 Model 733DX-04AR01  F06-02-01 H yd r a uli c Act ua tion, L o ca l R e setti ng D eluge Va lve, P res sure Cont rol   Se r i e s 70 0D/ DG / DX - 04 / 14AR01  G e ne r a l D e scri p tion The Inbal  Pressure Control, Hydraulica lly Actuated Delu ge V alve is specifically designed for use in fire  pr ot ec tio n sy st ems wh ic h re qu ir e  pressure cont rol, actuate d by a detection and release system of wet pilot sprinklers and/or hydraulic manual control. The Inbal  Valve, when in operation, automatically reduce a higher inlet  pressure to a preset delivery pressure which remains steady and unattached by the variations or fluctuations in the  pressure inlet line. The Inbal  Pressure Control, Hydraulica lly Actuated Delu ge V alve is used for automatic or manual hydr aulic operation. The wet pilot line functions as a thermal detector equipped with fixed temperature release. When one or more of the sprinkler heads located on the pilot line fuses, or when a manual release station is operated locally or remotely, the Inbal Deluge Valve opens to allow water to flow from all open sprinklers and/or nozzles on the system. While the valve operates, the deluge system pressure is maintained at the  preset lev el with in a narrow r ange. If the downstream pressure changes slightly the pilot control responds immediately to modulate the Inbal Valve for the preset  pressure. The use of the Inbal Pressure Control Deluge V alve balances the distr ibution of the water capacity available, throughout the system and prevents a higher demand from the areas which are of lower altitude or are located closer to the  pressure source. Thus, the total system demand is balanced and the excess flow through the system with high pressure water supplies is reduced to the desired level. The adjustment of the valve's delivery pressure can be easily modified at the site. Standard material Inbal  Pressure Control Deluge Valves are rated to 300  psi (21 bar) and are available in sizes 1½" (40 mm) to 12" (300 mm) with threaded, flanged, grooved, or wafer ends. The only moving part in the Inbal Valve, when it operates, is the reinforced sleeve which forms a drip tight seal with the corrosion resistant core. It has a smooth opening to prevent any water hammer in the piping system . The unique design of the Inbal V alve a nd the pilot control, and variety of materials and coatings, make the Inbal Pressure Control Deluge Valve suitable for use with brackish or sea water similar to those found in chemical and  petrochemical facilities or in offshore  platforms. Te chni cal Dat a Approvals The basic Inbal Deluge Valve is FM Approved to 300 psi (21 bar ) in sizes 3", 4", 6", and 8" (80, 100, 150, and 200 mm). Inbal Valves are Lloyd's, DNV, and ABS Type Approved in sizes 1½" (40 mm) to 12" (300 mm) to a working p ressure of 300 psi (21 ba r) . Model Numbers I nlet E nd Outle t E nd Mod e l No. Threaded Threaded 711DG-04AR01 Threaded Grooved 716DG-04AR01 Flanged Flanged 733DG-04AR01 Flanged Grooved 736DG-04AR01 Gro ove d Gro ove d 766DG-04 AR0 1 Wafer Wafer 799DG-04AR01 "DG" can be replaced with "D" or "DX" depends on the Inbal Automatic Water Contr ol Valve series in use. See bulletins F02-01-01, F02-02-01, and  F02-03-01. The above model numbers refer to fully trimmed valves. For basic trim replace "04" with "14". (See also bulletin F01-03-01 for control trim "24" & "34"). For example: 733D-14AR01 is a flanged ends deluge valve with basic, hydraulically actuated, pressure control trim. Mil Ltd.

Upload: alissonkalil

Post on 14-Oct-2015

596 views

Category:

Documents


29 download

TRANSCRIPT

  • Model 733DX-04AR01

    F06-02-01

    Hydraulic Actuation, Local Resetting Deluge Valve, Pressure Control Series 700D/DG/DX - 04/14AR01

    General Description

    T h e I n b a l P r e s s u r e C o n t r o l , Hydraulically Actuated Deluge Valve is specifically designed for use in fire protection systems which require pressure control, actuated by a detection and release system of wet pilot sprinklers and/or hydraulic manual control. The Inbal Valve, when in operation, automatically reduce a higher inlet pressure to a preset delivery pressure which remains steady and unattached by the variations or fluctuations in the pressure inlet line.T h e I n b a l P r e s s u r e C o n t r o l , Hydraulically Actuated Deluge Valve is used for automatic or manual hydraulic operation. The wet pilot line functions as a thermal detector equipped with fixed temperature release. When one or more of the sprinkler heads located on the pilot

    line fuses, or when a manual release station is operated locally or remotely, the Inbal Deluge Valve opens to allow water to flow from all open sprinklers and/or nozzles on the system.While the valve operates, the deluge system pressure is maintained at the preset level within a narrow range. If the downstream pressure changes slightly the pilot control responds immediately to modulate the Inbal Valve for the preset pressure. The use of the Inbal Pressure Control Deluge Valve balances the distribution of the water capacity available, throughout the system and prevents a higher demand from the areas which are of lower altitude or are located closer to the pressure source. Thus, the total system demand is balanced and the excess flow

    through the system with high pressure water supplies is reduced to the desired level. The adjustment of the valve's delivery pressure can be easily modified at the site.Standard material Inbal Pressure Control Deluge Valves are rated to 300 psi (21 bar) and are available in sizes 1" (40 mm) to 12" (300 mm) with threaded, flanged, grooved, or wafer ends. The only moving part in the Inbal Valve, when it operates, is the reinforced sleeve which forms a drip tight seal with the corrosion resistant core. It has a smooth opening to prevent any water hammer in the piping system .The unique design of the Inbal Valve and the pilot control, and variety of materials and coatings, make the Inbal Pressure Control Deluge Valve suitable for use with brackish or sea water similar to t hose found i n chemica l and petrochemical facilities or in offshore platforms.

    Technical Data

    ApprovalsThe basic Inbal Deluge Valve is FM Approved to 300 psi (21 bar) in sizes 3", 4", 6", and 8" (80, 100, 150, and 200 mm). Inbal Valves are Lloyd's, DNV, and ABS Type Approved in sizes 1" (40 mm) to 12" (300 mm) to a working pressure of 300 psi (21 bar) .

    Model NumbersInlet End Outlet End Model No.Threaded Threaded 711DG-04AR01Threaded Grooved 716DG-04AR01Flanged Flanged 733DG-04AR01Flanged Grooved 736DG-04AR01Grooved Grooved 766DG-04AR01 Wafer Wafer 799DG-04AR01

    "DG" can be replaced with "D" or "DX" depends on the Inbal Automatic Water Control Valve series in use. See bulletins F02-01-01, F02-02-01, and F02-03-01.The above model numbers refer to fully trimmed valves. For basic trim replace "04" with "14". (See also bulletin F01-03-01 for control trim "24" & "34"). For example: 733D-14AR01 is a flanged ends deluge valve with basic, hydraulically actuated, pressure control trim.

    Mil Ltd.

  • F06-02-01-002

    OptionalCast Steel ;Bronze ;Nickel Aluminum Bronze ;Stainless Steel AISI 316 ;Super Austenitic Stainless Steel ;Super Duplex Stainless Steel ;Titanium.

    CoatingStandardPowder epoxy coated. Thickness: 0.004" (0.1 mm) external and internal surfaces.OptionalHigh built epoxy coated and polyure- thane finish. Thickness: 0.01" (0.3 mm).

    Halar coated. Thickness: 0.02" (0.5 mm) .Halar is a registered trade mark of Ausimont USA Inc.

    Control Trim

    The control trim includes Deluge Pilot Valve, Pressure Reducing Pilot Valve, Emergency Release Valve, Pressure Gauges, Pressure Gauge Valves, fittings, and tubing. On standard the control trim is supplied preassembled in sections. See the applicable Trim Chart for complete components list.

    Features

    ! Dual function control trim on a single valve body saves the use of two different control valves.! No Moving Mechanical Parts

    (N.M.M.P.) construction ensures a long life of dependable operation and provides stable delivery pressure and a gradual closure, in case of increasing delivery pressure, to eliminate surges.! Quick, yet soft opening performance -

    eliminates water hammer and conse-quent damages.! Fast and easy reset by merely pulling a

    knob.! Supplied as standard preassembled in

    sections - saves the self assembly cost.! Can be installed vertically or

    horizontal ly .! Compact design - minimum space for

    valve and trim.! Unique principle of operation prevents

    false operation due to water surges.! Pressure rating to 300 psi (21 bar) for

    standard material valve.! Balanced, single seat design pilot

    control for very accurate performance- not affected, even slightly, by inlet pressure fluctuations.! Long spring design pilot control for

    sensitive setting and maintaining precise delivery pressure.! Easily adjusted to the desired system

    pressure.! Hydrodynamically designed Inbal

    Valve with streamline flow path- provides increased flow capacity.! Wide range of sizes for an ideal system

    design.! Control trim made of high grade

    materials as standard.! Epoxy coating supplied as standard -

    ensures excellent corrosion resistance.! Variety of available materials - to

    ensure corrosion-free service even under severe conditions.

    Operation

    The Control Chamber of the Inbal Automatic Water Control Valve is the annular space between the Valve Housing and the Sleeve. The valve is held in a closed position as long as inlet pressure is maintained in the Control Chamber. The wet pilot line, equipped with closed sprinkler heads, is pressurized through the valve trim and located over the protected area. The wet pilot line serves the dual purpose of thermal detection and release system.In the set position, water pressure is applied to the Control Chamber of the Inbal Deluge Valve and to the hydraulic release system from the upstream of the Water Supply Valve. Consequently, the Inbal Deluge Valve stays closed.The Inbal Deluge Valve opens when one or more of the sprinkler heads installed on the wet pilot line fuses and water pressure is allowed to escape, or when a hydraulic manual release opens.Either one of these operations releases water from the Deluge Pilot Valve which opens to release water from the Inbal Valve Control Chamber. The flow through the Pressure Reducing Pilot Valve responds to changes in the downstream pressure while controlling the pressure at the Inbal Valve Control Chamber. When the delivery pressure decreases, the pilot valve and the Inbal Valve open wider to increase the pressure. When the delivery pressure increases, the pilot valve and the Inbal Valve close to throttle further the flow

    SizesThreaded End:1", 2", 2", & 3" (40, 50, 65,&80 mm).Flanged and Grooved Ends:1", 2", 2", 3", 4", 6", 8", 10", & 12" (40, 50, 65, 80, 100, 150, 200, 250, & 300 mm). Wafer End: 3", 4", 6"; 8",10", & 12" (80, 100, 150, 200, 250, & 300 mm).

    End StandardsThreaded End: NPT or BSPT.Flanged End:ANSI B16.5 class 150 & 300 ;ISO 7005 - PN 10, 16 & 25 ;BS 10 Table D & E ;AS 2129 Table D & E ;Jis B2212; 2213, & 2214.Wafer End:Fits most of the abov e standards.Grooved End:ANSI/AWWA C606-87.

    Pressure RatingMaximum working pressure*: 300 psi (21 bar).

    * Standard material valve.

    Adjustment RangeStandard*30 to 300 psi (2 to 21 bar).

    * Marked red.

    Temperature RangeWater: Max. +150F (+65C).

    Installation PositionVertical or horizontal.

    MaterialsStandardValve Housing:Carbon Steel (SAE 1021).Valve Ends and Wafer Flow Test & Drain Ends:Ductile Iron (ASTM A536-65 45 12).Threaded, Flanged, and Grooved Flow Test & Drain Ends:Carbon Steel (SAE 1020).Sleeve: SMR5 Elastomer reinforced with poly-ester and Kevlar.Control Trim:Brass Nickel Chrome plated, Stainless Steel, and Galvanized Steel.

  • 00000

    1 Inbal AutomaticWater Control Valve

    2 Emergency Release Station3 Automatic Drain Valve4 Trim Shutoff Valve5 Y-Strainer

    0

    0

    6 Check Valve 7a Supply Pressure Gauge 7b System Pressure Gauge9 Pressure Reducing

    Pilot Valve19 Restriction Orifice

    _ Schematic Control Diagram 700DG- 04AR01

    OPEN

    CLOSEE

    MERG

    ENCY

    MANU

    AL VAL

    VE

    2

    6

    9

    26

    4

    19

    5

    6 35

    25

    7b

    7a

    ToDrain

    ToDrain

    To AlarmPressureSwitch

    To Drain

    3Wet Pi

    lot Line

    Inspector'sTest Valve

    F06-02-01-003

    25 Deluge Pilot Valve26 Flow Control Unit35 Alarm Test Valve38a Flow Test Valve38b Drain Valve

    38a

    To Drain

    To System

    To Drain

    38b

    1To WaterMotorAlarm

    WaterSupplyValve

    and consequently the delivery pressure is decreased. Thus, the outlet pressure is maintained within a close limit. The operation of the Inbal Deluge Valve will flow water from any open sprinklers and/or spray nozzles on the system while activating the system's alarm devices.Once the Deluge Pilot Valve operates, it latches in an open position, preventing the Inbal Pressure Control deluge Valve from closing even if the open releasing wet pilot line closes. The Inbal Valve will close only when the Resetting procedure is followed.The Deluge Pilot Valve spring tension is adjusted to open wide when the wet pilot line operates and to be in a drip tight closed position when the wet pilot line is reset. The Emergency Release Valve is used for emergency actuation of the Inbal Deluge Valve and for routine testing.

    Installation

    Refer to the Trim Chart applicable to the specific Inbal Pressure Control Deluge Valve model in use.

    1.When the Inbal Deluge Valve is delivered, carefully unpack and visually check that there has been no damage to the operating components, piping, and fittings.

    2.Always flush the pipelines before installing the Inbal Valve.

    3.Place the Inbal Valve in the piping at the outlet of the Water Supply Valve. Verify that the arrow on the valve Housing matches the actual flow direction. Determine which side the system will be accessed from and locate the Inbal Deluge Valve accordingly.

    4.Install the Inbal Deluge Valve in the pipeline. Use gaskets, bolts, stud bolts, bolt sleeves, and nuts as required by the valve ends.

    5.Complete the trim assembly by connecting the preassembled sections, or assemble the trim if ordered in loose component form. Refer to the applicable Trim Chart and Installation Guide

    6.The water pressure supply to the control trim must always be sourced from the inlet of the Water Supply Valve through a " pipe.

    7.Connect the drain tube of the Deluge Pilot Valve and all the other drain tubes to the drainage system.

    8.It is recommended to install an

    0

    0

    0

    0

    0

    0

    0

    0

    inspector's test valve on the hydraulic release system. The inspector's test valve is a locked closed ball valve with an outlet end orifice equivalent to the smallest orifice of releasing device provided on the system. The inspector's test valve may be used to verify adequate operation of the deluge system when a releasing device operates.

    9.Connect the wet pilot line to the Deluge Pilot Valve. Open the Trim Shutoff Valve and allow water pressure to build up in the trim, Inbal Valve Control Chamber, and the pilot line. Open the inspectors test valve and verify that the Deluge Pilot Valve opens fully. If the Deluge Pilot Valve opens partially or remains closed, tighten the adjusting screw until full open position is obtained. Close the inspectors test valve, reset the Deluge Pilot Valve [see (7) in Resetting], and verify that the Deluge Pilot Valve is drip-tight closed. See

    0

    Graph (1) in bulletin F33-03-01 for Deluge Pilot Valve adjustment range.

    10.The downstream pressure adjustment is recommended at a minimum flow velocity of 1.5 ft/sec (0.5 m/sec). When it is not feasible to flow the system, close the system shutoff valve and open the Drain Valve.

    11.Operate the system to establish the minimum flow. Check the System Pressure Gauge reading. If adjust- ment is required turn the Pressure Reducing Pilot Valve adjusting screw clockwise to increase or counter-clockwise to decrease the pressure setting.

    12.Open the system shutoff valve and close the Drain Valve.

    13.Set the Inbal Pressure Control Deluge Valve by following the Resetting procedure.

    14.Test the Inbal Deluge Valve, the trim and the alarm according to the Testing procedure.

  • March 2000 / F06-02-01

    Deluge Valve, Pressure Control Series 700D/DG/DX - 04/14AR01

    Resetting

    The Inbal Pressure Control Deluge Valve system must be reset and restored to service as soon as possible after auto- matic, emergency, or manual actuation. 1.Close the Water Supply Valve. The

    water flow alarms are reset.2.Close the Trim Shutoff Valve.3.Open the Flow Test and Drain Valves,

    allowing all the water to drain.4.Inspect and replace any portion of the

    detection system subjected to fire conditions.

    5.Inspect the trim and alarm Y-Strainers. Clean if necessary.

    6.Verify that the Emergency Release Valve is in a closed position.

    7.Open the Trim Shutoff Valve and allow the water to fill up the pilot line. Pull the reset knob of the Deluge Pilot Valve and position the Resetting Indicator. As soon as the pilot system pressure exceeds the preset pressure, the Resetting Indicator should fall off, hanged by the Secured Chain. If Deluge Pilot Valve adjustment is required see (10) in Installation.

    .Close the Flow Test Valve.9.Fully open the Water Supply Valve.

    Verify that there is no flow from the Drain Valve downstream of the Inbal Valve.

    10.Close the Drain Valve.

    Maintenance, Inspection, & Testing

    It is recommended that periodic inspec-tions and tests be conducted by qualified personnel to ensure that the Inbal Pressure Control Deluge Valve and related equipment are in good operating condition. The inspection and testing activities should be done according to NFPA Standards, the guidelines and regulations of the authorities having jurisdiction, and the following instructions. It is recommended that the Pressure Control Deluge Valve be tested, operated, cleaned, and inspected at least on a routine basis.

    0

    00

    0

    0

    0

    0

    008

    InspectionA weekly Inspection is recommended:1. Verify that the Water Supply Valve is

    sealed in full open position.2. Verify that the required water pressure

    is being applied to the Inbal Deluge Valve inlet and trim.

    3. Verify that the Trim Shutoff Valve, Alarm Test Valve, Emergency Release Valve, Pressure Gauge Valves, and Drain Valve are in se t position .

    4.Check the Supply and System pressure gauge readings.

    5. Visually inspect for broken or missing parts, or other evidence of impaired protection.

    Strainer CleaningA quarterly Strainer Cleaning is r e c o m m e n d e d :1. Close the Trim Shutoff Valve.2. Remove the covers of the trim and

    alarm Y- Strainers. Clean if necessary.3. Open the Trim Shutoff Valve.

    Alarm TestingA quar ter ly Alarm Tes t ing i s r e c o m m e n d e d :1. Test the Water Motor Alarm or Alarm

    Pressure Switch by opening the Alarm Test Valve.

    2. Water Motor Alarm should be audible. Alarm Pressure Switch should activate.

    3. Close the Alarm Test Valve. All local alarms stop sounding and pressure switch is reset.

    4. Verify that the supply piping to alarm drains properly .

    Deluge Trim TestingA semi-annual Deluge Trim Testing is recommended. Testing of the control trim is conducted with no flow of water to the system.1.Open the Flow Test Valve to flush

    away debris or foreign particles which may have accumulated in the Inbal Deluge Valve inlet.

    2.Close the Flow Test Valve.3.Close the Water Supply Valve installed

    in the inlet of the Inbal Valve.4.Open the inspector's test valve

    installed on the hydraulic release

    system. Water should be drained from the deluge trim. If an adjustment of the Deluge Pilot Valve is needed see (10) in Installation and (7) in Resetting.

    5.Reset the Valve by performing the instructions in Resetting.

    Trip TestingAn annual Trip Testing is recommended. By performing the Trip Testing, water will flow from all open sprinklers and/or nozzles. Prevent damage by taking the necessary precautions.1.Trip the Inbal Valve to open by

    opening the inspector's test valve. The water in the Inbal Valve Control Chamber is released to the atmosphere. The Inbal Deluge Valve will open and water will flow to the system.

    2.Check the Supply and System Pressure Gauge readings. Verify that the delivery pressure is as predetermined.

    3.Record the actual flow rate and upstream and downstream pressures.

    4.Verify that all the alarms operate properly.

    5.Close the inspector's test valve.6.Reset the valve by performing the

    instructions in Resetting.

    RemovalTo remove the Inbal Deluge Valve:1.Close all the pressure supplies:

    a) Water Supply Valve.b) Trim Shutoff Valve.

    2.Open the Emergency Release Valve to release the water pressure from the Inbal Valve Control Chamber.

    3.Open the Drain Valve to allow all the water to drain.

    4.Disconnect the union and remove the trim from the valve.

    5.Remove the Inbal Valve from the line for inspection.

    6.To reinstall, follow the Installation procedure (use new gaskets for flanged or wafer valve).

    Inquiries/Orders

    The Data Sheet For Inquiries/Orders (bulletin F01-05-01) should be submitted.

    Mil Ltd. 17 Moshe Beker Street, P.O.Box 15200, Rishon Lezion 75051, Israel. Tel: +972 3 966 4350, Fax: +972 3 966 4320, E-mail: inbalvl@ attglobal.net

  • Model 799D

    Mil Ltd.

    Automatic Water Control Valve Series 700D

    F02-01-01

    General DescriptionThe Inbal Automatic Water Control Valve series 700D is a pressure operated, sleeve actuated, axial valve, designed from basic concepts, with a built-in actuator to function as control valve in fire protection system. The Inbal series 700D is used as deluge, preaction, dry pipe, remote control, pressure reducing, pressure relief, pump control, water level control, and other types of control valves. The standard material Inbal Valve is rated to 300 psi (21 bar) and requires a minimum line pressure of 20 psi (1.5 bar) for operation. Upon removal of the control pressure the Inbal Valve opens instantaneously, yet very smoothly, to prevent any water hammer in the piping system. The Inbal 700D performance and ease of resetting are not affected by vertical or horizontal installation.The Inbal Automatic Water Control

    Valve utilizes the unique N.M.M.P. (No Moving Mechanical Parts) design. The only moving part when the Inbal Valve operates, is the reinforced sleeve which forms a drip-tight seal with the corrosion resistant core. The Inbal design also prevents false operation due to transient surges in water supply pressure. The N.M.M.P. design and variety of mater- ials and coatings make the Inbal Auto-matic Water Control Valve ideally suitable for use with brackish or sea water similar to those found in chemical and petrochemical facilities or in offshore platforms. It can also be used as a foam concentrate control valve in foam/water systems.The Inbal Automatic Water Control Valve series 700D is available in sizes 1" (40 mm) to 12" (300 mm). The valves have threaded, flanged, or wafer inlet and outlet ends.

    Technical Data

    ApprovalsThe Inbal Automatic Water Control Valve is FM approved to 300 psi (21 bar) in sizes 3", 4", 6", and 8" (80, 100, 150, and 200 mm). Consult the FM Approval Guide for acceptable applications.Inbal Deluge Valves have Lloyd's, DNV, and ABS Type Approvals for all sizes and most models.

    Model NumbersInlet End Outlet End Model No.Threaded Threaded 711D Flanged Flanged 733DWafer Wafer 799D

    SizesThreaded End:1", 2", 2", & 3"(40, 50, 65, & 80 mm). Flanged End:2", 2", 3", 4", 6", 8", 10", & 12" (50, 65, 80, 100, 150, 200, 250, & 300 mm).Wafer End:3", 4", 6", 8", 10", & 12" (80, 100, 150, 200, 250, & 300 mm).

    End StandardsThreaded End:NPT or BSPT. Flanged End: ANSI B16.5 class 150 & 300 ;ISO 7005 - PN10, 16 & 25 ;*BS 10 Table D & E ;**AS 2129 Table D & E ;**Jis B 2212, 2213, 2214 ;**Wafer End:Fits all above standards.** * Compatible with DIN 2501 and BS 4504.** Exclude: BS 10 Table E 6" (150 mm); AS 2129 Table E 6" (150 mm); Jis B2212 regular flange in sizes 4", 8", &12" (100, 200, & 300 mm).

    Pressure RatingMaximum working pressure*: 300 psi (21 bar). Minimum Working Pressure: 20 psi (1.5 bar). * Standard material valve.

  • F02-01-01-002

    Full open operationWhen pressure in the Control Chamber is relieved to the atmosphere, the Inbal Valve opens wide. The sleeve assembly is safely enveloped by the housing.

    Tight closing operationWhen pressure from the valve inlet (or an equivalent independent operating pressure) is applied to the Control Chamber, the Inbal Valve closes drip tight. The fabric sleeve safely envelopes the resilient sleeve giving full support.

    Modulating actionA stable throttling position is obtained when a quantity of pressurized fluid is held in the Control Chamber. It is the amount of fluid in the Control Chamber that determines the position of the sleeve assembly. The Control Chamber can be alternately filled or exhausted to achieve the desired operating condition.

    Figure (1) Figure (2) Figure (3)

    Temperature Rangeo oWater: Max. +150 F (+65 C).

    Installation PositionVertical or horizontal.

    MaterialsStandardValve Housing:Carbon Steel (SAE 1021).Valve Ends: Ductile Iron (ASTM A536 65-45-12).Sleeve:SMR5 Elastomer reinforced with Poly- ester and Kevlar.OptionalCast Steel ;Bronze ;Nickel Aluminium Bronze ;Stainless Steel AISI 316 ;Super Austenitic Stainless Steel ;Super Duplex Stainless Steel ;Titanium.

    CoatingStandardPowder epoxy coated. Thickness: 0.004" (0.1 mm) external and internal surfaces.OptionalHigh built epoxy coated and polyure- thane finish. Thickness: 0.01" (0.3 mm).

    Halar coated. Thickness: 0.02" (0.5 mm).Halar is a registered trade mark of Ausimont USA Inc.

    Features

    ! The Inbal Valve, designed for control valve service from basic concepts, utilizes a built-in sleeve actuator.! No Moving Mechanical Parts

    (N.M.M.P.) construction ensures a long life of dependable operation, reducing the cost of maintenance.! The N.M.M.P. Design assures

    frictionless operation. No sticking after staying for prolonged periods in a closed position. Suitable for brackish and sea water.! Quick, yet soft opening performance -

    eliminates water hammer and conse-quent damage.! The line pressure or an equivalent

    independent operating pressure, is sufficient to close the Inbal Valve tightly.! Soft closure performance due to

    inherent characteristics of the Inbal Valve. Utilizes no spring to ensure surge-free closing.! Pressure rating of 300 psi (21 bar) for

    standard materials valve due to rigid construction.! Suitable for vertical or horizontal

    installation with no effect on Inbal Valve performance.! Lightweight - easy to be installed and

    maintained.

    ! Available with threaded, flanged, and wafer ends to various standards.! Unique principle of operation prevents

    false operations due to water surges.!Wide range of sizes for an ideal system

    design.! Compact design - minimum space for

    valve and trim. Enable installation in confined spaces.! Epoxy coating supplied as standard-

    ensures excellent corrosion resistance.! Variety of available materials - to

    ensure corrosion-free service even under severe conditions.! Compatible with electric, pneumatic,

    and/or hydraulic release.! Excellent regulating performance in a

    wide range of flows and line pressures.!Wide selection of pilot valves,

    actuators, and accessories to design the ideal control valve for the purpose.! A single Inbal Automatic Water

    Control Valve can perform multi-function controls.! Every single valve is hydraulically

    tested in real flow and pressure conditions.! Innovative design with a long record of

    proven performance.

  • Operation

    The Control Chamber of the Inbal Automatic Water Control Valve is the annular space between the valve Housing and the Sleeve. The valve is held in a closed position as long as inlet pressure is maintained in the Control Chamber. In the set position, the water pressure is transmitted from the upstream through the valve trim to the Control Chamber, and the Inbal Valve stays closed. Actuation of the valve by a manual, hydraulic, pneumatic, or electric release system allows venting of the pressure in the Inbal Valve Control Chamber, and the valve opens wide, permitting a flow of water to the piping system. When a pressure or flow control is added, the Control Chamber is monitored to modulate a preset delivery pressure, maximum inlet pressure, or flow rate.The principle of operation is illustrated in Figures (1) through (3). The nominal pressure losses are shown in Graph (1).

    Installation

    Refer to the Trim Chart applicable to the specific Inbal Valve model in use. 1. When the Inbal Valve is delivered,

    carefully unpack and visually check that there has been no damage to the operating components, piping, and fittings.

    2. The Inbal Valve must be installed in an area not subject to freezing conditions.

    3. Always flush the pipelines before installing the valve.

    4. Place the Inbal Valve in the piping in the outlet of the Water Supply Valve. Verify that the arrow on the valve housing matches the actual flow direction. The Inbal Valve may be installed in any position. Determine which side the valve will be accessed from and locate all the components accordingly.

    5. Install the Inbal Valve in the piping system. Refer also to the applicable Installation Guide.Threaded End Valve - connect the female threaded ends of the Inbal Valve to the male threads of the piping. Use the pipe joint compound sparingly on the male threads only.Flanged End Valve - connect with bolts and nuts, the valve flanges to the existing flanges in the piping system, using gaskets in between. Complete bolting with uniform tightening.

    0

    0

    0

    0

    0

    Wafer End Valve - Install the Inbal Valve between the piping flanges. Place gaskets between the valve ends and the pipe flanges. Insert four of

    othe stud bolts, 90 apart around the valve, through the bolt sleeves and the pipe's flanges, and tighten with nuts. Complete bolting with uniform tightening.

    6. Complete the trim assembly by connecting the preassembled sections, or assemble the trim if ordered in loose component form. Refer to the applicable Trim Chart and Installation Guide.

    7. The pressure supply to the trim must always be sourced from either inlet of Water Supply Valve or Inbal Valve upstream, through a " pipe.

    8. Exhaust tube must be free of any back pressure. Provide an air gap between the exhaust tube and drain facility.

    9. Set the Inbal Valve by following the applicable Resetting procedure.

    10. Test the Inbal Valve, the trim, and alarms according to the applicable Testing procedure.

    ResettingThe Inbal Automatic Water Control Valve system must be reset and restored to service as soon as possible after automatic, emergency, or manual actuation. Refer to the relevant bulletin for detailed procedure.

    0

    0

    0

    0

    F02-01-01-003

    Core

    Sleeve Assembly

    Housing

    End

  • Mil Ltd. 17 Moshe Beker Street, P.O.Box 15200, Rishon Lezion 75051, Israel. Tel: +972 3 966 4350, Fax: +972 3 966 4320, E-mail: inbalvl@ attglobal.netMarch 2000 / F02-01-01

    Automatic Water Control Valve Series 700D

    Flow Chart

    Graph (1)Flow Rate

    4 5 6 7 10 20 30 40 50 75 100 200 300 500 1000150 2000 3000

    2 3 4 5 10 15 20 30 40 50 100 150 200 300 500 700

    20 30 40 50 100 200 1000 2000 3000 5000 10000300 500

    6"4"3"2"1 12"300

    10"250

    8"200150100805040

    inch

    mm

    l/s

    gpm

    3m /h

    bar

    0.10.98

    0.2

    0.3

    0.40.5

    3

    1 0.1

    0.01

    0.02

    0.03

    0.040.05

    1.5

    2

    2

    3

    45

    10

    10

    15

    20

    30

    40

    50

    100

    54

    0.15

    0.2

    0.3

    0.40.5

    11

    psi

    0.14

    0.3

    0.4

    0.2

    0.5

    1

    KPa m H O2Inbal Valve Size

    Hea

    d Lo

    ss

    15

    10

    3

    1.5

    2

    54

    Valve Size Flow Factor mm inch Kv Cv 40 1'' 60 70 50 2'' 90 105 80 3'' 140 162 100 4'' 330 383 150 6'' 610 708 200 8'' 1150 1334 250 10'' 1630 1891 300 12'' 2365 2743

    Flow Factor

    Q = Flow rate in 3 m / h.

    Kv = Flow factor. Use Table (1)

    QKv ( )

    2DP =

    DP = Head loss i n b ar.

    Table (1)

    Table (2)

    Valve Size Displacement U.S.

    mm inch liter gallon

    40 1" 0.3 0.08 50 2" 0.3 0.08 80 3" 0.3 0.08 100 4" 0.5 0.13 150 6" 1.7 0.45 200 8" 3.5 0.92 250 10" 8.1 2.1 300 12" 12.7 3.4

    Control Chamber Displacement

    To define the head loss through an Inbal valve at a specific flow rate use the following equation (for water only):

    The Flow Factor Cv (Kv) is defined as 3the flow rate in gpm (m /h) of liquid at

    0 068 F (20 c), flowing at 1 psi (1bar) head loss.

    Q = Flow rate in gpm.

    Cv = Flow factor.

    QCv ( )

    2DP =

    DP = Head loss i n psi.

    Trim Testing and/or Control Testing, as well as a Quarterly Testing as listed in the applicable data sheet of the specific application in which the Inbal Auto-matic Water Control Valve participates.An Annual Testing shall include Trip Testing, Semi-Annual Testing, and Quarterly Testing as listed in the appli- cable data sheet of the specific appli- cation in which the Inbal Automatic Water Control Valve participates.

    RemovalTo remove the Inbal Valve:1.Close all the pressure supply valves:

    a) Water Supply Valveb) Trim Shutoff Valve.

    2.Open the Emergency Release Valve to release the water pressure from the Inbal Valve Control Chamber.

    3.Open the drain valves to allow all the water to drain.

    4.Remove the trim from the Inbal Valve.5.Remove the Inbal Valve from the line

    for inspection.6.To reinstall, follow the Installation

    procedure section (use new gaskets for flanged or wafer valve).

    Inquiries/OrdersThe Data Sheet For Inquiries/Orders (bulletin F01-05-01) should be submitted.

    Maintenance, Inspection,& Testing

    It is recommended that periodic inspections and tests be conducted by qualified personnel to ensure that the Inbal Automatic Water Control Valve and related equipment are in good operating condition. The inspection and testing activities should be done according to NFPA Standards, the guidelines and regulations of the authorities having jurisdiction, and the following instructions. It is recom- mended that the Inbal Valve be tested, operated, cleaned, and inspected on a routine basis.A Weekly Visual Inspection shall include Water Supply Valve position, free pressure access, and major trim compo-nents as listed in the applicable data sheet of the specific application in which the Inbal Automatic Water Control Valve participates.A Quarterly Testing shall include Alarm Testing, Strainer Cleaning, and major components testing as listed in the applicable data sheet of the specific application in which the Inbal Auto- matic Water Control Valve participates.A Semi-Annual Testing shall include

  • Model 711D

    Model 733D

    Model 799D

    * Refe r t o Standar d Materia l Valve.

    "

    L

    A

    " (TYPx2)

    * Refer to Standard Material Valve. ** Refer to flange standard ANSI B16 150.

    * Refer to Standard Materia l Valve.

    SIZE A L Weight*1 "

    40 mm

    2" 50 mm

    2 " 65 mm

    3" 80 mm

    93

    93

    93

    93

    195

    195

    195

    8"203

    188

    lbs

    kg

    8 kg

    lbs18

    8 kglbs18

    7.5

    16.5kg

    lbs

    53 "8/

    53 "8/

    53 "8/

    53 "8/

    57 "8/

    57 "8/

    57 "8/

    300 mm12"

    200 mm

    250 mm10"

    8" 150 mm

    48319"

    447

    30834316"406 363

    13 "279 246

    3"

    6"

    100 mm

    80 mm4"

    SIZE

    7 "

    9 "

    7 "9"

    11"229 190

    191 161

    D** L

    171178 65 mm

    50 mm2 "

    2"

    7" 6 "

    114250

    52

    88

    193

    114

    32

    29

    70

    17

    1337

    Weight*

    13

    291226

    lbskg

    kg

    lbskg

    lbs

    kg

    lbs

    kglbs

    kglbs

    kg

    kg

    lbs

    lbs6 "

    165

    6 "171

    517 "8/

    314 "8/

    36 "8/

    112 "8/

    Weight*

    150 mm

    200 mm8"

    100 mm6"

    3" 80 mm

    4"

    SIZE D L

    kglbskg

    lbs

    kg

    lbskg

    lbs

    300 mm

    250 mm12"

    10"

    kg

    lbs

    kglbs

    130

    160

    6 "

    218

    27310 "

    32412 "

    381

    1576 "

    186

    238

    302

    35013 "

    44317 "

    6

    13

    920

    2146

    35.578

    53.5117

    81

    178

    58 "8/

    37 "8/

    39 "8/

    711 "8/

    15 "8/

    L

    "

    D

    " (TYPx2)

    "

    L

    D

    " (TYPx2)

    15"

    Series 700DOverall Dimensions & Weights