(side view)

Mounting height

Grounded metalBallast