Page 1: Indelac Controls, Inc. · LED will blink on and off. If the WIPER voltage is less than 0.25V, the MOTOR 2 output is disabled, the red LED turns off, and the green LED blinks. Low
Page 2: Indelac Controls, Inc. · LED will blink on and off. If the WIPER voltage is less than 0.25V, the MOTOR 2 output is disabled, the red LED turns off, and the green LED blinks. Low

Indelac Controls, Inc.

1 Indelac Controls

DC MOTOR CONTROLLER

+5V 1

2

3

4

5

6

WIPER

GND

MOTOR 2 OUTPUT

MOTOR 1 OUTPUT

to Motor

to Feedback Pot

1

2

3

4

6+5V OUT

EARTH

BAT POSto DC Power

to Signal

ELECTRICALCONNECTIONS

J1

J2

5

7

8

LIMIT COMMON

LIMIT SW1LIMIT SW2

COMMAND ( )

BAT NEG

COMMAND (+)

COMMANDTYPE SW1 SW2 SW3 SW4

LOSS OF COMMANDOPERATION

ON

OFF

ON

ON

ON

OFF

ON

ON

ON

ONOFF

OFF

ON

ON

ON

ONOFF

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

OFF

OFF OFF

OFF

OFF OFF

4-20mA

1-5V

2-10V

0-5V

0-10V

Motor off

Close (Zero setting)

Open (Span setting)

NA

NA

Motor off

Motor off

Close (Zero setting)

Close (Zero setting)

Open (Span setting)

Open (Span setting)

SW5CONTROL FUNCTION

Normal

Log Rate

OFF

ON

COMMAND INPUT SIGNAL CONFIGURATION

S1

NOTE: All other settings are not valid and can cause abnormal operation.

J1 J2

3.50" 0.25"0.25"

1.36"

1.36"

1.15"

87654321 654321

COM

NC

NO

RES

GND

OFF

ON

51

DEADBANDGRN LED

RED LED

#6 clear hole(2) places

TRIP ADJUST

TRIP RESET

TRIP (YEL LED)

Z S

DMC-102A only

OPTIONAL TRIPCONNECTOR

S1

FUSE

ZERO & SPAN ADJUST

DMC-102

(OPTIONAL)

10-30VDC

12345678

123456

DMC-102

Page 3: Indelac Controls, Inc. · LED will blink on and off. If the WIPER voltage is less than 0.25V, the MOTOR 2 output is disabled, the red LED turns off, and the green LED blinks. Low

DMC-102

Indelac Controls 2

INDICATORS and FAULT CONDITIONS The on-board green and red LED indicators pro-vide the user with information about various conditions about the actuator. The table below provides a summary of the indications which is followed by a description of each condition.

GRN RED CONDITION - ON MOTOR 1 on (+)

ON - MOTOR 2 on (+)

- flash LIMIT SW1 disconnected

flash - LIMIT SW2 disconnected

blink OFF Feedback WIPER < 0.25V

OFF blink Feedback WIPER > 4.75V

blink blink Low Battery Voltage

ON ON Overvoltage Motor Output ON - When conditions are normal, the red LED indicator turns on when the MOTOR 1 output is pos-itive, and the green LED turns on when the MOTOR 2 output is positive. For Direct Acting applications, the red LED indicates when the actuator is moving toward open, and conversely, for Reverse Acting applications, the red LED indicates when the actuator is moving toward closed. Limit Switch - Many actuators are equipped with limit switches at the open and closed positions which are in-tended to disconnect power to the motor to prevent me-chanical damage. The actuator's limit switches should be set outside of the operating range set by zero and span. Limit switches exhibit wide variations, and the DMC-102 can position the actuator more precisely than the limit switches. A limit switch serves better as a failsafe device. When LIMIT SW1 disconnects J1 pin 7 from J1 pin 6, the red LED will flash and power to the MOTOR 1 output is disabled. Likewise, when LIMIT SW2 disconnects J1 pin 8 from J1 pin 6, the green LED will flash and power to the MOTOR 2 output is disabled.

Feedback Signal Out of Range - The DMC-102 detects when the feedback potentiometer signal is out of range. If the voltage at the WIPER exceeds 4.75V, the MOTOR 1 output is disabled, the green LED is turned off, and the red LED will blink on and off. If the WIPER voltage is less than 0.25V, the MOTOR 2 output is disabled, the red LED turns off, and the green LED blinks. Low Battery Voltage and Overvoltage - The DC power connected to J2 pins 1 and 2 are monitored continuously. If the voltage drops below 10V, the motor outputs are dis-abled and both LED's will blink on and off to indicate a Low Battery Voltage condition. The motor will remain off, and the LED's will blink, for 3 seconds after power returns to 10V or more. If the voltage exceeds 30V for more than 1 second, the motor outputs are disabled and both LED's will turn on to indicate an Overvoltage condi-tion. The motor and LED's resume normal operation when power returns to 30V or less.

DC MOTOR CONTROLLER

The DMC-102 is used for proportional positioningof DC powered actuators. The DMC-102 is rated tohandle up to 10A continuous motor load or 60A locked rotor. An external command signal is input to the controller board to precisely position the actuator. Seethe chart on Page 1 for input command signal options.