indirect fired heater training module
DESCRIPTION
Heater training moduleTRANSCRIPT
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 1/25
Human Development Consultants Ltd.
Describe and Operate
Indirect-F
ired
Line Heaters
Training Module
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 2/25
Cover PhotoC ou r te sy of P r e ss on E N E RF LEX and Pet r o -C anada
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 3/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
© 2006 and 2014 HDC Human Development Consultants Ltd.
All ri ght s r e s e r v ed . No part of this publication may be copied, reproduced, stored in a computer or retrieval system, published, distributed, or transmitted in any form or by any means whatsoever, including
without limitation by mechanical means, photo copying, recording, digital or electronic media, the Internet,or otherwise, without the express prior written permission of HDC Human Development Consultants Ltd.(HDC). HDC grants to the purchaser of a Single User License (as defined in the agreement with suchpurchaser) a limited license to store the electronic file(s) on one computer only and to make a singlepaper copy of this publication. HDC grants to the purchaser of a Site License (as defined in theagreement with such purchaser) a limited license to store the electronic file(s) on one local area network server accessible by individual users' computers at one site or location only and to make paper copies ofthis publication for a company’s employees at the same site or location only. Each site or location mustpurchase a separate Site License for employees at that site. HDC grants the purchaser of a CorporateLicense (as defined in the agreement with such purchaser) a limited license to store the electronic file(s) on its intranet and on computers at company sites or locations and to make paper copies for any or all employees. Nothing in the foregoing restricts, amends or abrogates the provisions of the agreementbetween HDC and the purchaser of the applicable license. Any copying or use other than pursuant tosuch a license is illegal. For further information, please consult the applicable license agreement.
This publication is designed to provide general information regarding the sub ject matter covered. Carehas been taken to ensure the accuracy of the information and that the instructions contained in this publication are clear and reflect sound practice. The user understands that HDC is not providingengineering services. The user understands that any procedures (task steps) that are published or referenced may have to be modified to comply with specific equipment, work conditions, company standards, company policies and practices, legislation, and user qualifications. HDC does not make any representations, guarantees, or warranties of any kind whatsoever with respect to the content hereof andthe results to be achieved by implementing the procedures (task steps) herein. To the maximum extentpermitted by applicable law, in no event shall HDC be liable for any damages whatsoever (includingwithout limitation, direct or indirect damages for personal in jury, damages to the environment, damages tobusiness property, loss of business profit, or any other pecuniary loss). The use of the information andprocedures (task steps) herein is undertaken at the sole risk of the user.
ISBN 1-55338-040-1
Canadian Cataloguing in Publication Data
1. Pipelines—Equipment and supplies. I. HDC Human Development Consultants.TP757.F48 2005 665.7’44 C2005-906879-5
This training kit consists of the following parts:
Training Module and Self-Check Knowledge Check and Answer Key Blank Answer Sheet
Performance Check ExerciseJob Aid
Published by HDC Human Development Consultants Ltd.
Published in Canada
HDC Human Development Consultants Ltd.
Website: www.hdc.ca E-mail: [email protected] Phone: (780) 463-3909
Augu s t , 2014
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 4/25
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 5/25
Contents Training Objectives 1
1 Introduction 1
2 Heat Medium Components 7
2.1 Heater Shell 7
2.2 Produced Gas Flow Coil 8
3 Combustion Components 12 3.1 Fuel Gas Supply 12
3.2 Fuel Gas Conditioning System 16
3.3 Burner Fuel Gas 17
3.4 Burner Assembly 21
3.5 Fire Tube Assembly 27
4 Combustion Safety Controls 28
4.1 Hazardous / Upset Conditions that Shut Down the
Line Heater 29
4.2 Pneumatic Combustion Safety Controls 29
4.3 Microprocessor-Based Combustion Safety Controls 32
5 Site Layouts 37
5.1 Gas Wellsites 37
5.2 Gathering System Sites 39
6 Choke Operation 40
Augu s t , 2014 Pa g e i of ii
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 6/25
Augu s t , 2014 Pa g e ii of ii
Contents (continued)
7 Site Systems and Equipment 41 7.1 Cold-Climate Enclosure Building 41
7.2 Chemical In jection Systems 44
7.3 Downhole Heat String 44
7.4 Flow Measurement 46
7.5 Combustible Gas, Toxic Gas, and Fire Detection 48
7.6 SCADA (Supervisory Control and Data
Acquisition) System 49
7.7 Electrical Power System 51
7.8 Emergency Shutdown (ESD) Pushbuttons 52
8 Line Heater Safety 52
8.1 Safety While Traveling to the Line Heater Site 52
8.2 Safety at the Line Heater Site 53
8.3 Safety at the Line Heater Building 57
8.4 Safety When Leaving the Line Heater Site 58
9 Operating Variables 58
10 Prepare Line Heater for Startup 59
10.1 Investigate Line Heater Shutdown 59
10.2 Restart Line Heater 61
11 Light Line Heater Burner Manually 61
12 Self Check 66
13 Answer Key 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 7/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
Training
Objectives
Upon completion of this training kit, you will be able to:
Describe the purpose and importance of indirect-fired line
heaters
Describe line heater:
components and their function
combustion safety controls
Describe line heater site layouts
Describe line heater site systems and equipment
Describe line heater safety
Describe manual lighting of line heater burner
Describe line heater operating variables and operations
monitoring
Troubleshoot line heaters
1 Introduction Indirect-fired line heaters are used to heat natural gas before
the gas is shipped by pipeline for processing or for distribution
to residential and industrial customers.
During shipping, processing, and distribution, the natural gas
cools as:
heat is lost to cooler surroundings (e.g., a subsurface gas pipeline loses heat to the surrounding soil)
the pressure of the gas is reduced
Gas cooling can cause problems downstream on the pipeline:
the formation of hydrates which can block the pipeline (see
the textbox on page 4 about hydrates and their hazards)
hydrates formed in meters can cause inaccurate readings
the chilling of downstream equipment:
in mechanical equipment (e.g., meters, regulators, and
valves), cold temperatures may prevent lubricatedinternal components from operating effectively
in gas analysis instrumentation, cold temperatures may
contribute to inaccurate sampling results
Augu s t , 2014 Pa g e 1 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 8/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
Figure 1 —Typical Line Heater Locations in Natural Gas Processing/ Distribution
Augu s t , 2014 Pa g e 2 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 9/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
Indirect-fired line heaters heat the natural gas to prevent
hazardous hydrate blockages and frozen downstream
equipment.
Line heaters are typically installed:
at gas wellsites where the high wellhead pressure must be
reduced so that gas can flow via lower pressure piping to a
downstream gas plant. A ma jor drop in gas pressure causes
significant cooling of the gas to the point where hydrates
could form. Line heaters are installed at the site to heat the
gas to prevent hydrate formation.
along gas gathering system pipelines that link remote gas
fields to gas processing plants. Gas cools as it passes
through the pipeline and loses heat to the surrounding
subsoil. Line heaters along gas gathering system pipelines
reheat the gas to prevent hydrates from forming.
at city gate stations where local distribution companies
purchase, meter, regulate, and odorize the processed
natural gas received from transmission pipelines. The city
gate station’s pressure regulators reduce the gas pressure
from its high transmission line pressure to the lower local
distribution line pressure. Line heaters at city gate stations
provide enough heat to prevent chilling of downstream
equipment.
This module focuses on the operation of indirect-fired line
heaters at gas wellsites and along gas gathering system
pipelines.
Figure 2 — Indirect-Fired Line Heater atWellsite(C ou r te sy of P r e ss onE N E RF LEX and Pet r o - C anada )
Augu s t , 2014 Pa g e 3 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 10/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
Hydrates and Their Hazards
Hydrates are a mixture of water and gas that forms crystals under certain temperature
and pressure conditions. In a hydrate, gas molecules (such as methane, ethane,
propane, butane, hydrogen sulphide, and carbon dioxide) are embedded inside a
lattice of water molecules. Hydrate crystals deposit on solid surfaces and restrict gas
flow. Hydrates can plug valves, meters, instruments, and flow lines.
Hydrates:
- can form at high pressure, even when the temperature
of the flowing gas is above the freezing point of water
- can form when free water condenses in the gas stream
- tend to form at sharp bends in flow lines and at locations where the pressure drops. However, hydrates can occur
anywhere the temperature drops below the hydrate
formation point.
Hydrate formation can be prevented by:
- operating at high gas temperatures
- operating at low gas pressures
- operating at a lower water content
- in jecting a hydrate inhibitor, such as methanol
Preventing hydrates from forming is important:
- Clearing hydrate blockages is a high-risk activity. Incorrect hydrate removal can
cause pipeline/equipment rupture and put people in harm’s way.
- Hydrate blockages interrupt business: a hydrate blockage means that gas is unable
to flow.
TEMPERATURE
HYDRATE "TRIANGLE"
HYDRATE P R E S S U R
EF R
E E W A T E R
Indirect-Fired Line Heater ––Operating Principle
In an i nd ir e c t -fired line heater, a fire tube immersed in a heat
medium (HM), such as glycol, heats the HM (Figure 3). Thenatural gas passes through a flow coil that is also immersed in
the HM bath and is heated indirectly.
NOTE In a d ir e c t -fired line heater, the fire tube is immersed in the
product being heated.
Augu s t , 2014 Pa g e 4 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 11/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
Augu s t , 2014 Pa g e 5 of 77
NOTE In this module, the terms li ne heate r and heate r refer only to
indirect-fired line heaters.
Figure 3 ––Line Heater Operating Principle
The fire tube heats the HM bath as follows:A fire tube is submerged in the lower part of the HM bath. A
flame travels down the fire tube and transfers heat to the
HM. Cooled combustion gases flow from the fire tube and
rise up a stack.
As the HM’s temperature increases, its density decreases to
create thermal circulation in the bath:
Hot, less dense HM rises to the upper part of the shell.
The gas flowing in the gas flow coil absorbs heat from
the HM.
The HM’s temperature decreases and its density
increases. The cooled HM sinks to the bottom of the
shell to be reheated.
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 12/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
Line Heater Application and Site Requirements
A line heater must be appropriate for site conditions: it must be
able to heat the gas enough to prevent hydrate formation.
Line heaters are usually skid-mounted and can be transferred
between sites. Before a line heater is transferred to a new site,
your company will ensure that:
the heater’s design specifications match conditions at the
new site
the heater and its components comply with regulatory
requirements for the new site
This module describes line heaters that are correctly designed
for site conditions and meet regulatory requirements.
Indirect-Fired Line Heater ––Operator’s Role
Careful monitoring and control of indirect-fired line heaters
contribute to the safe and efficient operation of the heater and
prevents hydrate formation in downstream piping. Operations
include:
monitoring operating variables (temperature, pressure, bath
level, flow) to assess /optimize heater operation
starting up and shutting down the heater
troubleshooting heater problems and rectifying minor problems
promptly reporting ma jor problems
Additional Operator responsibilities are described in Section 10.
Module Contents
For indirect-fired line heaters, this module describes:
heat medium components
combustion components
combustion safety controls site layouts
site systems and equipment
safety
line heater burner lighting
operating variables and operations monitoring
troubleshooting
Augu s t , 2014 Pa g e 6 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 13/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
Augu s t , 2014 Pa g e 7 of 77
2 Heat Medium Components This section describes the indirect-fired line heater’s shell and
produced gas flow coil.
NOTE In this module:
the term p r odu c ed ga s refers to the natural gas flowing
through the coil and being heated
the term fue l ga s refers to the gas that fuels the burner
the term i n s t r u m entat i on ga s refers to the natural gas or
propane used to operate pneumatic controls
2.1 Heater Shell
The heater shell is a horizontal, cylindrical vessel that operates
at atmospheric pressure. The shell holds the large volume of
HM that transfers heat from the fire tube to the produced gas
flow coil. The heater shell has two end flanges:
the produced gas flow coil is installed through one end
flange
the fire tube is installed through the other end flange
WARNING
For colder climates, the shell may be insulated. On older line
heaters, asbestos may have been used for insulation. Follow your company procedures for handling asbestos.
Expansion Tank
The heater shell has a top expansion tank (also called a s u r ge
tan k or r e s e r v o ir ). The tank has sufficient volume:
to ensure that the heater shell is completely filled with HM
(i.e., the liquid fully covers the produced gas flow coil)
to accommodate HM expansion when the HM temperature
increases during cold startup
The expansion tank has a top hatch (thief hatch) that serves as
both an HM fill port and a vent/breather. Because the shell can
only withstand atmospheric pressure, the hatch’s vent/breather
provides both overpressure and vacuum protection:
Venting prevents shell rupture:
During line heater startup, the HM is heated to operating
temperature and expands. Air is pushed out the hatch.
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 14/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
Augu s t , 2014 Pa g e 8 of 77
In case the flow coil ruptures, venting protects the shell
from overpressure rupture.
Breathing prevents shell vacuum collapse. After the line
heater is shut down, the HM cools and contracts. Air is
drawn in through the hatch to compensate for the decrease
in HM volume.
NOTE For line heaters that have w ate r baths, the expansion tank
minimizes water vapor loss. This type of expansion tank is
known as a w ate r s a v e r . The lower temperature at the top of
the expansion tank condenses the steam rising off the liquid
surface.
Heating Medium
The HM is either water or a glycol-water solution. A glycol-
water mixture has a lower freezing point and a higher boiling
point than water. The type of HM used depends on the climate
and required heating:
Water is used in hot climates where the HM does not have
to be protected from freezing. When using a water bath, a
line heater is operated below water’s boiling point to protect
against boiling off the bath water.
Distilled water may be used in colder climates. Compared
to water with impurities, distilled water freezes at a lower temperature.
Glycol-water bath solutions are used:
in cold climates where the bath must not freeze (in case
the line heater shuts down during cold weather
operations)
in any climate where a high bath temperature is required
The water and glycol-water solutions used in line heaters are
treated with corrosion inhibitors to prevent internal fouling and
corrosion. Your company may stipulate that:
a specific glycol-water mixture be used instead of vehicle
antifreeze
HM be sampled regularly to verify glycol / water
concentration, freezing/boiling points, and corrosion inhibitor
strength
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 15/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
The level of the heat medium is determined by two factors:
The fire tube and gas flow coils must be covered
Some empty space is required for thermal expansion
Follow the manufacturer’s recommendations for the required
level of the heat medium.
2.2 Produced Gas Flow Coil
The produced gas flow coil (also called the tube bundle) is a
removable length of piping installed above the fire tube in the
HM bath. Pressurized produced gas from the wellhead or
pipeline is directed through the flow coil for heating.
The gas flow coil must always be completely submerged in theHM during line heater operation. Keeping the coil submerged
ensures that the produced gas in the coil is effectively heated.
The coil must remain submerged even after the line heater is
shut off and has cooled. Remaining submerged ensures that
the coil is not exposed to the corrosive effects of the air (drawn
in through the vent/breather during cool down).
Engineering and/or regulatory codes dictate how the produced
gas flow coil is manufactured, pressure-tested, and re-tested/
inspected during the coil’s service life to ensure the coil canwithstand the high gas pressures.
The configuration of the coil depends on both:
the number of heating stages needed by the produced gas
heating application (either one or two stages)
the number of coils needed to handle the produced gas flow
rate (either one coil for low flow rates or multiple parallel
coils for higher gas flow rates)
Heating Stages
One heating stage is used on line heaters which must provide
only a moderate temperature increase (such as those on
gathering system pipelines).
Figure 4 on the following page show a one heating stage line
heater.
Augu s t , 2014 Pa g e 9 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 16/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
Figure 4 —One-StageProduced Gas Flow Coil
Two heating stages are used on line heaters which must
provide a great amount of heating to counter the intense
cooling caused by a large pressure reduction. (Large pressure
reductions commonly occur at sites where the wellhead gas
pressure must be reduced to match lower gathering system
pressure.) On two-stage line heaters (see Figures 5 and 6), the
coil provides a preheating stage befo r e the pressure reduction
and a reheating stage afte r the pressure reduction. (Preheating
the gas before a large pressure reduction ensures that the
cooling caused by the pressure drop does not chill the gas to
below hydrate-formation temperature.)
The produced gas flows through the two-stage heater as
follows:
the produced gas flow enters the preheat coil and is heated
the heated produced gas flow leaves the preheat coil and
passes through the pressure reduction valve (choke)
after pressure reduction (and resulting cooling), the
produced gas flows into the line heater’s reheat coil, is
heated to the final temperature, and then exits the line
heater. (The reheat coil is also known as the post-heat coil.)
For line heaters equipped with preheat and reheat coils:
The preheat coil is built to withstand higher pressure than
the reheat coil.
The configuration of the pressure reduction valve (choke)
between the preheat and reheat coils can vary:
Augu s t , 2014 Pa g e 10 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 17/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
The valve may be a manual valve whose body is
immersed in the HM bath.
The valve may be an external control valve that is
automatically positioned as part of a wellhead pressure
control or flow control strategy to maintain flow and/or
pressure setpoint (as described in Section 6).
NOTE For a detailed description of process control and control loop
strategies, refer to these HDC training kits:
D e sc ri be Ba s i c In s t r u m entat i on and C ont r o l St r ateg i e s
D e sc ri be P r o c e ss C ont r o l M ode s and P r o c e ss C ont r o l
T e c hno l og y
Figure 5 —Two-StageProduced Gas Flow Coil
Refer to the next page for a picture of a two stage gas coil and
choke.
Number of Produced Gas Coils
Depending on the gas flow to be heated, a line heater’s
produced gas coil may consist of a single coil or multiple,
parallel coils:
single coil. A single coil may be sufficient to heat a small
gas flow. A single coil is configured as a spiral-wound
bundle or as a tube-type bundle (where the coil makes
numerous passes back and forth before leaving the line
heater).
Augu s t , 2014 Pa g e 11 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 18/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
Figure 6 —Line Heater with Two-Stage Produced Gas Coil and Choke(C ou r te sy of La r s en & D’ Ami c o M fg. Ltd. )
multiple, parallel coils. To heat a large gas flow, the flow to the line heater branches outside of the heater to feed
multiple, parallel, tube-type coils. After passing through the
heater, the flows recombine.
3 Combustion Components The burner directs a flame into the submerged fire tube to heat
the HM. The following components support the heater’s
combustion operation (see Figure 7):
fuel gas supply fuel gas conditioning system
burner fuel gas train
burner assembly
fire tube assembly
flame arrestor / wind box
Augu s t , 2014 Pa g e 12 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 19/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
3.1 Fuel Gas Supply
A line heater needs a reliable source of fuel gas. The fuel gas
source may be:
a drawoff from the line heater produced gas outleta natural gas utility distribution network or nearby gas
processing plant
a propane storage system
Figure 7 —Line Heater’s Combustion Components
Drawoff from Line Heater Outlet
The produced gas heated in the gas flow coil may be of
sufficient quality to support efficient combustion. In this case, a
slipstream of heated produced gas is withdrawn downstream of
the line heater. The produced gas may contain toxic
contaminants at trace levels that do not impair reliable
combustion. However, some contaminants are hazardous /toxic,
even at trace levels. Refer to Section 8.3 for safety precautions
at line heater sites.
Augu s t , 2014 Pa g e 13 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 20/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
Augu s t , 2014 Pa g e 14 of 77
In applications where produced gas is used as the fuel gas
source, the fuel gas drawoff may be equipped with:
a manual isolation block valve
a pressure regulator to reduce the gas pressure
WARNING
When produced gas is used as fuel gas, the fuel gas typically
does not contain a leak detection odorant. Although the fuel
gas may have a petroleum odor, don’t assume that you will be
able to smell a fuel gas leak.
Natural Gas Utility or Nearby Gas Plant
If the produced gas is not suitable, fuel gas may have to be
supplied from offsite. Two sources are:
commercial-quality natural gas piped from a gas utility distribution network
sales-quality natural gas from a nearby gas plant
NOTE At some remote gas plants, a slipstream of sales gas is
withdrawn to supply equipment in the surrounding gas fields.
In applications where the fuel gas arrives from offsite, the fuel
gas piping may be equipped with:
a manual isolation block valve
an ESD (emergency shutdown) valve to close automatically in case of a site emergency
a pressure regulator to reduce the gas pressure to an
intermediate pressure
a flowmeter to record fuel gas consumption
WARNING
Find out if the fuel gas at your site is odorized:
Fuel gas arriving from an offsite location may contain a leak
detection odorant.
Fuel gas from a gas utility is typically odorized, whereas
fuel gas from a gas processing plant may not be. Don’t
assume that you will be able to smell a fuel gas leak.
Propane Storage System
If the produced gas is not suitable for use as fuel gas, another
option is to use propane supplied from a storage system. The
propane storage system consists of an outdoor propane
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 21/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
storage tank that holds a large volume of liquid propane under
pressure. The propane is withdrawn from the tank using either:
propane li qu i d drawoff (for larger capacity systems)
propane v apo r drawoff (for smaller capacity systems)
Propane Liquid Drawoff
Propane liquid flows or is pumped from the bottom of the tank
through the tank’s manual liquid isolation valve. The propane
liquid is then heated in a specialty heater known as a propane
vaporizer.
Propane Vapor Drawoff
Propane vapor leaves the top of the tank through the tank’s
manual isolation valve and is directed through a regulator to
reduce the propane pressure.
A propane tank configured to supply propane vapor may have
difficulty supplying sufficient vapor during cold weather. A
propane tank’s ability to discharge vapor declines as the
outdoor temperature drops and the tank’s propane level drops.
To prevent an interruption in propane vapor flow, the propane
tank may be winterized with an external flameless heater (a
catalytic heater, described in Section 7.1). The heater provides
radiant heat to the tank’s wall to ensure sufficient propane
vapor.
Propane System Monitoring
The Operator checks the propane system to ensure continued
fuel gas supply:
monitors propane storage tank pressure and requests a
propane refill, if necessary
confirms that the propane system’s valves are correctly
configured
during the winter, confirms the operation of the propane
tank’s heater and flow of propane vapor from the tank
WARNING
At sites where propane is used as fuel gas, your personal
combustible gas detector must be able to detect:
propane fuel gas leaks
methane produced gas leaks
Consult your company’s health and safety practices.
Augu s t , 2014 Pa g e 15 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 22/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
3.2 Fuel Gas Conditioning System
All fuel gas undergoes conditioning (see Figure 7):
fuel gas preheating
fuel gas scrubbingadditional fuel gas filtration
Fuel Gas Preheating
The fuel gas passes through a preheat coil immersed in the HM
bath. After heating, the fuel gas flow branches and flows
through pressure regulators in the main burner and pilot burner
supply lines. Preheating the fuel gas before it flows through the
pressure regulators prevents hydrates from forming.
Fuel Gas Scrubbing
Liquids entrained in the fuel gas must be removed to prevent:
poor burner operation; the liquids may not burn consistently:
the burning liquids may produce a smoky flue gas
exhaust
the liquids may not burn and may pool at the bottom of
the firebox housing. This pooled liquid may drain out of
the firebox flame arrestor, creating a fire hazard. The
pooled liquid may suddenly ignite or explode.
discharge of flammable droplets out the top of the flue stack
which may ignite surrounding vegetationliquid entry into instrumentation lines. Liquids interfere with
the operation of pneumatic controls and instrumentation.
The fuel gas scrubber is a small separator where liquids in the
incoming fuel gas settle to the bottom and the gas rises to the
top outlet.
In case of a high liquid level in the scrubber, the scrubber’s
protective controls stop the flow of fuel gas, shutting down the
line heater burner. The scrubber’s high level protective controls may consist of:
an internal float ball that rises with the liquid until the ball
seals off the scrubber’s fuel gas outlet
a float level switch that is triggered at a preset liquid level to
stop the flow of fuel gas by closing a shutoff valve.
Augu s t , 2014 Pa g e 16 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 23/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
The scrubber’s drain valve depends on the liquid content of the
fuel gas:
At sites where the fuel gas normally contains liquid, the
scrubber has a drain valve that automatically opens at a
preset level to empty the scrubber to a liquid drain system.
At sites where the fuel gas does not normally contain
liquids, the scrubber may have only a manual drain valve.
Because liquid accumulation in the scrubber is abnormal,
any liquid would be drained manually to a portable container
and disposed by the Operator. The Operator must perform
liquid drainage/disposal in accordance with company safety
procedures and company / regulatory waste/effluent disposal
policies.
The fuel gas scrubber has a pressure safety valve (PSV) that
opens to relieve excessive pressure to prevent scrubber
rupture. Overpressurizing of the scrubber can be caused by
upstream regulator failure.
Additional Fuel Gas Filtration
Some line heaters may be equipped with fuel gas filtration,
depending on the contaminant(s) to be removed:
To remove solids, a metal mesh strainer or a particulate
filter is used. The strainer’s removable mesh element can
be cleaned and reinstalled; a particulate filter’s internal elements are replaceable.
To remove liquid mist, a coalescing filter is used. The
coalescing filter’s elements are replaceable.
3.3 Burner Fuel Gas
The burner fuel gas piping/ valving assembly:
receives conditioned fuel gas
branches to direct the fuel gas to the heater’s main burner
and pilot burner controls the flow of fuel gas to ensure safe operation of the
heater’s main burner and pilot burner
The specific fuel gas valving/ control configuration is determined
by regulatory and insurance requirements and company
policies.
Augu s t , 2014 Pa g e 17 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 24/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
The more stringent requirements incorporate a higher level of:
safety redundancy
burner safety controls to automate burner operation and the
burner’s safe startup/ shutdown
instrumentation to enable local and remote monitoring
This section describes fuel gas valving; Section 4 describes
how the valving is controlled as part of safe line heater
operation, startup, and shutdown. Figure 8 shows the main
burner and pilot burner fuel gas flows.
Figure 8 —Main Burner and Pilot Burner Fuel Gas Flows
Augu s t , 2014 Pa g e 18 of 77
7/21/2019 Indirect Fired Heater Training Module
http://slidepdf.com/reader/full/indirect-fired-heater-training-module 25/25
D escri b e a nd O p era t e
I nd irec t-F ire d Li n e H ea t ers
Augu s t , 2014 Pa g e 19 of 77
Fuel Gas Flow to the Main Burner
Conditioned fuel gas flows to the burner fuel gas train and
passes through the following components to feed the main
burner:a manual block valve used to isolate the line heater from
the fuel gas supply when the line heater is shut down
a pilot gas drawoff. As described later, this drawoff may be
located either upstream or downstream of the burner safety
shutoff valve.
a pressure regulator that reduces the fuel gas pressure to
the optimum main burner pressure. The regulator is typically
equipped with a pressure gauge.
one or two main burner safety shutoff valves that
automatically closes to shut off the fuel gas flow duringabnormal operation. Shutting down the flow prevents an
accumulation of fuel gas, which could lead to a line heater
explosion. Abnormal operation includes: