Page 1: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com © 2004 – 2010

Improved Efficiency & Reliability

for Data Center Servers Using

Immersion Cooling Technology November 20, 2014

DfR Solutions Webinar

Cheryl Tulkoff

[email protected]

Page 2: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Immersion Cooling Technology Overview

o News & Competition

o Technology Benefits

o Technology Challenges

o Reliability Opportunities

o Summary

Agenda

Page 3: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Not a new concept!

o Direct liquid immersion

cooling has been used within

IBM for over 20 years to

cool high powered chips

o Early supercomputers relied

on liquid cooling technologies

o Cray 2 supercomputer

Liquid Immersion Cooling

http://www.electronics-cooling.com/1996/05/direct-liquid-immersion-cooling-

for-high-power-density-microelectronics/

Page 4: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Why Immersion Cooling?

Page 5: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Single-phase immersion cooling

o Oil remains in the liquid phase throughout the cooling cycle

o Two-phase immersion cooling

o Cooling liquid is boiled off

o Vapor is captured & condensed before being recirculated

o Phase change from liquid to gas allows for higher heat

removal

o Adds to the complexity

o Liquid used in two-phase systems costs more than mineral

oil

Single Phase & Two Phase Immersion Cooling Tech

Page 6: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Single Phase: Cooling Using Dielectric Oil

More

effective at

removing

heat than

air

Oil costs ~$500 per 55 gallon barrel

Page 7: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o 3M Novec

o Two-phase immersion cooling technology

o Reduce water consumption and energy use

o Increase supercomputer efficiency

o Used in fire extinguishing equipment also

Two-Phase: Cooling Using Engineered Fluids

http://solutions.3m.com/wps/portal/3M/en_US/NA-

DataCenters/DataCenters/AboutUs/3MInnovation/

Page 8: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Tanks can dissipate 40kW of power or more

Page 9: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Researchers helped lead

the way

o CERN

o University of Leeds

o Reaching a more mature

level

o Demands of large, web-scale

and cloud operations

creating a new market for

server & rack-level cooling

solutions

Immersion Cooling Technology Maturing

Liquid cooling in the rack at CERN

http://www.datacenterdynamics.com/focus/archive/2013/06/viscosity-liquid-

cooling&u=2911

Page 10: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Liquid Submersion Blade Server

o LiquidCool Solutions

o Supports High Frequency

Trading with Liquid Submersion

Cooled Computers

o Released in 2010

o 2012: World’s 1st rack-mounted

total liquid submerged server

Liquid Immersion Cooling Example

http://www.liquidcoolsolutions.com/

Page 11: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Prototype supercomputer @

Tokyo Institute of Tech

submerged in tank of mineral

oil

o Named in Nov ‘14 in Green500

as the most energy-efficient

machine of its kind

o Green Revolution: mineral oil is

almost as effective as Novec &

costs much less

o Mineral oil < $10 a gallon

o 3M Novec 1230 costs ~ $70 a

gallon

Liquid-Cooled Supercomputers: Trim the Power Bill

http://www.nytimes.com/2014/02/12/business/international/

improving-energy-efficiency-in-supercomputers.html?_r=0

Page 12: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Rapidly Expanding Options

Page 13: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Negates the need for air

conditioning, chillers, humidity

control systems…

o Two-phase cooling

o Uses 3M™ Novec™ Engineered

Fluid

o Nonconductive

o Inert

o Excellent convection properties

o Provides fire protection at the

component level

Iceotope

http://www.iceotope.com/

Page 14: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Two-Phase Cooling

o Uniform device temperatures

o Reduce maintenance, improve

reliability & eliminate risk due to fluid

contact

o Boiling behavior improves the cooling

efficiency

o Even with outside air > 120 F

o Phase change allows > 2,000 watts

cooling per server.

http://www.xconomy.com/wisconsin/2014/04/03/ebullient-nears-boiling-point-in-path-

to-computer-cooling-market/2/

Ebullient Cooling

Page 15: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Green Revolution

Cooling

http://www.hpcwire.com/2014/02/14/im

mersion-cooling-floated-green-energy-

solution/

Page 16: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Liquid Cooled Datacenter

Containers

o Deploy data center capacity

anywhere and very quickly

o Temporary computing capacity in

war zones

o 6 countries, 3 continents

Applications for Military & Disaster Relief Operations

http://www.datacenterdynamics.com/focus/archive/2013/07/us-military-

servers-be-submerged-oil-data-center-containers

http://www.zdnet.com/liquid-cooled-datacenter-containers-7000017881/

Page 17: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Enhancing reliability by eliminating the root causes of failure: o < Solder joint failures

o Lower operating temperatures for board & components

o No oxidation/corrosion of electrical contacts

o No fretting corrosion of electrical contacts induced by structural vibration

o No moving parts, like fans, within the device enclosure

o No exposure to electrostatic discharge (ESD)

o No sensitivity to ambient particulate, humidity, or temperature conditions

Liquid Cool

http://www.liquidcoolsolutions.com/

Liquid submersion technology with an eco-

friendly di-electric liquid

Page 18: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Early success selling liquid-cooled gaming PCs & desktop workstations o > 1.3 million units sold

o Now in Data Center Liquid Cooling o Drop-in replacements for stock heat

sinks o No liquid ever comes in contact

with the electronics o Coolers installed into standard

commercial servers o Retrofit or on the manufacturing

line o Tubes exit through PCIe slot

Asetek

http://asetek.com/data-

center/technology/data-center-benefits.aspx

http://qz.com/69580/household-name-cloud-computing-

companies-are-preparing-to-dunk-their-servers-in-vats-

of-oil/

Page 19: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Business Value of Immersion Technology

o Reduced capital and operating expense vs.

conventional data centers

o Non-traditional facilities, including

transportable “pods”

o No need for air conditioning, raised floors or

chemical fire suppression

o Low impact on software or network

infrastructure

o Retraining of support personnel not required

o “Green” solution

o Reliability Enhancements

Redefine how

data centers

and servers

will be built

in the future

Page 20: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Typical Data Center Operating Costs Profile

8%

13%

18%

4%

57%

NetworkingEquipment

Power

Power Distribution& Cooling

OtherInfrastructure

Servers

Power costs

represent

25-40%

of monthly

operating

expenses

3 yr. Server; 10 yr. Infrastructure Amortization

Page 21: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Power Usage Efficiency (PUE)

PUE = Total Facility Power

IT Load

Total Facility Power

Power

• Switchgear

• UPS

• Battery Backup

• Lighting

• Etc.

Cooling

• Chillers

• CRACs

• Etc.

IT Load

• Servers

• Switches

• Storage

• Etc.

Any energy

expended

other than

that to drive

the IT Load

contributes to

inefficiency

Page 22: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Traditional Data Center vs. Immersion Cooled Data Center

Identical Processing Capacity Comparison (10,000 servers)

Traditional

Data Center*

Immersive Cooling

Data Center

Data Center

Size (sq. ft.)

Power

Consumption

(MW)

12,500

6.88

4,000

3.12

32%

45%

Of the Size

Of the Power

*Assumes PUE of 1.8

and Dell PowerEdge R520 servers

Page 23: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Traditional Data Center vs. Immersion Cooled Data Center

*Assumes PUE of 1.8

and Dell PowerEdge R520 servers

Identical Power Comparison (5 MW)

Traditional

Data Center*

Immersive Cooling

Data Center

Number of

Servers 16,030

6,430

7,275

9,100

120%

71%

More Processing Capacity

Of the Size

Data Center

Size (sq. ft.)

Page 24: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Preparation: Any OEM Server

Prep takes ~

10 minutes

Remove fans

Replace thermal paste

Use sealed or

solid-state drives

Page 25: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Skepticism

o Changing--Intel's recent positive report

o SuperMicro Computer is developing SKUs for immersion boards

o http://www.datacenterknowledge.com/archives/2012/03/22/su

bmerged-supermicro-servers-accelerated-by-gpus/

o Network gear manufacturers are lagging behind server vendors

o Disk Arrays

o Current hard disks leak, oil crashes the heads

o Solid State Drives (SSDs) are expensive

o Newer helium filled, hermetically sealed, drives an option

o http://www.hgst.com/press-room/2012/hgst-announces-radically-

new-helium-filled-hard-disk-drive-platform

Immersion Technology Challenges

Page 26: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Component specific

challenges

o Optical components

o TTCP transfer times and ping

times are very similar crossing

the switch network

o In all cases, no pings were lost

o Coolant immersion does not

appear to adversely affect

the error rate on the links.

Immersion Technology Challenges

Page 27: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o RF components

performance

o None detected yet

o Trials underway

o Image of Ethernet switch

which has been running

immersed since January

2011

Immersion Technology Challenges

Page 28: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Mineral Oil & Health, Flammability, Spills

o Class IIIB liquid with a flammability rating of 1 out

of 4

o Does not require any supplemental fire

suppression systems beyond what is normally used

in a data center

o Negligible health effects

o Spills & leaks considered low probability

Immersion Technology Challenges

Page 29: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o How do you work on a server in immersion oil cooling?

o Pull the server out, wait for it to drain

o Keep a paper towel nearby

o If you do get thermal paste into the system, filter it out

o Thermal paste dissolves in the oil, making it cloudy

o Maintenance

o Hot-swaps can be done in the oil

o Server can be lifted out of the tank & drained

o Repair at the circuit board level

o Clean to remove oil from circuit boards & components

Immersion Technology Challenges

Page 30: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Tin Whisker Mitigation

o Arcing

o Reduction in Corrosion & Electrochemical Migration

o Corrosive exposure reduction

o Moisture reduction

o Environmental contaminant reduction

o Dust, debris, particulates

o More stable and even thermal environment

o No hot spots

Potential Reliability Enhancements

Page 31: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Tin Whiskers

Hair-like single crystal metallic filaments that grow

from tin films

Unpredictability is the greatest concern

Page 32: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

What are the potential failure modes?

Direct Contact

Causes an electrical short (arcing)

Requires growth of sufficient length & in

the correct orientation

Electromagnetic (EM) Radiation

Emits or receives EM signal & noise at

higher frequencies

Debris

Whisker breaks off and shorts two

leads (primarily during handling)

Can be mitigated by immersion

cooling

Courtesy of P. Bush, SUNY Buffalo

Observation of tin whisker debris as

reported to NASA from Sanmina-SC

DfR Solutions

Page 33: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Contamination and Cleanliness

o Believed to be one of the primary drivers of field issues in electronics today

o Induces corrosion & ElectroChemical Migration (ECM)

o Intermittent behavior causes no-fault-found (NFF) returns

o Driven by self-healing behavior

o Difficult to diagnosis

o Pervasive

o Will continue to get worse

Page 34: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Future of Contamination / Cleanliness

o Continued reductions in pitch between conductors will make future packaging more susceptible

o Increased use of leadless packages (QFN, land grid array, etc.) results in reduction in standoff

o Will reduce efficiency of cleaning, which may lead to increased concentration of contaminants

o Increased product sales into countries with polluted and tropical environments (East Asia, South Asia, etc.)

o ECM occurrence very sensitive to ambient humidity conditions

o Pb-Free and smaller bond pads

o Require more aggressive flux formulations

Page 35: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Temperature

o Moisture

o Contamination

o Voltage/Electrical Field

o Temperature, moisture, and contamination can all be

reduced and/or eliminated with immersion cooling

Electrochemical Migration Drivers

Page 36: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Sources of Contaminants

o Printed board fabrication process

o Insufficiently cured polymers

o Rinse water

o Fluxes

o Handling

o Storage and use environment

Page 37: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Contaminants: Handling / Storage / Environment

o Handling

o Salts from human contact (KCl and NaCl)

o Storage

o Cleaning chemicals

o Outgassing

o Polymeric materials

o Use Environment

o Dust, Debris

o Moisture, Evaporated sea water

o Industrial pollutants

o Immersion cooling prevents these from accumulating on electronics

Page 38: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Influence of Pollutants: Creepage Corrosion

o Recent field issues with printed circuit boards (PCBs) plated with immersion silver

o Sulfur-based creepage corrosion

o Failures in customer locations with elevated levels of sulfur-based gases

o Rubber manufacturing

o Sewage/waste-water treatment plants

o Vehicle exhaust fumes (exit / entrance ramps)

o Petroleum refineries

o Coal-generation power plants

o Paper mills

o Landfills

o Large-scale farms

o Automotive modeling studios

o Swamps

o Immersion cooling would prevent this exposure!

P. Mazurkiewicz , ISTFA 2006

Page 39: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com 39

Creepage Corrosion Failure of ImAg

•Corrosion product is semi-conductive (resistance of about 1Mohm).

•Resistance decreases as humidity increases.

•Traces sensitive to leakage current trigger the system failure.

•Visual inspection required to identify failures (most are CNDs).

Initiation of

a short

Page 40: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Pollutants: Not Always in Industrial Settings

o Chinese Drywall Cited in Building Woes o The drywall is emitting sulfur-based gases that are corroding air-

conditioner coils, computer wiring and metal picture frames.

o Drywall blamed for A.C. failures o Air-conditioning coils have turned black, along with wiring, piping and

even silver jewelry.

o "We have definitely identified that a combination of sulfide gases

are the cause of the corrosion," said Robert P. DeMott, managing

principal of Environ.

o "Foul odors reported by people living in the homes may also be

caused by the combination of sulfur gases being released from the

drywall,

o Chinese drywall class action lawsuit o LEE COUNTY, Fla. - The Lawsuit was filed against Knauf Plasterboard

Tianjin Co., LTD, The Knauf Group, Rothchilt International Limited and

the Banner Supply Company.

o Known as "Chinese Drywall", it was manufactured oversees and was

made from waste materials. As a result, it emits sulfur compounds that

corrode copper wiring and other metals found in homes.

Copper Corroded by Sulfur flumes

Drywall Sulfur Fumes Blamed for A.C. & Electrical Equipment failures

Page 41: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Infra-Red Thermal Evaluation

D11 Alum Caps

Q16

Thermal Anomalies Detected

- Q16 producing heat when is it supposed to

be in an off state - sneak circuit detected

- D11 detected a hot spot that exceeded

thermal limit

Expect hot spot reduction and improved thermal

uniformity using immersion oil cooling

Page 42: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Intel tests oil immersion to cool servers

o “If you are going to add a significant amount of capacity and have

systems with a lot of density and don’t have good air flow in your

data center, this is worth looking at,” said Mike Patterson, a senior

thermal architect for data centers at Intel who supervised the test.

o “We asked a lot of tough questions and they had pretty good

answers for all of them so we put a pilot together,” said Patterson.

“There’s almost an emotional reaction [against oil immersion] at first,

so people say they would never do that, but when they see the

potential [energy] savings, they see there’s something there,” he

said.

Industry Evaluation – Intel Experience

Page 43: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o With all this in mind, Intel plans to start developing

motherboards optimized for immersion cooling. Various

OEMs involved in server hardware are expected to

create modified designs with oil immersion in mind as

well. In the future, this technology might even make it to

the consumer level in a more official way.

o Intel also found that no computer components —

processors, hard drives etc. – were damaged from the

yearlong immersion in mineral oil.

Industry Evaluation – Intel Experience

http://green.blogs.nytimes.com/2012/09/06/cooling-a-computer-

server-with-mineral-oil/

Page 44: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Immersion cooling offers significant environmental, cost,

performance & reliability advantages

o Reduces potential for failure in:

o Tin Whisker Mitigation via arcing

o Corrosion & Electrochemical Migration (ECM)

o Moisture reduction

o Environmental contaminant reduction

o Fretting

o Provides stable thermal environment

Summary

Page 45: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

Presenter Biography

o Cheryl has over 20 years of experience in electronics manufacturing focusing on failure analysis and reliability. She is passionate about applying her unique background to enable her clients to maximize and accelerate product design and development while saving time, managing resources, and improving customer satisfaction.

o Throughout her career, Cheryl has had extensive training experience and is a published author and a senior member of both ASQ and IEEE. She views teaching as a two-way process that enables her to impart her knowledge on to others as well as reinforce her own understanding and ability to explain complex concepts through student interaction. A passionate advocate of continued learning, Cheryl has taught electronics workshops that introduced her to numerous fascinating companies, people, and cultures.

o Cheryl has served as chairman of the IEEE Central Texas Women in Engineering and IEEE Accelerated Stress Testing and Reliability sections and is an ASQ Certified Reliability Engineer, an SMTA Speaker of Distinction and serves on ASQ, IPC and iNEMI committees.

o Cheryl earned her Bachelor of Mechanical Engineering degree from Georgia Tech and is currently a student in the UT Austin Masters of Science in Technology Commercialization (MSTC) program. She was drawn to the MSTC program as an avenue that will allow her to acquire relevant and current business skills which, combined with her technical background, will serve as a springboard enabling her clients to succeed in introducing reliable, blockbuster products tailored to the best market segment.

o In her free time, Cheryl loves to run! She’s had the good fortune to run everything from 5k’s to 100 milers including the Boston Marathon, the Tahoe Triple (three marathons in 3 days) and the nonstop Rocky Raccoon 100 miler. She also enjoys travel and has visited 46 US states and over 20 countries around the world. Cheryl combines these two passions in what she calls “running tourism” which lets her quickly get her bearings and see the sights in new places.

Page 46: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o 1. Danielson, R.D., Tousignant, L., and Bar-Cohen, A.,Saturated Pool Boiling Characteristics of Commercially Available Perfluorinated Liquids, Proc. of ASME/JSME Thermal Engineering Joint Conference, 1987.

o 2. Bergles, A.E., and Bar-Cohen, A., Immersion Cooling of Digital Computers, Cooling of Electronic Systems , Kakac, S., Yuncu, H., and Hijikata,K., eds, Kluwer Academic Publishers, Boston, MA, pp. 539-621, 1994.

o 3. Mudawar, I., and Maddox, D.E., Critical Heat Flux in Subcooled Flow Boiling of Fluorocarbon Liquid on a Simulated Chip in a Vertical Rectangular Channel, Intl. J Heat and Mass Transfer, 32, 1989.

o 4. Chrysler, G.M., Chu, R.C., and Simons, R.E., Jet Impingement Boiling of a Dielectric Coolant in Narrow Gaps, IEEE Trans. CHMT-Part A, Vol. 18 (3), pp.527-533, 1995.

o 5. Danielson, R.D., Krajewski, N., and Brost, J., Cooling a Superfast Computer, Electronic Packaging and Production, pp. 44-45, July 1986.

Other References

Page 47: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Oil bath monitoring for water (primarily initial

equipment insertion) and contaminants (over time,

leaching out from cables, plastics, etc).

o People who use immersion cooling currently are doing things

like broadcast RF amplifiers, radars, and similar high voltage

applications.

o In those cases they monitor the resistance of the oil.

o Wondering about potential electrolyte leakage from

capacitors, so been thinking about adding pH monitoring.

Future Work – Questions & Challenges

Page 48: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o 1. Danielson, R.D., Tousignant, L., and Bar-Cohen, A.,Saturated Pool Boiling Characteristics of Commercially Available Perfluorinated Liquids, Proc. of ASME/JSME Thermal Engineering Joint Conference, 1987.

o 2. Bergles, A.E., and Bar-Cohen, A., Immersion Cooling of Digital Computers, Cooling of Electronic Systems , Kakac, S., Yuncu, H., and Hijikata,K., eds, Kluwer Academic Publishers, Boston, MA, pp. 539-621, 1994.

o 3. Mudawar, I., and Maddox, D.E., Critical Heat Flux in Subcooled Flow Boiling of Fluorocarbon Liquid on a Simulated Chip in a Vertical Rectangular Channel, Intl. J Heat and Mass Transfer, 32, 1989.

o 4. Chrysler, G.M., Chu, R.C., and Simons, R.E., Jet Impingement Boiling of a Dielectric Coolant in Narrow Gaps, IEEE Trans. CHMT-Part A, Vol. 18 (3), pp.527-533, 1995.

o 5. Danielson, R.D., Krajewski, N., and Brost, J., Cooling a Superfast Computer, Electronic Packaging and Production, pp. 44-45, July 1986.

Other References

Page 49: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o “Are Zinc Whiskers Growing in Your Computer Room?” R. Hill, Data Clean Corp.; http://www.dataclean.com/pdf/ zincwhiskers3.pdf.

o “Testing Your Mettle: Zinc Whiskers in the Data Center,”B. Brown, Network World, Nov. 2004, http://www.nwfusion.com/news/2004/110104widernetwhiskers.html

o Pesky ‘Whiskers’ Zap PCs in Secretary of State’s Office,” Aldo Svaldi, The Denver Post, 1 July 2004, pp. C-01.

o • “Precautions Against Zinc Whiskers,” Compaq Corp., Power Requirements for Non-Stop Himalaya Servers—429905-001, http://h71033.www7.hp.com/TechPubs/PDF/Power_Requirements/TPSEC05.pdf.

o “What Nasty Little Things Are Lurking Inside Your Data Center?” S. Tucker, Unisys World Monthly, Nov. 2002; http://www.unisysworld.com/monthly/2002/11/whiskers.shtml.

o “Zinc Whisker Abatement,” Worldwide Environmental Services; http://www.wes.net/field_engineering_services-zinc_

o whisker_detail.htm.

o “Zinc Whiskers: Could Zinc Whiskers Be Impacting Your Electronics?” J. Brusse, Apr. 2003; http:// nepp.nasa.gov/whisker/reference/tech_papers/Brusse2003-Zinc-Whisker-Awareness.pdf.

o “Zinc Whisker Contamination: A Paper on the Effect and Abatement of Zinc Whiskers in Data Processing Centers,” D. Loman, HP Services; http://www.dataclean.com/pdf/ZincWhiskerWhitePaper.pdf.

o “Zinc Whiskers Growing on Raised Floor Tiles are Causing Conductive Contamination Failures and Equipment

o Shutdowns,” The Uptime Institute; http://www.upsite.com/TUIpages/tuiflashzinc.html.

o “Zinc Whiskers on Floor Tiles,” Infinite Access Floors; http://www.accessfloors.com.au/zincwhiskers.htm.

o “Zinc Whisker Induced Failures in Electronic Systems,” ERA Technology, Winter 2003, http://www.era.co.uk/news/rfa_feature_06.asp.

o “Whisker Alert,” Japan Electronics & Information Technology Industries Association (JEITA), Jan. 2002; http://it.jeita.or.jp/infosys/info/whisker/ (in Japanese).

o http://www.layerzero.com/Innovations/stainless_steel_hardware.html (Data Center & Zinc whisker mitigation)

Zinc Whisker References

Page 50: Improved Efficiency & Reliability for Data Center Servers of … · 2017-10-08 · Improved Efficiency & Reliability for Data Center Servers Using Immersion Cooling Technology November

© 2004 - 2007 © 2004 - 2010 9000 Virginia Manor Rd Ste 290, Beltsville MD 20705 | 301-474-0607 | www.dfrsolutions.com

o Process from Mark at SFIVE

o Step 1. – Power down and REMOVE from the environment any and all equipment that you can. If the whole room can be shut down, do it!

o Step 2. – Power down as many air conditioning units as you can for the remaining load.

o Step 3. – Protect remaining equipment with plastic barrier tents. Create safe envelopes for equipment by sealing plastic sheeting between the ceiling and the floor. If you still have airflow under the floor, you will need to create underfloor barriers as well. This step is critical since these barriers will protect your equipment from zinc-laden airflow during the replacement process. Note: This step is often difficult to perform because of the physical layout of the room. If this step cannot be performed, compensating changes to the work plan must be implemented.

o Step 4. – Remove affected panels by carefully lifting (without sliding or jostling them) and placing them in a plastic bag. Place only one panel in a bag and fold and seal the bag. Remove the panel from the room. Don’t reuse the bags!

o Step 5 – Clean the underfloor plenum, flooring understructure, and underfloor infrastructure using HEPA vacuums and wet wiping.

o Step 6 – Clean the underside of unmovable panels (under equipment that cannot be moved) using wet wiping.

o Step 7 – Install replacement panel

o Step 8 – Repeat Steps 4 – 7 throughout remainder of affected area.

o Step 9 – Clean the entire room and its contents. Zinc Whisker contamination does not remain in the underfloor plenum. The whiskers can and do end up on the walls, ceiling, and all items within the room.

o Step 10 – Carefully remove barriers, reinstall equipment. Remember to map or mark panels that were not removed, if any. These panels should be monitored for continued whisker growth and replaced coincident with future equipment moves.

Zinc Whisker – Data Center Remediation Plan