indea stoomcursus

75
FATALE STOOMCURSUS WILLY SOMERS INDEA

Upload: valerie-de-groote

Post on 27-Jul-2015

2.668 views

Category:

Technology


11 download

TRANSCRIPT

Page 1: Indea stoomcursus

FATALE STOOMCURSUS

WILLY SOMERS

INDEA

Page 2: Indea stoomcursus

FATALE STOOMCURSUS

DE OMGEKEERDE DENKWIJZE:

• STEEDS VERTREKKEN VAN PROCESANALYSE/BEHOEFTE: IS

ER ABSOLUUT (FATAAL) STOOM NODIG OM TE VOLDOEN AAN

DE WARMTEBEHOEFTE? KAN AAN DE WARMTEBEHOEFTE

VOLDAAN WORDEN MET RECUPERATIEWARMTE, MET EEN

ENERGETISCH BETERE EN GOEDKOPERE VOORZIENING?

• KAN VOOR DE FATALE STOOMBEHOEFTE BEROEP GEDAAN

WORDEN OP AFVALWARMTE? ROOKGASSEN VAN EEN GAS-

OF DIESELMOTOR (STOOMPRODUCTIE TOT 25 BAR EN 340°C

IS MOGELIJK). DAMPRECOMPRESSIE? EVAPORATIVE

COOLING OP EEN OVEN?

Page 3: Indea stoomcursus

BOEK “HET KETELHUIS”

Page 4: Indea stoomcursus

INHOUD FATALE STOOMCURSUS

• DENKEN IN FATALE STOOM: EENHEDEN, WAT IS STOOM, WAAROM STOOM, VUISTREGELS

• HET KETELHUIS: APPARATUUR

• ENERGIE- EN MASSABALANS MET BBT MAATREGELEN EN EUROPESE NORMEN RENDEMENT

• WETGEVING: BBT, ENERGIEPLAN, ENERGIESTUDIE, RENDEMENT

Page 5: Indea stoomcursus

WAT IS CENTRALE WARMTEPRODUCTIE?

• 1. Opwarmen van een fluidum: water, stoom, thermisch olie

• tot gewenste temperatuur in een ketelhuis

• 2. Transport van heet fluidum naar warmtetoepassing

• 3. Geheel of gedeeltelijke terugvoer van het fluidum naar het ketelhuis

Page 6: Indea stoomcursus

WARMTEVOERENDE FLUIDA

• WARMWATER: GESLOTEN SYSTEEM TOT 100°C

• OVERVERHIT WATER: GESLOTEN SYSTEEM ONDER DRUK TOT 15

BAR TOT 180°C

• THERMISCHE OLIE: GESLOTEN SYSTEEM MET LAGE DRUK 2 BAR

EN HOGE TEMPERATUREN TOT 350°C

• STOOM: VERZADIGDE OF OVERVERHITTE STOOM TOT 40 BAR

Page 7: Indea stoomcursus

WAT IS STOOM?

• VOORBEELD: DE FLUITKETEL

• NATTE VERZADIGDE STOOM

• DROGE VERZADIGDE STOOM

• OVERVERHITTE STOOM

Page 8: Indea stoomcursus

WAAROM STOOM?

• WARMTEUITWISSELINGSCOËFFICIENT MET DROGE

VERZADIGDE STOOM IS MAXIMAAL: 10 À 100 KW/M²°C

• DE WARMTEUITWISSELING GEBEURT BIJ CONSTANTE

TEMPERATUUR

• OVERVERHITTE STOOM WORDT GEBRUIKT VOOR

AANDRIJVEN VAN STOOMTURBINES

Page 9: Indea stoomcursus

THERMODYNAMISCHE EIGENSCHAPPEN

VAN VERZADIGDE STOOM

• VOELBARE WARMTE: OM WATER BIJ

EEN BEPAALDE DRUK OP KOOKTEMPERATUUR

TE BRENGEN

• VERDAMPINGSWARMTE OM BIJ CONSTANTE TEMPERATUUR VAN

DE VLOEISTOFFASE NAAR DE VERZADIGDE DAMPFASE OVER TE

GAAN

• DRUK EN TEMPERATUUR VAN VERZADIGDE STOOM ZIJN AAN

ELKAAR VERBONDEN: EEN ÉÉNVOUDIGDE DRUKREGELING

REGELT OOK EXACT DE TEMPERATUUR.

Page 10: Indea stoomcursus

ENKELE BELANGRIJKE VASTSTELLINGEN

• TEMPERATUUR VAN VERZADIGDE STOOM NEEMT TOE ALS DE

DRUK STIJGT.

• DE TOTALE WARMTEINHOUD VAN DE STOOM VERANDERT

WEINIG MET TOENAME VAN DE TEMPERATUUR (EN DUS OOK

TOENAME VAN DE DRUK).

• DE VERDAMPINGSWARMTE DAALT NAARMATE DE VOELBARE

WARMTE STIJGT.

• VERMITS ENKEL DE VERDAMPINGSWARMTE WORDT BENUT

BIJ DE WARMTEGEBRUIKER MOET BIJ ZO LAAG MOGELIJKE

DRUK STOOM GEPRODUCEERD EN GETRANSPORTEERD

WORDEN OM ZOVEEL MOGELIJK WARMTE TE BENUTTEN.

Page 11: Indea stoomcursus

DE STOOMTABEL PG 332

Page 13: Indea stoomcursus

STILLE GETUIGEN

Page 14: Indea stoomcursus

DENKEN IN FATALE STOOM

• EENHEDEN

- ENERGIEFACTUREN OMREKENEN NAAR

PRIMAIRE ENERGIE

- 1 KWH = 3600 KJ

- WAT IS EEN PJP EN TJP?

- GASMETER BM³ NAAR NM³ (PG 324)

• VUISTREGELS

- PG 328 BOEK “KETELHUIS”

- VUISTREGEL TEMPERATUUR

VERZADIGDE STOOM UIT STOOMDRUK

- DE AARDGASPRIJS OP UW FACTUUR

PER MWH IS DE ENERGIEPRIJS VOOR

1 TON STOOM.

- VERLAGEN 02 BRANDER MET 2% IS 1

% BETER RENDEMENT

- ROOKGASTEMPERATUUR VERLAGEN

MET 20°C IS 1% BETER RENDEMENT

Page 15: Indea stoomcursus

GRIEKSE LES: WAT IS EEN TJ, PJPRIMAIR?

ALLE ENERGIEVECTOREN OMREKENEN NAAR CO2! •Vergrotende voorvoegsels

•voorvoegsel

•symbool

•factor

•yotta

•Y

•1024

•zetta

•Z

•1021

•exa

•E

•1018

•peta

•P

•1015

•tera

•T

•1012

•giga

•G

•109

•mega

•M

•106

•kilo

•k

•103

•hecto

•h

•102

•deca

•da

•101

•Verkleinende voorvoegsels

•voorvoegsel

•symbool

•factor

•deci

•d

•10-1

•centi

•c

•10-2

•milli

•m

•10-3

•micro

•µ

•10-6

•nano

•n

•10-9

•pico

•p

•10-12

•femto

•f

•10-15

•atto

•a

•10-18

•zepto

•z

•10-21

•yocto

•y

•10-24

Page 16: Indea stoomcursus

WAT BETEKENEN NU DIE TJ EN PJ?

• 0,1 PJ

= 0,1 / 3600 PWH

= 27.800 MWH

• 10 TJ

= 10 / 3600 TWH

= 2.778 MWH

• CIJFERS WETGEVING: PRIMAIRE ENERGIEVERBRUIKEN!

• ELEKTRICITEITSVERBRUIK OMREKENEN: /0,4

Page 17: Indea stoomcursus

INHOUD FATALE STOOMCURSUS

• DENKEN IN FATALE STOOM: EENHEDEN, WAT IS STOOM, WAAROM STOOM, VUISTREGELS

• HET KETELHUIS: APPARATUUR

• ENERGIE- EN MASSABALANS MET BBT MAATREGELEN EN EUROPESE NORMEN RENDEMENT

• WETGEVING: BBT, ENERGIEPLAN, ENERGIESTUDIE, RENDEMENT

Page 18: Indea stoomcursus

HET VOLLEDIGE STOOMNET

Page 19: Indea stoomcursus

HET KETELHUIS

Page 20: Indea stoomcursus

KETELHUISAPPARATUUR

• STOOMKETEL OF RECUPERATIEKETEL

• BRANDER EN BRANDSTOFFEN

• VOEDINGSWATERPOMP

• KETELSPUI

• ONTGASSER OF VOEDINGSWATERTANK? MET NAKOELER?

• ONTHARDER OF DEMIN?

• ECONOMISER

• LUVO

• ROOKGASCONDENSOR

• CONDENSAAT/SPUI FLASHSTOOM

• LEIDINGDIAMETER STOOM EN CONDENSAAT BEREKENEN

Page 21: Indea stoomcursus

STOOMKETEL OF RECUPERATIEKETEL

• PROCESANALYSE MAKEN VOOR BENUTTEN AFVALWARMTE

• DAMPRECOMPRESSIE

• SOORTEN STOOMKETELS EN RECUPERATIEKETELS

Page 22: Indea stoomcursus

KETELRENDEMENT FUNCTIE VAN WERKDRUK

•Ketelrendement:

- rookgasverliezen

- stralings- convectieverlies

- spuiverlies

•Ketelrendement functie van:

•- werkdruk

- ketelbelasting

Page 23: Indea stoomcursus

INPUT OUTPUT RENDEMENT STOOMKETEL

Page 24: Indea stoomcursus

BRANDER EN BRANDSTOFFEN

• VENTILATORBRANDERS MET FREQUENTIEREGELING

• LUCHTVOORVERWARMING BIJ MONOBLOC EN DUOBLOC

• CALORISCHE ONDERWAARDE EN BOVENWAARDE

• AARDGAS

• GASOLIE

• ANDERE BRANDSTOFFEN

Page 25: Indea stoomcursus

VENTILATORBRANDER LOW NOX

•Low NOx aardgasbranders •Low NOx gasoliebranders

Page 26: Indea stoomcursus

CALORISCHE ONDERWAARDE EN BOVENWAARDE

• HET CALORISCH VERMOGEN IS DE HOEVEELHEID WARMTE DIE VRIJKOMT BIJ

DE VOLLEDIGE VERBRANDING VAN EEN VOLUME-EENHEID BRANDSTOF.

• HET CALORISCH VERMOGEN WORDT ONDERWAARDE GENOEMD WANNEER

DE GEVORMDE HOEVEELHEID WATER IN DE DAMPFASE BLIJFT EN MET DE

ROOKGASSEN WORDT AFGEVOERD. IN BELGIË WORDT RENDEMENT

UITGEDRUKT MET DE CALORISCHE ONDERWAARDE ALS REFERENTIE:

DAAROM RENDEMENTEN HOGER DAN 100% BIJ CONDENSATIEKETELS.

• HET CALORISCH VERMOGEN WORDT BOVENWAARDE GENOEMD WANNEER

DE GEVORMDE WATERDAMP CONDENSEERT TOT WATER EN DE AFGESTANE

WARMTE WORDT BENUT.

• VOOR AARDGAS IS DE “VERPLICHTE” EUROPESE OMREKENINGSFACTOR

0,903 (11%)

Page 27: Indea stoomcursus

GASOLIELEVERING:TEMPERATUURSCORRECTIE

! Relatieve dichtheid

Basiscorrectie voor 1°C meer of minder

van 0,600 tot 0,700 0,00090

van 0,700 tot 0,800 0,00080

van 0,800 tot 0,840 0,00075

van 0,840 tot 0,880 0,00070

van 0,880 tot 0,920 0,00065

van 0,920 tot 1,000 0,00060

Page 28: Indea stoomcursus

BRANDSTOFTABEL

Page 29: Indea stoomcursus

VOEDINGSWATERPOMP

• BEREKENING OPGENOMEN VERMOGEN: VUISTREGEL PG 329.

SPIRAALKETELS HEBBEN EEN VEEL HOGER OPGENOMEN

VERMOGEN DOOR DE GROTE WATERZIJDIGE WEERSTAND

VAN DE SPIRAAL.

• FREQUENTIESTURING

Page 30: Indea stoomcursus

OPGENOMEN VERMOGEN VOEDINGSWATERPOMP

VUISTREGEL:

DELTA P(BAR) X Q (M³/H)

X 2,72/Η

Page 31: Indea stoomcursus

WAAROM SPUIEN? PG 173

• DROGE STOOM BEVAT GEEN OPGELOSTE ZOUTEN. DAAROM

GAAN DE ZOUTEN DIE ZICH IN HET SUPPLETIEWATER

BEVINDEN ZICH CONCENTREREN IN HET KETELWATER EN

SLIB VORMEN.

• DIT SLIB IS ZEER NADELIG VOOR DE WARMTEOVERDRACHT IN

DE KETEL. BIJ VORMING VAN KETELSTEEN STOKEN WIJ DE

KETEL KAPOT!

• DAAROM IS ER EEN BODEMSPUI VOORZIEN OM DIT SLIB WEG

TE SPUIEN UIT DE KETEL.

• TE HOGE ZOUTBELASTING IN DE KETEL VEROORZAAKT NATTE

STOOM MET SLECHTE WARMTEOVERDRACHT EN CORROSIE IN

STOOMNET TOT GEVOLG.

Page 32: Indea stoomcursus

KETELSPUI

• SPUI OP GELEIDBAARHEID: ALS SPUIWARMTE NIET WORDT

BENUT KAN TOT 5% VAN DE BRANDSTOFENERGIE NAAR

RIOOL AFGEVOERD WORDEN.

• AUTOMATISCHE BODEMSPUI

• ER IS GEEN SPUI BIJ GESLOTEN SYSTEMEN EN ER IS

NAUWELIJKS SPUI BIJ OSMOSE.

stoomproductie 10.000 kg/h

% retourcondensaat 30 %

retourcondensaat 3.000 kg/h

suppletie 7.093 kg/h

spuiberekening:

stoomkwaliteit 99,50 %

% vocht in stoom 0,50 %

max. geleidbaarheid ketel 2 mS/cm

geleidbaarheid suppletie 40 µS/cm

geleidbaarheid na osmose 40 µS/cm

spui is: 93 kg/h

Page 33: Indea stoomcursus

ONTGASSER OF VOEDINGSWATERTANK

• WANNEER EEN THERMISCHE ONTGASSER?

• HALFGESLOTEN SYSTEEM MET CONDENSAATDRUKTANK EN

DIRECTE TERUGVOER NAAR DE STOOMKETEL?

• WANNEER EEN VOEDINGSWATERTANK?

• APARTE CONDENSAATTANK?

Page 34: Indea stoomcursus

ONTHARDER OF DEMIN?

• ONTHARDER MET IONENWISSELAAR

• DEMIN MET KATION EN ANION IONENWISSELAAR

• OMGEKEERDE OSMOSE

Page 35: Indea stoomcursus

WATERBEHANDELING

• AANPASSEN VAN DE WATERKWALITEIT MET CHEMICALIËN

VOOR VERMIJDEN VAN KALKAANSLAG EN CORROSIE.

Page 36: Indea stoomcursus

ECONOMISER

• ALTIJD TE VOORZIEN?

• RENDEMENTSBEREKENING

• MODULERENDE WATERREGELING

• BYPASS NOODZAKELIJK?

Page 37: Indea stoomcursus

STOOMKETEL MET ECONOMISER

Page 38: Indea stoomcursus

RENDEMENT KETEL EN ECO FUNCTIE VAN

WERKDRUK

• RENDEMENT STOOMKETEL MET ECO:

– FUNCTIE VAN WERKDRUK

– FUNCTIE VAN DE BELASTING

– FUNCTIE VAN DE

VOEDINGSWATERTEMPERATUUR

• BEOORDELING EFFICIËNCY VAN ECO:

– OP PINCH ROOKGAS T°-

VOEDINGSWATER T°

Page 39: Indea stoomcursus

LUVO

• VOORVERWARMEN VERBRANDINGSLUCHT ENKEL BIJ

NIEUWBOUW?

- 40°C BIJ MONOBLOK BRANDER

- 200°C BIJ DUOBLOKBRANDER

• RENDEMENTSBEPALING

Page 40: Indea stoomcursus

ROOKGASCONDENSOR

• GELIJKTIJDIGHEID NOODZAKELIJK OF ANDERE KOUDE

BRONNEN?

• RENDEMENTSBEREKENING

• HERWINNEN CONDENSAAT UIT CONDENSOR?

Page 41: Indea stoomcursus

HERWINNEN WATER UIT CONDENSOR?

330 kJ

680 kJ

153 kJ

0,88 %

1,82 %

0,41 %

40724 kJ

41343 kJ

41888 kJ41888 kJ

545 kJ

112,12 %

110,66 %

1,46 %

112,12 % tot OUTtot IN

Gas(CBW) 1164 kJ 3,12 %

Nuttige warmte

Trookgas = 25 °C

H (Ekofisk 99)

Condensaat = 1,465 kg

Waterdamp

0,267 kg

0,32 m³(n)

ENTHALPIE BILAN MET CONDENSATIE

Enthalpie [kJ] [%COW]

1 m³(n)

Tdauwpt = 57,3 °C

Vochtige lucht (7.2gH2O/kg lucht)

Luchtovermaat = 10 %

11,04 m³(n)

20 °C

RENDEMENT

[%COW]

Gas(COW) = 37360 kJ

109,00 %

Droge rookgassen

9,94 m³(n)

O2 = 2,09%

CO2 = 10,83%

•10% suppletiewater kan ingevuld worden met condens

Page 42: Indea stoomcursus

WARMTERECUPERATIE OP ROOKGASSEN

Page 43: Indea stoomcursus

WARMTERECUPERATIE OP ROOKGASSEN

Page 44: Indea stoomcursus

ROOKGASCONDENSOR VOOR PROCES

WARMWATER

Page 45: Indea stoomcursus

FENOMEEN FLASHSTOOM

• BEREKENING FLASHSTOOM UIT SPUI OF CONDENSAAT

• VUISTREGEL PG 328: DELTA TEMPERATUUR VOOR EN NA

CONDENSPOT *0,2 = % FLASH

• FLASH OP SPUIWATER

• FLASH CONDENSAAT

Page 46: Indea stoomcursus

FLASHSTOOM UIT SPUI

Page 47: Indea stoomcursus

FLASH STOOM EN RESTWARMTE UIT SPUI

Page 48: Indea stoomcursus

FLASHSTOOM UIT CONDENSAAT

Page 49: Indea stoomcursus

LEIDINGDIAMETER STOOM EN CONDENSAAT • TABEL MET SNELHEDEN IN LEIDINGEN

• STEEDS BEREKENEN OP VOLUME M³!

• VUISTREGEL DIAMETER

CONDENSAATLEIDING IS GROTER DAN

STOOMLEIDING

Medium Functie Snelheid in m/sec

Stoom tot 3 bar 10 -15

Stoom 3 - 10 bar 15 - 20

Stoom 10 - 40 bar 20 - 40

Condensaatleiding

verdronken * 2

ontspanningsstoom ** 6 - 10

Voedingswater zuigleiding *** 0,5 - 1

persleiding 2

Water drinkwater 0,6

koelwater 2

Lucht perslucht 6 - 10

Page 50: Indea stoomcursus

SCHOORSTEEN Berekening schoorsteenhoogte

Berekening schoorsteendiameter

Bepalen van meetpunt

Afvoer condensaat

Materiaalkeuze

Page 51: Indea stoomcursus

CONDENSAAT KWALITEITSCONTROLE

Page 52: Indea stoomcursus

INHOUD FATALE STOOMCURSUS

• DENKEN IN FATALE STOOM: EENHEDEN, WAT IS STOOM, WAAROM STOOM, VUISTREGELS

• HET KETELHUIS: APPARATUUR

• ENERGIE- EN MASSABALANS MET BBT MAATREGELEN EN EUROPESE NORMEN RENDEMENT

• WETGEVING: BBT, ENERGIEPLAN, ENERGIESTUDIE, RENDEMENT

Page 53: Indea stoomcursus

ENERGIEBALANS STOOM

• VOLLEDIG STOOM/CONDENSAATSYSTEEM BEKIJKEN VANUIT

DE PROCESBEHOEFTE!

• BEST BESCHIKBARE TECHNOLOGIE

• EUROPESE NORM RENDEMENT 12953-11

• REKENMODELLEN KETELHUIS

• REKENMODEL VANUIT PROCESANALYSE

• METINGEN EN MEETAPPARATUUR

Page 54: Indea stoomcursus

STOOMBALANS EN RENDEMENT Beschikbare gegevens

gegevens stoomketel:

ketelvermogen: kW

verwarmd oppervlak m²

stoomdruk bar

brandervermogen kW

brandstof aardgas

brandermodulatie 1/5

Gemeten gegevens

water:

geleidbaarheid suppletiewater µS/cm

geleidbaarheid voedingswater µS/cm

geleidbaarheid condensaat µS/cm

hoeveelheid suppletiewater m³/h

brandstof:

brandstofverbruik Nm³/h

gasdruk voor de meter mbar

gastemperatuur voor de meter °C

verbrandingswaarde brandstof CBW (factuur) kWh/Nm³

verbrandingswaarde brandstof COW kWh/Nm³

rookgassen:

rookgastemperatuur bij verschillende belastingen 230 °C

CO2 9,2

O2

temperatuur van aangezogen verbandingslucht 20 °C

schoorsteenverlies (formule van Siegert): 10,5 %

rendement op rookgasverlies (Siegert): 89,5 %

rendement op rookgasverlies: euronorm 12953-11 88,9 %

Page 55: Indea stoomcursus

ENERGIEBALANS STOOM/CONDENSAAT

%

70% suppletie 60 °C

251,2 kJ/kg 9,0%

30% condensaat 100 °C

atmosferisch 418,6 kJ/kg 15,1%

voedingswater 72 °C voedingswater 97 °C

301,4 kJ/kg 10,8% 407 kJ/kg

brander

stoom 10 bar(g)

2779,7 kJ/kg 100,0%

verbruiker 184,07 °C

1998,6 kJ/kg 71,9%

condensaat

onder druk 781,1 kJ/kg 28,1%

revaporisatie 314,0 kJ/kg 11,3%

stoomdruk 0,5 bar(g)

condensaat 467,1 kJ/kg 16,8%

bij tegendruk 111,37 °C

Geen FLASH

Page 56: Indea stoomcursus

VOLLEDIGE BALANS VANUIT PROCESANALYSE

• KOSTPRIJS 1 TON STOOM= PRIJS AARDGASFACTUUR PER MWH

• KOSTPRIJS VAN 1M³ CONDENSAAT: € 8/M³

condensaat kost per m³

brandstof kost: 25 €/MWh

waterkost 1 €/m³

geleidbaarheid water 438 microS/cm

geleidbaarheid ketelwater 2.500 microS/cm

kost waterbehandeling: €/m³

ontharding: 0,2 €/m³

chemicaliën: 0,48 €/m³

ketelrendement (op COW) 90 %

keteldruk 7 bar

temperatuur condensaat 168 °C

kostprijs condensaat 8,1 €/m³

productie van 1 m³ warm water met een temperatuur van: 90 °C

koud water mengen met condensaat: 4,59 €/m³

met stoomwarmtewisselaar: 3,87 €/m³

rendement warmwaterketel 95,00 %

met warmwaterketel: 3,45 €/m³

Page 57: Indea stoomcursus

STOOMLEK, FLASHSTOOM: ZICHTBAAR!

0

100

200

300

400

500

600

700

1 2 3 4 5 6 7 8 10 12 14

stoomdruk bar(g)

kg

sto

om

/ u

ur

lek 3 mm lek 5 mm

lek 6,4 mm lek 7,5 mm

lek 10 mm lek 12,5 mm

Stoomlekken onmiddellijk herstellen

Page 58: Indea stoomcursus

ISOLATIE KETEL, TANKS, LEIDINGEN,

APPENDAGES DN Isolatiedikte mm €/meter €/afsluiter

40 40 45 140

50 60 65 160

80 60 75 180

100 80 90 210

150 80 105 240

200 100 140 300

Richtprijs isolatie leidingen en afsluiters 2007

Page 59: Indea stoomcursus

EUROPESE NORM RENDEMENT

• EUROPESE NORM IS FINAL DRAFT

• LIJST EN BESTELLEN: ZIE WWW.NBN.BE

• PREN 12953-11 VOOR VLAMPIJPKETELS

• PREN 12953-15 VOOR WATERPIJPKETELS

Page 60: Indea stoomcursus

REKENMODELLEN KETELHUIS

• BEREKENING ROOKGASVERLIEZEN MET ROOKGASANALYSER

EN REKENMODULE

• MASSABALANS OP BASIS VAN WATERMETER(S) EN

IONENBALANS (GELEIDBAARHEID OF BETER

CHLORIDEGEHALTE)

• ENERGIEBALANS OP BASIS MASSABALANS EN

BRANDSTOFMETER.

• STOOMMETINGEN MET BACKUP

• VERGEET DE ELEKTRISCHE VERBRUIKERS NIET (POMPEN,

VENTILATOR)

Page 61: Indea stoomcursus

RENDEMENT STOOMSYSTEEM: 60%?

Page 62: Indea stoomcursus

INHOUD FATALE STOOMCURSUS

• DENKEN IN FATALE STOOM: EENHEDEN, WAT IS STOOM, WAAROM STOOM, VUISTREGELS

• HET KETELHUIS: APPARATUUR

• ENERGIE- EN MASSABALANS MET BBT MAATREGELEN EN EUROPESE NORMEN RENDEMENT

• WETGEVING: BBT, ENERGIEPLAN, ENERGIESTUDIE, RENDEMENT, MEETAPPARATUUR

Page 63: Indea stoomcursus

BEST BESCHIKBARE TECHNOLOGIE

• TEKST VITO NOVEMBER 2007: “ENERGIEBESPARING IN STOOMNETWERKEN”

- ECONOMISER

- LUCHTVOORVERWARMER

- VERWIJDEREN KETELSTEEN

- MINIMALISEREN SPUI

- WARMTERECUPERATIE UIT SPUI

- MINIMALISEREN INTERMITTEREND GEBRUIK

- HOGE DRUK STOOMKETELS EN TEGENDRUKTURBINES VOOR PRODUCTIE ELEKTRICITEIT

- CONDENSPOTCONTROLE EN REPARATIE

- ISOLATIE VAN STOOM- EN CONDENSAATLEIDINGEN

- VERWIJDERBARE ISOLERENDE SCHALEN OP KRANEN EN KLEPPEN

- OPVANG CONDENSAAT EN HERGEBRUIK IN KETELHUIS

- HERGEBRUIK VAN FLASHSTOOM

- HERGEBRUIK FLASHSTOOM OP SITE ZELF OF CONDENSAATRECUPERATIE OP ONDERDRUK

Page 64: Indea stoomcursus

RENDEMENT: STOOM OF DIRECT AARDGAS?

Page 65: Indea stoomcursus

METINGEN EN MEETAPPARATUUR

• METEN VAN SUPPLETIEWATERDEBIET EVIDENT AAN

REGENERATIE IONENWISSELAAR.

• METEN DEBIET VOEDINGSWATER WARM AANBEVOLEN

• MAANDELIJKSE ROOKGASANALYSE BIJ VOLLAST EN

DEELLAST AANBEVOLEN

• MAANDELIJKSE WATERANALYSES SUPPLETIEWATER,

VOEDINGSWATER, KETELWATER EN CONDENSAAT

AANBEVOLEN.

• STOOMMETINGEN ALLEEN VOOR VERDELING ENERGIE NAAR

AFDELINGEN (HOUDT GEEN REKENING MET ENERGIE EN

KOSTPRIJS VAN CONDENSAAT; EEN VERSCHIL VAN 20 À

25%)

Page 66: Indea stoomcursus

GENORMEERDE ROOKGASMETINGEN

Page 67: Indea stoomcursus

EUROPESE WETGEVING

• EUROPEES SPREEKT MEN STEEDS OVER PRIMAIR

ENERGIEVERBUIK UITGEDRUKT IN JOULE OP CALORISCHE

ONDERWAARDE!

• EUROPEAN ENERGY MANAGER IN DE MAAK? EEN FULL-TIME

JOB OP NIVEAU IN UW BEDRIJF.

• ENERGIESTUDIE NOODZAKELIJK VOOR >0,1PJ BEDRIJVEN BIJ

VERVANGEN STOOMINSTALLATIE MET 10 TJ JAARVERBRUIK.

• GEEN ENERGIESTUDIE MOGELIJK ZONDER GEDETAILLEERD

ENERGIEPLAN.

• BEST BESCHIKBARE TECHNOLOGIE REEDS AANWEZIG IN

MER-RAPPORT.

• ENERGIELUIK BBT DRAFT VAN JULI 2007

Page 68: Indea stoomcursus

EUROPESE NOX

• NOX GRENSWAARDEN WORDEN STRENGER EN KOSTEN

GELD?

• NEC DOELSTELLING HALEN: HEFFING VAN 1,75 EUR/KG EN

EEN SUBSIDIE VAN 75% VAN DE REDUCTIEKOSTEN?

AARDGAS NOx (mg/Nm³) SO2 (mg/Nm³)

vanaf 2008 vanaf 2008

(droge basis) (droge basis)

Vergund na 01.01.2005

100-300 kW geen geen

300 kW - 2 MW 150 35

2 - 5 MW 150 35

5 - 20 MW 150 35

20 - 50 MW 150 35

Page 69: Indea stoomcursus

NU NIEUWE MILIEUVERGUNNING AANVRAGEN

• HET DECREET VAN 19 MEI 2006 STELT DAT, IN AFWIJKING

VAN DEZE REGELING, BEDRIJVEN REEDS EEN NIEUWE

VERGUNNING MOGEN AANVRAGEN TOT 48 MAANDEN VÓÓR

HET VERVALLEN VAN HUN LOPENDE VERGUNNING, IN

ZOVERRE DE EINDTERMIJN AFLOOPT TEN LAATSTE OP 1

SEPTEMBER 2011. M.A.W. U KAN NU VANAF 1 SEPTEMBER

2007 UW VERGUNNING AL HERNIEUWEN! DE BEDOELING IS

OM EEN MOGELIJKE GROTE TOESTROOM AAN AANVRAGEN

VOOR HET HERNIEUWEN VAN VERGUNNINGEN MEER TE

SPREIDEN IN DE TIJD.

Page 70: Indea stoomcursus

OFFERTE AANVRAAG NIEUW KETELHUIS

per ketel totaal

15 °C t/h 10 30

Gelieve te garanderen: de netto stoomproductie en het totaal

rendement van het ketelhuis. Gelieve de noodzakelijke

meetapparatuur aan te bieden.103 °C t/h 12

Alle prijzen in euro, zonder BTW en zonder enige andere taxen.

3 vuurgangvlampijpketel 10 bar met isolatie 120 mm3 TRD604/ 72 uur onbemand bedrijf: 2x turbiditeitsmeting1 conductiviteitsmeting condens + 3-wegklep3 voedingswaterpomp(en)3 frequentieregelaar voor voedingswaterpomp(en)1 watervoedingspomp extra als reserve:1 mixtbrander (gas/lichte olie)1 geluiddempers voor branders -20 dB(A)1 frequentieregeling ventilator brander1 gasdrukregelstation (van 500 mbar naar gevraagde

branderregeldruk)3 schoorsteen 12 m (totale hoogte) in inox steunend op

ketel/economiser3 geluiddempers in schoorsteen1 voedingswatertank liefst in inox 316 L1 ontgassingstoren inox 316 L3 economiser(s)3 rookgascondensor(s)3 LUVO voor voorverwarming verbrandingslucht3 warmtewisselaars suppletiewater/voedingswater3 volledig modulerende waterregeling (ketels, ontgasser,

suppletie, stoom)3 terugslagkleppen en toebehoren3 transport + op plaats brengen en voormontage3 automatische spui op geleidbaarheid1 spuitank volgens Vlarem1 controle retourcondensaat op kwaliteit (geleidbaarheid en 3-weg

sturing)3 ladders en loopbruggen voor wettelijke metingen1 elektrische kast met 25% vrije ruimte1 elektrische installatie1 elektrische hoofdschakelaar ketelhuis1 schilderwerken1 markeringen1 automatische cascaderegeling1 geïsoleerde stoomcollector1 turn key installatie1 isolatie leidingen, flenzen, afsluiters boven 60°C1 Stellingen en hoogtewerkers1 isolatie van kleppen, flenzen en toebehoren

dagen opstart, opleiding, metingen en integratie in integraal

milieujaarverslag en energieplan1 voorgemonteerde onthardingsinstallatie1 voorgemonteerde RO-installatie 5m³/h1 gekeurde waterdebietmeter (105°C) voor registratie van kWh

1 resthardheidscontrole voedingswater3 stoomdebietmeter tot max 20t/h1 gekeurde gasdebietmeter per brander met pulsuitgang1 automatisch gasafsluitstation gemonteerd4 watermonsterkoeler(s) inclusief volledig circuit:4 doseerinstallaties chemicaliën

prijzen in euro

Nieuwe stoominstallatie

• VRAAG APARTE PRIJZEN VOOR:

– ECONOMISER

– ROOKGASCONDENSOR

– OSMOSE

– SPUIWARMTERECUPERATIE

– EXTRA ISOLATIE

– LUVO

– SPUI OP GELEIDBAARHEID

Page 71: Indea stoomcursus

GARANTIE KETELHUISRENDEMENT INPUT

OUTPUT

Page 72: Indea stoomcursus

WEBCALCULATORS

• HTTP://WWW.SPIRAXSARCO.COM/RESOURCES/CALCULATORS.ASP

• HTTP://UNIVERSITY.ARMSTRONGINTERNATIONAL.COM/UNIVER

SITY/STEAMFORM.HTML

• WWW.INDEA.BE

Page 73: Indea stoomcursus

WEBSITES:

• WWW.INDEA.BE

• HTTP://WWW.EMIS.VITO.BE/EMIS/MEDIA/BBT_STOOMGIDS_

HERZIENING.PDF

Page 74: Indea stoomcursus

MAANDELIJKS ENERGIERAPPORT