Page 1: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 1

Page 2: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 2

Agenda

Company History, Organisation, Profile and Global Network

NBDK – IT Power SystemsMechanical, Features and Benefits

NBDK – IT Power SystemsElectrical Operation and Energy Flow

NBDK – IT Power SystemsControl and Monitoring

NBDK – IT Power SystemsSystem configuration

NBDK – IT Power SystemsHitzinger & On site service / maintenance / repair

NBDK – IT Power SystemsSummary and References

Page 3: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 3

NBDK – IT Power SystemsCompany History, Organisation, Profile, Global Network

Page 4: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 4

History

Dipl. Ing. Walter HITZINGER

Dipl. Ing. Hans SCHÄCKE

In June 1946, Dipl. Ing. Walter Hitzinger, Dipl. Ing. Hans Schäcke founded Dipl. Ing. Hitzinger & Co. for electrical installations and repairs located in Linz.

Page 5: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 5

Today, more than 230 highly skilled employees develop and produce high tech products in state-of-the-art technology in 3 production plants with a total area of 18.000 m² .

Hitzinger Products are:

Synchronous- and

Asynchronous Alternators

Rotary Frequency Converters

Dynamic Diesel UPS Systems

Airport Ground Power Systems

Diesel Generating Sets

History

Page 6: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 6

HITZINGER GLOBAL NETWORK

A reliable & competent partner

for more than 60 years !

Page 7: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 7

Production Facilities

Page 8: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 8

Production Facilities

Page 9: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 9

Production Facilities

Page 10: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 10

Production Facilities

Page 11: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 11

Production Facilities

Page 12: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 12

Company Organisation

3.1

Quality

Management

1.3

Customer Service

Management

3.3

Plant Management

1.3.1

Technical

Support

1.3.2

Customer

Service

3.3.1

Production

Management

1.0

IT Management

1

Managing Director

Sales & Logistic

3

Managing Director

Technical (QMB)

3.3.2

Process Planning

Management

1.1

Sales Management

2.1.1

Human Resource

Management

3.2

Projektmanagement

1.2.1

Mechanical

Strategic

Purchasing

1.2

Purchasing & Logistics

Management

1.2.3

Warehouse

Management

3.4

Research and

Development

Management

3.5

Technical Management

3.5.3

Electric Design

Management

3.5.2

Mechanical Design

Management

1.2.2

Electrical

Strategic

Purchasing

1.2.4

Shipping

Management

3.5.4

Electronic

Management

3.5.6

Test Bay

Management

2.0

Management

Assistance

2.0

Management

Assistance

4.0

Administration

1.1.3

Order

Management

2.1

Financial & Accounting

Management

2

Managing Director

Commercial

2.1.2

Controlling

2.1.3

Accounting

1.1.1

Sales Management

1.1.1.1

Business Area 1

Alternators VG

1.1.1.3

Business Area 3&4

Diesel Gen sets &

Dynamic UPS

systems

VA & VV

1.1.1.2

Business Area 2

Airport Equipment

& Converters

VF & VU

1.1.1.4

Product

Management

Page 13: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 13

Turnover 2004 - 2013

0

10

20

30

40

50

60

2004 2005 2006 2007 2008 2009 2010 2011 2012 Forecast

2013

Year

Reihe1

Page 14: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 14

Products

Page 15: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 15

Employees

Sales Personnel

Management & Administration

5%

Research &Development

Skilled workers

Apprentices 6 %Engineers

15%

6%

8%

60 %

Page 16: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 16

NBDK – IT Power SystemsMechanical, Features and Benefits

Page 17: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 17

Why DDUPS?

To save money!

Mains failures – even for milliseconds – can cause production and supply outages and subsequent financial problems. These sectors are plastic industry and semiconductor production, data centers, airports, hospitals and so on.

To prevent standstill or losses of production!

The increasing percentage of automation in modern production processes demands more than ever high-quality and absolute reliable and uninterruptible power supply to avoid production outages.

To be independent from extern influences!

Nowadays, a high-quality power supply system often has to be more than what can be provided by local grid providers. Certain sensitive economical fields need, more than ever, a constant mains supply quality.

These fields are, for example: hospitals, airports, semi-conductor production plants, the chemical industry, data processing centers, telecommunications, plastics-technology, computer-controlled industrial plants,…

Page 18: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 18

NBDK – IT Power systems

A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply of your consumers.Hitzinger Diesel UPS systems enable you to prevent production outages and financial losses.

A Hitzinger UPS system is a tailor made solution and guarantees a fast ROI.

Ratings up to 2500 kVA Voltage up to 11 kV Low maintenance costs High alternator efficiency High MTBF value (1.000.000 + hours) Power factor regulation High quality of components High overload capacity Proper mains failure supervision In-house developed PLC control system Tier complaint

That„s why we are sure that our no-break systems NBDK & NBDD are the best solution for our costumer„s power supply problems .

Page 19: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 19

TECHNOLOGY SHIFT:

Away from: Lead acid batteries Power Electronics

Towards: Kinetic Energy Storage Rotating Electric Machines (Alternators or Generators)

Diesel remains the common component

Redundant Power feeds are prone to common mode failure and thusoffer inadequate protection

NBDK – IT Power systems

Page 20: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 20

Why these Technologies?

Kinetic energy storage: clean Simple Reliable efficient

Alternators and Generators: Achieve levels of dynamic electrical performance, which power electronics

struggle to match.

NBDK – IT Power systems

Page 21: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 21

Solution Class

Power Circuit

Components

Ride through

Energy Storage

Power Generation

Power

electronics

Rotating

Electric

Machine

Batteries Kinetic

Energy

Diesel

Dynamic No Yes No Yes Yes

Hybrid

(Rotary)

Yes Yes No* Yes Yes

Static Yes No Yes Yes Yes

* Optional** Depending on power capacity

NBDK – IT Power systems

Page 22: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 22

Product Description

Hitzinger Dynamic Diesel UPS systems

Hitzinger Dynamic UPS systems are a complete critical power solution in one product.

Hitzinger Dynamic UPS employ kinetic energy to provide protection against short duration disturbances or outages.

And an integrated diesel motor to provide protections against prolonged disturbances or outages.

Hitzinger delivers the smallest foot print 2500 kVA unit on the market.

Page 23: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 23

Product Description

KIN module operation

WHY USE A KIN MODULE?

Inductive coupling allows precise speed regulation of inner rotor

Rapid Discharge and Recharge without capacity degradation

Reliability through a completely brushless design

Reliability through integrated vibration monitoring.

Page 24: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 24

Standard Ratings50 Hz / 60 Hz

More Scalability: Solutions for all size applications

Choose from a wide range of capacities and performance

Rating (kVA) Model

150 NBDK 1/10-150

250 NBDK 1/10-250

350 NBDK 1/10-350

500 NBDK 1/10-500

625 NBDK 1/10-625

800 NBDK 1/10-800

1000 NBDK 1/10-1000

1250 NBDK 1/10-1250

1500 NBDK 1/10-1500

1750 NBDK 1/10-1750

2000 NBDK 1/10-2000

2500 NBDK 1/10-2500

Page 25: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 25

NBDK 150kVA - 2500kVA

Operation Tolerance Operation Tolerance

Static +/- 1% During mains operation = mains frequency

DynamicChanging from mains to diesel operationLoad transfer 100% +/- 1%

At change of nominal load, cos φ = 0,8 +/- 10% Static during diesel engine operation

+/- 0,5%

Voltage recovery time 0,3 s

Short circuit at the input +/- 10%

After short circuit shutdown < 10%

Voltage recovery time 0,3 s

Mains shutdown at nominal voltage +/- 10%

Voltage recovery time 0,3 s

Other tolerance values are available on demand!

Voltage Frequency

Guaranteed values

Page 26: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 26

NBDK – IT Power SystemsAdvantages

Page 27: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 27

Reliable…

… usage: Redundant operation possible High dynamic overload capacity Uninterruptible bypass for maintenance works Accurate mains failure supervision 100% load acceptance

… handling: Simple operation POWERCON - PLC control system (also for multiple units) Remote monitoring and surveillance (optional)

… design: Brushless technology of all components Robust in view of environment EMC Certification according to EN 300386-2

Hitzinger UPS systems are worldwide in operation for more than 40 years.

NBDK – IT Power SystemsAdvantages

Page 28: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 28

Economic…

Optimized quality of system components, available wordwilde Low losses due to tailor-made machines Low maintenance costs Short maintenance time High MTBF value (1.000.000 + hours) High life time of all parts and components High efficiency Low TCO

NBDK – IT Power SystemsAdvantages

Page 29: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 29

Maintenance friendly…

Withdraw able type circuit breakers (optional) Remote diagnosis via modem (optional) Brushless technology in all system components Automatic regreasing unit (optional) Easy access to all maintainable parts (e.g. friction linings) KIN Module on the end of the machine Training program for users on site

NBDK – IT Power SystemsAdvantages

Page 30: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 30

Extremely available…

High quality of system components Maintenance and service during operation Choke with natural cooling and integrated harmonic filter Torque limiting design for flywheel and electromagnetic clutch Worldwide accepted diesel engines with local services, spares and

maintenance availability

NBDK – IT Power SystemsAdvantages

Page 31: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 31

Features and Benefits

Less Waste: Environmental impact

REDUCING HAZARDOUS WASTE

EXAMPLE 1: Typical waste of a 2000 kVA UPS after 20 years

Static UPS Dynamic UPS

3 x 33,000 kg batteries < 100 kg of steel(15 minutes autonomy time) (bearing material)- Plus power electronic components

A much GREENER Alternative!

Page 32: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 32

Features and Benefits

Less Waste: Environmental impact

REDUCING HAZARDOUS WASTE

EXAMPLE 2: Typical waste of a 8 MVA UPS after 20 years

Static UPS Dynamic UPS

3 x 100 tonnes batteries < 400 kg of steel- Plus power electronic components (bearing material)

A much GREENER Alternative!

Page 33: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 33

NBDK – Mechanical Design

1. Radiator

2. Diesel engine

3. Flexible Coupling & Electromagnetic clutch

4. Synchronous machine

5. Flexible coupling

6. Kinetic module

1

2

3

4

56

Page 34: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 34

NBDK – Mechanical Design

1. Radiator

2. Diesel engine

3. Flexible Coupling & Electromagnetic clutch

4. Synchronous machine

5. Flexible coupling

6. Kinetic module

2

3

4

5

6

Page 35: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 35

finishing varnish

1 layer

finishing varnish

1 layer

2-component varnish

2 layers

NBDK – Corrosion Protection

Page 36: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 36

NBDK – Corrosion Protection

Page 37: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 37

KINETIC ENERGY STORAGE MODULE (KIN) for UPS-Systems

with a frequency variation of max. 1 %!

Kinetic Energy Module

Page 38: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 38

In case of mains failure, the kinetic energy stored in the KIN provides the UPS load until the supply via the diesel engine can be assured.

Maximum frequency deviation : +/- 1%

Maximum voltage deviation : +/- 10 %

6 5 4 2 13

7

1) AC / DC exciter machine2) Stator winding of the exciter

machine3) Outer rotor mass 4) Squirrel cage5) Inner rotor with AC / DC

winding6) Inner KIN bearing 7) Outer KIN bearing

Kinetic Energy Module

Page 39: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 39

In case of mains failure, the inner rotor‘s magnetic field brakes the outer rotor and keeps the synchronous alternator‘s rotating speed constant.

Advantages:

Brushless Low maintenance High reliability High MTBF

Kinetic Energy Module

KIN-Modul

Outer Rotor(squirrel cage)rotating speed:2700 rpm

Diesel engine

2700 rpm1500

rpm

KIN-moduleSynchronous alternator

Inner Rotorrotating speed:1500 rpm

Page 40: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 40

DDUPS Room Layout

Page 41: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 41

NBDK – IT Power SystemsElectrical Operation and Energy Flow

Page 42: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 42

NBDK Principle Diagram

14 15 16 17e

9

5

6

8 7

1 2 3 4

a b c d

f

14 15 16 17e

9

5

6

8 7

1 2 3 4

14 15 16 17e

9

5

6

8 7

1 2 3 4

a b c d

f

1. Diesel engine2. Electromagnetic

clutch3. Synchronous

alternator4. Kinetic module5. Choke 6. Mains CB 7. Consumer CB 8. Alternator

protection 9. By-Pass CB

By-Pass operation

Stand-by operation

Diesel operation

a. Harmonic distortion

b. Voltage peaksc. Voltage dropsd. Power losse. Mains supplyf. Load output of

UPS

Consumer –Pure Sine Wave

Mains supply

Frequency deviation: < 1%

Page 43: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 43

The Magic Choke

In a UPS system, the coupling choke connects the incoming grid with the UPS output supply, that has to meet highest quality requirements.The choke„s and the alternator„s special design guarantees a high degree of decoupling between the grid and the UPS output.

The choke… Supports static and dynamic voltage decoupling on the UPS

collecting bar Decouples fluctuations and harmonics on the grid Upper harmonics filter Balancing of dynamic loads Restriction of current in case of short circuit

Uin Uout

Ualternator

X

Iin

Iout

Iin = line current

Iout = consumer current

Uin = line voltage

Uout = consumer voltage

Ualternator = alternator voltage

Uin Iin X Ualternator

Uout Ualternator

Page 44: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 44

The Magic Choke

This configuration„s output voltage is completely independent from the input side. The fundamentals (50Hz or 60Hz) are only determined by the alternator. Either the choke (since the reactance of the choke depends on the frequency) or the alternator blocks possible upper harmonics and transients.

The connection between the terms Uchoke = I . Xchoke and Xchoke = 2 . π . f . L shows, that the choke is a determining component for higher frequencies while the alternator with its special configuration of the stator winding eliminates lower frequencies‟ upper harmonics (e.g. 3rd, 5th, 7th,…harmonics)

Short circuits:In case of a short circuit on the input (equals a total mains failure in which the load is transferred from the input to the alternator via the choke), the choke limits the fault current until the cutoff of the input. The voltage drop on the choke‟s short circuit is added to the alternator‟s voltage via the choke‟s circuit. Therefore, the UPS‟s voltage equals approximately the alternator‟s voltage: ΔU = -10% to -15% (depending on the choke„s position)

Inverse operation of the input„s current transducer:As the inverse operation of the input„s current transducer depends on the temporary short circuit between two phases during the commutation period, the choke can avoid the influences on the not-affected power unit (UPS-mains), following the same principle.

Page 45: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 45

HochfahrenNetz-

betrieb

Netz-

ausfallAbschalten

Netz-

rückkehrStart up

Mains

operation

Mains

power

failure

Shut downMains

return

Description of Operation

By-pass circuit breaker closed

Diesel engine starts

KIN module charging

Synchronization to mains (“Make before Break”)

Diesel engine shut down

Page 46: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 46

Supply of the consumer load via choke from mains, synchronous machine in motor operation

Synchronous machine acts as an filter and provides stable voltage and reactive power to the consumers

Filtering of harmonics and balancing of asymmetric loads

Distortion factor < 3%

HochfahrenNetz-

betrieb

Netz-

ausfallAbschalten

Netz-

rückkehrStart up

Mains

operation

Mains

power

failure

Shut downMains

return

Description of Operation

Page 47: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 47

Mains circuit breaker opens

KIN module keeps load uninterruptedly supplied

Simultaneous start of diesel engine

Electromagnetic clutch closes

Load transfer from KIN module to diesel engine

Diesel engine provides the UPS supply and charges the KIN module

HochfahrenNetz-

betrieb

Netz-

ausfallAbschalten

Netz-

rückkehrStart up

Mains

operation

Mains

power

failure

Shut downMains

return

Description of Operation

Page 48: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 48

Mains within permitted tolerances for a certain period

Synchronization of the consumer load back to mains

Electromagnetic clutch opens

Shut down of diesel engine after cooling period

HochfahrenNetz-

betrieb

Netz-

ausfallAbschalten

Netz-

rückkehrStart up

Mains

operation

Mains

power

failure

Shut downMains

return

Description of Operation

Page 49: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 49

Bypass circuit breaker closes

Mains and consumer CB‟s opens

Machine runs down (energy consumption due to internal losses)

Alternative:

Electromagnetic clutch closes

Diesel engine ignition is blocked

Diesel engine compression is used to increase the energy consumption fast run down

HochfahrenNetz-

betrieb

Netz-

ausfallAbschalten

Netz-

rückkehrStart up

Mains

operation

Mains

power

failure

Shut downMains

return

Description of Operation

Page 50: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 50

Alternate redundant Diesel Engine Start

2700

1500

0 1 2 3 4 5 6 7

~800

Speed Kinetic Energy Storage

t [sec]

Speed [

rpm

]

Alternator speed

Standard Starting Procedure:

Diesel engine starts via electrical starter

Electromagnetic clutch closes at ~800rpm

Additional acceleration by KIN module

Redundant Starting Procedure:

Electromagnetic clutch closes

Diesel engine acceleration by KIN module to nominal speed

Page 51: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 51

NBDK – Energy Flow Diagram

Supply of the UPS load via the by-pass power switch directly from the mains

NBDK„s auxiliary power supply is taken from the UPS„s consumer bar

By-pass Operation

consumer

Die

sel

en

gin

e

fuel

Mains input

Control panel

Coolant preheater

Prelubrication

Battery charger

Active power kW

Reactive power kVAR

Au

xili

ary

po

we

r su

pp

ly

Page 52: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 52

Supply of the UPS load via the by-pass power switch directly from the mains

The diesel engine accelerates the synchronous machine and the KIN module up to nominal speed

Storage of the kinetic energy (needed for providing the UPS load) in the KIN module

Start up

consumer

Die

sel

en

gin

e

fuel

Mains input

Control panelCoolant preheater

Prelubrication

Battery charger

Active power kW

Reactive power kVAR

Au

xili

ary

po

we

r su

pp

ly

Active power kW

NBDK – Energy Flow Diagram

Page 53: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 53

Synchronization is performed with a slightly positive beat frequency compared to the mains

After the synchronization, the alternator delivers the reactive power

Reactive power flows back to the mains due to choke magnetization

Synchronization

consumer

Die

se

le

ng

ine

fuel

Mains input

Control panel

Coolant preheater

Prelubrication

Battery charger

Reactive power kVAR

Au

xili

ary

po

we

r su

pp

ly

Active power kW

Active power kW

Reactive power kVAR

Friction losses

NBDK – Energy Flow Diagram

Page 54: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 54

Consumers of the UPS load are supplied directly by the mains

The choke suppresses voltage interference caused by static discharge, commutation fall-off, overvoltage or upper harmonics

Equalizes unbalanced load

Diesel engine stops, synchronous machine runs as a motor

Stand-by Operation

consumer

Die

se

le

ng

ine

fuel

Mains input

Control panel

Coolant preheater

prelubrication

Battery charger

Reactive power kVAR

Au

xili

ary

po

we

r su

pp

ly

Active power kW

Friction losses

NBDK – Energy Flow Diagram

Page 55: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 55

The UPS alternator supplies the consumer load via the stored kinetic energy until the diesel engine has reached the nominal speed and can deliver full load

Diesel engine is accelerated via quick start

KIN module starts to charge

Mains Failure

consumer

Die

se

le

ng

ine

fuel

Mains input

Control panel

Coolant preheater

prelubrication

Battery charger

Reactive power kVAR

Au

xili

ary

po

we

r su

pp

ly

Active power kW

Active power kW

Quick start

NBDK – Energy Flow Diagram

Page 56: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 56

The diesel engine supplies the UPS load via the alternator

Energy is also transferred to the kinetic module (to charge the KIN module and compensate the losses)

Diesel Operation

consumer

Die

se

le

ng

ine

fuel

Mains input

Control panel

Coolant preheater

prelubrication

Battery charger

Reactive power kVAR

Au

xili

ary

po

we

r su

pp

ly

Active power kW

Friction losses

NBDK – Energy Flow Diagram

Page 57: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 57

Synchronization to the mains frequency

Transfer of the UPS load via the choke to the synchronized mains

Shutdown of the diesel engine after a cooling-down period

Machine returns to stand-by operation

Mains Return

consumer

Die

se

le

ng

ine

fuel

Mains input

Control panel

Coolant preheater

prelubrication

Battery charger

Reactive power kVAR

Au

xili

ary

po

we

r su

pp

ly

Active power kW

Reactive power kVAR

Friction losses

NBDK – Energy Flow Diagram

Page 58: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 58

0 100 200 ms

Software - Simulations Test Cabine - Measurements

NBDK – Performance Tests

Page 59: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 59

0 100 200 ms

Mains Failure Simulation Mains Failure Measurement

Tolerances NBDK:

Frequency: ± 1%

Voltage: ± 10%

NBDK – Performance

Page 60: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 60

NBDK – IT Power SystemsControl and Monitoring

Page 61: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 61

Control and Monitoring

Office

RS232/485Converter

EPS ROOM

+S1

SYSTEM 1 SYSTEM 2

powermonitoring

MONITORING&OPERATION

with

POWERCON Controller

Dieseloperation; U1=380V; U2=380V

TOCONSUMER

-Q11

-Q13

-Q12

System 2Alternator

Mains

K06203V01BL01

MAINSWITCHBOARD

UPS1

System 1Consumer

System 2MainsDisplay Powercon 2

Mains input

EPS ROOM

+S1

POWERCON[EPS]

SYSTEM 1 SYSTEM 2

-

MONITORING&OPERATION

MONITORING&OPERATION

UPS SYSTEM

POWERCON Controller

Alternator output

Diesel operation; U1=380V; U2=380V

TOCONSUMER

-Q11

-Q13

-Q12

System 2Alternator

Mains

K06203V01BL01

MAINSWITCHBOARD

UPS1

System 1Consumer

System 2MainsDisplay Powercon 2

Page 62: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 62

Control and Monitoring

Page 63: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 63

Control and Monitoring

Page 64: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 64

NBDK – IT Power SystemsSystem Configurations

Page 65: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 65

System ConfigurationsTIER Requirements Summary

TIER I TIER II TIER III TIER IVActive Capacity Components to Support

IT Load

N N+1 N+1 N after any failure

Distribution Paths 1 1 1 active and 1 alternative

2 simultaneously active

Concurrently Maintainable No No Yes Yes

Fault Tolerance

(single event)

No No No Yes

Compartmentalization No NO No Yes

Continuous Cooling Load density dependent

Load density dependent

Load density dependent

Yes (class A)

Page 66: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 66

TIER I TIER II TIER III TIER IV

Single source

No redundancy

Single source

After „N+1“

Double source

2 x „N“

„A-B“-supply

Path A Path B

Double source

Each N+1

Path A Path B

Enduser availability

99,67 %

Enduser availability

99,75 %

Enduser availability

99,98 %

Enduser availability

99,99 %

Enduser downtime

28,8 h

Enduser downtime

22,0 h

Enduser downtime

1,6 h

Enduser downtime

0,8 h

First introduced

1960-1970

First introduced

1960-1990

First introduced

since 1990

First introduced

Since 1994

System ConfigurationsTIER Requirements Summary

Page 67: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 67

Example:Two single units paralleled , one

Bypass- CB

System configuration:Parallel

System components:(N+I)2 + 0

Number of paths:(P)1

Description:N… number of UPS needed to

supply the load

I… number of redundant units

P.. number of paths

-1CCB

-1MCB

-2CCB

-2MCB

Critical load 1

G

D

A1

KIN

G

D

A2

KIN

-BCB

Utility

System ConfigurationsExample: Parallel Configuration

Page 68: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 68

-1CCB

-1MCB

-2CCB

-2MCB

Critical load 1

Utility

G

D

A1

KIN

G

D

A2

KIN

-BCB

-3CCB

-3MCB

G

D

A3

KIN

-MBCB

Parallel ConfigurationTo achieve a higher level of output availability

in N or N+1 configuration

N:System components ; paths3 ; 1 ; (Tier1)(unit A1+A2+A3 needed to supply the load)

Number of units:Low voltage- limited due short-circuit power

(8MWconfiguration)Middle voltage- nearby unlimited

Further Configuration:Further configurations are simplified without

manual Bypass-CB`s or additional switching devices

System ConfigurationsParallel Configuration, N

Page 69: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 69

-1CCB

-1MCB

-2CCB

-2MCB

Critical load 1

G

D

A1

KIN

G

D

A2

KIN

-3CCB

-3MCB

G

D

C1

KIN

-BCB

+1

Utility

System ConfigurationsParallel Configuration, N+I

Parallel ConfigurationTo achieve a higher level of output

availability in N or N+1 configuration

N+I: System components ; paths2+1 ; 1 ; (Tier2)A1+A2 >= load, A1+C1 >= load,A2+C1 >= load,

Key benefits:-Simple design-Small number of components-Easy Expandable

Drawbacks:-Single point of failure, failure on the

common bus bar affects the consumers/load

Page 70: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 70

System ConfigurationsIsolated Configuration

-1CCB

-1MCB

-2CCB

-2MCB

Critical load 1,Path B

G

D

A1

KIN

G

D

B1

KIN

-2BCB

Critical load 1,Path A

-1BCB

Critical load 1

+1

Utility

A B

Isolated ConfigurationThere is a higher level of output

availability possible, due independent/individual load supply

N+I: System components ; paths1+1 ; 2 ; (Tier3)A1 >= load, A2 >= load,

Key benefits:-This kind of system configuration

eliminates the single point of failure

-Higher number of components

Drawbacks:-Higher Acquisition costs-Higher Operating costs

Page 71: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 71

System ConfigurationsIsolated Parallel Redundant Configuration

Highest level of possible output availability(N+I)+(N+I): System components ; paths | (1+1)+(1+1) ; 2 ; (Tier4)Shown in this special configuration - each unit (A1,C1,B1,C2) able to supply the load.

Isolated Parallel Redundant Configuration

-1CCB

-1MCB

-2CCB

-2MCB

Critical load 1,Path A

G

D

A1

KIN

G

D

C1

KIN

-BCB

+1

-3CCB

-3MCB

-4CCB

-4MCB

Critical load 1,Path B

G

D

B1

KIN

G

D

C2

KIN

-BCB

+1

Critical load 1

Utility Utility

A B

Page 72: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 72

-1CCB

-1MCB

-2CCB

-2MCB

Critical load 1,Path A

G

D

A1

KIN

G

D

A2

KIN

-BCB

Critical load 1,Path BCritical

load 1

Utility B – High Availability

+1

Utility Utility

System ConfigurationsIsolated Parallel Configuration

Isolated Parallel Configuration

N+I: System components ; paths1+1 ; 2 ; (Tier3)A1 >= load, A2 >= load,

Key benefits:-This kind of system uses the high

availability of a second Utility-This kind of system configuration

eliminates the single point of failure

-Higher number of components-If there are two independent grid‟s

available it is a really Operating costs optimized solution

Drawbacks:-High Acquisition costs-High Operating costs

Page 73: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 73

System ConfigurationsIsolated Parallel Configuration

Isolated Parallel ConfigurationAll units are connected to a commonbus (IP-Bus) by isolation chokesIn case of short-circuit on the bus or unit failure, this chokes minimize fault currents to an acceptable level

N+I: System components ; paths1+1 ; 1 ; (Tier2)

power outage of two units >= total load,

Key benefits:-Load management for better

efficiency possible, this depends on the systems load configuration.

Drawbacks:-High Acquisition costs-not comparable to a totally isolated

system configuration, small influences in case of bus bar failure

-1CCB

-1MCB

Critical load 1

G

D

A1

KIN

-BCB

-1CHCB

-2CCB

-2MCB

Critical load 2

G

D

A2

KIN

-BCB

-2CHCB

-3CCB

-3MCB

Critical load 3

G

D

A3

KIN

-BCB

-3CHCB

Utility

Page 74: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 74

-1CCB

-1MCB

G

D

A1

KIN

-BCB

-1CHCB

-2CCB

-2MCB

G

D

B1

KIN

-BCB

-2CHCB

-3CCB

-3MCB

G

D

C1

KIN

-BCB

-3CHCB

+1

Critical load 1,Path A

Critical load 1,Path BCritical

load 1

Spare

Utility

System ConfigurationsIsolated Parallel Configuration

Isolated Parallel ConfigurationAll units are connected to a commonbus (IP-Bus) by isolation chokesIn case of short-circuit on the bus or unit failure, this chokes minimize fault currents to an acceptable level

N+I: System components ; paths1+1 ; 2 ; (Tier3)

power outage of two units >= total load,

Key benefits:-Load management for better

efficiency possible, this depends on the systems load configuration.

Drawbacks:-High Acquisition costs-not comparable to a totally isolated

system configuration, small influences in case of bus bar failure

Page 75: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 75

System ConfigurationsParallel Configuration, 3units, STS

Parallel ConfigurationAdditional unit is operating parallel tothe 2 load bus bars, they are connected due Static Load Transfer Switches.In case of unit failure the static transfer switches to the remaining available supply.

N+I: System components ; paths1+1 ; 1 ; (Tier2)

A1 or B1 or C1 >= load1 or load2,

Key benefits:-Redundant UPS is able to supply

each load without influencing to the other consumers.

-Maintenance

Drawbacks:-available only in the low voltage

range

-STS

-1CCB

-1MCB

-2CCB

-2MCB

Critical load 1

G

D

A1

KIN

G

D

C1

KIN

-BCB

-3MCB

G

D

B1

KIN

-STS

Critical load 2

-BCB

-3CCB

Utility

A B

Page 76: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 76

System ConfigurationsParallel Configuration, STS

-1MCBEPS

-1ACBEPS

-1CCB

-BCB

-1MCB

Non-critical load A

-STS A1 -STS A2

Critical load 1,Path A1

Critical load 1,Path A2

G

D

A1

KIN

Critical load 1

-2MCBEPS

-2ACBEPS

-2CCB

-BCB

-2MCB

Non-critical load B

-STS B1 -STS B2

Critical load 2,Path B1

Critical load 2,Path B2

G

D

B1

KIN

Critical load 2

-3MCBEPS

-3ACBEPS

-3CCB

-BCB

-3MCB

Non-critical load C

-STS C1 -STS C2

Critical load 3,Path C1

Critical load 3,Path C2

G

D

C1

KIN

Critical load 3

Utility

A

B

C

A

B

C

Isolated Parallel Configuration

High level of possible output availabilityThe Availability depends from load conditions

Page 77: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 77

-1CCBA

-1MCB

-2CCBA

-2MCB

Critical load 1,Path A

G

D

A1

KIN

G

D

A2

KIN

-BCBA

-BCBB

-2CCBB

-1CCBB

A

B

-CBA-B

-3CCBA

-3MCB

-4CCBA

-4MCB

Critical load 1,Path B

G

D

B1

KIN

G

D

B2

KIN

-BCBA

-BCBB

-4CCBB

-3CCBB

A

B

-CBB-A

Critical load 1

Utility A Utility B

+1 +1

System ConfigurationsParallel Configuration

Isolated Parallel Configuration

Highest level of possible output availability(N+I)+(N+I): System components ; paths | (1+1)+(1+1) ; 2 ; (Tier4)

Page 78: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 78

NBDK – IT Power SystemsHitzinger & on site service / maintenance / repair

Page 79: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 79

Hitzinger Services

Competent and experienced service team 24/7/365 service hotline Worldwide services available through agents /

representatives Available on site within 48 hours (in middle east

countries with no visa requirements)

Page 80: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 80

Hitzinger Maintenance Organisation

Total work experience: > 300 years!

Page 81: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 81

Hitzinger Maintenance

More Reliability: Less maintenance

Choose a solution which facilitates maintenance

Low annual service requirements

Automatic lubrication options

Module arrangement gives better KIN module access facilitating:

Easier routine maintenance Quicker overhauls

Page 82: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 82

Qualification:Level M1 … trained personal (customer operator)Level M2 … qualified personal (Hitzinger service and maintenance partner)Level M3 … specialist of DDUPS manufacturer and service and maintenance partner

Operation mode:A … automaticM … maintenanceT … test

Maintenance Overview

Page 83: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 83

Unit to be maintainedTasks

Qualifi-cation

Operation Mode

Daily 1 Monthly 4 Months 1 Year Max. Years Special periodor time limitation

Visual inspections

- alternator - kinetic energy module - re-greasing unit - cooling system - fuel system - exhaust system - ducts

M1 A

Bearing re-grease

- electromagnetic clutch - alternator - kinetic energy module (outer bearings)

M1 A automatic

Maintenance Schedule M1

Page 84: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 84

Unit to be maintainedTasks

Qualifi-cation

Operation Mode

Daily 1 Monthly 4 Months 1 Year Max. Years Special periodor time limitation

Functional tests, visual inspection and cleaning

- Alternator and KIN module- automatic re-greasing unit- cooling and fuel system- local and master control panels

M2 T

Electromagnetic Clutch

Check and re-adjust gap clearance M2 M Readjustment after 100 HSS

Replace friction linings M2 M 10 Theoretical figure

Kinetic Energy Storage Unit

Change lubrication oil of inside bearings M2 M Max. 3500 AWH

Maintenance Schedule M2

Page 85: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 85

Unit to be maintainedTasks

Qualifi-cation

OperationMode

Daily 1 Monthly 4 Months 1 Year Max. Years Special periodor time limitation

Kinetic Energy Storage Unit

Replace KIN-module inner bearings

M3 M 5 Theoretical figure

Maintenance Schedule M3

Page 86: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 86

Hitzinger Services in Turkey

Local support through Powerelektronik

Powerelektronik has various UPS installations above 20KVA

maintenance and service team for UPS

highly qualified trained engineers for UPS and electronic equipments support

Our main office is Istanbul

Hitzinger has already set a training program for 3 engineers from Powerelektronik in Linz / Austria

Page 87: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 87

Spare parts availabilityStock items at Powerelektronik

Bearings Clutch linings PLC‟s incl. input and output modules KIN control box AVR Relays Battery chargers Special tools

Page 88: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 88

Hitzinger Services in Turkey

Power Elektronik San. ve Tic. A.Ş. Armağanevler Mh. Samanyolu Cd.

İpekçi Sk. No : 12 Ümraniye ISTANBUL

Power Elektronik San. ve Tic. A.Ş. ANKARA BÖLGE MÜDÜRLÜGÜ

2. Cadde 1315. Sk. No: 12/A-14

Asagi Övecler, Cankaya

ANKARA

Page 89: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 89

NBDK – IT Power SystemsSummary and references

Page 90: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 90

Summary

Lower Total Cost of Ownership

Direct savings: Total system efficiency ~ 94-96% No additional heat input into the facility No Air Conditioning or infrastructure costs. Just ambient air. No major consumables to change during service life

Indirect savings: Redefined space requirements Less expensive “garage” style building Reduced space requirements

MINIMISE ENVIROMENTAL IMPACT Total system efficiency minimises GHG emissions Eliminate the hazardous waste of batteries

RELIABILITY Simple design low component count: System MTBF 1.000.000+ hours Redundant diesel start Completely brushless design Designed for 25 yr service life Vibration monitoring

Page 91: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 91

DYNAMIC ELECTRICAL PERFORMANCE

Achieved by Hitzingers own tailored range of synchronous alternators

Power capacities 150kVA – 2.5 MVA Scalability – 11 kV models High fault clearing / overload capability Mains filtering and harmonics attenuation Dynamic power factor correction Operates with leading, lagging or unity PF devices Completely brushless design

Energy Storage

Achieved by Htizingers range of KIN modules

Wide range of power capacities 150kVA – 2.5 MVA Lowest RPM design increases bearing service life Rapid discharging and recharging without degradation Easy access for maintenance and overhaul Vibration monitoring

Summary

Page 92: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 92

EN ISO 9001 Certificate

Page 93: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 93

Italy

Memc - Meran:

2 x 340 kW

2 x 150 kW

Mechanical UPS – uninterrupted drive of rotating machines (e.g. pumps).

STMicroelectronics Catania:

4 x 1750kVA

Page 94: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 94

Greece

International Airport Athens:

4 x 450kVA

Page 95: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 95

Great Britain

Governmental Data Centers

2 x 2000 kVA (dual output)

2 x 2000 kVA (dual output)

2 x 475 kVA (dual output)

Page 96: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 96

Great Britain

Data Centre – Global Switch London (22MVA in parallel Operation)

11 x 2000 kVA (11kV)

Page 97: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 97

Austria

General Hospital Linz

1 x 150 kVA

1 x 450 kVA

1 x 630 KVA

1 x 800 kVA

Hospital Braunau

1 x 350kVA

More than 10 MVA UPS power installed all over Austria.

Page 98: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 98

Austria

Austrian Parliament Vienna:

1 x 1225 kVA

Page 99: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 99

Switzerland

Prodor Piaget SA Geneva

1 x 850 kVA

Data Centre Bern

3 x 2000 kVA

Page 100: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 100

Northern-Cyprus & Slovenia

International Airport Lefkosa

1 x 325 kVA

International Airport Ljubljana

1 x 500 kVA

Page 101: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 101

Egypt & Malawi

International Airport Cairo:

2 x 600 kVA

2 x 800 kVA

Reserve Bank Malawi - Blantyre

1 x 1000 kVA (dual output)

Page 102: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 102

Nigeria & Zimbabwe

International Airport Lagos

2 x 250 kVA

International Airports Harare and Bulawayo

2 x 200 kVA

1 x 50 kVA

Page 104: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 104

South Africa

Telkom SA – Projects:

1 x 550 kVA

1 x 1000 kVA

2 x 800 kVA

2 x 1000 kVA

2 x 1500 kVA (dual output)

2 x 1500 kVA (dual output)

1 x 660 kVA (dual output)

1 x 1000 kVA

1 x 1000 kVA (dual output)

1 x 1000 kVA

1 x 750 kVA (dual output)

Page 105: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 105

Tanzania

Bank of Tanzania

4 x 2000 kVA

Page 106: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 106

Mexico

International Airport Cancun

1 x 290 kVA (60Hz)

Page 107: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 107

Venezuela

Venefoil C.A Caracas

1 x 1000 kVA (60Hz; dual output)

Page 108: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 108

Azerbaijan

International Airports

Uch Kuduk & Baku

2 x 300 kVA

Page 109: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 109

China

ITT – LDK Solar:

9 x 55 kW

9 x 90 kW

9 x 225 kW

9 x 500 kW

Page 110: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 110

India

PVD Plast Mould Industries Ltd. **Fiberweb (INDIA) Ltd:

1 x 500 kVA

1 x 1000 kVA

Page 111: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 111

Iraq

Various Hospitals:

1 x 100 kVA

1 x 250 kVA

3 x 250 kVA

6 x 1000 kVA

Page 112: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 112

Israel

Avgol Ltd. Barkan

1 x 975 kVA

2 x 1000 kVA

3 x 1500 kVA (dual output)

4 x 1300 kVA (dual output)

Page 113: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 113

Malaysia

X-FAB - Kuching

(previous 1St Silicon Waferfab Plant)

4 x 1500 kVA

Page 114: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 114

Malaysia

Securities Commission Building, Kuala Lumpur

2 x 150 kVA USV

Infineon Power Fab Kulim

6 x 2000 kVA USV (6,6kV)

2 x 2250 kVA ESV (6,6kV)

Prime Minister Office Putrajaya

1 x 1500 kVA (dual output)

Page 115: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 115

Pakistan

International Airport Lahore:

1 x 200 kVA

1 x 250 kVA

Adamjee Group:

1 x 500 kVA

Page 116: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 116

Russian Federation

Moscow Interbank Currency Exchange:

1 x 500 kVA

Unicom Bank Moscow:

1 x 250 kVA

Moscow Government Central District:

1 x 150 kVA

Page 117: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 117

Singapore

Siltronic Samsung PTE Ltd

1 x 2000 kVA (dual output)

STMicroelectronics:

2 x 2000 kVA (dual output)

1 x 625 kVA (dual output)

2 x 1500 kVA

1 x 330 kVA (H-Vcon)

Page 118: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 118

Taiwan

Veterans Hospital Taipei

2 x 400 kVA 60 Hz

2 x 600 kVA 60 Hz

Page 119: Hitzinger UPS Systems · 2019-02-15 · HITZINGER GmbH 18 NBDK –IT Power systems A Hitzinger DDUPS system is a high-quality and permanent solution concerning clean power supply

HITZINGER GmbH 119

Thailand

Royal Thai Air Force:

1 x 120 kVA

VVIP Terminal – Suvarnabhumi Airport Bangkok:

1 x 550 kVA