1 Dynamic Contact Resistance Measurements on HV Circuit Breakers by Michel Landry, IREQ Fouad Brikci, Zensol Automation Inc. IEEE/PES Switchgear Committee Meeting (Montréal, October 4, 2005) Zensol Automation Inc. 2 Zensol Automation Inc. Interrupting chamber of an SF 6 circuit breaker Fixed contacts Moving contacts

Upload: buinguyet

Post on 18-Mar-2018

220 views

Category:

Documents


4 download

TRANSCRIPT

1

Dynamic Contact Resistance Measurementson HV Circuit Breakers

byMichel Landry, IREQ

Fouad Brikci, Zensol Automation Inc.

IEEE/PES Switchgear Committee Meeting(Montréal, October 4, 2005)

Zensol Automation Inc.

2 Zensol Automation Inc.

Interrupting chamber of an SF6 circuit breaker

Fixed contacts Moving contacts

2

3 Zensol Automation Inc.

Measuring system and sensors for Dynamic Contact Resistance Measurements (DRM)

3 signals to be recordedThe injected current (IDC) of at least 100 AThe voltage drop (VD) across the breaker contactsThe breaker contact travel curve

Features of the acquisition unit3 analog 12-bit resolution inputsSampling frequency ≤ 10 kHzTotal acquisition time = 30-100 sConnection to a portable computer

SensorsHall-effect current sensor (LEM type)Voltage sensorLinear or rotary contact travel sensor

4 Zensol Automation Inc.

Measuring parameters

DRM during closing operations is impracticalAbrupt resistance variation from infinity (open contacts) to arcing contact resistance value (≈ 200 µΩ)Undesired noise level due to transient DC current at the moment of arcing contact touch

DRM during opening operationsLow contact speed (≈ 0.002 - 0.2 m/s)Reproducible measurementsEasy to interpretAdequately simulates the actual operating condition of an in-service HV circuit breaker

3

5 Zensol Automation Inc.

Not obvious resistance transition from infinityto arcing contact resistance value (≈ 200 µΩ)

Impractical DRM during closing operations

R (m

Ω)

0

2

4

6

8

0 0.5 1.0 1.5t (ms)

6 Zensol Automation Inc.

DRM on a break of a 315-kVcapacitor-bank SF6 circuit breaker

No reproducible measurements

0.5 ms

500 µΩ

Main contact part

At rated speedArcing contact part

t

R (µ

Ω)

Main contact part

Contact speed=0.2 m/s 0.15 m/s

50 ms

100 µΩ

At low speed

Arcing contact part

t

R (µ

Ω)

4

7 Zensol Automation Inc.

DRM on a break of a 120-kVcapacitor-bank SF6 circuit breaker

2 ms

500 µΩ

Presumed main contact part

Arcing contact part

t

R (µ

Ω)

At rated speed5 s

500 µΩ

Main contact part

Arcing contact part

Contact speed= 0.002 m/s

tR

(µΩ)

At low speed

8 Zensol Automation Inc.

735-kV 8-break air-blast PK circuit breaker

5

9 Zensol Automation Inc.

Relatively newfixed contact

(F1)

New movingcontact

(M1)

Slightly wornmoving contact

(M2)

Contact sets of PK breakers used fordeveloping new contact wear algorithm

10 Zensol Automation Inc.

Seriously damagedmoving contact

(M4)

Worn moving contact

(M3)

Contact sets of PK breakers used fordeveloping new contact wear algorithm

6

11 Zensol Automation Inc.

Laboratory test set-up usinga vertical CNC milling machine

12 Zensol Automation Inc.

Contact wear analysis by evaluating the area beneath the dynamic resistance curve

1

2

34

4 3

2

1 1:Contact set F1-M12:Contact set F1-M23:Contact set F1-M34:Contact set F1-M4

R (m

Ω)

Ar

(mΩ

.s)

0.5 s1 mΩ

0.5 s

1 mΩ.s

2.7 mΩ.s

5.4 mΩ.s

3.9 mΩ.s

2.8 mΩ.s

t

t

7

13 Zensol Automation Inc.

Rm

Dm

Da

Pa

Time

Ra

Ra * Da

Rm

Da

Pa

Dm

Parameters to be extractedfrom dynamic resistance curve

Arcing contact partArcing contact part

Main contact part

Main contact part

Dynamic resistance curve

Contact travel curve

t0

Contact travel (mm)

R (m

Ω)

R a

nd C

onta

ct tr

avel

14 Zensol Automation Inc.

Case Study No. 1315-kV capacitor-bank SF6 circuit breaker

8

15 Zensol Automation Inc.

Case Study No. 1DRM on a 315-kV capacitor-bank SF6 circuit breaker

15 25 355Contact travel (mm)

0

1

3

2

R (m

Ω)

Arcing contact in excellent condition

3.6Ra*Da(mΩ. mm)

34.6Pa(mm)

19.5Da(mm)

15.1Dm(mm)

185Ra(µΩ)

29Rm(µΩ)

2492Operation counter reading

Maincontactpart

16 Zensol Automation Inc.

Contact travel (mm)

R (m

Ω)

Case Study No. 2DRM on a 120-kV capacitor-bank SF6 circuit breaker

10.3Ra*Da(mΩ. mm)

45.9Pa(mm)

24.6Da(mm)

21.3Dm(mm)

420Ra(µΩ)

37Rm(µΩ)

687Operation counter reading

0

1

3

2

20 300 10 40 50

Defective arcing contact

Maincontactpart

9

17 Zensol Automation Inc.

1 off-center moving arcing contact tip Damaged fixed arcing contact

Case Study No. 2Damaged moving and fixed arcing contacts

18 Zensol Automation Inc.

Case Study No. 2DRM on the same break after contact overhaul

3.4Ra*Da(mΩ. mm)

50.5Pa(mm)

19.7Da(mm)

30.8Dm(mm)

173Ra(µΩ)

33Rm(µΩ)

< 20Operation counter reading

Normal arcing contact

R (m

Ω)

0

1

3

2

25 355 15 45 55

Contact travel (mm)

Maincontactpart

10

19 Zensol Automation Inc.

Case Study No. 3230-kV reactor SF6 circuit breaker

20 Zensol Automation Inc.

Case Study No. 3DRM on a 230-kV reactor SF6 circuit breaker

60.3Ra*Da(mΩ. mm)

65.7Pa(mm)

34.2Da(mm)

31.4Dm(mm)

1768Ra(µΩ)

74Rm(µΩ)

204Operation counter reading

Internal restrike

R (m

Ω)

0

1

3

2

20 400 60Contact travel (mm)

11

21 Zensol Automation Inc.

Case Study No. 3Arcing spots on the fixed contacts

22 Zensol Automation Inc.

Case Study No. 3DRM on a healthy break of another phase of a

230-kV reactor SF6 circuit breaker

3.1Ra*Da(mΩ. mm)

67.2Pa(mm)

33.5Da(mm)

33.8Dm(mm)

93Ra(µΩ)

34Rm(µΩ)

201Operation counter reading

R (m

Ω)

0

1

3

2

20 400 60Contact travel (mm)

Maincontactpart

Normal arcing contact

12

23 Zensol Automation Inc.

Dynamic Resistance Measurement KitZ-DRM-2

Stable DC current source

Data acquisition system

Voltage and current sensors

24 Zensol Automation Inc.

Resdyn software(R as a function of the breaker contact travel)

13

25 Zensol Automation Inc.

Dynamic Resistance Measurement KitZ-DRM-2 (Contact travel sensors)

26 Zensol Automation Inc.

Conclusion

New DRM methodOpening operations at low contact speedReproducible curves easy to analyze and interpretVital information about the breaker contact conditionUseful tool for maintenance planning

Six vital diagnostic parametersAverage main contact resistanceAverage arcing contact resistanceMain contact wipeArcing contact wipePosition of the breaker contact at the arcing contact partCumulative area beneath the resistance curve(mΩ.mm)