ht cable schedule, r1

Upload: kxalxo

Post on 09-Jan-2016

249 views

Category:

Documents


5 download

DESCRIPTION

Cable Schedul

TRANSCRIPT

Top Sheet

1. Cable sizes, route length and number of runs have been considered based on available detail provided in Technical Specification.

2. Make, type and specification of cables shall be as per TS ( Cl. No. 4.12.1)NOTES :1. Cable sizes, route length and number of runs have been considered based on available detail provided in Technical Specification.2. Make, type and specification of cables shall be as per TS ( Cl. No. 4.12.1)

101.08.13Revised for re-submission to MECON for ApprovalRNBRNBABCRev. No.DateDescriptionByChekdAppvdCategory of DrawingXApprovalInformationReferenceRecordConstructionSAIL - ROURKELA STEEL PLANT, ROURKELA

HT/ LT SUB STATION FOR LIME PLANT, CED, PROPANE PLANT WITH INTERPLANT CABLING & MISC. ELECTRICAL WORKS4.2 MTPA EXPANSION, PACKAGE No. - 73ACONSULTANT: MECON LIMITEDCONTRACTOR:STERLING & WILSON LTD., KOLKATANameDateNameDateINTER PLANT HT ( 33 KV & 6.6 KV)DesignedRNB15.02.13CABLE SCHEDULEDrawnScale :NTSCheckedRNB15.02.13Project's Drg. No.RSP-ROURKELA/S&WL/20/29/DE/242SheetRev.ApprovedABC15.02.13SAIL-RSP Drg. No.1 of 41

PCS

STERLING & WILSON LTD., KOLKATA ECC Division - EDRCPROJECTHT/ LT SUB STATION FOR LIME PLANT, CED, PROPANE PLANT WITH INTERPLANT CABLING & MISC. ELECTRICAL WORKS, PACKAGE No. - 073ADOCUMENT NO RSP-ROURKELA/S&WL/20/29/DE/242DATE8/30/13TITLEHT (33kV & 6.6kV CABLE SCHEDULE PREPARED CHECKEDSHEETRNBRNB1 of 1

Sl. No.Cable NoFromPanel No.ToPanel NoConnected LoadCABLE DETAILSRoute Length(km)Total Length(km)TermnJointsDrum length (m)REMARKSVoltage (kV)MaterialRunsCoreArea Sq.mmInsul.

A33 KV173A-00-02-H1-001MSDS-3 (O/D)CPP-3 (GIS)33CU13400XLPE0.90.921500Along Trays in Existing Cable Tunne/ Cable Bridge.273A-02-01-H1-002CPP-1 (AIS - I/D)CPP-3 (GIS)33CU23400XLPE2.14.248500Along Trays in Existing Cable Tunne/ Cable Bridge, Buried U/G.

BLBDS-13173A-06-03-H2-001ALBSS-1LBDS-13 HT Sw. Board, Incoming Feeder-16.6AL43240XLPE2.18.48161000Existing Cable Tunne / Cable Bridge, Buried U/G, On trays within SS (S2, A4)273A-06-03-H2-002ALBSS-1LBDS-13 HT Sw. Board, Incoming Feeder-26.6AL43240XLPE2.18.48161000Existing Cable Tunne / Cable Bridge, Buried U/G, On trays within SS (Y1, A4)73A-06-03-H2-003/1LBSS-1HT Isolator-16.6AL13240XLPE0.040.0420100073A-06-03-H2-003HT Isolator-1630 KVA Trafo-1 atLBDS-136.6AL13240XLPE0.0040.004201000373A-06-03-H2-003LBSS-1630 KVA Trafo-1 atLBDS-136.6AL13240XLPE2.12.1241000Y2, A7, D3, F373A-03-03-H2-004/1LBSS-1HT Isolator-26.6AL13240XLPE2.12.124100073A-03-03-H2-004HT Isolator-2630 KVA Trafo-2 atLBDS-136.6AL13240XLPE0.0040.004201000473A-03-03-H2-004LBDS-13 HT Sw. Board630 KVA Trafo-2 atLBDS-136.6AL13240XLPE0.040.04201000A7, D3573A-03-03-H2-005ALBDS-13 HT Sw. BoardExisting NCP, Fdr.-16.6AL23250XLPE0.61.2421000A4 / A5, K2 /K3, Buried U/G673A-03-03-H2-006ALBDS-13 HT Sw. BoardExisting NCP, Fdr.-26.6AL23250XLPE0.61.2421000A4 / A5, K2 /K3, Buried U/G773A-03-03-H2-007LBDS-13 HT Sw. BoardExisting MarshallingYard S/S, Fdr.-16.6AL13600XLPE0.250.25201000A4 / A5, K2 /K3, Buried U/G873A-03-03-H2-008LBDS-13 HT Sw. BoardExisting MarshallingYard S/S, Fdr.-26.6AL13600XLPE0.250.25201000A4 / A5, K2 /K3, Buried U/G73A-03-03-H2-009LBDS-13 HT Sw. Board1MVAr Capacitor bank-1 6.6AL13240XLPE0.040.0420100073A-03-03-H2-010LBDS-13 HT Sw. Board1MVAr Capacitor bank-26.6AL13240XLPE0.040.04201000

CLTSS- 01A173A-07-04-H2-001LBSS-2HT Isolator-16.6AL13240XLPE0.10.1201000Buried U/G, Pipes273A-07-04-H2-001/1HT Isolator-1LTSS-01A, 1600 KVA Trafo-16.6AL13240XLPE0.080.08201000On trays373A-07-04-H2-002LBSS-2HT Isolator-26.6AL13240XLPE0.10.1201000Buried U/G, Pipes473A-07-04-H2-002/1HT Isolator-2LTSS-01A, 1600 KVA Trafo-26.6AL13240XLPE0.10.1201000On trays

DLBDS-15173A-08-05-H2-001Existing NSP - S/SLBDS-15 HT Sw. Board, Incoming Feeder-16.6AL23240XLPE1.252.5441000Buried U/G, Existing Cable Tunne, Buried U/G, On trays within SS (S3,A4)273A-08-05-H2-002Existing BP- II, HT S/SLBDS-15 HT Sw. Board, Incoming Feeder-26.6AL13240XLPE1.41.4221000Existing Cable Tunne, Buried U/G, On trays within SS ( S3, A4)373A-08-05-H2-003LBDS-15 HT Sw. Board1600 KVA Trafo-1 at LBDS-15 ( Open Bus- Bar)6.6AL13240XLPE0.050.05201000A6, D3473A-08-05-H2-004LBDS-15 HT Sw. Board1600 KVA Trafo-2 at LBDS-15 (Open Bus- Bar)6.6AL13240XLPE1.41.4221000A6, D3, F3573A-08-05-H2-005LBDS-15 HT Sw. BoardHRLS6.6AL13240XLPE0.20.2201000A3, S2, Buried U/G673A-08-05-H2-006LBDS-15 HT Sw. BoardCPTI6.6AL13240XLPE1.11.1221000A6, D3, F3, Pipes, Buried U/GNote: Buried 33 kV cable shall have water swellable tape.

Voltage & No of CoreSizeLength (Km)Term (Nos)Joints (Nos)6.6 kV , 3 Core,AL24031.098665433 kV , 3 Core,CU4005.169

PCS-1INTER PLANT HT ( 33 KV & 6.6 KV) POWER CABLE SCHEDULE

Sl.No.Circuit No.FROM(A-End)TO(Z-End)No. OfCoreCond.Size (Sq mm)Cable DescriptionRouteLength, as per TS (M)Route DetailRemarks

A33 KV173A-00-02-H1-001MSDS-3 (O/D)CPP-3 (GIS)340033 KV, CU, XLPE,Armd.900Along Trays in Existing Cable Tunne/ Cable Bridge.273A-02-01-H1-002ACPP-1 (AIS - I/D)CPP-3 (GIS)340033 KV, CU, XLPE, Armd.2100Along Trays in Existing Cable Tunne/ Cable Bridge, Buried U/G.373A-02-01-H1-002BCPP-1 (AIS - I/D)CPP-3 (GIS)340034 KV, CU, XLPE,Armd.2100doBLBDS-13

173A-06-03-H2-001ALBSS-1LBDS-13 HT Sw. Board, Incoming Feeder-132406.6 KV( UE ), AL, XLPE, ST2, inner and outer sheathed, Armd.2100Existing Cable Tunne / Cable Bridge, Buried U/G, On trays within SS (S2, A4)273A-06-03-H2-001BLBSS-1do3240do2100do373A-06-03-H2-001CLBSS-1do3240do2100do473A-06-03-H2-001DLBSS-1do3240do2100do573A-06-03-H2-002ALBSS-1LBDS-13 HT Sw. Board, Incoming Feeder-23240do2100Existing Cable Tunne / Cable Bridge, Buried U/G, On trays within SS (Y1, A4)673A-06-03-H2-002Bdodo3240do2100do773A-06-03-H2-002Cdodo3240do2100do873A-06-03-H2-002Ddodo3240do2100do973A-06-03-H2-003LBSS-1630 KVA Trafo-1 atLBDS-133240do2100Y2, A7, D3, F31073A-03-03-H2-004LBDS-13 HT Sw.Board630 KVA Trafo-2 atLBDS-133240do40A7, D31173A-03-03-H2-005ALBDS-13 HT Sw.BoardExisting NCP, Fdr.-13250do600A4 / A5, K2 /K3, Buried U/G1273A-03-03-H2-005BLBDS-13 HT Sw.BoardExisting NCP, Fdr.-13250do600A4 / A5, K2 /K3, Buried U/G1373A-03-03-H2-006ALBDS-13 HT Sw.BoardExisting NCP, Fdr.-23250do600A4 / A5, K2 /K3, Buried U/G1473A-03-03-H2-006BLBDS-13 HT Sw.BoardExisting NCP, Fdr.-23250do600A4 / A5, K2 /K3, Buried U/G1573A-03-03-H2-007LBDS-13 HT Sw.BoardExisting MarshallingYard S/S, Fdr.-13600do250A4 / A5, K2 /K3, Buried U/G1673A-03-03-H2-008LBDS-13 HT Sw.BoardExisting MarshallingYard S/S, Fdr.-23600do250A4 / A5, K2 /K3, Buried U/G

INTER PLANT HT ( 33 KV & 6.6 KV) POWER CABLE SCHEDULESl.No.

CCircuit No.FROM(A-End)TO(Z-End)No. OfCoreCond.Size (Sq mm)Cable DescriptionRouteLength, as per TS (M)Route DetailRemarksSl.No.

CLTSS- 01A173A-07-04-H2-001LBSS-2HT Isolator-132406.6 KV( UE ), AL, XLPE, ST2, inner and outersheathed, Armd.100Buried U/G, Pipes273A-07-04-H2-001/1HT Isolator-1LTSS-01A, 1600 KVATrafo-13240do8On trays373A-07-04-H2-002LBSS-2HT Isolator-23240do100Buried U/G, Pipes473A-07-04-H2-002/1HT Isolator-2LTSS-01A, 1600 KVATrafo-23240do8On trays

DLBDS-15173A-08-05-H2-001AExisting NSP - S/SLBDS-15 HT Sw. Board, IncomingFeeder-132406.6 KV( UE ), AL, XLPE, ST2, inner and outersheathed, Armd.1250Buried U/G, Existing Cable Tunne, Buried U/G, On trays within SS (S3,A4)273A-08-05-H2-001BExisting NSP - S/SLBDS-15 HT Sw. Board, IncomingFeeder-13240do1250do373A-08-05-H2-002Existing BP- II, HT S/SLBDS-15 HT Sw. Board, IncomingFeeder-23240do1400Existing Cable Tunne, Buried U/G, On trays within SS ( S3, A4)373A-08-05-H2-003LBDS-15 HT Sw. Board1600 KVA Trafo-1 at LBDS-15 ( Open Bus- Bar)3240do50A6, D3473A-08-05-H2-004LBDS-15 HT Sw. Board1600 KVA Trafo-2 at LBDS-15 (Open Bus- Bar)3240do1400A6, D3, F3573A-08-05-H2-005LBDS - 15HRLS3240do200A3, S2, Buried U/G673A-08-05-H2-006LBDS - 15CPTI3240do1100A6, D3, F3, Pipes, Buried U/G