POWER SYSTEMS ENGINEERING SERVICES (PSES) IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt Capacitor and Reactor Switching May 19, 2015 Prepared by: Mitsubishi Electric Power Products, Inc. (MEPPI) Power System Engineering Services Department Warrendale, Pennsylvania

Upload: others

Post on 18-Oct-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

IEEE Fort Worth PES Chapter

Presentation on:

Potential Concerns and Mitigation

for Shunt Capacitor and Reactor Switching

May 19, 2015

Prepared by:

Mitsubishi Electric Power Products, Inc. (MEPPI)

Power System Engineering Services Department

Warrendale, Pennsylvania

Page 2: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Overview of Topics in Presentation

• Shunt Capacitor Bank Switching – Applicable Standards and Criteria

– Overview of Shunt Capacitor Bank Potential Concerns

– Example Simulation Waveforms

– Mitigation Solutions

• Shunt Reactor Bank Switching – Applicable Standards and Criteria

– Overview of Shunt Reactor Bank Potential Concerns

– Example Simulation Waveforms

– Mitigation Solutions

2

Page 3: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

3

Page 4: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Shunt Capacitor Bank Switching

4

Page 5: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What is a Shunt (Power) Capacitor Bank?

5

Page 6: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Why Do We Install Shunt Capacitor Banks?

• Voltage/VAR Support – Often sized and located based on power flow/stability analysis

– Located at Transmission or Distribution voltage level

– Increase voltage by reducing the VAR flow in the system and the resulting voltage drop

• Harmonic Filtering – Tuned to reduce level of system harmonic distortion

– Often associated with power electronic devices

• Power Factor Correction at Customer Level – Sized to increase power factor to desired level

6

Page 7: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Example One-Line Diagram of Substation with a Shunt Capacitor

Power

Transformer

Capacitor Bank

No. 1

Circuit breaker/switcher

for capacitor bank

Power

Transformer

345 kV Line

345 kV Line

North

345 kV Bus

South

345 kV Bus

Substation

circuit breaker

Current-limiting

reactor (CLR)

Surge

arrester

Surge

arrester

Capacitor Bank

No. 2

7

Page 8: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Applicable Standards and Criteria

• C37.06: “IEEE Standard for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current

Basis-Preferred Ratings and Related Required Capabilities for Voltages Above 1000 V)”

• C37.06.1: “Guide for High-Voltage Circuit Breakers Rated on Symmetrical Current Basis

Designated “Definite Purpose for Fast Transient Recovery Voltage Rise Times”

• IEEE Std 1036: “IEEE Guide for Application of Shunt Power Capacitors”

• C37.99: “IEEE Guide for the Protection of Shunt Capacitor Banks”

• C37.012: “IEEE Application Guide for Capacitance Current Switching for AC High-Voltage Circuit

Breakers”

• IEEE Std 519: “IEEE Recommended Practices and Requirements for Harmonic Control in

Electrical Power Systems”

• IEEE Std 80: “IEEE Guide for Safety in AC Substation Grounding”

• IEEE 1313.2: “IEEE Guide for the Application of Insulation Coordination”

• C62.22: “IEEE Guide for the Application of Metal-Oxide Surge Arresters for Alternating-Current

Systems”

8

Page 9: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Potential Concerns for

Installing a Shunt Capacitor Bank

9

Page 10: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Steady-State Change In Voltage

• Energizing the capacitor bank will result in an increase in the fundamental

frequency voltage at the capacitor bank.

• To minimize the impact of the voltage change on customer loads, it is often

limited to 2-3%, where:

∆𝑉 = 𝑀𝑣𝑎𝑟

𝑀𝑉𝐴𝑆𝐶× 100%

• Where:

Mvar = shunt capacitor bank rating (Mvar)

MVASC = the available 3-phase short-circuit current MVA at capacitor bank

10

Page 11: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What Does the Voltage Change Look Like?

Change in Voltage from

1.00 p.u. to 1.07 p.u. (7%)

Change in Voltage from

1.07 p.u. to 1.15 p.u. (7%)

11

Page 12: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What are Mitigation Options for the Voltage Change?

Potential Solutions:

• Switching in smaller increments decreases the Mvar switched and

reduces the voltage change when energizing the capacitor bank.

12

Page 13: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Inrush Current

• When a capacitor bank is energized, a high frequency inrush current will

flow through the capacitor bank and anything in series (i.e., circuit

breaker/switcher, current-limiting reactor, buswork, etc.).

• Severity of the inrush current is proportional to the number of capacitor

banks at the substation that are online during switching and the mitigation

equipment used to limit the currents.

• What are potential concerns for inrush current: – Circuit breaker/switcher damage

Rupture (oil)

Contact and nozzle degradation (gas, air, vacuum)

– Increased circuit breaker maintenance

– Control circuit interference

– Transient ground potential rise

13

Page 14: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Potential Concerns for Capacitor Bank Switching

(Inrush Current)

Stationary Main Contact

Stationary

Arcing Contacts

Moving Main Contact

Moving Arcing

Contacts

Nozzle

Contact/nozzle

erosion from

repeated use.

Shockwave from

initial di/dt in arc.

14

Page 15: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What Does Inrush Current Look Like?

High frequency inrush current

through breaker/switch.

15

Page 16: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What are Mitigation Options for Inrush Current?

Potential Solutions:

• Current-limiting reactors increase series inductance, therefore lower peak

and frequency.

• Pre-insertion resistors lower the voltage dropped across the

breaker/capacitor, therefore lower the peak but not frequency.

• Pre-insertion inductors lower the voltage dropped across the

breaker/capacitor and increase series inductance, therefore lower peak and

frequency

• Synchronous-close control lowers the voltage dropped across the

breaker/capacitor, therefore lower the peak but not frequency. However,

the added benefit of synchronous control is consistent (reduced) arcing

times and less breaker wear.

16

Page 17: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Outrush Current

• When a close-in fault occurs near a substation with a shunt capacitor bank,

if a line/bus breaker re-closes into the fault or has a re-strike during opening

a high frequency outrush current will flow through the breaker.

• Severity of the outrush current is proportional to the number of capacitor

banks at the substation that are online during switching, the mitigation

equipment used to limit the currents, and the location of the fault.

• What are potential concerns for outrush current: – Circuit breaker/switcher damage (more concern for oil circuit breakers).

Rupture (oil)

Contact and nozzle degradation (gas, air, vacuum)

– Transient ground potential rise

17

Page 18: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What Does Outrush Current Look Like?

High frequency outrush current

through breaker/switch.

18

Page 19: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What are Mitigation Options for Outrush Current?

Potential Solutions:

• Current-limiting reactors increase series inductance, therefore lower peak

and frequency.

• Note that pre-insertion devices and synchronous-close control for the

capacitor bank breakers will not mitigate the outrush current because the

line breaker is the breaker re-closing into the fault or having a re-strike

during opening.

19

Page 20: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Transient Overvoltages

• When a shunt capacitor bank is energized the voltage at the capacitor bank

is forced from zero to system voltage by collapsing ~1.0 p.u. voltage across

the circuit breaker/switcher which could result in ~2.0 p.u. at the capacitor

bank from the resulting overshoot.

• Traveling waves propagating throughout the system can stress equipment

at remote stations as well.

• Potential resonance conditions can also be a cause for concern such as

voltage magnification.

• What are potential concerns for the transient overvoltages: – Flashovers of equipment

– Damaged surge arresters and other equipment

– Power quality/voltage distortion

20

Page 21: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Transient Overvoltages (continued)

• When a shunt capacitor bank is energized with a nearby capacitor at a

lower voltage, the potential for voltage magnification may exist when the

following condition is true:

𝐿1𝑥𝐶1 = 𝐿2𝑥𝐶2

• Furthermore, when C1>>C2, and L1<<L2 the condition can be exaggerated.

21

Page 22: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What Does Voltage Magnification Look Like?

Example 1.95 p.u. overvoltage at HV

bus when capacitor bank is switched.

Example 4.39 p.u. overvoltage at LV

bus when capacitor bank is switched.

22

Page 23: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What are Mitigation Options for Transient Overvoltages?

Potential Solutions:

• Current-limiting reactors, pre-insertion resistors/inductors, and

synchronous-close control: Reduce the inrush current and the voltage

collapsed across the circuit breaker helping to reduce the voltage surge

generated during switching.

• Surge Arresters: Mitigate the overvoltages generated by the switching

operation.

23

Page 24: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Re-Strikes During De-Energization

• When a shunt capacitor bank is de-energized a trapped DC charge is left on

the capacitor, which results in a near 2.0 p.u. voltage across the

breaker/switcher a half cycle later when the system voltage is at an opposite

polarity peak.

• If a re-strike occurs at a voltage peak (~2.0 p.u.) across the

breaker/switcher, transient overvoltages with nearly twice the severity as

normal energizing may occur.

• One of the primary causes of re-strikes is poor contact health.

24

Page 25: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Re-Strikes During De-Energization (continued)

Current Through Switching Device Voltage on Each Side of Switching Device

Current is

interrupted

First restrike

occurs and

current is re-

established

High

frequency

current is

interrupted

Second restrike

occurs and current

is re-established

Voltage on

capacitor bank

side of switching

device (DC

trapped charge)

Voltage on

system side of

switching device

Peak overvoltage

from 1st restrike

Peak overvoltage

from 2nd restrike

25

Page 26: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What are Mitigation Options for Re-Strikes?

Potential Solutions:

• Current-limiting reactors, pre-insertion resistors/inductors, and

synchronous-close/open control: Reduce the inrush current and the

voltage collapsed across the circuit breaker helping to reduce the voltage

surge generated during switching.

• Surge Arresters: Mitigate the overvoltages generated by the switching

operation.

26

Page 27: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Transient Recovery Voltages (TRV)

• When a fault occurs at a capacitor bank with a current-limiting reactor where

the capacitor bank is shorted out and the breaker interrupts current limited

by the current-limiting reactor, a TRV with a high rate-of-rise is imposed on

the breaker.

• What are potential concerns for the transient overvoltages: – Failure of circuit breaker to interrupt

• Some common misconceptions: – Installing the CLR on the bus-side of the breaker eliminates the problem

– Installing the CLR in the capacitor neutral eliminates the problem

– Very large TRV capacitors are required (hundreds of nF)

27

Page 28: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Transient Recovery Voltages (continued)

Transient limiting

inductor (TLI)

Capacitor

bank Fault phase-to-

ground or

phase-to-phase

Circuit

breaker Transient limiting

inductor (TLI)

Capacitor

bank

Circuit

breaker

Fault phase-to-

ground or

phase-to-phase

Transient limiting

inductor (TLI)

Capacitor

bank Fault across

capacitor bank

Circuit

breaker

Example with circuit breaker before TLI Example with circuit breaker after TLI

Example with TLI in the capacitor bank neutral

28

Page 29: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What Does the TRV Look Like (Reactor-Limited Fault)?

Example extrapolated

terminal fault TRV

capability (T20) based

on IEEE C37.06-2009.

Example TRV capability for fast TRV rise times

based on IEEE C37.06.1-2000 (at 30% duty).

TRV imposed on capacitor bank

breaker for a fault across the capacitor

bank (shorting out the capacitor bank).

29

Page 30: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What are Mitigation Options for Transient Recovery Voltages?

Potential Solutions:

• TRV Control Capacitors: Reduce the frequency and the rate-of-rise of the

TRV.

• Eliminating the CLR: Eliminates the reactor-limited fault TRV.

• Synchronous-Open Control: Helps for normal de-energizing but not the

reactor-limited fault TRV.

30

Page 31: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Harmonics

• Shunt capacitors do not generate harmonics, however they can create

paths for harmonic currents to flow which could result in increased stress to

the capacitor bank.

• Capacitor banks can shift the equivalent harmonic impedance as viewed

from the bus which may result in higher harmonic distortions.

• If capacitors are tuned to harmonics existing in the system, excessive

heating and damaged fuses/cans can occur.

31

Page 32: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What Does Harmonic Distortion Look Like? With Shunt Capacitor Offline

With Shunt Capacitor Online

32

Page 33: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What are Mitigation Options for Harmonics?

Potential Solutions:

• Modifying Size of Capacitor/Reactor: De-tuning the capacitor bank from

a specific harmonic.

• Increasing Ratings: Increase ratings to handle additional current and

dielectric stress from harmonics.

33

Page 34: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Transient Ground Potential Rise (TGPR)

• When a capacitor bank is energized, the inrush current can flow through the

ground grid resulting in transient ground potential ride which may lead to

high step and touch voltages as well as induced voltage/current into control

circuits.

• Substations ground grids are often designed and based on 60 Hz fault

current calculations, and when capacitor banks are added to a substation

the grounding system may need evaluated.

• Installing capacitor banks significant distances apart in a substation can

exaggerate transient ground potential rises.

34

Page 35: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What Does Transient Ground Potential Rise Look Like?

-200 300 800

X AXIS (FEET)

-250

250

750

1250

Y A

XIS

(

FE

ET

)

Touch Voltage Magn. (Volts) [Wors]

Scalar Potentials/Touch Voltages/Worst Spherical [ID:Rector_PNG_R1 @ f=2074.0000 Hz ]

LEGEND

Maximum Value : 4402.675

Minimum Value : 0.153

4402.68

3962.42

3522.17

3081.92

2641.67

2201.41

1761.16

1320.91

880.66

440.41

Potential for high step

and touch potentials

near capacitor banks

during energization.

35

Page 36: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What are Mitigation Options for TGPR?

Potential Solutions:

• Current-limiting reactors, pre-insertion resistors/inductors, synchronous-close

control: Reducing inrush current will improve transient ground potential rise because

there is less current injected into the grounding system.

• Improved grounding: Increasing the density of the ground grid near the capacitor

banks for direct grounding, Increasing insulation level of neutral for single-point

grounding, Isolating capacitor banks from the rest of the substation for peninsula

grounding to avoid high touch voltages.

Connection to

other capacitor

bank neutrals.

Capacitor bank

ground grid tied to

station grid by a

limited number of

connections.

Direct Grounding Single Point Grounding Peninsula Grounding

36

Page 37: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Shunt Reactor Bank Switching

37

Page 38: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What is a Shunt Reactor Bank?

38

Page 39: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Why Do We Install Shunt Reactor Banks?

• Reducing Overvoltages – Often sized and located based on power flow/stability analysis

– Installed at line/cable ends to account for charging current and reduce open-ended voltages

39

Page 40: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Example One-Line Diagram of Substation with a Shunt Reactor

Power

Transformer

Circuit breaker/switcher

for reactor bank

Power

Transformer

345 kV Line

345 kV Line

North

345 kV Bus

South

345 kV Bus

Substation

circuit breaker

Shunt

reactor

Surge

arrester

40

Page 41: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Applicable Standards and Criteria

• C37.015: “IEEE Application Guide for Shunt Reactor Switching”

• C37.06: “IEEE Standard for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current

Basis-Preferred Ratings and Related Required Capabilities for Voltages Above 1000 V)”

• C37.06.1: “Guide for High-Voltage Circuit Breakers Rated on Symmetrical Current Basis

Designated “Definite Purpose for Fast Transient Recovery Voltage Rise Times”

• IEEE Std 519: “IEEE Recommended Practices and Requirements for Harmonic Control in

Electrical Power Systems”

• IEEE Std 80: “IEEE Guide for Safety in AC Substation Grounding”

• IEEE 1313.2: “IEEE Guide for the Application of Insulation Coordination”

• C62.22: “IEEE Guide for the Application of Metal-Oxide Surge Arresters for Alternating-Current

Systems”

• IEC 62271-110: “High-voltage switchgear and controlgear – Part 110: Inductive load

switching”

41

Page 42: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Potential Concerns for

Installing a Shunt Reactor Bank

42

Page 43: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Inrush Current

• When a reactor bank is energized, an inrush current with a dc offset will flow

through the reactor bank and anything in series (i.e., circuit

breaker/switcher, buswork, etc.).

• Severity of the inrush current is proportional to the shunt reactor

characteristics (saturated reactance) and the system strength at the shunt

reactor.

• What are potential concerns for inrush current: – Circuit breaker/switcher stress

– Relay mis-operation

– Exciting resonance conditions and overvoltages

43

Page 44: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What Does Inrush Current Look Like?

Inrush current though shunt

reactor breaker/switcher.

44

Page 45: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What are Mitigation Options for Inrush Current?

Potential Solutions:

• Pre-insertion resistors lower the voltage dropped across the

breaker/capacitor, therefore lower the peak but not frequency.

• Synchronous-close control lowers the voltage dropped across the

breaker/capacitor, therefore lower the peak but not frequency. However,

the added benefit of synchronous control is consistent (reduced) arcing

times and less breaker wear.

45

Page 46: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Transient and Temporary Overvoltages

• When a reactor bank is energized the inrush current can excite transient or

temporary voltages that can stress equipment insulation and potentially

over-duty surge arresters.

• Voltage sags can result from the inrush current during energizing which may

result in tripping of sensitive loads in severe cases.

46

Page 47: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What Do the Overvoltages Look Like?

47

Page 48: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What are Mitigation Options for Overvoltages?

Potential Solutions:

• Pre-insertion resistors lower the voltage dropped across the

breaker/capacitor, therefore lower the peak but not frequency.

• Synchronous-close control lowers the voltage dropped across the

breaker/capacitor, therefore lower the peak but not frequency. However,

the added benefit of synchronous control is consistent (reduced) arcing

times and less breaker wear.

48

Page 49: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Resonance from Connected to De-Energized Lines

• When a reactor bank is connected to a de-energized line that runs parallel

to an energized line, there is a potential for a resonance condition between

the shunt reactor and the capacitance between the two lines that could

cause high voltages on the de-energized line.

• The high voltages can cause concerns for working on the de-energized line,

excessive duty on connected surge arresters, excessive duty on ground

switches connected to the de-energized line.

• Note that placing the reactor on the bus can eliminate this concern, however

then the shunt reactor cannot be used for controlling open-ended line

voltages.

49

Page 50: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What Do the Resonance Overvoltages Look Like?

Peak overvoltage

= 2.94 p.u.

It is anticipated that the line equipment

would be capable of withstanding at

least 1.5 p.u. for 100 ms.

Line breakers open to

trip the line at 200 ms.

The shunt reactors should be tripped

within 550 ms of the line breakers

tripping to avoid excessive

overvoltages for this case.

Anticipated temporary overvoltage

(TOV) capability (1.5 p.u. for 100 ms).

50

Page 51: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What are Mitigation Options for the Resonance?

Potential Solutions:

• Tripping Reactors: Removing the reactors from the line when the line is

de-energized.

• Modifying the Reactor Size: Modifying the reactor size can de-tune the

resonance condition.

• Neutral Reactors: Adding reactors to the neutral can be used to de-tune

the resonance condition.

51

Page 52: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Transient Recovery Voltages from Normal De-Energizing

• When a reactor bank is de-energized the current flowing through the circuit

breaker can be interrupted before a current zero (current chop) which can

result in high transient recovery voltages imposed on the circuit breaker.

• If the circuit breaker contact parting is initiated during the re-ignition window

of the circuit breaker, the current will be re-established after interruption at

the first current zero as shown on the next slide.

• Where frequent operation of the shunt reactor occurs, repeated re-ignitions

can result in excessive contact wear and potential circuit breaker failure.

52

Page 53: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

General Concept for Controlled Switching for Reactor Banks

Re-ignition window (if contact parting

begins during this timeframe it is

anticipated that a re-ignition will occur).

36o 54o 72o 90o 108o 126o 144o 162o

180o 198o 216o 234o 252o 270o 288o 306o 324o 342o 360o

If contact parting

begins here, successful

interruption will occur

at the first current zero

with no re-ignition.

Reference

current zero.

EXAMPLE RE-IGNITION

WINDOW FOR ILLUSTRATION

PURPOSES ONLY. ACTUAL

VALUES SHOULD BE

PROVIDED BY SUPPLIER OF

SWITCHING DEVICE.

Re-ignitions in this window

are of low energy and not a

concern for the breaker.

53

Page 54: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What Does a Re-Ignition Look Like?

Plot of the Current Through the Breaker

54

Current is interrupted, but re-

ignition occurs on Phase B.

Current is interrupted

at next current zero.

Page 55: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

55

What Does a Re-Ignition Look Like?

Plot of the Voltage Across the Breaker

Peak simulated TRV = 450 kV (2.25

p.u. on a 245 kV Base) at 6000 Hz.

Current is interrupted, but re-

ignition occurs on Phase B.

Contacts begin to

part (breaker opens).

Current is interrupted

at next current zero.

Page 56: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Illustration of Dielectric Coordination

Between Arcing and Main Contacts During Switching

Stationary

Main Contact

Stationary

Arcing

Contacts

Moving

Main Contact

Moving

Arcing

Contacts

Nozzle

Tra

ns

ien

t R

ec

ove

ry V

olt

ag

e (

p.u

.)

0.0 1.0 2.0 3.0 4.0 5.0

Withstand between arcing contacts

Withstand between main contacts

Time (ms)

For long arcing times and high TRVs, a

potential for arcing between main contacts

could occur if proper coordination does not

exist between the arcing and main contacts.

With proper coordination,

arcing stays between the

arcing contacts.

With improper coordination, or

very high TRVs, arcing may

occur to the main contacts

potentially through the nozzle.

This coordination is a

function of circuit

breaker design.

TRV magnitudes are a function

of the system as well as

breaker characteristics.

2.20 p.u. is the anticipated limit

where dielectric coordination

is maintained between the

arcing and main contacts.

EXAMPLE COORDINATION CURVE FOR

ILLUSTRATION PURPOSES ONLY. ACTUAL

VALUES SHOULD BE PROVIDED BY

SUPPLIER OF SWITCHING DEVICE.

56

Page 57: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What are Mitigation Options for the TRV?

Potential Solutions:

• Synchronous-open control controls the arcing time to control the

chopping current and ensure contact parting time outside the re-ignition

window to achieve successful interruption of the current at the first current

zero reducing contact wear.

• Surge arresters mitigate the transient overvoltages after a re-ignition to

reduce the transient recovery voltage imposed on the breaker so that it can

interrupt the current at the second current zero (if a re-ignition occurs).

• TRV control capacitors can potentially help reduce the transient recovery

voltage imposed on the circuit breaker.

57

Page 58: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Transient Recovery Voltages from Internal Reactor Fault

• When an internal fault occurs on a shunt reactor where a portion of the

reactor windings are shorted out, a transient recovery voltage with a high

rate-of-rise can be imposed on the circuit breaker interrupting the fault

similar to the reactor-limited fault for a shunt capacitor bank.

58

Page 59: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What Do the Transient Recovery Voltages Look Like?

IEEE defined TRV capability

(interpolated) for 362 kV 63 kA breaker

interrupting 20% fault current (T20)

based on IEEE C37.06-2009.

TRV with 7000 pF added

capacitance (Fault 1%

into reactor).

IEEE defined TRV capability

for 362 kV 63 kA breaker

tested to IEEE C37.06.1-2000.

TRV with 7000 pF

added capacitance

(Fault 25% into reactor). TRV with 7000 pF added

capacitance (Fault 10%

into reactor).

59

Page 60: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

What are Mitigation Options for the TRV?

Potential Solutions:

• TRV Control Capacitors: TRV control capacitors can be added between

the circuit breaker/switcher to reduce the rate-of-rise of the TRV.

60

Page 61: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Overall Summary

• Shunt Capacitor Bank Switching – Potential Concerns: Voltage Change, Inrush/Outrush, Overvoltages, TRV

– Mitigation Solutions: Cap sizes, CLR, Sync-Control, Pre-Insertion Devices, Surge Arresters,

TRV Control Capacitors

• Shunt Reactor Bank Switching – Potential Concerns: Inrush Currents, Overvoltages, TRV

– Mitigation Solutions: Sync-Control, Pre-Insertion Devices, Surge Arresters, TRV Control

Capacitors

61

Page 62: IEEE Fort Worth PES Chaptersite.ieee.org/fw-pes/files/2013/01/IEEE_ShuntCapacitorReactor... · IEEE Fort Worth PES Chapter Presentation on: Potential Concerns and Mitigation for Shunt

POWER SYSTEMS ENGINEERING SERVICES (PSES)

Questions/Discussion