index to drawings dwg total drawing name drawing …

9
DWG # DRAWING NAME TOTAL SHEETS DRAWING TITLE 01 HA2019-CV 1 COVER SHEET 02 HA2019-FP 1 FOUNDATION PLAN 03 HA2019-EP 1 ELECTRICAL PLAN 04 HA2019-E5 1 26KV ELEVATIONS 05 HA2019-ED 1 ELECTRICAL DETAILS 06 HA2019-CP 1 CONDUIT & GROUNDING PLAN 07 HA2019-CS 1 CONDUIT SCHEDULE 08 HA2019-CT 1 CABLE SCHEDULE 09 HA2019-LV 1 STATION SERVICE & ELECTRICAL PANELS INDEX TO DRAWINGS

Upload: others

Post on 17-Mar-2022

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: INDEX TO DRAWINGS DWG TOTAL DRAWING NAME DRAWING …

DWG # DRAWING NAME TOTAL

SHEETS DRAWING TITLE

01 HA2019-CV 1 COVER SHEET02 HA2019-FP 1 FOUNDATION PLAN03 HA2019-EP 1 ELECTRICAL PLAN04 HA2019-E5 1 26KV ELEVATIONS05 HA2019-ED 1 ELECTRICAL DETAILS06 HA2019-CP 1 CONDUIT & GROUNDING PLAN07 HA2019-CS 1 CONDUIT SCHEDULE08 HA2019-CT 1 CABLE SCHEDULE09 HA2019-LV 1 STATION SERVICE & ELECTRICAL PANELS

INDEX TO DRAWINGS

Page 2: INDEX TO DRAWINGS DWG TOTAL DRAWING NAME DRAWING …

--

-

-

-

------

------

------

-

-

-

- HA2019-FP

02

- - - - -

- - - - -

- - - - -

- - - - -

-

- SUBSTATION & TRANSMISSION PROJECTS 20410

HA2019

09

8005239

BLS

BLS

HAMILTON STREET SUBSTATION

N

CABLE TRENCH

T1

T2

25

T2

25

T1

PANEL "YP"

BK

R

64

6B

KR

663

BKR 6T1T2

307

308

312

31

03

11

(S

PA

RE)

30

9

FOUNDATION PLAN & DETAILS

FOUNDATION PLANEXISTING FOUNDATION

CL

3' - 10 1/2"

2'-6" 2'-6"

5'-0"

2'-6"

2'-6"

5'-0"

3' - 10 1/2"

FDN& BKR

LEGEND:

FOUNDATION DETAILS

SCALE: „" = 1'-0"

AS SHOWN

SCALE: 1" = 1'-0"

(4 PLACES)

& PAINT WITH EPOXY COATING

FLUSH WITH CONCRETE SURFACE

EXISTING ANCHOR BOLTS, GRIND

CONTRACTOR SHALL CUT OFF

IN BREAKERCONDUIT WINDOW

CLFDN& BKR

CONSTRUCTION NOTES

FOUNDATION (TYP.)

EXISTING 5' X 5'

BREAKER 307, 308, 310, 311, & 312 REPLACEMENTS

7-23-2019

7-23-2019

SCALE: PROJ #:

DRAWING #:

DRAWING NAME:ENGINEERING

DATE

BY

REVIEW

DRAFTING

REVISION DESCRIPTIONREV DATE PROJ # BY REVIEW

JE

A A

RC

H-D 2

4X36 (02/1

7)

OF

DATE

BY

REVIEW

PE:

DATE:

LIC. NO.:

STATE:

THE RESPONSIBLE SUPERVISION OF

ORIGINALLY PREPARED UNDER

LATEST REVISION

ENGINEER'S SEAL

PROFESSIONAL

DRAWING SET

ISSUED FOR BID

JACKSONVILLE, FLORIDA 32202

21 W CHURCH ST.

16:0

5 -

2017-6-2

3

HR

172E

D1.d

gn

PROJECTION.

WASHER PER BOLT W/ 2 1/2"

HEX NUT & ONE (1) 2" DIAM. FLAT

WEDGE ANCHORBOLTS W/ ONE (1)

FOUR (4) 1" DIAM. X 10" LONG S.S.

CONTRACTOR TO PROVIDE & INSTALL

2. FOR PROPER BUSHING ORIENTATION, SEE ELECTRICAL DETAIL DWG.

FOR THE BREAKERS AS SHOWN.1. THE CONTRACTOR SHALL REUSE THE EXISTING FOUNDATIONS

Page 3: INDEX TO DRAWINGS DWG TOTAL DRAWING NAME DRAWING …

--

-

-

-

------

------

------

-

-

-

-

03

- - - - -

- - - - -

- - - - -

- - - - -

-

- SUBSTATION & TRANSMISSION PROJECTS 20410

HA2019

098005239

BLS

BLS

BREAKER 307, 308, 310, 311 & 312 REPLACEMENTS

HAMILTON STREET SUBSTATION

8-12-2019

8-12-2019

SCALE: PROJ #:

DRAWING #:

DRAWING NAME:ENGINEERING

DATE

BY

REVIEW

DRAFTING

REVISION DESCRIPTIONREV DATE PROJ # BY REVIEW

JE

A A

RC

H-D 2

4X36 (02/1

7)

OF

DATE

BY

REVIEW

PE:

DATE:

LIC. NO.:

STATE:

THE RESPONSIBLE SUPERVISION OF

ORIGINALLY PREPARED UNDER

LATEST REVISION

ENGINEER'S SEAL

PROFESSIONAL

DRAWING SET

ISSUED FOR BID

JACKSONVILLE, FLORIDA 32202

21 W CHURCH ST.

14:3

2 -

2017-6-2

2

HR

172

CV1.d

gn

1" - 6' - 0"

ELECTRICAL PLANHA2019-EP

TO 6

9K

V Y

AR

DT

O 6

9K

V Y

AR

D

ELEVATIONS.

2. REFER TO DRAWING HA2019-E5 FOR SECTION

LIST & SHALL BE DISREGARDED FOR THIS PROJECT.

SHOWN REFER TO THE ORIGINAL PROJECT MATERIAL

(REF. DWG # HA712EP1) NUMERICAL CALLOUTS

1. THIS DRAWING IS FOR REFERENCE ONLY

NOTES:

Page 4: INDEX TO DRAWINGS DWG TOTAL DRAWING NAME DRAWING …

6'-0" 6'-0"

~12'-2"

9'-8"

(TYP.)NOTE 1

MECHANISM SIDE TYPICAL SECTION VIEW

3'-0"3'-0"

--

-

-

-

------

------

------

-

-

-

-

04

- - - - -

- - - - -

- - - - -

- - - - -

-

- SUBSTATION & TRANSMISSION PROJECTS 20410

HA2019

098005239

BLS

BLS

BREAKER 307, 308, 310, 311 & 312 REPLACEMENTS

HAMILTON STREET SUBSTATION

8-12-2019

8-12-2019

SCALE: PROJ #:

DRAWING #:

DRAWING NAME:ENGINEERING

DATE

BY

REVIEW

DRAFTING

REVISION DESCRIPTIONREV DATE PROJ # BY REVIEW

JE

A A

RC

H-D 2

4X36 (02/1

7)

OF

DATE

BY

REVIEW

PE:

DATE:

LIC. NO.:

STATE:

THE RESPONSIBLE SUPERVISION OF

ORIGINALLY PREPARED UNDER

LATEST REVISION

ENGINEER'S SEAL

PROFESSIONAL

DRAWING SET

ISSUED FOR BID

JACKSONVILLE, FLORIDA 32202

21 W CHURCH ST.

14:3

2 -

2017-6-2

2

HR

172

CV1.d

gn

1" - 4' - 0"

9'-8"

7'-6"

(TYP.)NOTE 1

26KV ELEVATIONSHA2019-E5

FOR THIS PROJECT.

SHOWN REFER TO THE ORIGINAL PROJECT MATERIAL LIST & SHALL BE DISREGARDED

VARY WITHIN A FEW INCHES AND MUST BE FIELD VERIFIED. NUMBERICAL CALLOUTS

3. THIS DRAWING WAS REPRODUCED FROM DRAWING HA712E51. DIMENSIONS MAY

2. ELEVATIONS SHOWN ARE TYPICAL - NOT EVERY BREAKER IS SHOWN ON THIS DWG.

TO FINAL PLACEMENT OF BREAKER.

SHALL CONTRACT PROJECT REPRESENTATIVE FOR REVIEW AND APPROVAL PRIOR

PART IS >9'6" ABOVE GRADE. SHOULD ADJUSTMENT(S) BE REQUIRED, CONTRACTOR

1. CONTRACTOR SHALL PLACE NEW BREAKERS SO THAT LOWEST ENERGIZED

CONSTRUCTION NOTES:

Page 5: INDEX TO DRAWINGS DWG TOTAL DRAWING NAME DRAWING …

--

-

-

-

------

------

------

-

-

-

- HA2019-ED

05

- - - - -

- - - - -

- - - - -

- - - - -

-

- SUBSTATION & TRANSMISSION PROJECTS 20410

HA2019

8005239

BLS

BLS

N.T.S.

ELECTRICAL DETAILS

1288.1

MAX.

967.7

MAX.

2

4

6

BUSHING NUMBER

MECHANISM SIDE

CONTROL SIDE

1

3

5

SWING

97.0° APPROX. DOOR

BB

SECTION B-B

17.68"

449

60.34"

1532.7

[50.71"]

MIN.

[17.25"]

438.1

[38.10"]

MIN.

[4.63"]

117.7

[51.52"]

1308.7

[57.37"]

1457.2

FOR BUSHING REMOVALDISTANCE REQUIRED

2.50"

63.546.52"

1181.751.52"

1308.7

23.26"

590.9

10.21"

259.3

1.74"

44.2

46.52"

1181.7

51.52"

1308.7

12.0

1"

12.01"

124.84"

3170.8

CONSTRUCTION NOTES:

BREAKER INFORMATION:22.4

6"

HAMILTON STREET SUBSTATION

INSTRUCTION BOOK POCKET,

BCT NAMEPLATE,

(MOUNTED ON POCKET)

INSIDE

MAX.

MAX.

5 3 1

MAX.

MIN.

78.22"

111.64"

128.98"

MIN.

95.17"

34.87"

MIN.

1.41"

01

03

02

19.50"19.50"

SIDECONTROL

0505

0404

SPACESVENT/FILTER

INSIDE

TYP. 2 PLACES

NOTE 3

NOTE 4

71" 5'-11"

50" 4'-2"

25" 2'-1"

13" 1'-1"

7" 0'-7"

(in) (ft-in)

Min. Phase-Ground

89" 7'-5"

63" 5'-3"

31" 2'-7"

18" 1'-6"

12" 1'-0"

(in) (ft-in)

Min. Phase-Phase

14'-10" 27'

12'-2" 25'

10'-5" 23'

9'-6" 22'

9'-0" 21'

Personnel (ft-in) Roadway (ft)

Min. Above Grade

900

650

350

200

110

(kV)

BIL

230

138

69

34.5

13.2

(kV)

Voltage

16'

14'

12'

10'

10'

Horizontal (ft)

Min. to Fence

11'-0"

8'-0"

5'-0"

3'-0"

2'-0"

(ft-in)

Phase Spacing

Reference RUS Bulletin 1724E-300 (2001), & NESC (2007)

BREAKER 307, 308, 310, 311, & 312 REPLACEMENTS

6. CONTRACTOR SHALL LABEL THE NEW BREAKERS.

MANUFACTURER'S INSTRUCTIONS.

PLUS MOLDS MANUFACTURED BY CADWELD. INSTALLATION SHALL STRICTLY FOLLOW

SHALL BE INSTALLED FROM THE GROUND GRID USING APPROVED EXOTHERMIC CADWELD

- IF EXISTING GROUND TAIL CANNOT REACH EQUIPMENT, THEN A NEW 7#5 COPPERWELD

BREAKER AS SHOWN

5. BOND EXISTING COPPER FROM GROUND GRID TO EQUIPMENT ON EACH SIDE OF THE

4. INSTALL JUMPERS AND TERMINALS AS SHOWN.

WHERE CLEARANCES ARE AN ISSUE.

THIS IS THE RECOMMENDED HEIGHT, BUT MAY NEED TO BE ADJUSTED FOR LOCATIONS

3. SET BOTTOM OF BREAKER CABINETS TO HEIGHT OF ~29" FROM TOP OF FOUNDATION

BREAKERS SHALL BE SET AT CENTER OF EXISTING FOUNDATIONS.

2. INSTALL BREAKERS TO MATCH BUSHING NUMBERS RELATIVE TO NORTH ARROW.

WITH SOCC AND SUB/RELAY O&M.

TO JEA'S WESTSIDE SERVICE CENTER HAZMAT BUILDING DURING SCHEDULED OUTAGES

1. CONTRACTOR SHALL REMOVE FROM FOUNDATION AND TRANSPORT EXISTING BREAKERS

7-23-2019

7-23-2019

SCALE: PROJ #:

DRAWING #:

DRAWING NAME:ENGINEERING

DATE

BY

REVIEW

DRAFTING

REVISION DESCRIPTIONREV DATE PROJ # BY REVIEW

JE

A A

RC

H-D 2

4X36 (02/1

7)

OF

DATE

BY

REVIEW

PE:

DATE:

LIC. NO.:

STATE:

THE RESPONSIBLE SUPERVISION OF

ORIGINALLY PREPARED UNDER

LATEST REVISION

ENGINEER'S SEAL

PROFESSIONAL

DRAWING SET

ISSUED FOR BID

JACKSONVILLE, FLORIDA 32202

21 W CHURCH ST.

16:0

5 -

2017-6-2

3

HR

172E

D1.d

gn

09

Page 6: INDEX TO DRAWINGS DWG TOTAL DRAWING NAME DRAWING …

--

-

-

-

------

------

------

-

-

-

- HA2019-CP

06

- - - - -

- - - - -

- - - - -

- - - - -

-

- SUBSTATION & TRANSMISSION PROJECTS 20410

HA2019

09

8005239

BLS

BLS

HAMILTON STREET SUBSTATION

LEGEND

7

N

CABLE TRENCH

T1

T2

25

T2

25

T1

345 126

CONTROL PANELS

RTUPANEL

RELAY

DA

OVERHEAD CABLE TRAY

PANEL

CONTROL

COMMUNICATION RACK

9 8

EXISTING CONDUIT

EXISTING 7#5 COPPERWELD GROUND CABLE

NEW 7#5 COPPERWELD GROUND CABLE

NEW EXOTHERMIC GROUND CONNECTION

NEW MECHANICAL GROUND CONNECTION

307

308

312

31

03

11

(S

PA

RE)

30

9

NOTE 6

CONDUIT & GROUNDING PLAN

SCALE: „" = 1'-0"

N.T.S.

AS SHOWN

~80' TO CNTRL HSE

EQUIPMENT LOCATION DETAILCONTROL HOUSE

CONSTRUCTION NOTES:

BREAKER 307, 308, 310, 311, & 312 REPLACEMENTS

DETAIL 1

26KV CONDUIT, CABLE TRENCH, AND PARTIAL GROUNDING PLAN

CONNECTION

TYPICAL GROUND

COPPERWELD

7 #5

COPPERWELD

7 #5

& SUBPANEL

PANEL "YP"

7-23-2019

7-23-2019

SCALE: PROJ #:

DRAWING #:

DRAWING NAME:ENGINEERING

DATE

BY

REVIEW

DRAFTING

REVISION DESCRIPTIONREV DATE PROJ # BY REVIEW

JE

A A

RC

H-D 2

4X36 (02/1

7)

OF

DATE

BY

REVIEW

PE:

DATE:

LIC. NO.:

STATE:

THE RESPONSIBLE SUPERVISION OF

ORIGINALLY PREPARED UNDER

LATEST REVISION

ENGINEER'S SEAL

PROFESSIONAL

DRAWING SET

ISSUED FOR BID

JACKSONVILLE, FLORIDA 32202

21 W CHURCH ST.

16:0

5 -

2017-6-2

3

HR

172E

D1.d

gn

THE SAME DAY.

MECHANICALCONNECTORS. ALL EQUIPMENT AND STRUCTURES ERECTED IN THE SUBSTATION MUST BE GROUNDED

TRANSFORMERS, BREAKERS, LIGHTNING ARRESTERS, ETC. SHALL BE CONNECTED USING OWNER FURNISHED

8. ALL ABOVE GRADE CONNECTIONS OF GROUND CONDUCTOR TO STRUCTURES AND EQUIPMENT, SUCH AS

TO STRUCTURES AND EQUIPMENT IS ABOVE GRADE.

AND SHALL BE INSTALLED 24" BELOW GRADE (28" BELOW ROCK SURFACE) EXCEPT WHERE CONECTION

ALL GROUND GRID CONDUCTORS AND TAPS SHALL BE CONNECTED USING CADWELD EXOTHERMIC CONNECTIONS

7. ALL 7#5 COPPERWELD CONDUCTOR SHALL BE FURNISHED BY JEA AND INSTALLED BY THE CONTRACTOR.

WITHIN WORK AREA IS SHOWN ON THIS DRAWING.

6. EXISTING GROUND GRID IS 7#5 COPPERWELD PER SUBSTATION RECORD DWGS. ONLY GROUND GRID

LENGTHS AND LOCATIONS.

5. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL CONDUIT, CABLE, AND GROUND CONDUCTOR

TO THE CABLE TRENCH. ALL CONDUIT RUNS SHALL ALSO BE CLEARLY LABELED AT BOTH ENDS.

4. ALL CABLES SHALL BE CLEARLY LABELED AT BOTH ENDS AND AT ALL ENTRANCE AND EXIT POINTS

TRIPPING HAZARDS WHILE WORKING IN THE CONTROL CABINET.

CONFORM TO THE FOUNDATION AND STRUCTURE TO WHICH IT IS TO BE MOUNTED AND TO MINIMIZE

RESISTANT PVC, SCHEDULE 40. ABOVE GRADE CONDUIT SHALL BE INSTALLED TO CLOSELY

3. ALL ABOVE GRADE CONDUIT SHALL BE EITHER RIGID GALVANIZED STEEL OR ULTRA-VIOLET

IN THE NEW GAS CIRCUIT BREAKER CONTROL PANEL. JEA WILL TERMINATE IN CONTROL HOUSE PANELS.

ALL CABLES LISTED IN THE CABLE SCHEDULE. THE CONTRACTOR SHALL ONLY TERMINATE CABLES

AS LISTED IN THE CONDUIT SCHEDULE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PULLING

2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING AND INSTALLING ALL CONDUIT

BACK/CAP ANY UNUSED CONDUITS BELOW GRADE.

1. THE CONTRACTOR SHALL REUSE EXISTING CONDUITS PER THE CONDUIT SCHEDULE AND CUT

Page 7: INDEX TO DRAWINGS DWG TOTAL DRAWING NAME DRAWING …

--

-

-

-

------

------

------

-

-

-

- HA2019-CS

07

- - - - -

- - - - -

- - - - -

- - - - -

-

- SUBSTATION & TRANSMISSION PROJECTS 20410-

HA2019

098005239

BLS

BLS

CONDUIT SCHEDULE

PROTECTION, WITH PENETRATION PROPERLY SEALED.BLOCK WALL SHALL UTILIZE PVC COATED ALUMINUM TO PROVIDE SUFFICIENT ALKALI CORROSION ALL RUNS WITHIN BATTERY ROOM SHALL UTILIZE ALUMINUM CONDUIT. PENETRATIONS THROUGH THE 4.

SHALL NOT CONCEAL ALUMINUM CONDUIT RUNS.HOUSE CONDUIT WITHIN BLOCK WALLS UNLESS STATED OTHERWISE IN THE DRAWINGS. CONTRACTOR CONTROL HOUSE CONDUIT EXPOSED RUNS SHALL BE EMT. CONTRACTOR MAY CONCEAL CONTROL 3.

LENGTHS ARE APPROXIMATE.THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL CONDUIT LENGTHS. CONDUIT 2.

FITTINGS.THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY CONDUIT MATERIALS, INCLUDING 1.

CONDUIT NOTES:

SQAURE WIREWAYWWLIQUID-TIGHT FLEXIBLE METALLIC CONDUITLFMINTERMEDIATE METALLIC CONDUITIMCRIGID METALLIC (GALVANIZED STEEL) CONDUITRMCELECTRICAL METALLIC TUBINGEMTUV RESISTANT PVC CONDUIT, SCH 40UV

CONDUIT LEGEND:

CONDUIT SCHEDULE

BREAKER 307, 308, 310, 311, & 312 REPLACEMENTS

HAMILTON STREET SUBSTATION

BREAKER 307CONSTRUCTION NOTES:

BREAKER 308

BREAKER 310

BREAKER 311

BREAKER 312

1. USE EXISTING 3" AND 5" CONDUITS; INSTALL LB AND/OR FLEX TO NEW BREAKER CONDUIT OPENING

SCALE: PROJ #:

DRAWING #:

DRAWING NAME:ENGINEERING

DATE

BY

REVIEW

DRAFTING

REVISION DESCRIPTIONREV DATE PROJ # BY REVIEW

JE

A A

RC

H-D 2

4X36 (02/1

7)

OF

DATE

BY

REVIEW

PE:

DATE:

LIC. NO.:

STATE:

THE RESPONSIBLE SUPERVISION OF

ORIGINALLY PREPARED UNDER

LATEST REVISION

ENGINEER'S SEAL

PROFESSIONAL

DRAWING SET

ISSUED FOR BID

JACKSONVILLE, FLORIDA 32202

21 W CHURCH ST.

14:3

2 -

2017-6-2

2

HR

172

CV1.d

gn

7-23-2019

7-23-2019

Page 8: INDEX TO DRAWINGS DWG TOTAL DRAWING NAME DRAWING …

--

-

-

-

------

------

------

-

-

-

- HA2019-CT

08

- - - - -

- - - - -

- - - - -

- - - - -

-

- SUBSTATION & TRANSMISSION PROJECTS 20410-

HA2019

098005239

BLS

BLS

CABLE SCHEDULE

LENGTHS ARE APPROXIMATE.THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL CABLE LENGTHS. CABLE 3.

THE CONTRACTOR SHALL FURNISH ALL OTHER CABLE, AS SPECIFIED.2.

TYPE B, BS, F, AND FO CABLE SHALL BE FURNISHED BY THE OWNER, UNLESS OTHERWISE SPECIFIED.1.

CABLE NOTES:

CABLE TRENCHTRENCHCONTROL HOUSE CABLE TRAYTRAYSINGLE CONDUCTORSMULTIPLE CONDUCTORMFIBER OPTIC CABLEFOINSTRUMENT CABLEFRHW, THHW, OR THWN INSULATED COPPER CONDUCTORCSHIELDED CONTROL CABLEBSCONTROL CABLEBTHHN INSULATED COPPER CONDUCTORA

CABLE LEGEND:

CABLE SCHEDULE

BREAKER 307, 308, 310, 311, & 312 REPLACEMENTS

HAMILTON STREET SUBSTATION

BREAKER 307

BREAKER 308

BREAKER 310

BREAKER 311

BREAKER 312

SCALE: PROJ #:

DRAWING #:

DRAWING NAME:ENGINEERING

DATE

BY

REVIEW

DRAFTING

REVISION DESCRIPTIONREV DATE PROJ # BY REVIEW

JE

A A

RC

H-D 2

4X36 (02/1

7)

OF

DATE

BY

REVIEW

PE:

DATE:

LIC. NO.:

STATE:

THE RESPONSIBLE SUPERVISION OF

ORIGINALLY PREPARED UNDER

LATEST REVISION

ENGINEER'S SEAL

PROFESSIONAL

DRAWING SET

ISSUED FOR BID

JACKSONVILLE, FLORIDA 32202

21 W CHURCH ST.

14:3

2 -

2017-6-2

2

HR

172

CV1.d

gn

7-23-2019

7-23-2019

Page 9: INDEX TO DRAWINGS DWG TOTAL DRAWING NAME DRAWING …

--

-

-

-

------

------

------

-

-

-

- HA2019-LV

09

- - - - -

- - - - -

- - - - -

- - - - -

-

- SUBSTATION & TRANSMISSION PROJECTS 20410

HA2019

09

8005239

BLS

BLS

N.T.S.

TO 25KV BUS TO 25KV BUS

1

3

5

2

4

6

15A15A

40A

87

40A

125 V.D.C.

BATTERY BANK

100A

EMERGENCY LTG.

S/N

1 2

60A3 4

225 AMP

MAIN

AC PANEL "YP-3P"

BREAKER 307, 308, 310, 311, & 312 REPLACEMENTS

HAMILTON STREET SUBSTATION

CONNECTED WYE DELTA

1-50 & 1-25KVA 14,400 - 120/240V

STATION SERVICE TRANSFORMERS

DISCONNECTS

FUSED

DISCONNECTS

FUSED

400A 400A

AUTOMATIC TRANSFER SWITCH

60A

30A

60A

60A1

3

5

2

4

6

30A

60A

S/N

SPARE

SPARE

YARD RECPT. #1

YARD RECPT. #2

SPARE

SPARE

225A MAIN

70A 70A

30A

30A

30A

15A

15A

6

UNKNOWN

BKR 307

UNKNOWN

BKR 311

BKR 312

8

10

12

AC T2 CNTRL PNLUNKNOWN

30A

15A

15A

15A

15A

UNKNOWN

UNKNOWN 5

7

9

UNKNOWN

11

13

BLANK

BLANK

BLANK

BLANK

BLANK

BLANK

BLANK

HIGH LEG

S/N

60A

20A

20A

20A

30A

15A

BATTERY CHARGER 11

13

15

17

19

SPACE

SPACE

HIGH LEG

SPACE 1

3

5

7

20A

9 20A

21

23

25

27

29

20A

20A

20A

20A

60A

20A

20A

AIR CONDITIONER

SPACE

20A

20A

20A

20A

20A

20A

2

4

6

8

10

12

14

16

18

20

22

24

26

28

30

SPACE FOR FUTURE SPACE FOR FUTURE

20A

30A

30A

CONTROL HOUSE LIGHTING

PROBE POLE LIGHTS (NE)

25KV SWITCHYARD RECP

CONTROL HOUSE RECP (WEST)

PANEL HEATERS

AIR CONDITIONING STRIP HEATERS

CONTROL PANEL HEATERS

SPACE

PROBE POLE LIGHTS (SE)

PROBE POLE LIGHTS (CENTER)

SPACE

OUTDOOR LIGHTING ON CONTROL HOUSE

PROBE POLE LIGHTS (NW)

69KV SWITCHYARD RECP

CONTROL HOUSE RECP (E)

SPARE

PANEL HEATERS

SPARE

SPARE

PROBE POLE LIGHTS (SW)

SPACE

SPACE

SPARE

SPARE

20A 20A

15A 15A

PANEL (FUTURE)SUPERVISORY CONTROL

SPARE SPARE

69KV CONTROL PANEL

(FUTURE) CONTROL PANELS

(FUTURE)CONTROL PANELS

SPARE

SPACE ONLY

UNKNOWN SOURCE

AC PANEL "CH"

MOUNTED IN CONTROL HOUSE

GENERAL ELECTRIC TYPE "NAB" ORAPPROVED EQUAL,

THREE PHASE 4 WIRE S/N NEMA-1 SURFACE MOUNTED

APPROVED EQUAL, MOUNTED ON 25KV STRUCTURE COLUMN

SURFACE MOUNTED GENERAL ELECTRIC TYPE "NAB" OR

THREE PHASE 4 WIRE S/N NEMA-3 OUTDOOR ENCLOSED

EQUAL, LOCATED IN CONTROL HOUSE

GENERAL ELECTRIC TYPE "NAB" ORAPPROVED

125V DC 2 WIRE NEMA-1SURFACE MOUNTED

APPROVED EQUAL, MOUNTED ON 25KV STRUCTURE COLUMN

SURFACE MOUNTED GENERAL ELECTRIC TYPE "NAB" OR

THREE PHASE 4 WIRE S/N NEMA-3 OUTDOOR ENCLOSED

9

SUB AC PANEL

D.C. PANEL "EM"

(CONFIGURATION UNKNOWN)

JUNCTION BOX

BKR 308

BKR 309

BKR 310

7-23-2019

7-23-2019

SCALE: PROJ #:

DRAWING #:

DRAWING NAME:ENGINEERING

DATE

BY

REVIEW

DRAFTING

REVISION DESCRIPTIONREV DATE PROJ # BY REVIEW

JE

A A

RC

H-D 2

4X36 (02/1

7)

OF

DATE

BY

REVIEW

PE:

DATE:

LIC. NO.:

STATE:

THE RESPONSIBLE SUPERVISION OF

ORIGINALLY PREPARED UNDER

LATEST REVISION

ENGINEER'S SEAL

PROFESSIONAL

DRAWING SET

ISSUED FOR BID

JACKSONVILLE, FLORIDA 32202

21 W CHURCH ST.

16:0

5 -

2017-6-2

3

HR

172E

D1.d

gn

SEE NOTES

SEE NOTES

BREAKER #.

3) CONTRACTOR SHALL LABEL ALL 30A FEEDS WITH RESPECTIVE VACUUM

REMOVE OLD CONDUCTORS AND INSTALL NEW 3C #8 IN EXISTING CONDUIT.

AND INSTALL NEW 30A DOUBLE POLE BREAKER. CONTRACTOR SHALL

VACUUM BREAKER. IF SMALLER THAN 30A, CONTRACTOR SHALL PROVIDE

FROM EXISTING AC PANEL "YP-3P" ARE PROVIDING 120/240V TO EACH 28KV

2) CONTRACTOR SHALL VERIFY 30 AMP BRANCH CIRCUIT BREAKERS

VERIFIED

AND VISIBLE FIELD CONDITIONS. PANEL "CH" CONFIGURATION NOT FIELD

EXISTING STATION SERVICE CONFIGURATION BASED ON DWG HA712LV1

1) THIS DRAWING IS BEING PROVIDED TO SHOW THE SUBSTATION'S

NOTES:

STATION SERVICE & ELECTRICAL PANELS