Zio® / Zio Plus LCD Wall Module Feature Brief

• Used with Spyder® Controller with Sylk®

• Two-wire polarity-insensitive bus interface

• Up to four Zios per Sylk bus

• Pull down and view almost any point in the Spyder controller

• Link setpoint limits to a network variable

• Assign labels for enumerated values

• Multiple override options

• VAV balancing from Zio

• Customizable home screens

• Password protect access to controller parameters

• Use the Spyder tool to customize your configurations

• Very large backlit display

• Easy to use, borrows from Honeywell homes thermostat design

Page 3: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

3 HONEYWELL - CONFIDENTIAL3

Zio/Zio Plus TR70 Series Models

• Only four models do it all: TR71, TR71-H, TR75, TR75-H- TR70/TR70-H have been replaced by TR71/TR71-H models

New Features Zio TR70 Zio TR71 Zio Plus TR75

Scheduling     x

Parameter Memory (bytes)  1K 2K 4.9K

Multiple Zios on Sylk X* x x

Enumerated Values   x x

Setpoint Limits as NVs – linking now possible   x x

System and Fan command as NVs   x x

Password protection   x x

Firmware version/model visible on display   x x

0.5 and 5 value increments   x x

"-" and "/" characters  in parameter names   x x

xOnly 1 TR70 can be installed on any given sylk bus, and the address must be set to 1. Up to 4 TR71s and/or TR75s can be installed on any given sylk bus in any combination. If a TR70 resides on the bus, then the maximum number of Zios on the bus is 3.

Page 4: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

4 HONEYWELL - CONFIDENTIAL4

Compatibility

The new Zio TR71 and Zio Plus TR75 have functionality that is only available when using the new Spyder tool, and the new Spyder tool can only be used with the latest firmware versions of Spyder. See the chart below, and view the training presentation on the Spyder Re-Flash Tool for more info.

Tools supported: 2.0.8 (not 2.0.5) 3.x, 4.x, 5.x

Page 5: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

5 HONEYWELL - CONFIDENTIAL5

Zio Address Dial & Wire Terminals

Sylk Bus Address DialTR70 must be set to 1, only 1 TR70 per busTR71/TR75 set between 0 and 9Each wall module on the same Sylk bus must have a unique address.

Four Terminals1 and 2 for network jack (optional)

3 and 4 for Sylk Bus (to controller S-bus terminals)

Page 6: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

6 HONEYWELL - CONFIDENTIAL6

Zio Wiring

• Polarity insensitive• 22 AWG, unshielded, twisted pair,

solid wire recommended (smaller wire makes it easier to land two wires into one terminal).

• 18-24 AWG allowed depending on application

• 200 ft max on Sylk bus• Twisted pair recommended for wire

runs longer than 100 ft• Can use home run or daisy chain

wiring for multiple Zios. If wire size is too thick for two wires in the terminal, use pigtails as shown.

Page 7: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

7 HONEYWELL - CONFIDENTIAL7

Configuring Zio

• Zio is configured with S-bus Wall Module Configuration Wizard- This wizard is in the s-bus built-in in the Spyder Tool - Download the latest version of the Spyder Tool from the Buildings

Forum

Page 8: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

8 HONEYWELL - CONFIDENTIAL8

Add a Network and a Spyder

Page 9: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

9 HONEYWELL - CONFIDENTIAL9

Add a Wall Module to Spyder

Add the Spyder to the network, then right click on the Spyder and click

engineering mode to access the wire

sheet.

Page 10: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

10 HONEYWELL - CONFIDENTIAL10

SBusWallModule To Spyder Control Program

You can pull up an existing application

and replace the existing wall module block with the new S-BusWallModule built in. You will

need to recreate the parameters and

links.

Page 11: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

11 HONEYWELL - CONFIDENTIAL11

SBus WM Block imbedded in VAV App

Example of a S-BusWallModule imbedded in a VAV app

Page 12: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

12 HONEYWELL - CONFIDENTIAL12

General Settings

Right click the built-in to access

the wizard. Notice new options in the

left column, including

Schedule/Time and Password.

Page 13: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

13 HONEYWELL - CONFIDENTIAL13

Zio Parameter Screens

• Network parameters can be configured in the Configuration Wizard

• View and change parameters at Zio

• Parameters may include virtually any point in the controller.

• Sample parameter screens setup in the Configuration Wizard in the WEBs-AX Workbench:

Page 14: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

14 HONEYWELL - CONFIDENTIAL14

Categories and Parameters

Use Categories and Parameters tab to

set these up. Memory has been greatly expanded

for these parameters in the TR71 and TR75.

Page 15: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

15 HONEYWELL - CONFIDENTIAL15

Categories and Parameters

Click to add a parameter or

category, and click EDIT to customize.

Any screen showing this

parameter can be customized by

highlighted the pre-defined fields in the green screen at the

lower right.

Page 16: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

16 HONEYWELL - CONFIDENTIAL16

Categories and Parameters

Enter a name and an optional

description, then choose the

parameter type.

Page 17: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

17 HONEYWELL - CONFIDENTIAL17

Zio Customizable Home Screens• Multiple home screens can be saved to Zio with one set as the default• From the Home screen, the Tenant can

- Change the setpoint, fan speed and/or initiate override, if configured- View or view/change other parameters using the View More key if desired, if

configured

• Some sample home screens shown below:

Mix and match options for the home screen as desired

Page 18: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

18 HONEYWELL - CONFIDENTIAL18

Home Screen Options

Home screens can be customize, and

multiple home screens can be set up so that they can be later selected at

the wall module without needing to

go into the tool again.

Page 19: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

19 HONEYWELL - CONFIDENTIAL19

Home Screen Options

The drop down fields in the green

screen allow you to choose which

parameter values you want to show

in the home screen. Highlight the black segment fields as

desired.

Page 20: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

20 HONEYWELL - CONFIDENTIAL20

Occupancy and Override

Customize the occupancy and

override in this tab. The valid states chosen will show up when the user

presses the override button on

Zio.

Page 21: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

21 HONEYWELL - CONFIDENTIAL21

Occupancy and Override

Clicking settings will allow you to

choose the network bypass time, or

customize the time period yourself.

When a user presses override, they will see the

minimum time first, and they can

increment up to the maximum override

time if desired.

Page 22: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

22 HONEYWELL - CONFIDENTIAL22

Fan Command

New in the fan command is the

ability to designate the fan command

as a network setpoint, allowing it to be pulled up into a graphic for easy

access. This feature is not

available on the TR70.

Page 23: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

23 HONEYWELL - CONFIDENTIAL23

System Status and Command

The system command can also now be set up as a network setpoint,

like the fan command. Clicking

Show System Status brings up

the system modes on the top of the screen, as shown

below.

Page 24: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

24 HONEYWELL - CONFIDENTIAL24

System Status and Command

Right click the built-in to access

the wizard. Notice new options in the

left column, including

Schedule/Time and Password.

Page 25: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

25 HONEYWELL - CONFIDENTIAL25

Memory Usage Window

Click the memory usage button at

lower left to access memory allocation.

Exactly what resides in files A, B, C, and tips for helping reduce

memory if needed, are available in the Help menu – just

click Help. All fields must be

below 100% before attempting to

download.

Page 26: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

26 HONEYWELL - CONFIDENTIAL26

Schedule/Time

The Zio Plus TR75 provides access to

the Spyder schedule. Choose

the options you want in this tab. If multiple TR75s are used on the same Sylk bus, use the same schedule display for all

TR75s (8 day, etc).

Page 27: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

27 HONEYWELL - CONFIDENTIAL27

Password

The TR71 and TR75 now also offer

password protection. Enable

and choose a password in this

tab. Warning: If a password is

forgotten, the only way to access the

password is by reconnecting the

Spyder tool to access this screen.

Page 28: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

28 HONEYWELL - CONFIDENTIAL28

Preview – Tenant View

Preview allows you to simulate the Zio

interface before downloading, a

great way to make sure it is

configured as you expect. You can

view both the tenant mode and

the contractor mode.

or

Tenant view

Contractor view

Page 29: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

29 HONEYWELL - CONFIDENTIAL29

Finish Zio Configuration

1. Verify configuration in Preview window

2. Check memory usage

3. Click Finish

Page 30: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

30 HONEYWELL - CONFIDENTIAL30

Access Zio Contractor Mode

• Accessing Contractor Mode at the Zio

- Enter and exit the contractor mode by pressing Up, Down, and Middle softkey, then enter the password if password protected

- In the contractor mode, you can choose the home screen, select parameter access to tenant (Yes or No as desired), and view/change parameters.

- Parameters may include virtually any point in the controller.

- Contractor mode screens with parameter access

Page 31: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

31 HONEYWELL - CONFIDENTIAL31

Scheduling at the Zio Wall Module

The Spyder schedule is easily accessible on the Zio Plus TR75 Wall Module

• You can access either in the tenant mode (if unrestricted) and/or contractor mode.

• Set each daily time period or event (labeled E1-E4) to occupied, unoccupied, or standby, each with it’s own start time.

• The Zio Plus gives you access to the Schedule that resides in the Spyder. Access to the network schedule from the Zio is not currently supported.

Page 32: Honeywell Confidential New Zio®/Zio Plus Wiring & Configuration Basics

32 HONEYWELL - CONFIDENTIAL32

Additional Resources

• Zio Online DemoFind at customer.honeywell.com/zio

• Zio Sales OvervieweLearning Module and all training material

Find at customer.honeywell.com/zio