Current and Voltage (potential)

Instrument transformers

Instruction for installation, use and maintenance

Page 2: Indoor supporting current transformers TPU 4x.xx

2 1VLM000610 Rev.8, en 2011.04.26

Content:

1. Service conditions …………………………………………………………… 3

2. Technical details ……………………………………………………………. 3

3. Instruction for Installation ………………………………………………….. 5

General Information …………………………………………………… 5

Safety Instructions …………………………………………………… 5

Mounting ………………………………………………………………. 5

Primary connection …………………………………………………… 6

Secondary connection ……………………………………………….. 7

Capacitive voltage indicator (divider) ………………………………. 8

Fuses ………………………………………………………………….. 9

4. Instruction for use …………………………………………………………… 9

Routing test report …………………………………………………… 9

5. Instruction for maintenance ………………………………………………… 9

6. Transport and storage ……………………………………………………… 9

7. Disposal ………………………………………………………………………. 10

8. Handling with the transformer ……………………………………………… 10

9. Normative references ……………………………………………………… 10

Appendix 1. Example of secondary terminal marking ……………………… 11

Appendix 2. Wiring diagrams ………………………………………………… 13

Appendix 3. Damping ferroresonance for VT; VT-Guard ………………….. 17

Appendix 4. Handling with transformer ……………………………………… 19

Appendix 5. Dimensional drawings ………………………………………….. 21

Page 3: Indoor supporting current transformers TPU 4x.xx

3 1VLM000610 Rev.8, en 2011.04.26

Instruction for installation, use and maintenance for Current and Voltage (potential) transformers

This installation, use and maintenance guide is valid for current and voltage transformers operating in outdoor or indoor conditions.

These instructions are valid for Current transformer type: TPU; TPE; TPO; TP; TTR; BB;

BBO; KOKS; KOFA; IHBF

Voltage transformers types: TJE, TJC; TDC; TDO; TJO; TJP; TDP; KGUG; KGUGI; KRED

1. Service conditions

Indoor transformers

The transformers should be mounted in dry indoor conditions where the ambient air is not significantly polluted by dust, smoke, corrosive gases, vapours or salt.

The transformers are designed for standard ambient temperature between –5 C and

+40 C. The altitude for use should be lower than 1000 m above the sea level. The transformers may be used also in higher or lower ambient temperatures and higher altitudes when agreed between the manufacturer and purchaser.

Outdoor transformers

The transformers should be mounted in outdoor conditions where the ambient air may be polluted by dust, smoke, corrosive cases, vapours or salt.

The transformers are designed for standard ambient temperature between –40C and

+40 C. The average value of the ambient temperature, measured over a period of 24 hours,

should not exceed 35C.

2. Technical details

The technical details for each individual transformer are mentioned on the rating plate fastened on the transformer. Values mentioned on the rating plate must not be exceeded. Markings used on the rating plate are as follows:

Example of Indoor current transformer label:

Page 4: Indoor supporting current transformers TPU 4x.xx

4 1VLM000610 Rev.8, en 2011.04.26

Where: 1VLT1234567890 serial number + barcode TPU 40.13 transformer type code or.n. 12240 order number 50Hz rated frequency 200-400/1/1 A +CD rated transformer ratio + capacitive divider 1S1-1S2 terminal marking for core number 1, first tap (2S1-2S2 core 2) 1S1-1S3 terminal marking for core number 1, second tap (2S1-2S3 core 2) 5VA rated output 0.5FS5, 5P15 accuracy classes Ck-PE capacitive voltage divider ( see page 8.) 7,2/20/60 kV highest voltage for equipment / power-frequency withstand voltage / rated lightning-impulse voltage IEC 60044-1 referred standard(s) 50(1s) rated short time thermal current (thermal time) 125kA rated dynamic current 40°C ambient temperature 2002 year of production E temperature class

Example of Indoor Voltage transformers label:

Where: 1VLT1234567890 serial number + barcode TJC 4 Transformer type code or.n. 270303 order number 50Hz rated frequency

6600:3/100: 3/100:3 V rated voltage ratio a-n terminal marking for first secondary winding da-dn terminal marking for residual (open-delta) winding 30VA rated output 0.5, 6P accuracy classes 7,2/20/60 kV highest voltage for equipment / power-frequency Withstand voltage / rated lightning-impulse voltage IEC 60044-2 referred standard 40-65°C ambient temperature 2002 year of production E temperature class

Page 5: Indoor supporting current transformers TPU 4x.xx

5 1VLM000610 Rev.8, en 2011.04.26

3. Instruction for installation

General information Instrument transformer is an electrical equipment and the electrical installation shall be done by skilled person only. National legislation can set down the minimum age and the criteria for competence of skilled persons working on, with, or near an electrical installation. Where is not the national legislation requirements for competence, the criteria shall be used at least according to EN 50110-1.

Safety instructions

1. Always consider transformer as a part of the circuit to which it is connected, and do not touch the leads and terminals or other parts of the transformer unless they are known to be grounded.

2. Always ground the metallic bases of instrument transformer. 3. Always ground one secondary terminal of the transformer, except if the windings of

voltage transformer are connected to open delta. Residual voltage windings connected to open delta must have dn terminal earthed only on one of three transformers (earthing screws at dn terminals of others two transformers have to be removed). When the secondary of transformer is interconnected, there should be only one grounded point to prevent accidental paralleling with system grounding wire. In case of disconnection from the ground, the grounding screw has to be removed from the secondary terminal. Connection between secondary terminal and base plate (ground) is shown on the picture ―Crossection of double line terminal box―

4. Always short-circuit the secondary of the current transformer, which is not currently in use to prevent secondary voltages which may be hazardous to personnel or damaging to the transformer’s secondary. The secondary like this must be additionally grounded.

5. Never short-circuit the secondary terminal of a voltage transformer even this is not in use. A secondary short-circuit will cause the unit to overheat and fail in a very short period of time.

6. Protection of single pole insulated voltage transformers against feroresonance phenomena is stated in appendix 3. – Damping of the feroresonance in Voltage transformers type range TJx.

7. In case of the current transformer with voltage indication (coupling electrode included) is secondary terminal box equiped with PE terminal, which is connected with earthing screw to the base plate, which must be generally earthed.

Connection between secondary terminal and base plate is shown on the picture ―Crossection of single line terminal box―

Attention: Terminal PE must be always earthed, this is hold generally, even if the base plate is removed. In case of disassembling the base plate, producer doesn’t warranting the earthing.

Mounting

Following information is general and some details can differentiate according to type and variants of transformers. It is necessary to combine it with other technical and marketing specifications like catalogues, dimensional drawings and rating plate for specific transformer type.

Indoor current and voltage transformers

The mounting position of the indoor transformer can be freely chosen. The transformer is fixed using the mounting base with four screws M10 and washers. Fastening must be done on a smooth surface.

There is a M8 screw for earthing the transformer on the base plate.

Page 6: Indoor supporting current transformers TPU 4x.xx

6 1VLM000610 Rev.8, en 2011.04.26

Outdoor current and voltage transformers

The mounting position of the outdoor transformer is only horizontal. The other position can be agreed with the supplier. The transformer is fixed using the mounting base (VT) with four screws M10 and washers or two U profiles (CT) with M12 screws. Fastening must be done on a smooth surface.

There is a M12 screw for grounding of current transformer and M8 screw for grounding of voltage transformer.

Primary connection

Primary terminals of the current transformer are made of cooper and they are silver or tin plated. There are M12 (CT) and M10 (VT) screws used for fastening of primary conductor to the terminal. For primary reconnectable transformers the ratio can be reconnected by changing position of the links fixed by M8 screws without removing already fitted primary conductors.

Maximum allowed torques for screw connections of current transformers:

Screw Max. torque [Nm] Min. torque [Nm]

M5 3.5 2.8

M6 4 3

M8 20 16

M10 20 16

M12 70 56

Maximum allowed torque for screw connection of voltage transformer is 20 Nm. Maximum allowed cantilever strength is: Voltage transformers 2000 N. Current transformers 5000 N.

In case of Bus CT, there must be always connected CT shielding to the primary bar. Connection must be done at least on one side of the CT. One example of KOKS 12 shielding connection is described on the picture

Page 7: Indoor supporting current transformers TPU 4x.xx

7 1VLM000610 Rev.8, en 2011.04.26

Outdoor CT primary cables or busbars must be connected on the primary flag (not directly to the primary terminal) see the picture on the right side. Cross-section of the connected cables or busbars must be designed according to the Primary current and Primary short-circuit current (in accordance to IEC 60044-1). Recommended current density is for Cu connection 3A/mm2 for Primary current and 180A/mm2 for Short-circuit current.

Secondary connections

The terminals, screws, nuts and washers are made of stainless steel. Secondary grounding screws and secondary terminal fastening screws are made of nickel-plated brass.

The secondary terminal cover box for indoor use is made from the plastic and provided with three detachable threaded inserts Pg16. The terminals are provided with M5 screws for secondary wiring connection and with through going holes for direct earthing of the secondary circuit by M5 screws. The terminal cover is seal able.

The secondary cover for outdoor CT is made of epoxy resin and provided with one insert Pg21. The secondary cover for outdoor VT is made of plastic and provided with two insert Pg21. Degrees of IP protection Indoor transformers: IP40, or IP30 for transformers TTR, BB, KOKS Outdoor transformers: IP54

For terminal marking see appendix 1.

Example of current transformers terminal boxes

TJE, TJC,TDC TJC7 TJC,TDC

Page 8: Indoor supporting current transformers TPU 4x.xx

8 1VLM000610 Rev.8, en 2011.04.26

TJP,TJC,TDC TJO7 TJO6,TDO6

Example of voltage transformers terminal boxes

Cross section of double line secondary terminal box

Capacitive voltage indicator (divider)

The transformer can be supplied with the capacitive voltage indicator on the request. Integrated voltage detection system is coresponding to Separble Voltage Detection System according to IEC 61234-5. It is integrated coupling electrode connected to secondary terminal (terminal Ck). Electrode act as a condensator where dielectric between electrode and primary winding (C1), or electrode and ground ( C2) is epoxy. If the electrode is connected to indication device ( not part of delivery – it is part of switchgear ) it works as indication of voltage presence – more in IEC 61234-5

There are two possible solutions: a. HR – Indicator complies with the IEC 61234-5 standard for high resistive

voltage indicators, without any other specification b. CE – Where the values of capacity C1 and C2 are measured. C1 is the

capacitance between primary winding and Ck terminal and C2 is the capacitance between grounded parts and CK terminal. These values are mentioned on the rating plate.

CE capacity according to nominal voltage Ub (kV) C1 (pF) C2 (pF)

3 – 5,5 28 – 55

20 - 90

5,5 – 7,2 23 – 40

10 – 13,8 19 – 33

13,8 – 17,5 13 – 23

20 – 24 10 - 18

Page 9: Indoor supporting current transformers TPU 4x.xx

9 1VLM000610 Rev.8, en 2011.04.26

Fuses

The fuse can be a part of a supply of voltage transformers with fuse. We can supply following fuses:

0.3A – 12 and 24 kV products……….fuse type JT6 specially designed for voltage

transformers. For U1n>6600:3 V 0.6A – 12 kV products ……… ………fuse type JT6 specially designed for voltage

transformers 2A – 6.3A all products up to 24 kV …IEC fuses manufacturer SIBA / ABB 2A products for 36kV ………..IEC fuses manufacturer BUSSMANN

For safety fuse replacement see Instruction for installation, use and maintenance for Voltage (potential) transformers Fuse replacement (1VLM000614).

4. Instruction for use

Current and Voltage instrument transformers are used: - to convert large currents or voltage in the primary circuit to an appropriate level for

secondary circuit equipment (relays and meters) - to insulate primary and secondary circuit from each other to protect the secondary

equipment from the harmful effects of large current or voltage appearing during the operation (short circuits)

The use of current or voltage transformer for other purpose then described above is forbidden if not agreed with the producer.

Routine test report

Together with instrument transformer are delivered: - routine test report - two rating plates (one plastered on the transformer and one free)

The following information can be included on the request. These are free of charge. - theoretical current/voltage errors and phase displacement values - theoretical excitation curves

There are additional extra paid reports which can be supplied on request: - accuracy test report - magnetizing curve ( for current transformers ) - additional labels (if more then 2) - verification tests

5. Instruction for maintenance

Excessive dust or other kind of pollution must be brushed off the transformer. Polluted transformers can be cleaned with spirit, petrol or toluene.

Traces of arcs and minor surface damages can be easily removed with sandpaper after which the surface is to be treated by applying a thin layer of silicone paste on it.

Instruction for repairing greater surface damages must be requested from the manufacturer.

Page 10: Indoor supporting current transformers TPU 4x.xx

10 1VLM000610 Rev.8, en 2011.04.26

6. Transport and storage

The permissible transport and storage temperature is from –40 C to +70 C. During transport and storage the transformers must be protected against direct sunshine. The transformers are delivered fastened to a transport pallet.

7. Disposal

Materials used in instrument transformers are considered as materials without dangerous environmental impact and materials are not toxic. Disposal of instrument transformers is controlled by national legislation of communal waste.

8. Handling with the transformers

Handling with the transformer is described in the Appendix 4.

9. Normative references

IEC60044-1… Instrument transformers – Current transformers IEC60044-2… Instrument transformers – Voltage transformers IEC61243-5… Voltage detectors – Voltage detecting systems (VDS) IEC60529…… Degrees of protection provided by enclosures (IP Code) ISO12100…… Safety of machinery — Basic concepts, general principles for design EN 50110-1 …Operation of electrical installations

Current and Voltage transformers are designed, tested and produced according to

international or national standards required by custommers and agreed by producer. Specific standard is always mention on the Rating plate of transformer

For example these standards:

IEC 60044-1; IEC 60044-2 ; IEC 60044-6 AS 60044-1; AS 60044-2 AS 1243-1982; AS 1675-1986 ČSN 351301; ČSN 351302; ČSN 351361 ČSN EN 60044-1; ČSN EN 60044-2 ; ČSN EN 60044-6 IEEE Std C57.13.6-2005 ANSI C57.13-1978 CSA Std CAN3-C13-M83 GOST 1516.3-96; GOST 7746-2001 BS 3939:1973 ; BS EN 60044-1

If it is agreed between custommer and producer is possible to deliver also other standard or standards which are mention above with different revision.

Page 11: Indoor supporting current transformers TPU 4x.xx

11 1VLM000610 Rev.8, en 2011.04.26

Appendix 1. Examples of secondary terminal marking for cast terminal box for current transformers

No tap 1s1 1s2 1s1 1s2 Ck PE

1 tap 1s1 1s2 1s3 1s1 1s2 1s3 Ck PE

2 taps 1s1 1s2 1s3 1s4 1s1 1s2 1s3 1s4 Ck PE

3 taps 1s1 1s2 1s3 1s4 1s5 1s5

1s1 1s2 1s3 1s4 Ck PE

4 taps 1s1 1s2 1s3 1s4 1s5 1s6 1s5 1s6

1s1 1s2 1s3 1s4 Ck PE

No tap 1s1 1s2 2s1 2s2 1s1 1s2 2s1 2s2 Ck PE

1 tap 1s1 1s2 1s3 2s1 2s2 2s3 1s3 2s3

1s1 1s2 2s1 2s2 Ck PE

2 taps 1s3 1s4 2s3 2s4 1s3 1s4 2s3 2s4

1s1 1s2 2s1 2s2 1s1 1s2 2s1 2s2 Ck PE

3 taps 1s4 1s5 2s4 2s5

1s1 1s2 1s3 2s1 2s2 2s3

No tap 1s1 1s2 2s1 2s2 3s1 3s2 1s2 2s2 3s2

1s1 2s1 3s1 Ck PE

1 tap 1s3 2s3 3s3 1s2 1s3 2s3 3s2 3s3

1s1 1s2 2s1 2s2 3s1 3s2 1s1 2s1 2s2 3s1 Ck PE

2 taps 1s3 1s4 2s3 2s4 3s3 3s4

1s1 1s2 2s1 2s2 3s1 3s2

No tap 1s2 2s2 3s2 4s2 1s2 2s2 3s2 4s2

1s1 2s1 3s1 4s1 1s1 2s1 3s1 4s1 Ck PE

1 tap 1s2 1s3 2s3 3s2 3s3 4s3

1s1 2s1 2s2 3s1 4s1 4s2

No tap 1s2 2s2 3s2 4s2 5s2

1s1 2s1 3s1 4s1 5s1

No tap 1s2 2s2 3s2 4s2 5s2 6s2

1s1 2s1 3s1 4s1 5s1 6s1

2nd line of terminal -terminal not earthed

1st line of terminal -terminal earthed

Two cores

4 cores 4 cores with CD

One core

Two cores with CD

One core with CD

3 cores 3 cores with CD

6 cores 6 cores with CD

5 cores 5 cores with CD

Page 12: Indoor supporting current transformers TPU 4x.xx

12 1VLM000610 Rev.8, en 2011.04.26

Examples of secondary terminal marking for cast and assembled (phoenix) terminal box for Voltage transformers

One pole insulated voltage transformer

1a 1n 2a 2n N PE

a n da dn N PE

Assembled secondary terminal (Phoenix)

2 measuring and residual

winding

2 measuring double rations

winding

2 ratios measuring and

residual winding

Double pole insulated transformer

1a 1b 2a 2b PE

a1 a2 b PE

a1 a2 n N PE

a n N PE

1a 1n 2a 2n da dn N PE

1a1 1a2 1n 2a1 2a2 2n N PE

a1 a2 n da1 da2 dn N PE

a b PE

2 measuring windings

2 measuring windings

Measuring and residual

winding

2 ratios measuring winding

One measuring winding

2 measuring windings

2 measuring windings

2 ratios measuring winding

One measuring winding

Page 13: Indoor supporting current transformers TPU 4x.xx

13 1VLM000610 Rev.8, en 2011.04.26

Appendix 2.

Wiring diagram examples

Current transformers:

Page 14: Indoor supporting current transformers TPU 4x.xx

14 1VLM000610 Rev.8, en 2011.04.26

Wiring diagram examples

Voltage transformers:

Page 15: Indoor supporting current transformers TPU 4x.xx

15 1VLM000610 Rev.8, en 2011.04.26

Examples of current transformers connection

Page 16: Indoor supporting current transformers TPU 4x.xx

16 1VLM000610 Rev.8, en 2011.04.26

Examples of voltage transformers connection

Page 17: Indoor supporting current transformers TPU 4x.xx

17 1VLM000610 Rev.8, en 2011.04.26

Appendix 3.

Damping ferroresonance for voltage transformer type range TJx

TECHNICAL BACKGROUND Ferroresonance is a phenomenon usually characterized by over-voltages and very irregular

wave shapes and is associated with the excitation of one or more saturable inductors through capacitance in parallel with nonlinear inductor. The saturable inductor usually is present in the form of an instrument transformer, power transformer or reactor witch utilizes an iron core.

Ferroresonance of single-pole insulated transformers in unearthed network is one of the most common ferroresonance case. Depending on the supply voltage, capacitance and inductance the oscillation can be either periodic (over- or sub-harmonic or with fundamental frequency) or aperiodic.

Using damping resistor or VT guard in the residual voltage secondary, shown in Fig.1, can considerably reduce the risk for ferroresonance.

There is additionally factor that can in some cases reduce or totally eliminate the risk for ferroresonance and it is over-voltage factor. According to IEC standard is the rated over-voltage factor 1.9xUn/ 8h. Higher rated over-voltage factor shift the operating point towards lower flux values of voltage transformer. It results in smaller sensitivity of transformer to some kind of transients usually initiate ferroresonance.

RECOMMENDATION Rated voltage factor: We recommended using the voltage transformers with the over-voltage

factor in the range (2.5-3) xUn/8h. We cannot guarantee the value of the over-voltage factor if the requirements for the secondary winding are too high.

Damping resistor: See the recommended value of damping resistor below:

Voltage of residual winding

Value of Rdamp

Damping power

100:3 V 22 450 W

110:3 V 27 450 W

Fig.1.

Page 18: Indoor supporting current transformers TPU 4x.xx

18 1VLM000610 Rev.8, en 2011.04.26

VT Guard – function

1. VT-Guard description:

VT Guard is a preventive device against the ferroresonance phenomenon which may be triggered in power networks with ungrounded or not directly grounded neutral point. VT Guard should be used in cooperation with voltage transformers connected in open delta – more in User’s manual.

Important: Read the User’s manual before use.

2. Basic operating states:

Simple diagram

a) In case of full balance in a three-

phase network, there is zero voltage on an open delta winding (VT Guard terminals) Uo=0. No current flows through VT Guard. The device isn’t active.

b) In case of unbalance in a three-phase network, there is voltage on VT Guard terminals Uo>0.

If the Uo is lower than threshold voltage Ut (Ut =20-24V), then current

21)//( RRRR

UoI

EFIPTC flows

through the device. Total resistance value is higher then

100ohm and voltage Uo is max 24V in this case. Current flowing thorough the device has very low value.

c) In case Uo is higher then treshold voltage (ferroresonance), the „switching circuit― is switched on and current flows

trough RPTC//REFI and R1. Because of low values of these resistors there is steep increase of current and fast ferroresonance dumping. High current flows trough the device for short time, the PTC resistors arn’t warm up significantly.

d) In case Uo is higher then treshold voltage(earth fault), the „switching circuit― is switched on and current flows trough RPTC//REFI and R1. Because of low values of these resistors there is steep increase of current. High current flows trough the device and cause to warm up PTC resistors. PTC resistor increase their resistance (The resistance is proportional to flowing current). Current is limited. Time needed for worming up PTC resistors for Uo = 100V is approximately 1.4s. After earth-fault is removed, the PTC resistors cool-down (approximately 3 min). It is necessary to mount VT Guard in vertical position far from other thermal sources.

REFI

Page 19: Indoor supporting current transformers TPU 4x.xx

19 1VLM000610 Rev.8, en 2011.04.26

Appendix 4. Handling with transformers

There are few possibilities of handling:

1) Manual handling. Transformers are possible to handle by hands in case if the weight of the transformer is not higher than 25kg. Always use the glows in case of manual handling. For grasp of the transformers always use handling grip (see the picture), or the base of the transformer. Note. Types TJP or TDP never handle by gripping of the fuse holder – risk of break.

2) Handling by the belt Transformers where it is possible, from safety reasons, can be handling by hanging on the belts. Than the handling can be done by hanging of the transformer on the crane. Note: This system is recommended for types: TTR, TSR, BB(O), KOKS. Hanging systems for those types are visualized on pictures. Safety warning ! Lifting capacity of the belts and the crane has to be 200kg at. Always make sure that the belts hold safely on the crane and on the transformer. TTR, TSR KOKS, BB(O)

3) Handling by the self-locking hooks. With transformers which are equiped with handling grips is possible to handle by self-locking hooks hanging on the crane. With transformer without this handling grips is possible to grip the hooks under the base of the transformer. Note. This system is recommended for types: TPU, TPE, TJC, TJCL, TJP, TDP, TDC, KGUG, KGUGI. This handling system is vizualized on the pictures. Safety warning ! Lifting capacity of the hooks and the crane has to be 200kg at least. Always make sure that the hooks hold safely on the crane and on the transformer.

Page 20: Indoor supporting current transformers TPU 4x.xx

20 1VLM000610 Rev.8, en 2011.04.26

4) Handling by the self-locking hooks under primary screws. In case of indoor current transformers, which are equiped with primary terminal screws M12, there is possible to hanging the transformer on with self-locking hooks holding under primary. The handling can be done by hanging of the hooks on the crane. Note. This system is recommended for types:TPU, TPE, IHBF, KOFA, KAKV. This handling system is vizualized on the picture. Safety warning! Lifting capacity of the hooks and the crane has to be 200kg at least. Always make sure that the hooks hold safely on the crane and on the transformer.

5) Handling by the chain and loops. All transformers wich are equiped with the base plate is possible to handle by using chains and loops. Srew the loops (at least M10) into the baseplate and hang on the crane by chains as it is shown on the picture. Note. This system is recommended for most transformers with baseplate and with weight more than 40kg mainly for types: TPO, TJO, TDO, TDC7, TJC 7, TJP 7. This handling system is vizualized on the picture. Safety warning! Lifting capacity of the chains, loops and the crane has to be 200kg at least. Always make sure that the loops and chains hold safely on the transformer and chain s hold safely on the crane.

SAFETY WARNING: During the manipulation with transformer is necessary to follow safety work instructions. Never stay under the freight. Always make sure that the freight is safely locked on the crane and make sure that there is no risk of unexpected release or turnover of the freight. Note: Holding jigs, described in this chapters, are not a part of delivery.

Page 21: Indoor supporting current transformers TPU 4x.xx

21 1VLM000610 Rev.8, en 2011.04.26

Appendix 5. Dimensional Drawings´

Page 22: Indoor supporting current transformers TPU 4x.xx

22 1VLM000610 Rev.8, en 2011.04.26

Page 23: Indoor supporting current transformers TPU 4x.xx

23 1VLM000610 Rev.8, en 2011.04.26

Page 24: Indoor supporting current transformers TPU 4x.xx

24 1VLM000610 Rev.8, en 2011.04.26

Page 25: Indoor supporting current transformers TPU 4x.xx

25 1VLM000610 Rev.8, en 2011.04.26

Page 26: Indoor supporting current transformers TPU 4x.xx

26 1VLM000610 Rev.8, en 2011.04.26

Page 27: Indoor supporting current transformers TPU 4x.xx

27 1VLM000610 Rev.8, en 2011.04.26

Page 28: Indoor supporting current transformers TPU 4x.xx

28 1VLM000610 Rev.8, en 2011.04.26

Page 29: Indoor supporting current transformers TPU 4x.xx

29 1VLM000610 Rev.8, en 2011.04.26

Page 30: Indoor supporting current transformers TPU 4x.xx

30 1VLM000610 Rev.8, en 2011.04.26

Page 31: Indoor supporting current transformers TPU 4x.xx

31 1VLM000610 Rev.8, en 2011.04.26

Page 32: Indoor supporting current transformers TPU 4x.xx

32 1VLM000610 Rev.8, en 2011.04.26

Page 33: Indoor supporting current transformers TPU 4x.xx

33 1VLM000610 Rev.8, en 2011.04.26

Page 34: Indoor supporting current transformers TPU 4x.xx

34 1VLM000610 Rev.8, en 2011.04.26

Page 35: Indoor supporting current transformers TPU 4x.xx

35 1VLM000610 Rev.8, en 2011.04.26

Page 36: Indoor supporting current transformers TPU 4x.xx

36 1VLM000610 Rev.8, en 2011.04.26

Page 37: Indoor supporting current transformers TPU 4x.xx

37 1VLM000610 Rev.8, en 2011.04.26

Page 38: Indoor supporting current transformers TPU 4x.xx

38 1VLM000610 Rev.8, en 2011.04.26

Page 39: Indoor supporting current transformers TPU 4x.xx

39 1VLM000610 Rev.8, en 2011.04.26

Page 40: Indoor supporting current transformers TPU 4x.xx

40 1VLM000610 Rev.8, en 2011.04.26

Page 41: Indoor supporting current transformers TPU 4x.xx

41 1VLM000610 Rev.8, en 2011.04.26

Page 42: Indoor supporting current transformers TPU 4x.xx

42 1VLM000610 Rev.8, en 2011.04.26

Page 43: Indoor supporting current transformers TPU 4x.xx

43 1VLM000610 Rev.8, en 2011.04.26

Page 44: Indoor supporting current transformers TPU 4x.xx

44 1VLM000610 Rev.8, en 2011.04.26

Page 45: Indoor supporting current transformers TPU 4x.xx

45 1VLM000610 Rev.8, en 2011.04.26

Page 46: Indoor supporting current transformers TPU 4x.xx

46 1VLM000610 Rev.8, en 2011.04.26

Page 47: Indoor supporting current transformers TPU 4x.xx

47 1VLM000610 Rev.8, en 2011.04.26

Page 48: Indoor supporting current transformers TPU 4x.xx

48 1VLM000610 Rev.8, en 2011.04.26

Page 49: Indoor supporting current transformers TPU 4x.xx

49 1VLM000610 Rev.8, en 2011.04.26

Page 50: Indoor supporting current transformers TPU 4x.xx

50 1VLM000610 Rev.8, en 2011.04.26

Page 51: Indoor supporting current transformers TPU 4x.xx

51 1VLM000610 Rev.8, en 2011.04.26

TP xx.x

Page 52: Indoor supporting current transformers TPU 4x.xx

52 1VLM000610 Rev.8, en 2011.04.26

TTR 4x.xx

Page 53: Indoor supporting current transformers TPU 4x.xx

53 1VLM000610 Rev.8, en 2011.04.26

TTR 6x.xx

Page 54: Indoor supporting current transformers TPU 4x.xx

54 1VLM000610 Rev.8, en 2011.04.26

Page 55: Indoor supporting current transformers TPU 4x.xx

55 1VLM000610 Rev.8, en 2011.04.26

Page 56: Indoor supporting current transformers TPU 4x.xx

56 1VLM000610 Rev.8, en 2011.04.26

KOKS 24

Page 57: Indoor supporting current transformers TPU 4x.xx

57 1VLM000610 Rev.8, en 2011.04.26

Weight approx. 20kg

Weight approx. 18kg

Page 58: Indoor supporting current transformers TPU 4x.xx

58 1VLM000610 Rev.8, en 2011.04.26

Weight approx. 24kg

Weight approx. 18kg

Page 59: Indoor supporting current transformers TPU 4x.xx

59 1VLM000610 Rev.8, en 2011.04.26

Weight approx. 27kg

Weight approx. 19kg

Page 60: Indoor supporting current transformers TPU 4x.xx

60 1VLM000610 Rev.8, en 2011.04.26

Weight approx. 14kg

Weight approx. 14kg

Page 61: Indoor supporting current transformers TPU 4x.xx

61 1VLM000610 Rev.8, en 2011.04.26

Weight approx. 14kg

Page 62: Indoor supporting current transformers TPU 4x.xx

62 1VLM000610 Rev.8, en 2011.04.26

TJE 3 ; TJE 4

Weight approx. 11,5kg Creepage distance: 245mm

Page 63: Indoor supporting current transformers TPU 4x.xx

63 1VLM000610 Rev.8, en 2011.04.26

TJE 3.1 ; TJE 4.1

Weight approx. 11,5kg Creepage distance: 245mm

Page 64: Indoor supporting current transformers TPU 4x.xx

64 1VLM000610 Rev.8, en 2011.04.26

TJC 4 , TJC 5

Weight approx. 19kg

Page 65: Indoor supporting current transformers TPU 4x.xx

65 1VLM000610 Rev.8, en 2011.04.26

TJC 6

Weight approx. 36kg

Page 66: Indoor supporting current transformers TPU 4x.xx

66 1VLM000610 Rev.8, en 2011.04.26

TJC 6-G

Weight approx. 36kg

Page 67: Indoor supporting current transformers TPU 4x.xx

67 1VLM000610 Rev.8, en 2011.04.26

TJC 7

Weight approx. 47kg

Page 68: Indoor supporting current transformers TPU 4x.xx

68 1VLM000610 Rev.8, en 2011.04.26

Page 69: Indoor supporting current transformers TPU 4x.xx

69 1VLM000610 Rev.8, en 2011.04.26

TJC 7.0-G Weight approx.: 45kg

Page 70: Indoor supporting current transformers TPU 4x.xx

70 1VLM000610 Rev.8, en 2011.04.26

TDC 4, TDC 5

Weight approx. 20kG

Page 71: Indoor supporting current transformers TPU 4x.xx

71 1VLM000610 Rev.8, en 2011.04.26

TDC 6

Weight approx. 36kg

Page 72: Indoor supporting current transformers TPU 4x.xx

72 1VLM000610 Rev.8, en 2011.04.26

TDO 6

Page 73: Indoor supporting current transformers TPU 4x.xx

73 1VLM000610 Rev.8, en 2011.04.26

Page 74: Indoor supporting current transformers TPU 4x.xx

74 1VLM000610 Rev.8, en 2011.04.26

TJO 7

Weight approx. 52 kg

Page 75: Indoor supporting current transformers TPU 4x.xx

75 1VLM000610 Rev.8, en 2011.04.26

TJP 4.0 TJP 5.0 , fuse IEC 60282-1

Page 76: Indoor supporting current transformers TPU 4x.xx

76 1VLM000610 Rev.8, en 2011.04.26

TJP 4.0-F TJP 5.0-F , fuse IEC 60282-1

Weight: 27kg

Page 77: Indoor supporting current transformers TPU 4x.xx

77 1VLM000610 Rev.8, en 2011.04.26

TJP 4.1 , TJP 5.1 fuse JT6 300,600mA TJP 4.2 , TJP 5.2 fuse IEC 60282-1 TJP 4.1 , TJP 5.1 TJP 4.2 , TJP 5.2

Page 78: Indoor supporting current transformers TPU 4x.xx

78 1VLM000610 Rev.8, en 2011.04.26

Page 79: Indoor supporting current transformers TPU 4x.xx

79 1VLM000610 Rev.8, en 2011.04.26

TJP 6.2-G fuse IEC 60282-1 Weight approx.: 42kg

Page 80: Indoor supporting current transformers TPU 4x.xx

80 1VLM000610 Rev.8, en 2011.04.26

Page 81: Indoor supporting current transformers TPU 4x.xx

81 1VLM000610 Rev.8, en 2011.04.26

Page 82: Indoor supporting current transformers TPU 4x.xx

82 1VLM000610 Rev.8, en 2011.04.26

TDP 4.1 fuse JT6 300,600mA TDP 4.2 Fuse IEC 600282-1

Page 83: Indoor supporting current transformers TPU 4x.xx

83 1VLM000610 Rev.8, en 2011.04.26

TDP 6.1 fuse JT6 300,600mA TDP 6.2 Fuse IEC 600282-1

Page 84: Indoor supporting current transformers TPU 4x.xx

84 1VLM000610 Rev.8, en 2011.04.26

Page 85: Indoor supporting current transformers TPU 4x.xx

85 1VLM000610 Rev.8, en 2011.04.26

TDC 7 (KRED 36B1)

Weight approx: 72kg

Page 86: Indoor supporting current transformers TPU 4x.xx

86 1VLM000610 Rev.8, en 2011.04.26

The data and ilustrations in this catalogue are not binding.

We reserve the right to make changes of the content, in the course of technical development of the product.

ABB s.r.o. PPMV Brno Vídeňská 117 61900 Brno, Czech Republic E-mail: [email protected]

http://www.abb.cz/ejf

Page 87: Indoor supporting current transformers TPU 4x.xx

Indoor supporting current transformers TPU 4x.xx

Highest voltage for equipment [kV] 3,6 up to 12

Power frequency test voltage, 1 min. [kV] 10 up to 42

Lighting impulse test voltage [kV] 40 up to 95

Rated primary current [A] 10 - 3200

Rated short-time thermal current [kA] 2 up to 100…1s

Burdens, classes [VA/cl] 5-30 / 0.2-5 / 5P ; 10P(acc. to other param. - Ith)

Reconnectable (primary till 400-800 A) primary. or secondary

Description

The TPU 4x.xx transformers are cast in epoxy resin and designed for insulation voltages up to 12 kV. The 3,6 kVand 7,2 kV versions have the same dimensions as the 12 kV.For certain types of panels there is a need for extra long creepage distance on the transformers. For this purposeyou can order current transformers with „ribs on the top”.The transformers are manufactured in conformity with dimensions stated hereunder. The TPU4x.xx transformers aredesigned as single-turn or multi-turn versions, with one transformer ratio or with double ratio having the possibilityto be reconnectable on the primary or on the secondary side.The number of secondary windings (from 1 to 6 – max. 12 secondary terminals - 2 rows), depends on thecombination of the technical parameters (such as the accuracy class, burden, short-circuit current, overcurrentfactor…) and the transformer dimensions size.When agreed between the manufacturer and the customer the TPU transformers can be provided with the voltageindication system. For this purpose, however, it is necessary to know in what insulation level the transformers shallbe operated.The secondary windings are used for measurement or protection purposes, or for special use (testing winding, „X”or „PL“ classes windings). One terminal of each secondary winding used and one terminal of short-circuited and notused winding have to be earth during the transformer operation. The secondary windings are lead out into a cast-type secondary terminal box with plastic cover. The terminal cover is sealable. The terminals are provided with M5screws for the termination and with throughgoing holes for direct earting (first row of secondary terminals)The transformer can be mounted in any position. The transformer body is fixed by using four screws. Earth clampM8 is on the transformer base plate.

Technical data

Rated primary voltages are 3.6 kV; 7.2 kV; 12 kV Rated primary currents are 10;15;20;25;30;40;50;60;75;100;150;200;300;400;500;600;750;1000;1250;1500;2000;2500; 3000 and 3200 A;primary reconnectable modification max till 400-800 A.Other primary currents can also be agreed upon with the customer.Rated secondary currents...5 A; 1 A , others on request (possibility to combine different values in one transformer)Accuracy classes: 0,2, 0,2S, 0,5, 0,5S, 1, 3, 5 5P10, 5P15, 5P20, 10P10, 10P15, 10P20, others on request.Rated frequency ... 50 Hz or 60 Hz, others on requestThe transformers are designed and manufactured in conformity with the following standards and recommendations:IEC, VDE, ANSI, BS, GOST and CSN, others on request.Cantilever strength: 5 kNPermissable torques for screw connectionsM5 max /Nm/ …3,5 min /Nm/…2,8 M8 max /Nm/ …20 min /Nm/…16M12 max /Nm/ …70 min /Nm/…56

Page 88: Indoor supporting current transformers TPU 4x.xx

Dimensions

TPU 40.11TPU 43.11

Weight: 20-24 kg

drawing N: polarity44614000 P1 to sec. term.44614010 P2 to sec. term.

TPU 40.12TPU 43.12

Weight: 20-24 kg

drawing N: polarity44614020 P1 to sec. term.44614030 P2 to sec. term.

TPU 40.13TPU 43.13

Weight: 20-24 kg

drawing N: polarity44614040 P1 to sec. term.44614050 P2 to sec. term.

TPU 40.14TPU 43.14

Weight: 20-24 kg

drawing N: polarity44614060 P1 to sec. term.44614070 P2 to sec. term.

Page 89: Indoor supporting current transformers TPU 4x.xx

Dimensions

TPU 40.21TPU 43.21

Weight: 32-35 kg

drawing N: polarity44614080 P1 to sec. term.44614090 P2 to sec. term.

TPU 40.22TPU 43.22

Weight: 32-35 kg

drawing N: polarity44614100 P1 to sec. term.44614110 P2 to sec. term.

TPU 40.23TPU 43.23

Weight: 32-35 kg

drawing N: polarity44614120 P1 to sec. term.44614130 P2 to sec. term.

TPU 40.24TPU 43.24

Weight: 32-35 kg

drawing N: polarity44614140 P1 to sec. term.44614150 P2 to sec. term.

Page 90: Indoor supporting current transformers TPU 4x.xx

Dimensions

TPU 40.31TPU 43.31

Weight: 23-27 kg

drawing N: polarity44614160 P1 to sec. term.44614170 P2 to sec. term.

TPU 40.33TPU 43.33

Weight: 23-27 kg

drawing N: polarity44614180 P1 to sec. term.44614190 P2 to sec. term.

TPU 40.41TPU 43.41

Weight: 35-38 kg

drawing N: polarity44614200 P1 to sec. term.44614210 P2 to sec. term.

TPU 40.43TPU 43.43

Weight: 35-38 kg

drawing N: polarity44614220 P1 to sec. term.44614230 P2 to sec. term.

Page 91: Indoor supporting current transformers TPU 4x.xx

Dimensions

TPU 44.11TPU 45.11TPU 46.11TPU 47.11TPU 48.11

Weight: 25-28 kg

drawing N: polarity44614240 P1 to sec. term.44614250 P2 to sec. term.

TPU 44.13TPU 45.13TPU 46.13TPU 47.13TPU 48.13

Weight: 25-28 kg

drawing N: polarity44614260 P1 to sec. term.44614270 P2 to sec. term.

TPU 44.21TPU 45.21 TPU 46.21TPU 47.21TPU 48.21

Weight: 40-45 kg

drawing N: polarity44614280 P1 to sec. term.44614290 P2 to sec. term.

TPU 44.23TPU 45.23TPU 46.23TPU 47.23TPU 48.23

Weight: 40-45 kg

drawing N: polarity44614300 P1 to sec. term.44614310 P2 to sec. term.

Page 92: Indoor supporting current transformers TPU 4x.xx

Dimensions

TPU 44.31TPU 45.31TPU 46.31TPU 47.31TPU 48.31

Weight: 28-31 kg

drawing N: polarity44614320 P1 to sec. term.44614330 P2 to sec. term.

TPU 44.33TPU 45.33TPU 46.33TPU 47.33TPU 48.33

Weight: 28-31 kg

drawing N: polarity44614340 P1 to sec. term.44614350 P2 to sec. term.

TPU 44.41TPU 45.41TPU 46.41TPU 47.41TPU 48.41

Weight: 43-48 kg

drawing N: polarity44614360 P1 to sec. term.44614370 P2 to sec. term.

TPU 44.43TPU 45.43TPU 46.43TPU 47.43TPU 48.43

Weight: 43-48 kg

drawing N: polarity44614380 P1 to sec. term.44614390 P2 to sec. term.

Page 93: Indoor supporting current transformers TPU 4x.xx

Code designation -TPU current transformers

Standartized insulation levels of TPU 4x.xx transformers

3.6 / 21 / 45 kV 12 / 28 / 75 kV3.6 / 10 / 40 kV 12 / 35 / 75 kV7.2 / 27 / 60 kV 12 / 42 / 95 kV7.2 / 20 / 60 kV

Secondary terminal box (3 secondaries and voltage indicator)

a) Single-core design b) Double-core design c) Three-core design

d) Single-core design, e) Double-core design, f) Double-core design, reconnectable on the secondary side reconnectable on the secondary side reconnectable on the primary side

Marking of current transformer outlets - example

Secondary terminal box (2 secondaries and grounding screw)

TPU transformer with ribs

TPU x x . x x

voltage current dimension primary terminals4….up to 12 kV 0… to 600 A multiturn 1..short 148 mm, DIN 1..no pr.rec., no ribs /40x80mm, 80x80mm/

3…to 1250 A singleturn 2..long 148 mm, DIN 2..prim. rec., no ribs /40x80mm, 80x80mm/

4…to 1500 A singleturn 3..short,wide.. 184 mm 3..no pr.rec., with ribs /60x68mm, 80x80mm/

5…to 2000 A singleturn 4..long, wide…184 mm 4..prim. rec., with ribs /40x80mm, 80x80mm/

6…to 2500 A singleturn

7…to 3000 A singleturn

8…to 3200 A singleturn

Page 94: Indoor supporting current transformers TPU 4x.xx

Table 1

In 100 x In Category 125 x In Category 150 x In Category 200 x In Category 250 x In Category 300 x In Category 400 x In Category 500 x In Category 600 x In Category 800 x In Category 1000 x In Category( A ) ( kA ) ( kA ) ( kA ) ( kA ) ( kA )

10 2 K 2 K 2 K 2 K 4 G 4 G 4 G 6,3 D 6,3 D 8 C 10 B15 2 O 2 O 4 K 4 K 4 K 6,3 H 6,3 H 8 G 10 F 12,5 C 16 C20 2 R 4 N 4 N 4 N 6,3 K 6,3 K 8 J 10 H 12,5 F 16 E 20 C25 4 P 4 P 4 P 6,3 M 6,3 M 8 L 10 K 12,5 H 16 G 20 E 25 C30 4 R 4 R 6,3 O 6,3 O 8 N 10 M 12,5 J 16 I 20 G 25 D 31,5 C40 4 T 6,3 R 6,3 R 8 Q 10 N 12,5 M 16 L 20 J 25 G 31,5 E 40 C50 6,3 T 6,3 T 8 S 10 Q 12,5 N 16 N 20 L 25 I 31,5 G 40 E 50 C60 6,3 U 8 T 10 S 12,5 Q 16 O 20 N 25 K 31,5 I 40 G 50 D 63 B75 8 V 10 T 12,5 S 16 R 20 P 25 M 31,5 K 40 I 50 F 63 C

100 10 W 12,5 U 16 U 20 S 25 P 31,5 N 40 L 50 I 63 E150 16 W 20 U 25 T 31,5 R 40 M 50 M 63 I200 20 X 25 V 31,5 U 40 S 50 P 63 L250 25 W 31,5 V 40 U 50 R 63 N300 31,5 W 40 T 50 T 63 P400 40 X 50 V 63 S500 50 W 63 U600 63 V

( kA ) ( kA ) ( kA ) ( kA ) ( kA ) ( kA )

How to select transformer

A. Multiturn curent transformers – from 10 A to 600 A1. To select primary current In –table 12. To find Ithn according to In –table 13. To specify category (A,B,….Z)- table 14. To choose suitable measuring or protective parameters (burden, class, FS or limit factor…)-table 25. To select the height (H) of each core in the „category”column table 26. To calculate „Total height” for transformer and compare with the limits for short and long versions – see C.7. To specify type of current transformer8. If „total height” of transformer is more as limit (see C), you have to reduce some parameters or

secondary windings

B. Singleturn current transformers – from 400 A to 3200 A1. To select primary current In – table 32. To choose suitable measuring or protective parameters (burden, cless, FS or limit factor…)- table 33. To select the height (H) of each core in the column (according to In) – table 34. To calculate „Total height” for transformer and compare with the limits for short and long versions – see C5. To specify type of current transformer6. If „total height” of transformer is more as limit (see C), you have to reduce some parameters or

secondary windings

C. Possible combination of secondary windings (total H)1 - „Short” size - sum of the core heights, at maximum.....

1 secondary winding... 1002 secondary windings.. 803 secondary windings.. 604 secondary windings.. 40

2 - „Long” size - sum of the core heights, at maximum…..1 secondary winding... 2002 secondary windings..1803 secondary windings..1604 secondary windings..140

For models with voltage indication the core height for all the respective options should be reduced by20 mm.

Page 95: Indoor supporting current transformers TPU 4x.xx

Table 2

TPU 40... Category A B C D E F G H I J K L M N O P Q R S T U V W X Y ZAz 100 120 150 180 200 220 240 270 300 330 360 400 440 480 540 600 680 750 820 900 1000 1200 1500 1600 2000 2400

Zátěž Třída hight hight hight hight hight hight hight hight hight hight hight hight hight hight hight hight hight hight hight hight hight hight hight hight hight hightBurden Class H H H H H H H H H H H H H H H H H H H H H H H H H H

0.2 Fs5 --- --- --- --- 30 20 20 20 20 10 10 10 10 10 10 10 10 10 --- --- --- --- --- --- --- ---

0.2 Fs10 --- 100 80 40 30 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

0.5 Fs5 60 50 40 30 20 20 20 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

2.5 VA 0.5 Fs10 50 50 40 30 30 20 20 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

1 Fs5 60 50 40 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 10 10 --- --- --- --- --- ---

5 P 10 100 80 60 40 30 30 30 30 30 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

5 P 15 100 80 60 60 50 50 50 40 40 40 30 30 30 30 30 30 30 30 30 30 30 20 20 20 30 30

5 P 20 140 120 100 80 70 60 60 50 50 50 50 40 40 40 40 40 40 40 40 40 40 30 30 40 50 50

0.2 Fs5 --- --- 120 80 60 40 30 20 20 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 10 10

0.2 Fs10 --- 180 120 80 60 40 30 20 20 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 10 10

0.5 Fs5 100 80 60 40 30 20 20 20 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 10 10 10

5 VA 0.5 Fs10 100 80 60 40 40 30 30 20 20 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 10 10

1 Fs5 60 40 30 20 20 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 10 10 10 --- --- ---

5 P 10 120 100 80 60 50 50 40 40 40 40 30 30 30 30 30 20 20 20 20 20 20 20 20 20 20 20

5 P 15 160 140 100 80 80 70 60 60 50 50 50 40 40 40 30 30 30 30 30 30 30 30 30 40 30 30

5 P 20 200 180 140 120 100 100 100 80 80 70 70 60 60 50 50 50 50 40 40 40 40 40 40 40 50 50

0.2 Fs5 --- --- --- 100 80 80 60 50 40 40 30 30 20 20 20 20 20 20 20 10 10 10 10 10 10 10

0.2 Fs10 --- --- --- 100 80 80 60 50 40 40 30 30 20 20 20 20 20 20 20 10 10 10 10 10 10 10

0.5 Fs5 200 160 80 50 40 40 40 40 30 30 20 20 20 20 20 20 10 10 10 10 10 10 10 10 10 10

10 VA 0.5 Fs10 200 160 100 80 80 60 60 50 40 40 40 30 30 30 20 20 20 20 10 10 10 10 10 10 10 10

1 Fs5 80 80 60 50 40 40 30 30 30 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 10 10

5 P 10 --- 200 160 120 100 100 80 80 70 60 60 50 50 50 40 40 40 40 40 30 30 30 20 30 20 20

5 P 15 --- --- 200 180 160 140 120 120 100 90 90 80 70 70 60 60 50 50 50 40 40 40 40 50 50 50

5 P 20 --- --- --- --- 200 200 180 160 140 140 120 120 100 100 90 80 80 70 60 60 60 50 60 80 60 60

0.2 Fs5 --- --- --- 200 180 120 100 80 80 60 50 40 40 30 30 30 30 20 20 20 20 20 10 10 10 10

0.2 Fs10 --- --- --- 200 180 120 100 80 80 60 50 40 40 30 30 30 30 20 20 20 20 20 10 10 10 10

0.5 Fs5 200 160 120 80 70 60 60 50 40 40 40 40 30 30 30 20 20 20 20 20 10 10 10 10 10 10

15 VA 0.5 Fs10 200 160 120 80 70 60 60 60 50 40 40 40 40 40 30 30 20 20 20 20 10 10 10 10 10 10

1 Fs5 120 100 80 60 60 60 50 40 40 30 30 20 20 20 20 20 10 10 10 10 10 10 10 10 10 10

5 P 10 --- --- 200 180 160 140 120 120 100 90 90 80 70 70 60 60 60 50 50 40 40 40 40 40 40 40

5 P 15 --- --- --- --- --- 200 180 160 140 140 140 120 120 100 90 80 70 70 60 60 60 50 60 60 60 50

5 P 20 --- --- --- --- --- --- --- --- 200 180 180 160 160 140 140 120 120 100 100 100 100 90 90 80 100 90

0.2 Fs5 --- --- --- 200 200 180 160 140 120 100 60 50 40 40 40 30 30 30 20 20 20 20 10 10 10 10

0.2 Fs10 --- --- --- 200 200 180 160 140 120 100 60 50 40 40 40 30 30 30 20 20 20 20 10 10 10 10

0.5 Fs5 --- 200 160 120 100 80 80 60 60 60 50 40 40 30 30 30 20 20 20 10 10 10 10 10 10 10

20 VA 0.5 Fs10 --- 160 120 100 80 80 80 80 80 80 80 60 60 50 40 30 20 20 20 20 10 10 10 10 10 10

1 Fs5 160 160 120 80 80 80 60 60 50 40 40 30 30 20 20 20 20 20 10 10 10 10 10 10 10 10

5 P 10 --- --- --- 200 200 180 160 140 140 120 120 100 100 90 80 80 60 60 50 50 50 40 50 50 40 30

5 P 15 --- --- --- --- --- --- --- 200 180 180 160 140 140 120 120 120 100 100 80 80 80 60 80 80 80 70

5 P 20 --- --- --- --- --- --- --- --- --- --- --- --- 200 180 160 160 140 120 120 120 120 100 90 100 120 120

0.2 Fs5 --- --- --- --- 200 200 160 140 120 100 80 70 60 60 60 50 40 40 30 30 30 20 20 20 20 10

0.2 Fs10 --- --- --- --- 200 200 160 140 120 100 80 70 60 60 60 50 40 40 30 30 30 20 20 20 20 10

0.5 Fs5 --- --- 200 180 160 140 120 100 80 80 60 60 50 50 40 40 30 30 20 20 20 20 20 20 10 10

30 VA 0.5 Fs10 --- --- 200 180 160 120 100 100 80 80 60 60 60 60 50 40 40 30 30 20 20 20 20 20 10 10

1 Fs5 --- 200 160 120 100 100 100 80 80 60 60 50 50 40 30 30 20 20 20 20 20 20 10 20 10 10

5 P 10 --- --- --- --- --- --- --- --- 200 180 160 160 140 120 120 100 100 90 80 70 70 60 70 70 60 60

5 P 15 --- --- --- --- --- --- --- --- --- --- --- --- 200 200 180 160 140 140 140 120 120 100 120 100 140 120

5 P 20 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 200 180 180 160 160 160 160 140 --- ---

Example:

Curent transformer 100 / 5 / 5 A, 25 kA (DIN - without ribs):see table 1 ... category P (I n = 100 A, I thn = 25 kA)see table 2 ... category (column) P

1 core 15 VA 0,5 FS5 ... H = 201 core 15 VA 5P10 ... H = 60

Total ... H = 80 (short version)

see C ⇒ Type TPU 40.11

Page 96: Indoor supporting current transformers TPU 4x.xx

Table 3

TPU 41-48 Az 400 A 500 A 600 A 750 A 800 A 900 A 1000 A 1250 A 1500 A 2000 A 2500 A 3000 A 3200 AIthn 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 63 kA 63 kA 63 kA 80 kA 80 kA

Burden Class

0.2 Fs5 10 10 10 10 10 10 10 10 10 10 10 10 10

0.5 Fs5 10 10 10 10 10 10 10 10 10 10 10 10 10

0.5 Fs10 10 10 10 10 10 10 10 10 10 10 10 10 10

2.5 VA 1 Fs5 10 10 10 10 10 10 10 10 10 10 10 10 10

5 P 10 20 20 20 20 20 20 20 20 20 20 20 20 20

5 P 15 30 30 30 30 30 30 30 20 20 30 30 30 305 P 20 40 40 40 40 40 40 40 30 30 50 60 60 60

0.2 Fs5 20 20 20 20 10 10 10 10 10 10 10 10 10

0.5 Fs5 20 20 20 10 10 10 10 10 10 10 10 10 10

0.5 Fs10 30 20 20 20 10 10 10 10 10 10 10 10 10

5 VA 1 Fs5 10 10 10 10 10 10 10 10 10 10 10 10 10

5 P 10 40 40 30 30 30 30 30 30 20 20 20 20 20

5 P 15 70 60 50 40 40 40 40 40 40 40 40 40 405 P 20 100 90 70 60 50 50 50 50 50 50 60 60 60

0.2 Fs5 20 20 20 20 10 10 10 10 10 10 10 10 10

0.5 Fs5 20 20 20 10 10 10 10 10 10 10 10 10 10

0.5 Fs10 30 20 20 20 10 10 10 10 10 10 10 10 10

10 VA 1 Fs5 20 10 10 10 10 10 10 10 10 10 10 10 10

5 P 10 50 50 40 40 40 30 30 30 20 30 20 20 20

5 P 15 80 70 60 50 50 40 40 40 40 50 50 50 405 P 20 120 100 80 70 60 60 60 50 50 60 80 80 80

0.2 Fs5 40 30 20 20 20 20 20 20 10 10 10 10 10

0.5 Fs5 30 20 20 20 20 20 10 10 10 10 10 10 10

0.5 Fs10 40 30 20 20 20 20 10 10 10 10 10 10 10

15 VA 1 Fs5 20 20 20 10 10 10 10 10 10 10 10 10 10

5 P 10 80 70 60 50 50 40 40 40 30 40 40 40 30

5 P 15 120 90 80 70 60 60 60 50 50 60 60 60 605 P 20 160 140 120 100 100 100 100 90 80 120 120 120 120

0.2 Fs5 50 40 30 30 20 20 20 20 10 10 10 10 10

0.5 Fs5 40 30 30 20 20 10 10 10 10 10 10 10 10

0.5 Fs10 50 40 30 20 20 20 10 10 10 10 10 10 10

20 VA 1 Fs5 30 20 20 20 10 10 10 10 10 10 10 10 10

5 P 10 100 90 70 60 50 50 50 40 40 40 40 40 40

5 P 15 140 120 100 80 80 70 70 60 60 80 80 70 705 P 20 200 180 140 120 120 120 120 100 90 120 140 140 120

0.2 Fs5 70 60 40 30 30 30 30 20 20 10 10 10 10

0.5 Fs5 50 50 40 30 20 20 20 20 10 10 10 10 10

0.5 Fs10 50 50 40 30 30 20 20 20 20 10 10 10 10

30 VA 1 Fs5 50 40 30 20 20 20 20 20 10 10 10 10 10

5 P 10 160 120 100 80 80 70 60 60 50 60 60 50 50

5 P 15 --- 200 160 140 140 60 120 100 80 140 120 100 1005 P 20 --- --- --- 180 160 100 160 160 120 --- 200 180 180

Page 97: Indoor supporting current transformers TPU 4x.xx

Type Ithn/ldyn Ratio Burden Class FS/ALF Type Ithn/ldyn Ratio Burden Class FS/ALF[ kA ] [ A ] [ VA ] [ kA ] [ A ] [ VA ]

40,11 6,3/16 20//5 10 5P 15 40,11 40/100 400//5 30 5P 1540,21 6,3/16 20//5 20 5P 10 40,11 40/100 400//5/5 15/15 0,5/5P FS5/1540,21 6,3/16 20//5/5 15/15 0,5/5P FS5/10 40,11 50/125 400//5 15 5P 1540,21 12,5/31,5 20//5 10 5P 15 40,11 50/125 400//5/5 15/15 0,5/5P FS5/1540,21 12,5/31,5 20//5/5 15/15 0,5/5P FS5/540,21 16/40 20//5 10 5P 15 40,11 50/125 500//5 30 5P 1040,21 16/40 20//5/5 10/10 0,5/10P FS5/10 40,11 50/125 500//5/5 15/15 0,5/5P FS5/15

40,11 6,3/16 30//5 15 5P 15 40,11 50/125 600//5 30 5P 1040,11 6,3/16 30//5 20 5P 10 40,11 50/125 600//5/5 15/15 0,5/5P FS5/1540,21 6,3/16 30//5/5 15/15 0,5/5P FS5/1540,11 12,5/31,5 30//5 10 5P 15 41,11 50/125 400//5 10 5P 1040,21 12,5/31,5 30//5 20 5P 10 41,11 50/125 400//5/5 10/10 0,5/5P FS5/1040,21 12,5/31,5 30//5/5 15/15 0,5/5P FS5/1040,21 25/63 30//5 10 5P 15 42,11 50/125 600//5 20 5P 1040,21 25/63 30//5 15 5P 10 42,11 50/125 600//5/5 15/15 0,5/5P FS5/1040,21 25/63 30//5/5 10/10 0,5/5P FS5/10

43,11 50/125 750//5 15 5P 1540,11 6,3/16 50//5 15 5P 15 43,11 50/125 750//5 30 5P 1040,11 6,3/16 50//5 30 5P 10 43,11 50/125 750//5/5 15/15 0,5/5P FS5/1040,11 6,3/16 50//5/5 15/15 0,5/5P FS5/10 43,11 63/160 1000//5 10 5P 2040,11 16/40 50//5 10 5P 15 43,11 63/160 1000//5 20 5P 1540,11 16/40 50//5 20 5P 10 43,11 63/160 1000//5 30 5P 1040,21 16/40 50//5/5 15/15 0,5/5P FS5/15 43,11 63/160 1000//5/5 15/15 0,5/5P FS5/1040,21 31,5/80 50//5 10 5P 15 43,11 63/160 1250//5 15 5P 1540,21 31,5/80 50//5 20 5P 10 43,11 63/160 1250//5 30 5P 1040,21 31,5/80 50//5/5 15/15 0,5/5P FS5/10 43,11 63/160 1250//5/5 15/15 0,5/5P FS5/15

40,11 16/40 100//5 15 5P 15 44,11 63/160 1500//5 15 5P 1540,11 16/40 100//5/5 15/15 0,5/5P FS5/15 44,11 63/160 1500//5 30 5P 1040,21 31,5/80 100//5 15 5P 15 44,11 63/160 1500//5/5 15/15 0.5/5P FS5/1540,21 31,5/80 100//5/5 15/15 0,5/5P FS5/10

45,11 80/200 2000//5 15 5P 2040,11 31,5/63 200//5 15 5P 15 45,11 80/200 2000//5 30 5P 1540,11 31,5/63 200//5 30 5P 15 45,11 80/200 2000//5/5 15/15 0,5/5P FS5/1540,11 31,5/63 200//5/5 15/15 0,5/5P FS5/1540,11 40/100 200//5 15 5P 15 46,11 100/250 2500//5 15 5P 2040,11 40/100 200//5 30 5P 10 46,11 100/250 2500//5 30 5P 1540,11 40/100 200//5/5 15/15 0,5/5P FS5/10 46,11 100/250 2500//5/5 30/30 0,5/5P FS5/15

40,11 31,5/80 300//5 15 5P 15 47,11 100/250 3000//5 15 5P 1540,11 31,5/80 300//5 30 5P 10 47,11 100/250 3000//5 30 5P 2040,11 31,5/80 300//5/5 15/15 0,5/5P FS5/15 47,11 100/250 3000//5/5 30/30 0,5/5P FS5/1540,11 50/125 300//5 15 5P 15 48,11 100/250 3200//5 15 5P 1540,11 50/125 300//5 30 5P 10 48,11 100/250 3200//5 30 5P 2040,11 50/125 300//5/5 15/15 0,5/5P FS5/15 48,11 100/250 3200//5/5 30/30 0,5/5P FS5/15

Standartized transformers

Page 98: Indoor supporting current transformers TPU 4x.xx

Customer DateAddress Delivery requiredCountry Tel. Fax.Contact person E-mail

Current transformersProject ref.: Date Inquiry No.:

Offer No.:Um: kVIth: kA/1s Insulation level (BIL): kV/ kV/ kV

kA/3sfreq.: Hz Routine test certificates Idyn.: kA Additional name plate

Magnetisation curvesIndoor Remarks:Outdoor

Pos.: Pcs.:ratio (A) Class Burden (VA) ext 100% add. Requirment

core 1: ext 120%core 2: ext 150%core 3: ext 200%core 4: reconnectable Yes primary secondary

NoSupplier's remarks

Type

Unit price

Total priceComment

Pos.: Pcsratio Class Burden ext 100% add. Requirment

core 1: ext 120%core 2: ext 150%core 3: ext 200%core 4: reconnectable Yes primary secondary

NoSupplier's remarks

Type

Unit price

Total priceComment

ABB s.r.o.Org. Unit EJFDivision of Instrument Transformers Tel.: +420 5 4715 2602Vídeňská 117 +420 5 4715 2604619 00 Brno, Czech Republic Fax: +420 5 4715 2626E-mail: [email protected]://www.abb.cz/ejf

Order form TPU 4x.xx

A 3440-501-III/2001