high efficiency condensing systems

16
High efficiency condensing systems Commercial applications

Upload: baxi-spa

Post on 10-Mar-2016

224 views

Category:

Documents


0 download

DESCRIPTION

high efficiency condensing systems

TRANSCRIPT

Page 1: high efficiency condensing systems

High efficiency condensing systems

Commercial applications

Page 2: high efficiency condensing systems

2

Condensing technology is the latest face in boiler innovation. By employing

pre-mix burner know how, condensing boilers ensure higher performance

(efficiency up to 109,8%) thanks to the recovery of all the heat available

through combustion without wasting energy into the air, as happens with

traditional boilers.

IndexHigh efficiency condensing boilers 4Built-in heat-boxes - Luna Sat 6Luna Platinum 12 - 32 kW 7Luna Duo-tec MP 35 - 110 kW 8Luna HT 45 - 100 kW 9Cabinets (GMC) 10Power HT 45 - 150 kW 12Power HT 230 - 320 kW 13Luna Sat 14

Page 3: high efficiency condensing systems

3

High efficiency condensing systems

High efficiency installationsBaxi condensing systems represent the ideal

solution for installations where high outputs are

required.

The electronics platform of these boilers allows

the control of single and cascade installations and

a complete range of thermoregulation accessories.

It is therefore possible to have high energetic

efficiency system ensuring low emissions and

meeting any domestic comfort needs, total control,

DHW at the right comfort level always in the

maximum respect of the environment.

High modulation ratio The new ranges of high efficiency condensing

boilers are distinguished by a wider modulation

ratio that grants a better efficiency thanks to

reduced switch-on/ switch-off of the boiler.

Cutting edge electronics The sophisticated electronics of the high efficiency

condensing boilers allows to manage single or

cascade installation up to 16 boilers ( Luna Duo-

tec MP or Power HT 230-320). It is just needed

to connect the relevant accessories to the boiler’s

electronics.

Compact weight and dimensions Compact weight and dimensions of Baxi high

efficiency condensing systems, guarantee the

maximum flexibility and allow their installation also

in small heat generator rooms.

Page 4: high efficiency condensing systems

4

Highefficiency wall hung

condensingboilers

Luna Platinum1.12/1.18

Luna Platinum1.24

Luna Platinum1.32

Highefficiency wall hung

condensingboilers

Luna Duo-tec MP1.35

Luna Duo-tec MP1.50

Luna Duo-tec MP1.60

High efficiency floor

standing condensing

boilers

Power HT 1.450

Maximum Heat Output

80°/60° CkW

12/16,9 2432

Luna Platinum HT

33,8Luna Duo-tec MP

45 55

Maximum Heat Output

50°/30° C kW

13,1/18,4 26,134,9

Luna Platinum HT

36,6Luna Duo-tec MP

48,6Luna Duo-tec MP

48,7Power HT

59,4

A wide range of high efficiency solutions

Luna Platinum

Luna Platinum

Page 5: high efficiency condensing systems

5

High efficiency condensing systems

LunaDuo-tec MP

1.70

LunaDuo-tec MP

1.90

LunaDuo-tec MP

1.110

Power HT 1.650

Power HT 1.850

Power HT 1.1000

Power HT 1.1150

Power HT 1.1200

Power HT 1.1500

Power HT1.230

Power HT1.280

Power HT1.320

65 85

102Luna Duo-tec

MP

100Power HT

112 120 150 210,1 254,5 294

70,2Luna Duo-tec

MP

70,3Power HT

91,8Luna Duo-tec

MP

91,6Power HT

110,2Luna Duo-tec

MP

107,8Power HT

121,1 129,7 162 229,8 278,1 321,3

Baxi high efficiency condensing systems are available in a wide range of outputs from 12 to 320 kW, to satisfy every

installation need (wall hung and floor standing).

Page 6: high efficiency condensing systems

6

Wireless and M-BUS built-in heat boxes

Heating only

Luna SAT RC - Luna SAT RC-MBLuna SAT R/1 - Luna SAT R/1-MB Luna SAT RH - Luna SAT RH-MB

Luna SAT RH1 - Luna SAT RH1-MBLuna SAT RHG1 - Luna SAT RHG1-MB

Luna SAT RP/1 - Luna SAT RP/1-MBLuna SAT RPH - Luna SAT RPH-MB

Luna SAT RPB - Luna RPB-MBLuna SAT RPE - Luna SAT RPE-MB

Luna SAT RPEH - Luna SAT RPEH-MB

Luna SAT R2ZLuna SAT R2Z-MB

Combi

Luna SAT RS - Luna SAT RS-MBLuna SAT RST-MB

Luna SAT RSP - Luna SAT RA Luna SAT RSP-MB

Luna SAT R60 WH-MB(for wall hung installationwith integrated cylinder)

Luna SAT RS2Z - Luna SAT RA2Z

Heating and cooling

Luna SAT R2H - Luna SAT R2H-MB

Without pump (mixing valve) With pump To manage 2 zones

- Luna Sat R/1, RH, RPB, RPE, RPEH, RH1 and RHG1 and RHG1 are available also with built-in flow-meters

(M-BUS models as well)

- RH1 and RH1-MB models are available also with pressure reducer on the flow-meters.

Page 7: high efficiency condensing systems

7

High efficiency condensing systems

Removable control panel for wall-hung installation with •

wide text display, regulation knob, menu selection buttons

and back-lighting supplied with the boiler

Wide modulation ratio up to • 1÷10:betterefficiencythanks

to reduced switch-on/switch-off of the boiler

Gas Adaptive Control (GAC) system: combustion automatic•

controltomaintainconstantlythehighestlevelofefficiency

Integrated control of a solar system•

Complete soundproofing of the generator•

Circulating pump with full modulation•

Frontal access for advanced diagnostics•

Hydraulic system 3 way electric diverter valveStainless steel AISI 316L premixing burnerStainless steel AISI 316L water/flue heat exchangerStainless steel enhaced DHW exchanger to ensure condensation also in DHW modeModulating fan with electronic speed adjusting systemAutomatic by-passMulti-speeds low energy pump of the heating circuit with built- in air ventSystem to prevent pump and diverter valve sticking operating every 24 hoursCentral relief valve set at 3 bar

Thermoregulation systemBuilt-in climatic regulation (outdoor sensor available as optional)Control of multi-zones system optionCascade system installation optionRoom sensor, central heating and sanitary timers included in the control panel

Control system Overheat limit thermostat of the water/flue exchangerHydraulic pressure switch to prevent boiler operating in event of low waterSafety NTC sensor against flues overheatElectronic temperatures control by NTC sensorsFull anti-frost deviceElectronic thermometerDigital central heating pressure gauge

Luna Platinum 12-32 kW

1.12 1.18 1.24 1.32

Product code 7102665 n.a. 7106583 n.a.

Maximum heating heat input kW 12,4 17,4 24,7 33

Maximum heating heat output 80/60°C kW 12 16,9 24 32

Maximum heating heat output 50/30°C kW 13,1 18,4 26,1 34,9

Minimum heating heat output 80/60°C kW 2 2,4 2,4 3,2

Minimum heating heat output 50/30°C kW 2,2 2,7 2,7 3,5

Energetic efficiency (92/42/CEE)

Average efficiency (DIN 4702-T8) % 109,8 109,8 109,8 109,8

Nominal efficiency 80/60°C % 97,8 97,7 97,6 97,6

Nominal efficiency 50/30°C % 105,8 105,8 105,7 105,7

Efficiency 30% % 107,8 107,7 107,6 107,6

NOx class (EN 483) 5 5 5 5

Minimum working temperature °C -5 -5 -5 -5

Expansion vessel capacity/pre-charge l/bar 8/0,8 8/0,8 8/0,8 10/0,8

Heating temperature range. °C 25/80 25/80 25/80 25/80

Maximum pressure heating circuit bar 3 3 3 3

Coaxial flue system Ø 60/100 max length m 10 10 10 10

Dual flue system Ø 80 max length m 80 80 80 80

Maximum flue mass flow rate kg/s 0,006 0,008 0,012 0,016

Minimum flue mass flow rate kg/s 0,001 0,001 0,001 0,002

Maximum flue temperature °C 75 75 80 80

Dimensions (h x w x d) mm 760 x 450 x 345

Net weight kg 34,5 34,5 34,5 37,5

Gas type Natural Gas

Power consumption W 108 122 120 130

Grade of protection IPX5D IPX5D IPX5D IPX5D

Page 8: high efficiency condensing systems

8

Stainless steel AISI 316L single chamber•

(35 – 50 – 60 – 70 kW) and double chamber (90 – 110 kW)

exchanger: high output in compact size, reliability

and long life.

High modulation ratio (1• ÷9):betterefficiencythanks

to reduced switch-on/switch-off of the boiler

Digital control panel with push buttons and wide LCD •

display (numbers and symbols)

Compact size and minimal weight•

Complete range of accessories for single and cascade •

installations

Luna Duo-tec MP 35-110 kW

1.35 1.50 1.60 1.70 1.90 1.110

Product code 7106815 7104050 7104051 7104052 7104651 7104652

Maximum heating heat input kW 34,8 46,3 56,6 66,9 87,4 104,9

Maximum heating heat output 80/60°C kW 33,8 45 55 65 85 102

Maximum heating heat output 50/30°C kW 36,5 48,6 59,4 70,2 91,8 110,2

Minimum heat output 80/60°C kW 5 5 6,1 7,2 9,4 11,4

Minimum heat output 50/30°C kW 5,4 5,4 6,6 7,8 10,2 12,3

Energetic efficiency 92/42/CEE HHHH HHHH HHHH HHHH HHHH HHHH

Average efficiency (DIN 4702-T8) % 109,8 109,8 109,8 109,8 109,8 109,8

Nominal efficiency 80/60°C % 97,2 97,2 97,2 97,2 97,2 97,2

Nominal efficiency 50/30°C % 105 105 105 105 105 105

Efficiency at 30% % 107,7 107,8 107,4 107,1 107,5 107,4

NOx class (EN 483) 5 5 5 5 5 5

Minimum working temperature °C -5 -5 -5 -5 -5 -5

Water content lt 4 4 5 6 9 10

Heating system max pressure bar 4 4 4 4 4 4

Safety valve intervention pressure bar 4 4 4 4 4 4

Regulation of water temperaturein heating circuit

°C 25/80 25/80 25/80 25/80 25/80 25/80

Coaxial flue system max length m 10 (ø 80/125) 10 (Ø 80/125) 10 (ø 80/125) 10 (ø 80/125) 10 (ø 110/160) 10 (ø 110/160)

Dual flue system max length m 60 (ø 80) 60 (ø 80) 60 (ø 80) 60 (ø 80) 27 (ø 110) 27 (ø 110)

Maximum flue mass flow rate kg/s 0,016 0,021 0,026 0,031 0,04 0,047

Minimum flue mass flow rate kg/s 0,002 0,002 0,003 0,004 0,005 0,005

Maximum flue temperature °C 76 80 80 74 70 70

Dimensions (h x w x d) mm 766x450x377 766x450x377 766x450x377 766x450x505 952x600x584 952x600x584

Net weight kg 40 40 40 50 83 93

Gas type Nat. gas/LPG

Power consumption W 180 190 210 210 275 320

Grade of protection IPX5D IPX5D IPX5D IPX5D IPX5D IPX5D

Outputs from 35 to 110 kW

Hydraulic system Modulating pump included in the boilerSystem to prevent pump sticking operating every 24 hoursFlow and return NTC sensorsWater tray for condensate drain from supply air duct

Thermoregulation systemBuilt-in climatic regulation (outdoor sensor supplied as optional)Mixed zones systems (high and low temperatures) installation optionCascade system installation option (up to 16 boilers)NTC sensor for DHW cylinder control optionHeating and DHW timers integrated in the control panel

Control system Full electronic anti-frost deviceElectronic thermometerCentral heating pressure gaugeFlow over-temperature thermostat

Page 9: high efficiency condensing systems

9

High efficiency condensing systems

1.450 1.450P* 1.550 1.650 1.850 1.1000

Product code HSB 43545300 43545364 43555300 43565300 43508500 43510000

Maximum heating heat input kW 46,4 46,4 56,7 67 87,2 105

Maximum heating heat output 80/60°C kW 45 45 55 65 85 102

Maximum heating heat output 50/30°C kW 48,7 48,7 59,5 70,3 91,6 110,3

Minimum heat output 80/60°C kW 14,5 14,5 15,5 19,3 25,7 29

Minimum heat output 50/30°C kW 15,8 15,8 16,8 21 27,8 31,4

Energetic efficiency 92/42/CEE HHHH HHHH HHHH HHHH HHHH HHHH

Average efficiency (DIN 4702-T8) % 109,8 109,8 109,8 109,8 109,8 109,8

Nominal efficiency 80/60°C % 97,3 97,3 97,4 97,4 97,5 97,4

Nominal efficiency 50/30°C % 105,1 105,1 105,0 105,2 105,1 105,1

Efficiency at 30% % 107,6 107,6 107,5 107,6 107,3. 107,4

NOx class (EN 483) 5 5 5 5 5 5

Minimum working temperature °C -5 -5 -5 -5 -5 -5

Water content lt 5,1 5,1 5,6 6,5 13,7 21

Heating system max pressure bar 4 4 4 4 4 4

Safety valve intervention pressure bar 3 3 3 3 3 3

Regulation of water temperaturein heating circuit

°C 25/80 25/80 25/80 25/80 25/80 25/80

Coaxial flue system max length m 10 (ø 80/125) 10 (Ø 80/125) 10 (ø 80/125) 10 (ø 80/125) 10 (ø 110/160) 10 (ø 110/160)

Dual flue system max length m 60 (ø 80) 60 (ø 80) 60 (ø 80) 60 (ø 80) 27 (ø 110) 27 (ø 110)

Maximum flue mass flow rate kg/s 0,022 0,022 0,027 0,032 0,041 0,050

Minimum flue mass flow rate kg/s 0,007 0,007 0,008 0,010 0,013 0,015

Maximum flue temperature °C 74 74 78 75 74 79

Dimensions (h x w x d) mm 950x600x466 950x600x466 950x600x466 950x600x466 950x600x650 950x600x650

Net weight kg 64 64 68 72 94 98

Gas type Nat. gas/LPG

Power consumption W 75 75 80 125 150 200

Grade of protection IPX5D IPX5D IPX5D IPX5D IPX5D IPX5D

Outputs from 45 to 100 kW

Hydraulic system Stainless steel AISI 316L premixing burnerStainless steel AISI 316L water/flue exchangerSystem to prevent pump sticking

operating every 24 hours

Thermoregulation systemRemote controller and climatic regulator (supplied as optional)Built-in climatic regulation (outdoor sensor supplied as optional)Mixed zones systems (low and high temperature) installation option Cascade system installation optionNTC sensor for DHW cylinder control optionHeating and DHW timers integrated in the

control panel

Control system Central heating and indirect cylinder timerHydraulic pressure switch to prevent boiler operating in the event of low waterFull electronic anti-frost deviceElectronic thermometerCentral heating pressure gauge

Stainless steel double chamber exchanger: high output in •

compact size, reliability and long life

Digital control panel “advanced CPS system” with push •

buttons and wide LCD display with text and symbols

Minimal weight and size•

Complete range of accessories for single and cascade •

installations

(*) Model with integrated pump

Luna HT 45-100 kW

Page 10: high efficiency condensing systems

10

Minimum overall dimensions and maximum •

compactness

Easy installation in heating systems renovation •

Highflexibility:possibilitytoconnectupto3cabinets•

withflowandreturnhydraulicconnectionsontheleft

or on the right side

Easy installation and quick connection•

Easy handling with a mechanical power-lift option•

Hydraulic systemHydraulic connections between boilers and copper collectorsIntegration of the hydraulic safety accessoriesExpansion vessels includedFlow/return right or left side

* to install the hydraulic compensator and the system accessories sheltered from the bad weather it is possible to order an additional cabinet

CABINETmade of:

N° of installed Boilers

LUNA HT possible

configurationTot. installed kW

2 doors*

or

1.4501.550 1.650

4555658590

100110120130170185200

1.8501.1000

3 doors*

or

1.4501.550 1.650

90 100 110 120 130 135145155165 170175185195 200255270285300

1.8501.1000

Cabinets with condensinghigh efficiency boilers (GMC)

Page 11: high efficiency condensing systems

11

High efficiency condensing systems

Baxi has developed cabinets where Luna HT boilers can be installed to have high performance (efficiency up to 109,8%) and low

pollutant emissions. The range of Baxi cabinets allows solutions up to 3 doors, from 45 kW (1 cabinet with 2 doors 1x45 kW) to

600 kW ( 2 cabinets with 3 doors 3x100 kW). They are ideal for centralized, commercial applications and buildings.

It is possible to integrate them with the Baxi wide range of heat-boxes, LUNA SAT.

Integrated and compact system by Baxi for centralized, commercial installations and buildingsCabinets with condensing

high efficiency boilers (GMC)

Return manifoldEletricbox(not included)

Condensing trap

Cabinet

Manifold (flow/return/gas)

Holes for handling

Flow manifold

Dual flue terminal

Hydraulic separator (not included). It is made of:- frame- pipes- separator

Page 12: high efficiency condensing systems

12

Hydraulic system Stainless steel AISI 316L premixing burnerStainless steel AISI 316L water/flue exchangerSystem to prevent pump sticking operating every 24 hours

Thermoregulation system Remote controller and climatic regulator (supplied as optional)Built-in weather compensation function (outdoor sensor supplied as optional)Mixed zones systems (low and high temperature) installation option Cascade system installation optionNTC sensor for DHW cylinder control option

Control system Central heating and indirect cylinder timerHydraulic pressure switch to prevent boiler operating in event of low waterFull electronic anti-frost deviceElectronic thermometer Central heating pressure gauge

Power HT 45-150 kW

Outputs from 45 to 150 kW

1.450 1.650 1.850 1.1000 1.1150 1.1200 1.1500

Product code WHS 43104560 43106560 43108560 43110060 43111260 43112060 43115060

Maximum heating heat input kW 46,4 67 87,2 102,7 115 123,2 154

Maximum heating heat output 80/60°C kW 45 65 85 100 112 120 150

Maximum heating heat output 50/30°C kW 48,7 70,3 91,6 107,8 121,1 129,7 162

Minimum heat output 80/60°C kW 11,8 13,4 32,2 35,8 39 39 40,4

Minimum heat output 50/30°C kW 12,8 14,5 34,9 38,8 42,1 42,1 43,7

Energetic efficiency 92/42/CEE HHHH HHHH HHHH HHHH HHHH HHHH HHHH

Average efficiency (DIN 4702-T8) % 109,8 109,8 109,8 109,8 109,8 109,8 109,8

Nominal efficiency 80/60°C % 97,3 97,3 97,5 97,4 97,4 97,4 97,4

Nominal efficiency 50/30°C % 105,2 105,3 105,1 105 105,3 105,3 105,2

Efficiency at 30% % 107,6 107,6 107,3 107,4 107,5 107,5 107,2

NOx class (EN 483) 5 5 5 5 5 5 5

Minimum working temperature °C -5 -5 -5 -5 -5 -5 -5

Safety valve intervention pressure bar 3 3 3 3 3 3 3

Heating system max pressure bar 4 4 4 4 4 4 4

Regulation of water temperaturein heating circuit

°C 25/80 25/80 25/80 25/80 25/80 25/80 25/80

Primary circuit water flow (ΔT=20°C) l/h 1.935 2.795 3.700 4.300 4.800 5.200 6.500

Water content l 5,1 6,5 13,7 21 23,3 23,3 25,3

Flue tube ø mm 80 80 100 100 100 100 100

Flue ducts max length m 30 20 20 20 20 20 20

Maximum flue mass flow rate kg/s 0,022 0,031 0,041 0,049 0,054 0,059 0,073

Minimum flue mass flow rate kg/s 0,006 0,007 0,016 0,018 0,019 0,019 0,02

Maximum flue temperature °C 72 73 78 80 72 77 75

Dimensions (h x w x d) mm 850x450x621 850x450x693 850x450x801 850x450x871 850x450x1024 850x450x1024 850x450x1132

Net weight kg 60 68 75 83 95 95 103

Gas type Nat. gas/LPG

Power consumption W 90 110 100 160 128 135 235

Stainless steel double chamber exchanger: high output in •

compact size, reliability and long life

Digital control panel “advanced CPS system” with push •

buttons and wide LCD display with text and symbols

Complete range of temperature regulation accessories•

Minimal weight and size•

Complete range of accessories for single •

and cascade installations

Page 13: high efficiency condensing systems

13

High efficiency condensing systems

Hydraulic system Hydraulic connections on the rear sideSticking pump check systemFlow and return NTC sensorsPremixed low-emissions burner

Thermoregulation system Built-in climatic regulation (outdoor sensor supplied as optional)Mixed zones systems (high and low temperatures) installation optionCascade system installation option (up to 16 boilers)NTC sensor for DHW cylinder control optionHeating and DHW timers integrated in the control panel

Control system Full electronic anti-frost deviceElectronic thermometerFlow over-temperature thermostat

Power HT 230-320 kW

Outputs from 230 to 320 kW

Aluminium-Silicon exchanger with glass wool insulation:•

highefficiencyandreliability

High modulation ratio (1• ÷6)

Digital control panel with knob, buttons and wide •

backlighted LCD display with text and symbols

Easy to transport and to install•

Quiet operation•

Power HT 1.230 Power HT 1.280 Power HT 1.320

Product code LSX 411230600 . 411280600 . 411320600 .Nominal heat output kW 215,0 260,0 300,0

Maximum heating heat output 80/60°C kW 210,1 254,5 294,0

Maximum heating heat output 50/30°C kW 229,8 278,1 321,3

Minimum heat output 80/60°C kW 33,5 40,2 45,9

Minimum heat output 50/30°C kW 37,4 44,9 51,4

Energetic efficiency 92/42/CEE

Average efficiency (DIN 4702-T8) % 109,6 109,7 109,7

Nominal efficiency 80/60°C % 97,9 98,0 98,0

Nominal efficiency 50/30°C % 106,9 107,0 107,1

Efficiency at 30% % 105,4 105,6 105,7

NOx Class (EN 483) 5 5 5

Minimum working temperature °C -5 -5 -5

Heating system max pressure bar 6 6 6

Water content lt 38 45 53

Flue ducts max length m 60 (Ø200) 60 (Ø200) 60 (Ø200)

Maximum flue mass flow rate kg/s 0,097 0,118 0,136

Minimum flue mass flow rate kg/s 0,016 0,019 0,021

Maximum flue temperature °C 61 60 60

Dimensions (h x w x d)* mm 1458x692x1231 1458x692x1324 1458x692x1417

Net weight kg 285 314 344

Gas type Natural Gas / LPG

Power consumption W 330 350 410

(*) Flue ducts and hydraulic pipes included

Page 14: high efficiency condensing systems

14

Luna Sat-Heating only models

R/1: KSV 71411151R/1-MB: KSV 71411541

RC: KSV 71413111RC-MB: KSV 71413121

RP/1: KSV 71411161RP/1-MB: KSV 71411551

R2Z: KSV 71410101R2Z-MB: KSV 71411901

RH: KSV 71411321RH-MB: KSV 71411591

RPH: KSV 71411331RPH-MB: KSV 71411601

RPE: KSV 71411911RPE-MB: KSV 71411921

RPEH: KSV 71412451RPEH-MB: KSV 71412461

RPB: KSV 71411171RPB-MB: KSV 71411581

RH1: KSV 71411811RH1-MB: KSV 71411851

RHG1: KSV 71412361RHG1-MB: KSV 71412371

R2H: KSV 71412041R2H-MB: KSV 71412051

RC R/1 RP/1 R2Z RH RPH RPB RPE RPEH RH1 RHG1 R2H**

Models with pump - - • • - • • • • - - -

Models with 2nd zone - - - • - - - - - - - -

Heating temperature regulationwith high climatic curve °C - - - 25/80 - - - 25/80 - - - -

Heating circuit maximum pressure bar 4 4 4 4 4 4 4 4 4 4 4 4

Water contents I 0,5 1,5 2 3,5 1,5 2 2 2 2 1,5 2 1,5

Power supply voltage V 230 230 230 230 230 230 230 230 230 230 230 230

Power supply frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50

Power consumption W 15 15 110 210 15 110 110 110 110 15 15 15

Width of the case mm 450 600 600 800 650 600* 600 600 600 400* 500 800

Height of the case mm 450 650 650 750 650 716* 650 650 850 600* 850 750

Depth of the case mm 110 150 150 150 150 150* 150 150 150 200* 150 150

Net weight Kg 3,2 11 13 22 11 13 12 13,50 14 9 13 9

Maximum temperatureof the warm fluid (inlet)

°C 90 90 90 90 90 90 90 90 90 90 90 90

Feed flow (inlet) l/h700÷

1000 l/h700÷

1000 l/h700÷

1000 l/h700÷

1000 l/h700÷

1000 l/h700÷

1000 l/h700÷

1000 l/h700÷

1000 l/h700÷

1000 l/h700÷

1000 l/h700÷

1000 l/h700÷

1000 l/h

Flow-losses kPa 20Kpa at 700 l/h

20Kpa at 700 l/h

20Kpa at 700 l/h

20Kpa at 700 l/h

20Kpa at 700 l/h

20Kpa at 700 l/h

20Kpa at 700 l/h

20Kpa at 700 l/h

20Kpa at 700 l/h

20Kpa at 700 l/h

20Kpa at 700 l/h

20Kpa at 700 l/h

(*) The case can not be used. Measures are referred to RPH and RH1 models without casing including interception taps (**) For heating and cooling

Page 15: high efficiency condensing systems

15

High efficiency condensing systems

Luna Sat-Heatingand DHW production models

RS: KSV 71410081RS-MB: KSV 71411561

RSP: KSV 71410091RSP-MB: KSV 71411571

RS2Z: KSV 71410111

RA: KSV 71410771 R60WH-MBKSV 71413071

RST-MB: KSV 71413971RA2Z: KSV 71410781

RS RSP RS2Z RA R60WH RA2Z RSTDHW production • • • • • • •

Models with pump - • • • • • -

Models with 2nd zone - - • - - • -

Heating temperature regulation withhigh climatic curve

°C 25/80 25/80 25/80 25/80 25/80 25/80 25/80

DHW regulation °C 30/60 30/60 30/60 30/65 30/65 30/65 30/60

DHW production with ΔT=35°Cand inlet water temperature 75°C

l/m 14,3 14,3 14,3 14,3 14,3 14,3 14,3

Heating circuit maximum pressure bar 4 4 4 4 4 4 4

DHW circuit maximum pressure bar 8 8 8 8 8 8 8

DHW circuit minimum pressure bar 0,2 0,2 0,2 0,2 0,2 0,2 0,2

Water contents l 2 2,5 4 2 5 4 2

Power supply voltage V 230 230 230 230 230 230 230

Power supply frequency Hz 50 50 50 50 50 50 50

Power consumption W 15 110 210 150 110 210 15

Width of the case mm 600 600 800 600 910 800 600

Height of the case mm 650 650 750 650 450 750 600

Depth of the case mm 150 150 150 150 473 150 150

Net weight Kg 16 18 28 16 38 25 16

Maximum temperatureof the warm fluid (inlet)

°C 90 90 90 90 90 90 90

Feed flow (inlet) l/h 1000÷ 1500 1000÷ 1500 1000÷ 1500 1000÷ 1500 1000÷ 1500 1000÷ 1500 1000÷ 1500

Flow-losses kPa 20Kpa at 700 l/h 20Kpa at 700 l/h 20Kpa at 700 l/h 20Kpa at 700 l/h 20Kpa at 700 l/h 20Kpa at 700 l/h 20Kpa at 700 l/h

Page 16: high efficiency condensing systems

QualityEnvironment

Safety

QualityEnvironment

Safetyare Baxi strategic aims and the awarded certifications

ensure compliance with the specific regulations

The Company assumes no responsibility for any possible contents mistakes, and reserves the right to make changes in products, due to technical or commercial demands, at any time without notice.

Baxi S.p.A. 06-11 (E)

36061 BASSANO DEL GRAPPA (VI) - ITALYVia Trozzetti, [email protected]