IEC 61850 Short TutorialKlaus-Peter Brand

[email protected]

Page 2: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 2

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

LecturerLecturer

Klaus-Peter BrandABB Switzerland LtdABB University Switzerland & ABB Power Technology Systems (Utility Automation)Member of TC 57 WG10Editor of IEC 61850-5Co-editor of IEC 61850-7-4 Co-editor of IEC 61850-10 Member of Group of Experts handling amendments, updates and extensions of IEC 61850 Liaison officer CIGRE SC B5 – IEC [email protected]

[email protected]

Page 3: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 3

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Scope and SA structureScope and SA structure

Stationbus

Processbus

Stationgateway

Stationcomputer

HMI

IEC 61850 means Serial Communication for all functions both between Station/Bay Level and Bay/Process Level

Control Protection Protection& Control

Control Protection

Process Interface Process Interface Process Interface

Stationlevel

Baylevel

Processlevel Switchgear/Switchyard

Cu wires

Page 4: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 4

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Situation before IEC 61850Situation before IEC 61850

DNP LON 60870-5-101/4

60870-5-103 FIELDBUSMODBUS PROFIBUS

Protection1

Protection1

Protection2

Protection2

Station Gateway

CentralFunctions

HM I

Processinterface Processinterface Processinterface

MVB,CAN others

Protection& Control

Page 5: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 5

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Because of the• global, deregulated market• transnational business of utilities• international business of providers

one and only one global standardfor communication in substationsand beyond is needed

Market requirementMarket requirement

Page 6: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 6

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Requirements and meaningRequirements and meaning

Free configuration The standard shall support different philosophiesand allow a free allocation of functions e.g. it must work equally well for centralized (RTU like) or decentralized (SCS like) systems.

Interoperability The ability for IED’s from one or several manufacturer to exchange information and usethe information for the their own functions.

Long term stability The standard shall be future proof, i.e. it must be able to follow the progress in communication technology as well as evolving system requirements.

Page 7: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 7

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

The structure of IEC 61850 The structure of IEC 61850 –– (1)(1)

Configuration

Part 6: Configuration Languagefor electricalSubstation IEDs

Part 1: Introduction andOverview

System Aspects

Part 2: Glossary

Part 3: General Requirements

Part 4: System and ProjectManagement

Part 5: Comm. Requirementfor Functions andDevice Models

IEC 61850IEC 61850--x x (x = (x = part numberpart number))

IEC 61850is readyfor use

Page 8: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 8

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Part 10: Conformance Testing

Mapping to real Comm. Networks (SCSM)

Part 8-1: Mapping to MMS and to ISO/IEC 8802-3

Part 9-1: Sampled Values over Serial UnidirectionalMulti-drop Point-to-Point link

Part 9-2: Sampled values over ISO 8802-3

Testing

Part 7-3: Common Data Classes

Data Models

Part 7-4: Compatible Logical Node Classes and Data Classes

Part 7-1: Principles and Models

Abstract Communication Services

Part 7-2: Abstract Communication Services (ACSI)

IEC 61850IEC 61850--x x (x = (x = part numberpart number))

The structure of IEC 61850 The structure of IEC 61850 –– (2)(2)

IEC 61850

is ready

for use

Page 9: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 9

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Acceptance by Suppliers: see exhibition at Cigre exhibition Paris 2004

Booth of IEC 61850 Users Group „UCA International“

Page 10: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 10

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Acceptance by Suppliers: participation at the UCA International booth

Page 11: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 11

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Acceptance by Customers: Pilot projects Acceptance by Customers: Pilot projects

Pilot projects have been started at the end of 2004

They are not part of the Tutorial

but will be reportedin the

Workshops or in the

Manufacturers’ Forum

Page 12: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 12

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Approach and meaningApproach and meaning

ApplicationDomainSubstation

CommunicationTechnology

Slow

Fast

Problem for standardization approach

Solution for standardization approach

DATA MODELObjectsService

ISO/OSIseven layer stack

7654321

APPLICATIONswitching devices

protection & controlcommands, events,

alarms,…

COMMUNICATIONmessages,

telegrams, frameson the wire

Page 13: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 13

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Introduction of Logical nodesIntroduction of Logical nodes

Communication relations in a Substation Automation System

Information is exchanged between all devices (IED)which comprise the system

More precisely, data are exchanged between thefunctions and sub-functions residing in the devices

The smallest part of the function that exchanges datais called Logical Node (LN) in IEC 61850. The LNperforms some operations for the overall function

IED IEDLN LN

Page 14: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 14

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Circuit BreakerQ0_L1/XCBR

Gas density mon.Q0_L1/SIMG Primary technology

Secondary technology

ControlQ0/CSWIQ8/CSWIQ9/CSWI

Bay-HMIIHMI

Distance Protection

PDIS

IsolatorQ9_L1/XSWI

Gas density mon.Q9_L1/SIMG

Earthing SwitchQ8_L1/XSWI

Gas density mon.Q8_L1/SIMG

Logical Nodes in the Language of Substation Engineers

Example GIS

Page 15: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 15

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Logical Node Groups (First letter listed)Logical Node Groups (First letter listed)

L System LN (2)P Protection (28)R Protection related (10)C Control (5)G Generic (3)I Interfacing and archiving (4)A Automatic control (4)

M Metering and measurement (8)S Sensor and monitoring (4)X Switchgear (2)T Instrument transformers (2)Y Power transformers (4)Z Further power system

equipment (15)

ExamplesPDIF: Differential protectionRBRF: Breaker failureXCBR: Circuit breaker

CSWI: Switch controllerMMXU: Measurement unitYPTR: Power transformer

Page 16: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 16

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Data model: HierarchyData model: Hierarchy

Physical Device (IED)defined as Server

↑ Implementation

Bay Unit

Logical Device (LD)

↑ Grouping

Control

Logical Node (LN)Logical Node (LN) CSWI CSWI Switch Control

Data (Object)

Data ↓Position

AttributeProperties ↓

Value

Control Valueoff/on

Status Valueintermediate/off/on/bad

Page 17: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 17

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Common LLN0

ProtectionPTOC Str Op

LLN0

ControlCSWI Pos ctlVal stVal

LLN0

ControlSwitch ControlPosition

Control ValueStatus Value

ProtectionOvercurrentStart/Pick-upOperate/Trip

CommonLLN0Name plate

“Vendor etc.”

Data model: Hierarchical set of objectsData model: Hierarchical set of objects

Phys

ical

Dev

ice

(Ser

ver)

Example: Modeling of a combinedExample: Modeling of a combinedControlControl--Protection deviceProtection device

See IEC 61850-7-1,2,3,4

Data container with related data

Page 18: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 18

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Device Example: Combined Protection and Control Unit

Device Example: CombisensorDevice Example: Circuit Breaker

Device Example: Station Workplace

XCBR(Circuit Breaker)

TCTR(Current Transformer)

TVTR(Voltage Transformer)

CSWI(Switch Controller)

PDIS(Distance Protection)

IHMI(Human Machine IF)

LNs inin devices (IEDs)

Page 19: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 19

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Example for Logical Node: Example for Logical Node: LN XCBR out of IEC 61850LN XCBR out of IEC 61850--77--44

XCBR class Attribute Name Attr. Type Explanation T M/O

LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)

Data Common Logical Node Information see Example for Logical Node (1) LN shall inherit all Mandatory Data from Common Logical Node Class M Loc SPS Local operation (local means without substation automation communication,

hardwired direct control) M

EEHealth INS External equipment health O EEName DPL External equipment name plate O OpCnt INS Operation counter M Controls

Pos DPC Switch position M

BlkOpn SPC Block opening M

BlkCls SPC Block closing M

ChaMotEna SPC Charger motor enabled O

Metered Values

SumSwARs BCR Sum of Switched Amperes, resetable O

Status Information

CBOpCap INS Circuit breaker operating capability M

POWCap INS Point On Wave switching capability O

MaxOpCap INS Circuit breaker operating capability when fully charged O

Page 20: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 20

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

CDC double point control (CDC double point control (DPCDPC))

Attribute Name

Attribute Type

ctlVal BOOLEANoperTm TimeStampstVal CODED ENUMq Qualityt TimeStamp

Control and status

pulseConfig PulseConfigctlModel CtlModelssboTimeout INT32UsboClass SboClassesd Visible String255

Configuration and description

subEna BOOLEANsubVal CODED ENUMsubQ QualitysubID Visible String64

Substitution

intermediate/off/on/bad

off/on

Page 21: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 21

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

PDIS class Attribute Name Attr. Type Explanation T M/O LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2). Data Common Logical Node Information see Example for Logical Node (1) LN shall inherit all Mandatory Data from Common Logical Node Class. M OpCntRs INC Resetable operation counter O Status Information Str ACD Start M Op ACT Operate T M Settings PoRch ASG Polar Reach is the diameter of the Mho diagram O PhStr ASG Phase Start Value O GndStr ASG Ground Start Value O DirMod ING Directional Mode O PctRch ASG Percent Reach O Ofs ASG Offset O PctOfs ASG Percent Offset O RisLod ASG Resistive reach for load area O AngLod ASG Angle for load area O

more …

Example for Logical Node: Example for Logical Node: LN PDIS out of IEC 61850LN PDIS out of IEC 61850--77--44

Page 22: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 22

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Common data classes (CDC)Common data classes (CDC)

Status information (7)

Measured information (9)

Controllable status (5)

Controllable analogue (1)

Status settings (2)

Analogue settings (2)

Description information (3)

ExamplesSPS: Single point statusACT: Protection activation

informationMV: Measured valueWYE: 3 Phase measured value

DPC: Double point controlSPG: single point settingDPL: Device nameplate

Page 23: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 23

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

ServicesServices

read a value / attributewrite configuration attributes

control a device (direct operate / select before operate)event oriented communication with reportinglocal storage of time-stamped events in a logget directory informationfile transfer for e.g.

- parameter and software download- upload from monitoring information like travel curves or history of

gas density values

Transfer of generic object oriented system events (GOOSE)Transfer of sampled analog values (SAV)

StandardizedStandardized data accessdata access and and transfertransfer (Services)(Services)

Page 24: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 24

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

IEC 61850: Details for Communication services IEC 61850: Details for Communication services

Client Server Communication

Sampled Values

Data Model (Objects,Services)

Ethernet Link LayerEthernet Physical Layer with Priority tagging (100 Mbit/s)

Real timeCommunication

IPTCP

MMS

Stack selection according to the state-of-the-artCommunication technology

Mapping

GOOSE*

SA specific data modelevolves slowlyCommunication technologychanges quicklySplitting of SA specificdata model fromcommunication technology

StackInterface

AbstractCommunicationServicesInterface (ACSI)

ISO/OSI – StackHierarchical set ofRules how information is coded for transmissionAccording to state-of-the art communication technology

Model according to state-of-the-art SA technology

* Generic Object Oriented Substation Event

Page 25: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 25

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Client-server communication and reporting

Client-server communicationusing full seven layer stackconfirmed transmission layer very reliablerelatively time consuming.

Therefore, the client-server communication is not suited for time-critical data transmission but very well for the communication with an operator having a response time of the order of 1 s.

The clientasks the server for information.changes by parameter setting the behavior of the serverissues commands via the server e.g. to switchgearconfigures at the server conditions which allow the server to send a report automatically to the client (report control block)

The content of the report is defined by a data set. In contrast to master-slavemulitiple client-server links are possible.

The server communicationis the source of all data for the client

Page 26: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 26

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Time critical communication with GOOSE Time critical communication with GOOSE

time

No data change

GOOSE messages (content defined by data set) are repeated with maximum interval Tmax

Tmax = 1024 ms Tmax = 1024 ms

time

Data change GOOSE messages starts immediately with the changed values in some short repetition intervals (Tmin), then the interval will be increase (fast or slowly) to Tmax

Tmax = 1024 ms

Tmax = 1024 ms

b

Tmax = 1024 ms

Tmin = 2 ms

Problem for real-time data:No time for acknowledgementNo time for repetition after loss detected

Page 27: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 27

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Time critical data flow with SV (sample values)Time critical data flow with SV (sample values)

Problem for real-time data:No time for acknowledgementNo time for repetition after loss detected

Benefit for samples:Some few samples may be lost without impact on the function to be performed

Sampled values (SV) messages are very similar to GOOSE messages:

SV messages are defined with help of data sets; the start event is a continuous clocks pulse

The problem is the high synchronicity requested for phasors (about 1 µs);this problem has to be solved by time pulses for the time being.

An extensions for time synchronization over the bus according to IEEE 1588is not yet included but in preparation for IEC 61850

Page 28: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 28

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

Substation Configuration description Language (SCL)Substation Configuration description Language (SCL)

To provide interoperability a formal description of the Substation Automation System with all communication links is needed

All IED capabilities have to be described formally in an unambiguous way

All communication services applicable have to be described formally in an unambiguous way

The relationship between the switchgear (single line) and the data of the substation automation system have to be described formally in an unambiguous way

Formal description of device and system structure

Page 29: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 29

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

OutlookBU 1 BU 2 BU 3 BU 4

HMI GW

Topics of SCLTopics of SCL

Data model (server side) with services: IED capability description

Instatiable types of LNs (LN Type), Data objects (DO types), Data attributes (DA types)

What inputs, e.g. GOOSE messages belong to an IED? Input section !

Data sets and control blocks for report and GOOSE messages

Access points for LAN connection

Allocation to Single line diagram

Description of Single line diagram

Page 30: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 30

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

For the formal description is provided by theSubstation Configuration description Language (SCL)Substation Configuration description Language (SCL)

based on XMLdefined in part 6 of the standard (IEC 61850-6)

usable forIED Configuration Description (ICD) filesSystem Configuration Description (SCD) fileSystem functional specification (SSD)

and more

The engineering information is exchangeable between tools !!!

See IEC 61850-6

SCL: Formal description of device and system structureSCL: Formal description of device and system structure

Page 31: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 31

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

System specification description (SSD) file

SystemDocumentation

files

Dev

ice

Sele

ctio

n

Systemconfigurator

Single LineDiagram(S/S spec)

Feeder Block Diagram(function spec)

Device (IED)

System Configuration

Description (SCD) file

IED Capability De-scription (ICD) file

Device specific

tool

SCD file part per

IED

SCL files

The Engineering Process with SCLThe Engineering Process with SCL

Page 32: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 32

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

BU 1 BU 2 BU 3 BU 4

HMI GW

Design exampleDesign example

EthernetSwitch

EthernetRing

Bay Control and/or Protection Unit

Page 33: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 33

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

IEC 61850: What is standardized and what not ?IEC 61850: What is standardized and what not ?

Standardized

Not standardized

Data model with LN, DO, AttributesServicesConfiguration Language (SCL)ICD file (requested) and other SCL based files

LD and high plant identificationFunctions Allocation of functions to IEDsSA concepts and architecturesRedundancyTools and engineering process

Page 34: IEC61850-Tutorial - Cepelceb5.cepel.br/.../eventos_setor/antigo/brand_iec61850-tutorial.pdf · MODBUS PROFIBUS FIELDBUS Protection 1 Protection 1 Protection 2 ... Overview System

IEC 61850 Short Tutorial March2005 / Page 34

Market requirements

Scope

The standard structure

Acceptance

Approach

Logical Nodes and objects

Hierarchical data model

Services

SCL

Outlook

FutureFuture

Maintenance of IEC 61850 within substations Work started to use use IEC 61850 also outside the substation, i.e.

for wind power, for hydro power, for distributed energy resources (DER)

The feasibility of IEC 61850 for the link to the NCC has been proven, a harmonization between the data model of IEC 61850 and the CIM model on Network Level is in progress

New work items to use IEC 61850 for line protection (teleprotection) are in preparation.

The IEC TC57 WG10 takes care to the common data modelThe user group UCA International promotes the standard andtries to support all users.

The goal is a seamless communication architecture for utilities

Activities