honeywell confidential new zio®/zio plus wiring & configuration basics
TRANSCRIPT
Honeywell Confidential
New Zio®/Zio Plus Wiring & Configuration Basics
2 HONEYWELL - CONFIDENTIAL2
Zio® / Zio Plus LCD Wall Module Feature Brief
• Used with Spyder® Controller with Sylk®
• Two-wire polarity-insensitive bus interface
• Up to four Zios per Sylk bus
• Pull down and view almost any point in the Spyder controller
• Link setpoint limits to a network variable
• Assign labels for enumerated values
• Multiple override options
• VAV balancing from Zio
• Customizable home screens
• Password protect access to controller parameters
• Use the Spyder tool to customize your configurations
• Very large backlit display
• Easy to use, borrows from Honeywell homes thermostat design
3 HONEYWELL - CONFIDENTIAL3
Zio/Zio Plus TR70 Series Models
• Only four models do it all: TR71, TR71-H, TR75, TR75-H- TR70/TR70-H have been replaced by TR71/TR71-H models
New Features Zio TR70 Zio TR71 Zio Plus TR75
Scheduling x
Parameter Memory (bytes) 1K 2K 4.9K
Multiple Zios on Sylk X* x x
Enumerated Values x x
Setpoint Limits as NVs – linking now possible x x
System and Fan command as NVs x x
Password protection x x
Firmware version/model visible on display x x
0.5 and 5 value increments x x
"-" and "/" characters in parameter names x x
xOnly 1 TR70 can be installed on any given sylk bus, and the address must be set to 1. Up to 4 TR71s and/or TR75s can be installed on any given sylk bus in any combination. If a TR70 resides on the bus, then the maximum number of Zios on the bus is 3.
4 HONEYWELL - CONFIDENTIAL4
Compatibility
The new Zio TR71 and Zio Plus TR75 have functionality that is only available when using the new Spyder tool, and the new Spyder tool can only be used with the latest firmware versions of Spyder. See the chart below, and view the training presentation on the Spyder Re-Flash Tool for more info.
Tools supported: 2.0.8 (not 2.0.5) 3.x, 4.x, 5.x
5 HONEYWELL - CONFIDENTIAL5
Zio Address Dial & Wire Terminals
Sylk Bus Address DialTR70 must be set to 1, only 1 TR70 per busTR71/TR75 set between 0 and 9Each wall module on the same Sylk bus must have a unique address.
Four Terminals1 and 2 for network jack (optional)
3 and 4 for Sylk Bus (to controller S-bus terminals)
6 HONEYWELL - CONFIDENTIAL6
Zio Wiring
• Polarity insensitive• 22 AWG, unshielded, twisted pair,
solid wire recommended (smaller wire makes it easier to land two wires into one terminal).
• 18-24 AWG allowed depending on application
• 200 ft max on Sylk bus• Twisted pair recommended for wire
runs longer than 100 ft• Can use home run or daisy chain
wiring for multiple Zios. If wire size is too thick for two wires in the terminal, use pigtails as shown.
7 HONEYWELL - CONFIDENTIAL7
Configuring Zio
• Zio is configured with S-bus Wall Module Configuration Wizard- This wizard is in the s-bus built-in in the Spyder Tool - Download the latest version of the Spyder Tool from the Buildings
Forum
8 HONEYWELL - CONFIDENTIAL8
Add a Network and a Spyder
9 HONEYWELL - CONFIDENTIAL9
Add a Wall Module to Spyder
Add the Spyder to the network, then right click on the Spyder and click
engineering mode to access the wire
sheet.
10 HONEYWELL - CONFIDENTIAL10
SBusWallModule To Spyder Control Program
You can pull up an existing application
and replace the existing wall module block with the new S-BusWallModule built in. You will
need to recreate the parameters and
links.
11 HONEYWELL - CONFIDENTIAL11
SBus WM Block imbedded in VAV App
Example of a S-BusWallModule imbedded in a VAV app
12 HONEYWELL - CONFIDENTIAL12
General Settings
Right click the built-in to access
the wizard. Notice new options in the
left column, including
Schedule/Time and Password.
13 HONEYWELL - CONFIDENTIAL13
Zio Parameter Screens
• Network parameters can be configured in the Configuration Wizard
• View and change parameters at Zio
• Parameters may include virtually any point in the controller.
• Sample parameter screens setup in the Configuration Wizard in the WEBs-AX Workbench:
14 HONEYWELL - CONFIDENTIAL14
Categories and Parameters
Use Categories and Parameters tab to
set these up. Memory has been greatly expanded
for these parameters in the TR71 and TR75.
15 HONEYWELL - CONFIDENTIAL15
Categories and Parameters
Click to add a parameter or
category, and click EDIT to customize.
Any screen showing this
parameter can be customized by
highlighted the pre-defined fields in the green screen at the
lower right.
16 HONEYWELL - CONFIDENTIAL16
Categories and Parameters
Enter a name and an optional
description, then choose the
parameter type.
17 HONEYWELL - CONFIDENTIAL17
Zio Customizable Home Screens• Multiple home screens can be saved to Zio with one set as the default• From the Home screen, the Tenant can
- Change the setpoint, fan speed and/or initiate override, if configured- View or view/change other parameters using the View More key if desired, if
configured
• Some sample home screens shown below:
Mix and match options for the home screen as desired
18 HONEYWELL - CONFIDENTIAL18
Home Screen Options
Home screens can be customize, and
multiple home screens can be set up so that they can be later selected at
the wall module without needing to
go into the tool again.
19 HONEYWELL - CONFIDENTIAL19
Home Screen Options
The drop down fields in the green
screen allow you to choose which
parameter values you want to show
in the home screen. Highlight the black segment fields as
desired.
20 HONEYWELL - CONFIDENTIAL20
Occupancy and Override
Customize the occupancy and
override in this tab. The valid states chosen will show up when the user
presses the override button on
Zio.
21 HONEYWELL - CONFIDENTIAL21
Occupancy and Override
Clicking settings will allow you to
choose the network bypass time, or
customize the time period yourself.
When a user presses override, they will see the
minimum time first, and they can
increment up to the maximum override
time if desired.
22 HONEYWELL - CONFIDENTIAL22
Fan Command
New in the fan command is the
ability to designate the fan command
as a network setpoint, allowing it to be pulled up into a graphic for easy
access. This feature is not
available on the TR70.
23 HONEYWELL - CONFIDENTIAL23
System Status and Command
The system command can also now be set up as a network setpoint,
like the fan command. Clicking
Show System Status brings up
the system modes on the top of the screen, as shown
below.
24 HONEYWELL - CONFIDENTIAL24
System Status and Command
Right click the built-in to access
the wizard. Notice new options in the
left column, including
Schedule/Time and Password.
25 HONEYWELL - CONFIDENTIAL25
Memory Usage Window
Click the memory usage button at
lower left to access memory allocation.
Exactly what resides in files A, B, C, and tips for helping reduce
memory if needed, are available in the Help menu – just
click Help. All fields must be
below 100% before attempting to
download.
26 HONEYWELL - CONFIDENTIAL26
Schedule/Time
The Zio Plus TR75 provides access to
the Spyder schedule. Choose
the options you want in this tab. If multiple TR75s are used on the same Sylk bus, use the same schedule display for all
TR75s (8 day, etc).
27 HONEYWELL - CONFIDENTIAL27
Password
The TR71 and TR75 now also offer
password protection. Enable
and choose a password in this
tab. Warning: If a password is
forgotten, the only way to access the
password is by reconnecting the
Spyder tool to access this screen.
28 HONEYWELL - CONFIDENTIAL28
Preview – Tenant View
Preview allows you to simulate the Zio
interface before downloading, a
great way to make sure it is
configured as you expect. You can
view both the tenant mode and
the contractor mode.
or
Tenant view
Contractor view
29 HONEYWELL - CONFIDENTIAL29
Finish Zio Configuration
1. Verify configuration in Preview window
2. Check memory usage
3. Click Finish
30 HONEYWELL - CONFIDENTIAL30
Access Zio Contractor Mode
• Accessing Contractor Mode at the Zio
- Enter and exit the contractor mode by pressing Up, Down, and Middle softkey, then enter the password if password protected
- In the contractor mode, you can choose the home screen, select parameter access to tenant (Yes or No as desired), and view/change parameters.
- Parameters may include virtually any point in the controller.
- Contractor mode screens with parameter access
31 HONEYWELL - CONFIDENTIAL31
Scheduling at the Zio Wall Module
The Spyder schedule is easily accessible on the Zio Plus TR75 Wall Module
• You can access either in the tenant mode (if unrestricted) and/or contractor mode.
• Set each daily time period or event (labeled E1-E4) to occupied, unoccupied, or standby, each with it’s own start time.
• The Zio Plus gives you access to the Schedule that resides in the Spyder. Access to the network schedule from the Zio is not currently supported.
32 HONEYWELL - CONFIDENTIAL32
Additional Resources
• Zio Online DemoFind at customer.honeywell.com/zio
• Zio Sales OvervieweLearning Module and all training material
Find at customer.honeywell.com/zio
• Zio / Zio Plus Literature- 67-7071 Zio Sell Sheet- 62-0271 Zio Install Instructions- 63-1322 Zio Specification Data- 63-2719 Zio Operating GuideFind at customer.honeywell.com
customer.honeywell.com