    HIGH PRESSURE FITTINGS

    WEEK 13

    08:38

    1

  • 7/28/2019 High Pressur Fittings - Week 13

    2/39

    LEARNING

    OBJECTIVES

    A boiler and pressure vessel.

    A level 1 boilerand a critical pressure boiler.

    The various pressure fittings used on boilers.

    The types of safety valves on boilers.

    The components of a boilergauge glass.

    The proper procedures for removing a boilersgauge glass from service, disassembly of thegauge, inspection and replacement and rebuild of atypical gauge glass.

    08:38

    2

  • 7/28/2019 High Pressur Fittings - Week 13

    3/39

    BOILER

    A steam boiler is a closed

    pressure vessel in which

    water is heated to generate

    saturated steam.

    The water is heated by the

    gasses of combustion.

    A pressure vessel that

    produces hot water heated

    by the gasses of combustionis also a boiler.

    08:38

    3

  • 7/28/2019 High Pressur Fittings - Week 13

    4/39

    BOILER - CLASSIFICATION

    Boilers can be divided into two

    pressure related categories:

    Low pressure boilers operating

    at 15 psi and below.

    High pressure boilers operating

    above 15 psi.

    08:38

    4

  • 7/28/2019 High Pressur Fittings - Week 13

    5/39

    Boilers can also be categorized into Level ratings. A Level 1 boileris

    When the temperature and pressure of a boiler equals 1500 ormore.

    All of the components of a level one boiler designed with a safetyfactor of 5 and are tested and given serial numbers.

    08:38

    5

  • 7/28/2019 High Pressur Fittings - Week 13

    6/39

    SAFETY?

    Ultimate strength divided by

    allowable working stress or

    bursting pressure divided

    by safe working pressure.

    It can vary between four

    and seven depending on

    age, type of construction,

    and condition.

    Use five for mostcalculations

    08:38

    6

    (R)(FS)

    EtTSp

  • 7/28/2019 High Pressur Fittings - Week 13

    7/39

    CRITICALPRESSURE

    Many boilers operate atpressures 1000 to 3000 psi.

    Some operate at criticalpressure 3206 psi and

    705.08oFCritical pressure is the

    pressure at which steamand water at the samedensity.

    All critical pressure boilersmust have separate apump to create circulation.

    08:38

    7

  • 7/28/2019 High Pressur Fittings - Week 13

    8/39

    Drains

    All steam and

    water sections

    must havethese.

    The

    superheater will

    have drains.

    The drums and

    headers will

    have drains.

    EXTERNALFITTINGSAND

    CONNECTIONS08:38

    8

  • 7/28/2019 High Pressur Fittings - Week 13

    9/39

    Vent

    high pressure

    globe valve at

    high point in

    the boiler

    used when

    filling and

    emptying the

    boiler.

    EXTERNALFITTINGSAND

    CONNECTIONS08:38

    9

  • 7/28/2019 High Pressur Fittings - Week 13

    10/39

    EXTERNALFITTINGSAND

    CONNECTIONS

    Sampleconnections used for taking

    boiler water

    samples. Drains, vents,

    and samplingconnections willall have highpressure ratedglobe valvesattached to theconnection.

    08:38

    10

  • 7/28/2019 High Pressur Fittings - Week 13

    11/39

    EXTERNALFITTINGSAND

    CONNECTIONS

    Feed stop

    and check

    valves

    to manuallyregulate the

    flow of water

    to the drum.

    08:38

    11

  • 7/28/2019 High Pressur Fittings - Week 13

    12/39

    EXTERNALFITTINGSAND

    CONNECTIONS

    Steam stop

    valves

    located at the

    superheater

    and

    desuperheater

    outlets.

    Used to cut the

    boiler in or out

    of the main

    steam line.

    08:38

    12

  • 7/28/2019 High Pressur Fittings - Week 13

    13/39

    EXTERNALFITTINGSAND

    CONNECTIONS

    Safety valve two types

    (huddlingchamber andnozzle reactiontype).

    They are notrelief valves.

    Question What is the

    differencebetween thesafety andrelief valves?

    08:38

    13

  • 7/28/2019 High Pressur Fittings - Week 13

    14/39

    EXTERNALFITTINGSAND

    CONNECTIONS

    Soot blower

    Fixed and retractable

    08:38

    14

  • 7/28/2019 High Pressur Fittings - Week 13

    15/39

    INTERNALFITTINGS08:38

    15

  • 7/28/2019 High Pressur Fittings - Week 13

    16/39

    08:38

    16

  • 7/28/2019 High Pressur Fittings - Week 13

    17/39

    EXTERNALFITTINGSAND

    CONNECTIONS

    Water gage glass attached

    directly to the drum, they

    allow the operator to see the

    water level in the drum.

    All boilers operating over 400

    psi are required to have two

    independent means of

    determining water level.

    One will be a gauge glass

    attached directly to the steam

    drum; one will be a remote

    water level indicator.

    08:38

    17

  • 7/28/2019 High Pressur Fittings - Week 13

    18/39

    EXTERNALFITTINGSAND

    CONNECTIONS

    Temperature and pressure

    gauges

    Superheated steam flow

    indicators

    08:38

    18

  • 7/28/2019 High Pressur Fittings - Week 13

    19/39

    THEOPERATORCONTROLTHESAFE

    OPERATIONOFTHEBOILERS.08:38

    19

  • 7/28/2019 High Pressur Fittings - Week 13

    20/39

    GAUGE GLASS

    Two independent means

    of indication

    These can consist of two

    gauge glasses attached to

    the drum, or a single gaugeglass, and a remote water

    level indicator.

    A gauge is located so that:

    the lowest visible part of the

    glass is 2 above the lowestpermissible drum water level

    the upper most visible part of

    the glass is located 2 below the

    upper most

    08:38

    20

  • 7/28/2019 High Pressur Fittings - Week 13

    21/39

    GAUGE GLASS

    Boilers operating at

    pressures below 250 psi

    can be fitted with tubular

    type gauge glasses

    Above 250psi, flat type

    gauge glasses are

    required.

    Isolation valves are

    required on each leg ofthe gauge glass

    08:38

    21

  • 7/28/2019 High Pressur Fittings - Week 13

    22/39

    GAUGE

    GLASS

    There are high pressure glass type

    indicators that can be used instead

    of flat gauge glasses,

    for example, bicolor gauge glasses.

    Figure gauge glasses work on the

    principle of light refraction

    08:38

    22

  • 7/28/2019 High Pressur Fittings - Week 13

    23/39

    GAUGE GLASS

    Every gauge glass will have valves to

    isolate the gauge from the drum pressure

    for maintenance and emergency situations.

    The isolation valves are usually of the quick

    closing type, capable of being closed with

    turn of the handles. The handles will be connected by chain

    pulls so that an operator can pull on the

    chain and close both valves at the same

    time from a remote location.

    The bottom isolation valve will always befitted with a ball check device to prevent hot

    water from flowing through a broken gauge

    glass.

    08:38

    23

  • 7/28/2019 High Pressur Fittings - Week 13

    24/39

    GAUGE GLASS

    Each gauge glass assemble will be

    fitted with a blowdown connection to:

    Insure that the connections between the

    drum and gauge do not become clogged.

    To help the operator tell the level in theglass.

    If you are in doubt of the level in the

    glass, blow the glass down (open the

    gauge drain valve).

    If you blow a glass down, and you see the

    water level go up through the glass, then

    the drum level is high.

    If no level appears, then the level is high.

    08:38

    24

  • 7/28/2019 High Pressur Fittings - Week 13

    25/39

    GAUGE GLASS

    Leaks above the actual

    water level will indicate

    higher than normal

    levels.

    Leaks below the actual

    level will indicate lower

    than normal levels.

    08:38

    25

  • 7/28/2019 High Pressur Fittings - Week 13

    26/39

    GAUGE GLASS

    To blow a glass down for normal

    maintenance:

    Disconnect the pull chains

    Close the top valve and open the drain

    valve (blowdown valve). Let it drain for a

    few seconds.

    Open the top isolation valve and close

    the bottom isolation valve. Leave the

    drain open for a few more seconds.

    Close the drain valve.

    Open the bottom isolation valve andreattach the chains.

    08:38

    26

  • 7/28/2019 High Pressur Fittings - Week 13

    27/39

    FLATTYPEOF GAUGEGLASS

    CONSTRUCTION

    1. BODY

    2. FLAT GUAGE GLASS

    3. MICA SHEET

    4. ASBESTOS GASKETS

    5. ASBESTOS CUSHIONS

    6. COVERPLATES

    7. STUDS

    8. NUTS

    08:38

    27

  • 7/28/2019 High Pressur Fittings - Week 13

    28/39

    GAUGE GLASSESAND

    TRY COCKS

    Both the water column and gauge

    glass must blowdown daily

    Prevent sludge accumulations from

    blocking lines

    Observe the level when it is blown. When the valve is opened, the water

    should drop out of the glass rapidly.

    When the valve is closed, it should

    return rapidly to its previous level.

    If the glass water drains slowly This is an indication of clogging up.

    The situation must be corrected as

    quickly as possible, even if the coiler

    has to be shut down.

    08:38

    28

  • 7/28/2019 High Pressur Fittings - Week 13

    29/39

    08:38

    29

    There is one

    adjustment on

    the muddling

    chamber type

    safety valve

    Adjusting ring

    Question

    Who can adjustthe boiler

    safety setting

    pressure?

  • 7/28/2019 High Pressur Fittings - Week 13

    30/39

    08:38

    30

    There are two

    adjustments

    Adjusting ring

    Nozzle ring

    Question

    How to

    increase the

    blowdown

    pressure?

  • 7/28/2019 High Pressur Fittings - Week 13

    31/39

  • 7/28/2019 High Pressur Fittings - Week 13

    32/39

    GATEVALVE RISESTEM08:38

    32

  • 7/28/2019 High Pressur Fittings - Week 13

    33/39

    GLOBEVALVE08:38

    33

  • 7/28/2019 High Pressur Fittings - Week 13

    34/39

    SWINGCHECKVALVE08:38

    34

  • 7/28/2019 High Pressur Fittings - Week 13

    35/39

    BALLVALVE08:38

    35

  • 7/28/2019 High Pressur Fittings - Week 13

    36/39

    BUTTERFLYVALVE08:38

    36

  • 7/28/2019 High Pressur Fittings - Week 13

    37/39

    MARINEBOILEREXAMPLE

    WHATARETHESEFITTINGS?

    1 - Gauge Glass or Water Column

    2 - Main Steam, Safety, Auxilary Steam

    Valves

    3 - Pressure Gauge

    4 - Surface Blow

    5 - Skin Valve (through ship's side)

    6 - Bottom Blow

    7 - Hydrokineter (to increase water

    circulation)

    8 Furnaces

    9 - Fire-Tube bundles

    10 - Main Feed Valve

    11 - Auxiliary Feed Valve

    12 - Deep Blue sea