i-nx-q air cooled, 4 pipe chillers - low noise version

2
i-NX-Q Air Cooled, 4 Pipe Chillers - Low Noise version (45-139kW) Heat Pump - Three Phase Climaveneta’s range of small to medium sized i-NX-Q chillers are designed to produce chilled and hot water simultaneously and efficiently using variable frequency drive compressors. The super low noise variant offers up to a 7dB(A) reduction against the baseline model. Key Features: Simultaneous production of chilled water and hot water Two inverter scroll compressors Wide operating range ErP 2021 compliant Available with EC fans Available with factory installed pumps les.mitsubishielectric.co.uk The unit combines two variable speed scroll compressors in two separate refrigerant circuits. The full inverter solution applied on two separate refrigerant circuits ensures maximum reliability and total versatility, matching the thermal load request constantly and with maximum precision, while minimising energy consumption.

Upload: others

Post on 02-Dec-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: i-NX-Q Air Cooled, 4 Pipe Chillers - Low Noise version

i-NX-Q Air Cooled, 4 Pipe Chillers - Low Noise version(45-139kW) Heat Pump - Three Phase

Climaveneta’s range of small to medium sized i-NX-Q chillers are designed to produce chilled and hot water simultaneously and efficiently using variable frequency drive compressors. The super low noise variant offers up to a 7dB(A) reduction against the baseline model.

Key Features:Simultaneous production of chilled water and hot water

Two inverter scroll compressors

Wide operating range

ErP 2021 compliant

Available with EC fans

Available with factory installed pumps

les.mitsubishielectric.co.uk

The unit combines two variable speed scroll compressorsin two separate refrigerant circuits. The full inverter solutionapplied on two separate refrigerant circuits ensures maximumreliability and total versatility, matching the thermal load requestconstantly and with maximum precision, while minimising energy consumption.

Page 2: i-NX-Q Air Cooled, 4 Pipe Chillers - Low Noise version

Effective as of September 2019015015

UNITED KINGDOM Mitsubishi Electric Europe Living Environmental Systems Division, Travellers Lane, Hatfield, Hertfordshire, AL10 8XB, England. Telephone: 01707 282880 Fax: 01707 278881IRELAND Mitsubishi Electric Europe, Westgate Business Park, Ballymount, Dublin 24, Ireland. Telephone: (01) 419 8800 Fax: (01) 419 8890 International code: (003531)

Country of origin: United Kingdom - Japan - Thailand - Malaysia. ©Mitsubishi Electric Europe 2019. Mitsubishi and Mitsubishi Electric are trademarks of Mitsubishi Electric Europe B.V. The company reserves the right to make any variation in technical specification to the equipment described, or to withdraw or replace products without prior notification or public announcement. Mitsubishi Electric is constantly developing and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All goods are supplied subject to the Company’s General Conditions of Sale, a copy of which is available on request. Third-party product and brand names may be trademarks or registered trademarks of their respective owners.

Note: The fuse rating is for guidance only. Please refer to the relevant databook for detailed specification. It is the responsibility of a qualified electrician/electrical engineer to select the correct cable size and fuse rating based on current regulation and site specific conditions. Mitsubishi Electric’s air conditioning equipment and heat pump systems contain a fluorinated greenhouse gas, R410A (GWP:2088), R32 (GWP:675), R407C (GWP:1774) or R134a (GWP:1430). *These GWP values are based on Regulation (EU) No 517/2014 from IPCC 4th edition. In case of Regulation (EU) No.626/2011 from IPCC 3rd edition, these are as follows. R410A (GWP:1975), R32 (GWP:550), R407C (GWP:1650) or R134a (GWP:1300).

@meuk_les Mitsubishi Electric LivingEnvironmental Systems UK mitsubishielectric2 thehub.mitsubishielectric.co.uk@green_gateway greengateway.mitsubishielectric.co.uk

Telephone: 01707 282880email: [email protected]: les.mitsubishielectric.co.uk / microsite: mechillers.co.uk

MODEL

V/ph/Hz

kWkWkW/kW

kWkWkW/kW

kWkWkWkW/kW

kW-%

Kw-%-

l/skPa

l/skPa

N°N°kgkg

dB(A)dB(A)

mmmmmmkg

i-NX-Q SL 0402Pi-NX-Q SL 0352Pi-NX-Q SL 0302Pi-NX-Q SL 0262P i-NX-Q SL 0552Pi-NX-Q SL 0502Pi-NX-Q SL 0252Pi-NX-Q SL 0202Pi-NX-Q SL 0182Pi-NX-Q SL 0152P

i-NX-Q SL Air Cooled, 4 Pipe Chiller - Low Noise Version (45-139kW) Heat Pump - Three Phase

POWER SUPPLY PERFORMANCE COOLING ONLY (EN14511 VALUE)COOLING CAPACITY *1 *2

TOTAL POWER INPUT *1 *2

EER *1 *2

HEATING ONLY (EN14511 VALUE)TOTAL HEATING CAPACITY *2 *3

TOTAL POWER INPUT *2 *3

COP *2 *3

COOLING WITH TOTAL HEAT RECOVERYCOOLING CAPACITY *4

TOTAL POWER INPUT *4

RECOVERY HEAT EXCHANGER CAPACITY *4

TER SEASONAL COOLING EFFICIENCYP RATED CAPACITY *5

SEER *5 *6

PERFORMANCE ŋs *5 *7

SEASONAL HEATING EFFICIENCY *8

RATED HEAT OUTPUT AT T DESIGN H *9 *10

SCOP *9 *10

SEASONAL SPACE HEATING ENERGY EFFICIENCY *9 *10

SEASONAL SPACE HEATING ENERGY EFFICIENCY CLASS *9 *10

HEAT EXCHANGERS HEAT EXCHANGER USER SIDE IN COOLINGWATER FLOW RATE *1

PRESSURE DROP *1

HEAT EXCHANGER USER SIDE IN HEATINGWATER FLOW RATE *3

PRESSURE DROP *3

REFRIGERANT CIRCUITCOMPRESSORSNO. CIRCUITSREFRIGERANT CHARGE R410AOIL CHARGE NOISE LEVELSOUND PRESSURE *11

SOUND POWER LEVEL *12 *13

SIZE AND WEIGHTWIDTH (A) *14

DEPTH (B) *14

HEIGHT (H) *14

OPERATING WEIGHT *14

400/3+N/50

45.614.123.23

51.215.193.37

46.1413.7859.17.62

45.64.41174

37.03.93154A++

2.1826.1

2.4733.2

2226.74.6

4779

262513502070960

400/3+N/50

52.317.263.03

59.017.823.31

53.0616.5268.67.37

52.34.43174

43.03.97156A++

2.5134.4

2.8444

2227.34.6

4779

262513502070960

400/3+N/50

56.318.73.01

62.518.383.4

57.7517.2574.07.61

56.34.5177

45.03.98156A++

2.722.4

3.0127.9

2227.84.6

4880

262513502070990

400/3+N/50

105.037.372.81

114.234.093.35

109.433.52140.97.47

105.04.34170

79.04.01158-

5.0334.8

5.541.6

2245.813.4

5183

3250135020701440

400/3+N/50

89.530.862.9

98.128.433.45

94.5927.75120.77.77

89.54.33170

74.04.09161-

4.2927.0

4.7232.7

2240.613.4

5082

3250135020701330

400/3+N/50

138.449.782.78

153.245.333.38

145.544.93187.77.42

138.44.45175

115.04.13162-

6.6335.0

7.3843.3

2260.013.4

5587

4500135020701660

400/3+N/50

119.944.082.72

132.439.43.36

126.439.5163.67.34 119.94.4173 97.04.11161-

5.7535.3

6.3843.4

2253.413.4

5385

3875135020701520

400/3+N/50

84.0 29.272.87

93.127.633.37

84.6526.96110.07.21

84.04.25167

70.04.04159A++

4.0333.2

4.4841.1

2243.87.2

5082

3250135020701210

400/3+N/50

70.925.972.73

78.523.223.38

75.0922.9596.77.47

70.94.22166

59.03.97156A++

3.423.7

3.7829.3

2231.27.2

4981

2625135020701080

400/3+N/50

62.922.712.77

70.721.493.29

65.2220.4284.47.33

62.94.39173

52.04.0157A++

3.0127.9

3.435.6

2229.24.6

4981

262513502070990

Eurovent Certified Data

*1 Plant (side) cooling heat exchanger water (in/out) 12.0°C/7.0°C; Source (side) heat exchanger air (in) 35.0°C. *2 Values in compliance with EN14511. *3 Plant (side) heating heat exchanger water (in/out) 40.0°C/45.0°C; Source (side) heat exchanger air (in) 7.0°C at 87% R.H. *4 Plant (side) cooling heat exchanger water (in/out) 12.0°C/7.0°C; Plant (side) heating heat exchanger water (in/out) 40.0°C/45.0°C. *5 Parameter calculated according to [Regulation (EU) N. 2016/2281]. *6 Seasonal energy efficiency ratio. *7 Seasonal space cooling energy efficiency. *8 Weather conditions average, bivalent temperature -7.0°C. *9 Seasonal space heating energy efficiency class LOW TEMPERATURE [REGULATION (EU) N. 813/2013]. *10 Calculated with variableflow rate and variable temperature. *11 Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calcuated from the sound power level. *12 Sound power on the basis of measurements madein compliance with ISO 9614. *13 Sound power level in cooling and heating, outdoors. *14 Unit in standard configuration/execution, without optional accessories.