Page 1i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Geomagnetic Disturbances:
Impact on Power System
Components
Sakis Meliopoulos
Georgia Power Distinguished
Professor
School of Electrical and
Computer Engineering
Georgia Institute of
Technology
Atlanta, Georgia
Page 2i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
GIC Physics DC like currents in soil up to 10V/km
Corona Mass Ejection MagnetoSphere Interaction
Page 3i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Characteristics of Magnetic and Electric Field
From “Effects of Geomagnetic Disturbances on Electric Power Systems”, EPRI Report EL-7333, August 1991, by A. P. Sakis Meliopoulos et al.
Levels of magnetic field and rate of change of magnetic field makes the electric field appear as DC for the electric power system
Page 4i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Magnetic and Electric Field Exist Always and
Increase Drastically During Storms
1
1
2
2
3
3
4
4
5
5
6
6
7
7
A A
B B
C C
D D
E E
Advanced Grounding Concepts / WinSGM
August 11, 2004 Tooele Location
Step Voltage Measurement Setup
Scale (feet)
0' 45' 90' 135'
CR
3Y
2Y
1Y
3B
2B
1B
N
N39 24.344'0
W112 35.985'0
P1
P2
P3
P4P5
P6
P0SGM Location
219'
X
YGrid Spacing: 500.0 ft
Model A (Biquadratic)
Node Indexing DiscretizationExample earth surface voltage
measurements near Toole, UT
Indicates max voltages of about 2 V/mi
K-index not reported
-120.00
-100.00
-80.00
-60.00
-40.00
-20.00
0.00
20.00
1 2 3 4 5 6
Ste
p V
oltage (
mV
)
Probe Number
0 A (18:27)
100 A (18:45)
-100 A (19:04)
0 A (19:22)
Page 5i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Impact on Power System Components
Main Issues of Concern:
DC injection into Saturable Core Power Apparatus
Results into Current Distortion, Harmonics and Consequences
Vulnerable Power Equipment
Saturable Core Power Apparatus
• Generators: typically grounded via high impedance – secondary
concerns
• Solidly grounded transformers (two/three/four winding,
autotransformers)
• Solidly grounded saturable core reactors
Page 6i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Applicable Circuit for GIC – DC OnlyMagnetic Saturation Characteristics
DC Equivalent Circuit of Line Terminated to Transformers
Page 7i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Investigations Findings
Magnetic Saturation Characteristics
Typical Iron Core Magnetization Curve
Page 8i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Impact on DC Current Injection To TransformersMain Issues of Concern: Transformer/Reactor Saturation - Harmonics
Harmonic Currents on the 500 kV Side of a 360 MVA, 500/230 kV Transformer
with 75 A DC Injection
From “Mitigation of Geomagnetically Induced and DC Stray Currents”, EPRI Report EL-3295,
December 1983, by J. G. Kappenman, et al.
Page 9i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
The Effects of the March
13, 1989 Storm Felt as
South as New Jersey
Magnetic Field: ~1500 nT/min
Page 10i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Vulnerabilities Studies / Model Requirements
Modeling Issues
The main mechanism of DC current entry into saturable
core electrical equipment is via the grounding system of
substations and transmission lines
Page 11i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Vulnerability Studies / Modeling RequirementsFrequency Dependence of Line Parameters
Line Model
G. J. Cokkinides and A. P. Meliopoulos, "Transmission Line Modeling with Explicit Grounding
Representation," Electric Power Systems Research, vol. 14, no. 2, pp. 109-119, April 1988.
Page 12i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Example Parametric Study
Magnetic Saturation Characteristics
Steady State Direct Current through Transformer Winding
From “Effects of Geomagnetic Disturbances on Electric Power Systems”, EPRI Report EL-7333, August 1991, by A. P. Sakis Meliopoulos et al.
Page 13i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Example Simulation Results / Vulnerability StudyMain Issues Concern: Transformer/Reactor Saturation – Simulations
G12
V
V
V A
A
A
1 2
G
V
V
V
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
BU
S230A
BU
S230B
BU
S230B
B
BU
S230M
ID
GIC
2
GIC
MID
SO
UR
CE
1
SO
UR
CE
2
XFM
R1
XFM
R2
Page 14i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Vulnerabilities Studies / Focus Systems
Vulnerable System
Non-Vulnerable System
Non-vulnerable/vulnerable system / Series Compensated Line
Page 15i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Impact on Generators
Main Issues Concern:
Generator –Simulations
G12
V
V
V A
A
A
1 2
G
V
V
V
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
BU
S230A
BU
S230B
BU
S230B
B
BU
S230M
ID
GIC
2
GIC
MID
SO
UR
CE
1
SO
UR
CE
2
XFM
R1
XFM
R2
Generator Grounded with 1000 ohm Resistor
DC Current in Transformer Neutral: 80A
Generator Neg Seq Current: 138 A peak
Generator current THD: 8.4%
-73.55 A
-86.62 A
Neutral_DC_Current (A)
133.0 A
-138.0 A
Current_Negative_Sequence (A)
26.93 mA
-28.10 mA
Current_Zero_Sequence (A)
8.510 %
8.155 %
Current_THD_Phase_A (%)
39.31 ms 0.226 s
Page 16i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Impact on Generators
Main Issues Concern:
Generator –Simulations
G12
V
V
V A
A
A
1 2
G
V
V
V
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
BU
S230A
BU
S230B
BU
S230B
B
BU
S230M
ID
GIC
2
GIC
MID
SO
UR
CE
1
SO
UR
CE
2
XFM
R1
XFM
R2
-73.49 A
-79.54 A
Neutral_DC_Current (A)
133.0 A
-138.1 A
Current_Negative_Sequence (A)
27.79 mA
-26.69 mA
Current_Zero_Sequence (A)
8.512 %
8.343 %
Current_THD_Phase_A (%)
38.36 ms 0.125 s
Generator Grounded with 10 ohm Resistor
DC Current in Transformer Neutral: 80A
Generator Neg Seq Current: 138 A peak
Generator current THD: 8.4%
Page 17i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Mitigation Methods / Effectiveness
• Early Warning Systems
• Monitoring / Alarming Systems
• DC Block Systems
• Resistance Grounding
Page 18i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Mitigation Methods / Effectiveness
Important function of SOHO: Geomagnetic Storm Strength Measurement
Transmits K - Index
The “K-Index” is a 3-hourly quasi-logarithmic local index of geomagnetic
activity relative to an assumed quiet-day curve for the recording site.
Range is 0 to 9
The K-Index measures the deviation of the most disturbed horizontal
component of the magnetic field.
Active: K=4, Minor Storm: K=5, Major Storm: K=6 or higher
Warning Systems
Page 19i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Mitigation Methods / EffectivenessMonitoring / Alarming Systems
I
Global Time
Reference
(GPS)
GPS
Receiver
Micro
processorA/D
Phasor data
(time stamped)Serial
Communication
Port
Filt
er
To Control Center
Harmonics Data
Concentrator
(Located in Atlanta)
PMU Block Diagram
V
GPS Antena
ADD Bulletin
Board System
GIC Data
Concentrator
Located at NYPP
PMU
Computer
PMU
Computer
PMU
Computer
Asymmetric Power System Model
New York Power Authority
NYPA Project Launched: 1993, Completed: 1998, Meliopoulos & Cokkinides
This System is Presently Operational
and Participates in the North American
SynchroPhasor Initiative (NASPI)
MACRODYNE
PMU, 1992First Device Capable of
Synchronized
Measurements with
accuracy of
microsecond
Macrodyne PMU Based Harmonic
Measurement System
B. Fardanesh, S. Zelingher, A. P. Sakis Meliopoulos, G. Cokkinides and Jim Ingleson, ‘Multifunctional Synchronized
Measurement Network’, IEEE Computer Applications in Power, Volume 11, Number 1, pp 26-30, January 1998.
Page 20i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Mitigation Methods / Effectiveness
Harmonic Monitoring
• Harmonic Signature Due to GIC
• Neutral DC Monitoring - Hall Effect CT
Macrodyne PMU Based Harmonic Measurement System Detects GIC by:
(a) harmonic signature and
(b) neutral direct current measurement
B. Fardanesh, S. Zelingher, A. P. Sakis Meliopoulos, G. Cokkinides and Jim Ingleson, ‘Multifunctional Synchronized Measurement Network’, IEEE Computer Applications in Power, Volume 11, Number 1, pp 26-30, January 1998.
Page 21i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Mitigation Methods / EffectivenessDC Blocking Devices
Page 22i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Mitigation Methods / EffectivenessResistance Grounding
Page 23i-PCGRID Workshop 2015, SF, CA – March 25-27, 2015
Thank you for your Attention
Questions?