Huawei UPS2000-G Solutions
2
Content
3 UPS2000-G Series Product IntroductionUPS2000-G Series Product Introduction
2
1 Challenges and Trends in UPS System Challenges and Trends in UPS System
UPS2000-G Series SolutionsUPS2000-G Series Solutions
4 Successful CasesSuccessful Cases
3
Reliable UPS Against Poor Grid
Unavoidable grid problems
Blackout of Manhattan Blackout of USA and Canada
Harsh environment condition
Lightning Poor quality of grid
A variety of loadsPoor grid Damage of electrical device Adverse environment condition
4
Efficient UPS for Energy SavingHigh efficiency, low power consumption
It is estimated that the annual power consumption of the data centers all over the world is up to 40,000,000,000 kW·h.
Energy consumption of typical data center
If the efficiency of UPS is improved from 90% to 92%, the power consumption decreasing for UPS itself is about 21.7% and cost saving for data center is about 0.5 billion kW·h, reducing about 20 million tons of carbon emissions.
Business grow with low OPEX
5
Content
3 UPS2000-G Series Product IntroductionUPS2000-G Series Product Introduction
2
1 Challenges and Trends in UPS System Challenges and Trends in UPS System
UPS2000-G Series SolutionsUPS2000-G Series Solutions
4 Successful CasesSuccessful Cases
6
Huawei UPS Solutions
UPS5000-A(30/40kVA )
UPS2000-A 1kVA UPS2000-A 6/10kVA
UPS5000-A(400/500kVA)
UPS5000-E (25-125kVA)
25kVA power module 2U
UPS5000-E (50-300kVA)
50kVA power module 3UUPS5000-S (50-300kVA)
UPS5000-E (50-500kVA)
50kVA power module 3UUPS5000-S (50-500kVA)
UPS5000-E (50-600kVA)
50kVA power module 3UUPS5000-S(50-600kVA)
UPS5000-E (50-800kVA)
50kVA power module 3UUPS5000-S(50-800kVA)
UPS5000-A(600kVA)
UPS5000-A 800kVA
UPS5000-A(60/80/120kVA)
UPS5000-A(200A/300kV )
UPS5000-E (50-200kVA)
50kVA power module 3UUPS5000-S (50-200kVA)
UPS2000-G 15/20kVAUPS2000-G 6/10kVAUPS2000-G 1/3kVA
UPS2000-A 2kVA UPS2000-A 3kVA
Modular UPS5000-E 25-800kVA & UPS5000-S 50-800kVA
R/T UPS2000-G 1-20kVA
Tower UPS5000-A 30-800kVA
Tower UPS2000-A 1-10kVA
7
• Tower/rack convertible
• High expandability up to 4 units, easy to expand
• Battery intelligent management, flexible configuration
• Integrated monitoring Platform for the whole network
UPS2000-G Core Value
• Achieving the World‘s first batch of “ Energy Star ”certification
• High efficiency at low load rate
• Widest input voltage range
• 5kA lightning design
• Powerful overload capability
• Alarms for key components
Reliable
Efficient
Simple
8
• Input voltage range: 80V to 280V
• Input frequency range: 40 Hz to 70 Hz
• Supports DG adaptability
80V to 280V40 Hz to 70 Hz
Common Power Problems
Wide input voltage and frequency range
EfficientReliable Simple
80V AC input 280V AC input Spike wave input Serious distortion wave input
High Adaptability to Extend 50% of Battery Life
Minimizes battery use to extend battery
lifespan.
9
More than 70% of lightning accidents involve
the power supply system.
More than 90% of lightning accidents involve
computer network and communication
systems armed with UPS.
Unrecoverable hardware damage to IT equipment caused by lightning
5 kA lightning protection design by simulating actual lightning
Lightning design(Input common-mode)
HUAWEI 6 kV/5 kA
Traditional 4 kV/2 kA or none
Huawei UPS can prevent 90% of failures
caused by lightning by protecting equipment
input ports.
5 kA Lightning Protection Reducing 90% of Failure
EfficientReliable
Rocket-triggered lightening
Simple
10
125% overload for 5 minutes 150% overload for 1 minute
150% Overload
High Overload Capacity
Various Loads
• Output power factor: 0.9• Capacitive/inductive loads from
lead 0.5 to lag 0.5• High output load capacity ensuring
expansion demands in future
Capacity/ Inductive Loads
Electrical load with constant changes
High Overload & Adaptability to Ensure Supply Quality
EfficientReliable
Reduces transfer times to bypass mode, ensuring customer equipment power supply quality.
Load capacity
Simple
11
Failure Pre-Alarms against Potential System Risk
Capacitor failureBattery failureFan failure
• Capacity decrease caused by electrolytes drying out will decrease the quality of
the power supply and increase the risk of power off.
• Fan will slow down due to dust and drying of lubrication; UPS temperature will
increase quickly until transfer to bypass mode. UPS life will be shortened and
power quality can not be ensured.
• Battery runtime will be reduced due to battery aging.
Common failureReasons and consequences
EfficientReliable
Dissipative components in UPS system
Simple
12
1,000 hours at 40℃
Temperature, Humidity, Bias (THB)Temperature: 40℃
Humidity: 95% for 1,000h
Temperature shocksampling test
High temperature test
-40°C to 70 ℃HALT
Highly accelerated life test
-60 to 110 ℃ ℃
5 cycles
Global Certification Test Center
Long Life Test (LLT)Temperature: 40℃
6 months
Open field
Hainan open field
Airborne hygroscopic dust , salt
spray environment
Shenzhen open field
Lightning test
Rocket-triggered lightening
5 kA Lightning
Strictest Testing — Higher Than Industry Standard
EfficientReliable Simple
13
High humidity
Sulfide dust
14 days
Strengthen measures
Enhance environmental adaptability
Airborne Hygroscopic Dust Test for Higher Reliability
Hainan open field
EfficientReliable Simple
14
Energy star certification
• System efficiency: 6kVA: 94%
10kVA: 94.5%
15kVA/20kVA: up to 95%
• High efficiency up to 98% in ECO mode
Batch 1 Energy Star certification:
First in the UPS field worldwide
High efficiency , saving OPEX
The Highest Efficiency Up to 95%
efficiency
Load rate
10kVA efficiency test curve
EfficientReliable Simple
50% load rate of 10kW load,compared with other UPS,UPS2000-G save more than ¥ 4634/year
15
Multiple FormatsRack or Tower
• LCD rotating design, more convenient
for R/T conversion
• High power density, 2U/3U high, 650
mm depth
• Can be installed in 900 mm deep, 19-
inch rack
• 6 kVA supports 1ph input, 1ph output
• 10 kVA supports 3ph input, 1ph output;
1ph input, 1ph output
• 15 kVA/20 kVA supports 3ph input, 3ph
output; 3ph input, 1ph output; 1ph input,
1ph output
Three-phase five-wireSingle-phase three-wire
Friendly Interactive Interface
• LCD displays system status
• Supports five languages:
English, Chinese, French,
Spanish, and Russian
Various Installations for Multiple Scenarios
EfficientReliable Simple
16
Hierarchical power distribution Parallel system: Up to four units, easy to expand
• Auto-sensing parallel, easy to form N + X configuration
• Parallel systems require only one communication card
• The ring parallel line eliminates the failure of a single parallel
cable
• The 15/20 kVA parallel system shares batteries, reducing
customer battery costs
• The primary load is turned off when the system is
overloaded or in battery mode to extend quality of
the main load power supply.
Primary load Secondary load
Parallel System: Up to Four Units
EfficientReliable
Ring parallel line
Simple
17
Flexible Configuration and Maintenance Senior Management
•20 to 16 cells per string for 6K/10K; 32 to 40 cells per string for 15/20K. When removing damaged batteries, the remaining batteries will work normally.
Damaged battery due to thermal runaway
•Automatic identification of electrical environment, enabling intelligent hibernation mode in a healthy grid.
•Detects battery states in real time and supports battery pre-alarm.
Old batteries can be reused.
Intelligent Management to Extend Battery Life
Intelligent Charge and Discharge
•Automatic equalized and float-charging conversion and temperature compensation function prevent battery over- or under-charging to extend battery life.
•Automatically adjusts discharge termination voltage in accordance with load condition and the discharge time.
Battery discharging curve
Battery voltageConstant voltage
Temperature compensation
Battery hibernation
EfficientReliable
×
Simple
18
•Monitoring unit supports remote online
upgrade.
•Supports RS485, SNMP, USB, and dry
contact.
•Displays real-time system running state.
•Power supply and battery testing systems can
be controlled.
Remote online upgrade
Easy to manage
Integrated Monitoring System
EfficientReliable
Output reportReal-time monitoring
Pre-failure
Asset management
Single UPS monitoring (USB) Multiple UPS network management system SMS alarm Terminal remote management
NetEco 1000U
interface
Simple
19
Content
3 UPS2000-G Series Product IntroductionUPS2000-G Series Product Introduction
2
1 Challenges and Trends in UPS System Challenges and Trends in UPS System
UPS2000-G Series SolutionsUPS2000-G Series Solutions
4 Successful CasesSuccessful Cases
20 Page20
UPS2000-G Family Overview Description Remarks
UPS
1kVA long backup time model
3kVA long backup time model
6kVA Standard/long backup time model
10kVA Standard/long backup time model
15kVA long backup time model
20kVA long backup time model
Power distribution
Battery pack 240V ,7/9Ah; 36V,7Ah; 96V,7Ah
Battery box 40Ah/65Ah,36V;40Ah,96V
3/1 PDU Only for 6kVA to 20kVA UPS
3/3 PDU Only for 6kVA to 20kVA UPS
6kVA transformer 2:1:1 (Only for 6kVA to 20kVA UPS)
10kVA transformer 2:1:1 (Only for 6kVA to 20kVA UPS)
Optional accessories
SNMP card SNMP/Web monitoring management
Modbus card RS485 networking
Dry contact card Input and output signal
Battery temperature sensor Battery temperature monitoring
Temperature and humidity sensor
Environment temperature and humidity monitoring
SNMP card
Modbus card
Dry contact card
Temperature and humidity sensor
Battery temperature sensor
Transformer
Power Distribution Unit (PDU)
Battery pack
UPS
GSM Modem
21
UPS Port Introduction (1K to 3K)
1KVA
2KVA
C14 input4 C13 output Battery Terminals
GB Long Run Model IEC Long Run Model
Standard Model: No external battery interface
3 10A output 10A input Battery Terminals
4 10A output 10A input Battery Terminals C14 input6 C13 output Battery Terminals
3KVA
4 10A output 16A input Battery Terminals C20 input6 C13 output Battery TerminalsOT Terminals C19 Terminals
22
UPS Port Introduction (6K to 20K)
10K Model Example
Input circuit breaker
Maintenance bypass port
(MBS)
Controller Area Network (CAN) communications
Temperature sensor port : (40~80 )℃
• Optional card slot • SNMP card• Modbus card• Dry contact card
Battery ports: PP45
Parallel ports
AC output ports
AC input ports
Emergency Power Off
23
Flexible Installation: Tower/Rack
Support bases(Tower-installation )
Adjustable guide rails ( Rack-installation)
Rotate LOGO
Rotate control panel
Open the panel
Tower installation
• The support bases are delivered with the UPS.
•The support base length is adjustable, you can add components to increase the length.
• The installation brackets are delivered with the UPS.
•The guide rails are optional accessories
24
Mupltiple Formats: 1/1,3/1,3/3
3/1
1/11/1
10K model 15K model 20K model6K model
• Formats transformation is realized by short-circuit busbars.• Output format can be set on the LCD display.
One mains input
One mains input
One mains input
3/3
3/3
1/1
3/1
3/1
Two mains input
One mains input
Two mains input
One mains input
One mains input
3/3
3/3
1/1
3/1
3/1
Two mains input
One mains input
Two mains input
One mains input
One mains input
25
Battery Installation Type
Short backup time mode(Battery pack )
Long backup time mode(Battery rack )
IMPORTANT: 15K/20K requires cable distribution box in battery pack mode !!
Battery pack
6K/10K model :Battery ports: PP45 for
15K/20K model : Battery ports: OT
Battery pack
Batteryrack
26
Flexible Monitoring-USB/SNMP/Modbus/Dry Contact
Parallel system networking
Modbus networking modeNetwork monitoring : SNMP+ Ethernet
Network monitoring :Dry contact +User interface
Standard cable
Single monitoring : USB + NetEco 1000U Network monitoring : RS485 (Modbus)
Single UPS networking
Parallel networking
UPS and PC are connected by USB line in single UPS system
Modbus protocol YDN-23 protocol
Only one communication card
27
Optional Accessories: Battery Pack and Box (1K to 3K)
1K: Backup time schedule of battery pack
Type Model Capacity Brand UPS
Battery
pack
ESS-36V9Ah*2-BPVBB 36V/9Ah YUSA 1K
ESS-72V9Ah*2-BPVBB 72V/9Ah YUSA 2K
ESS-96V9Ah*1-BPVBB 96V/9Ah YUSA 3K
Battery
box
ESS-36V40Ah*1-BBNBB 36V/40Ah Shoto/B.B. 1K
ESS-36V65Ah*1-BBNBB 36V/65Ah Shoto/B.B. 1K
ESS-96V40Ah*1-BBNBB 96V/40Ah Shoto/B.B. 3K
No. Load Backup time
1
100% 15.0min75% 21.0min50% 39.0min25% 77.0min
2
100% 36.0min75% 47.0min50% 83.0min25% 159.0min
No. Load Backup time
1100% 6.5min75% 10.0min
2100% 17.0min75% 25.0min
3100% 39min75% 55min
4100% 63min75% 87min
No. Load Backup time
1100% 7min75% 11min
2100% 16min75% 25min
3100% 31min75% 45min
4100% 39min75% 55min
2K: Backup time schedule of battery pack 3K: Backup time schedule of battery pack
28
Part backup time schedule :
Model Capacity Brand
ESS-240V12-7AhBPVBA01 7Ah B.B.
ESS-240V12-7AhBPVBA02 7Ah Panasonic
ESS-240V12-9AhBPVBA01 9Ah B.B.
ESS-240V12-9AhBPVBA02 9Ah Panasonic
B.B. 7Ah
UPS Battery number
Backup
time
6K
Standard
model
1 6min
6K long
backup time
model
2 19min
3 29min
4 46min
B.B. 9Ah
UPSBattery number
Backup
time
6K
Standard
model
1 4min
10K long
backup time
model
2 12min
3 23min
4 32min
B.B. 9Ah
modelBattery number
Backup
time
15K long
backup time
model
4 19min
6 32min
8 48min
20Klong
backup time
model
4 12min
6 23min
8 32min
Optional Accessories: Battery Pack (6K to 20K)
29
Optional Accessories –Battery Rack and Switch Box
Battery rack
Battery switch box
More connection type of battery racks
•Type of battery rack depends on
battery number and capacity.
•2V and 12V series battery rack
Model Specifications UPS
PDC-63DC-440V 440VDC 63A 3K/6K/10K
PDC-63DC-660V 630VDC 63A 15K/20K
+
-+
-
+ - + - + -
UPS
Rack 1 Rack 2 Rack 3 Rack 4
more battery racks connections
30
Optional Accessories -PDU
Functions :• Input and output power distribution of
parallel system.
( 6K/10K 1+1,2+0 & 15K/20K 1+1 )
•Provide maintenance bypass in UPS single or
parallel system.
• Provide output sockets: OT ;4*C13;2*C19.
• Report voltage signals of PDU to UPS.
PDU model UPS model
PDC-0038V4ACIOA 15K/20K ( 3/3 )
PDC-0091V2ACIOA 6K/10K/15K/20K (3/1 , 1/1)
1. Maintenance bypass ports (MBS)
2. DIP switch 3. Voltage monitoring ports 4. Output ports
5. Bypass input ports 6. Mains input ports 7. Output socket group 1 (250 V AC, 15 A)
8. Output socket group 1 fuses
9. Output socket group 2 fuses
10. Output socket group 2 (250 V AC, 10 A)
11. UPS 1 mains input port (under the cover)
12. UPS 2 mains input port (under the cover)
13. UPS 1 bypass input port (under the cover)
14. UPS 2 bypass input port (under the cover)
15. UPS 1 output port (under the cover)
16. UPS 2 output port (under the cover)
31
Optional Accessories -PDU
端口连接
Maintenance bypass opening will trigger the maintenance bypass switch(MBS ) signal
Input and output circuit breakers
PDU rear panel (Cover plate removed)
PDU front panel ( Logo panel removed )
32
Optional Accessories - Transformer
Functions • Realize electric isolation
• Transformer ratio 2:1:1
• Output dual 110V or another 220V
Types• 6kVA transformers for 6K&15K UPS
•10kVA transformers for 10K&20K UPS
Configuration15K 3/3 : 3 x 6kVA transformers
20K 3/3 : 3 x 10kVA transformers
15/20K 3/1,1/1 : 2pcs 10kVA transformers
33
Optional Accessories –Monitoring Card
SNMP card
•Monitors, via NMS, NetEco, and the Web, the UPS.
operating status based on the computer network type.
• Environment temperature and humidity sensor can be
inserted in SNMP to monitor surrounding information.
Modbus card
• RS485 networking.
• Monitoring via the NetEco 1000U.
• Only one card required in parallel system.
Dry contact card
• 6 alarm outputs :( Normal mode , battery mode ,
bypass mode , Low battery voltage, Bypass
backfeed , UPS faults )
• 2 control inputs : Shutdown , reserved.
Monitoring card slot
Card slot can hold three types
of monitoring cards.
Monitoring card slot
34
Optional Accessories -NetEco 1000U
• Real-time monitoring. NetEco 1000U monitors UPSs in real
time and allows users to configure and control UPSs
• Delay shutdown, shut down the computer application system
and operating system
• USB, SNMP, Modbus networking communication
• Historical data query. Query historical data and UPS alarm logs
through the NetEco 1000U.
• Remote alarm notification. NetEco 1000U notifies users via by
emails or SMS short messages immediately after a UPS
reports an alarm
Notes: The SMS alarm requires GSM MODEM :
The free NetEco 1000U can only support monitoring within ten UPSs.
An installation CD of NetEco 1000U is delivered with the UPS.
35
Content
3 UPS2000-G Series Product IntroductionUPS2000-G Series Product Introduction
2
1 Challenges and Trends in UPS System Challenges and Trends in UPS System
UPS2000-G Series SolutionsUPS2000-G Series Solutions
4 Successful CasesSuccessful Cases
36HUAWEI TECHNOLOGIES CO., LTD. Page 36
Huawei Provides Smart Solutions to Saudi Aramaco
Saudi Aramaco
Huawei UPS
3kVA-10kVA UPS system with battery pack or battery rack. Customers can select rack/tower installation according to
requirement. UPS2000-G supports dual-live-input after customization. UPS2000-G supports SNMP, RS484, etc.
Various sites with different scenarios need UPS to adapt
different installation requirements. Some of the sites use dual-live power supply system. All the UPSs should be monitored by customer’s network
manage system.
Customer Requirements and Challenges
Huawei Solution and Customer Values
Project Background Saudi Aramaco is the largest oil production company, whose
business is worldwide. The company is providing continuous power
to management sites.
37HUAWEI TECHNOLOGIES CO., LTD. Page 37
HUAWEI Wins the Bid of London Underground
Challenge And Requirements
HUAWEI UPS Solution and Customer Value
Background The London Underground is a public metro system serving a large part of Greater
London and parts of the counties of Buckinghamshire, Hertfordshire and Essex. The
system serves 270 stations and has 402 kilometers (250 mi) of track, 55% of which is
above ground.
The original power supply system of London Underground is of various kinds of UPS
from different brands and different capacity. The UPSs have been used for over 10
years. All the UPS and batteries need to be replaced.
UPS for London Underground would support the public alarming system, CCTV, IT
system and emergency system, etc.
HUAWEI provides 1136 sets of UPS
All-in-one UPS solution: high power density, easy maintenance, flexible expansion,
front and rear access
Highly reliable UPS with wide input voltage, ensure the system stable operating.
Key Components have failure warning to avoid Potential System Risk
38
Turkey Halkbank
HUAWEI Solution and Customer Value
Customer Requirements and Challenges
Project Background Halkbank is one of the largest state-owned banks in Turkey, this project is a large
procurement of UPS, covering all the units in the nationwide, requirements for high
reliability and environment applicability is much stricter.
Requires high reliability, low THDI
UPS should be available for Ethernet network connection, as well as remote
monitoring of UPS conditions
HUAWEI provides 300 sets of UPS 2000-G-10kVA, with standard SNMP card
UPS 2000-G has super-wide input voltage and frequency range, suitable for harsh
power environment and is adopted in various units
The number of batteries in UPS 2000-G is between 16 and 20, and the batteries can
be recycled
39
Munich institute realizing the goal of energy saving Challenges of Munich institute
Requirement of high reliability, MTBF>300,000 hours and MTTR<1 hour.
Requirement of high efficiency and 50% reduction in carbon emission
compared with 2006.
Requirement of standard certification(EU CE).
Munich institute, one of the
most important institute of
Huawei, with an area of
about 3000m2, and 370
employee, among which 80%
is local employees in
German
Huawei solution & Customer Benefits
UPS2000-G 20kVA UPS 1+1 redundant system, 1
hour backup time.
Compared with traditional UPS, Huawei UPS2000-G
support a high efficiency of up to 95%, that can reduce
carbon emissions by 50% and provide a MTBF≥ 350
thousand hours.
UPS2000-G has achieved EU, CE, ROSH certification
and the global first batch of UPSs achieving Energy
Star certification.
Input
UPS1
UPS2
Servers
RAID
Minicomputer
Firewall
Officials of German government and Chinese consul-general visit Huawei Munich institute
UPS2000-G redundant system
THANK YOU
Copyright©2016 Huawei Technologies Co., Ltd. All Rights Reserved.The information in this document may contain predictive statements including, without limitation, statements regarding the future financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual results and developments to differ materially from those expressed or implied in the predictive statements. Therefore, such information is provided for reference purpose only and constitutes neither an offer nor an acceptance. Huawei may change the information at any time without notice.