industrial insulation · product performance and engineered value are only the most obvious...
TRANSCRIPT
1
All of which should make specifying them a lot easier. Product performance and engineered value are only the most obvious benefits that insulation offers a Power and Process Plant or Manufacturing Plant.
Insulation products also control process temperature, control condensation, and protect personnel. They make manufacturing processes more efficient, and give exposed piping and equipment a durable, finished appearance—and when those products are made by Knauf Insulation, they offer your facility an even higher performance level.
Knauf Insulation industrial insulation products have excellent thermal performance, lower installed cost and are more readily available than other conventional power and process insulation products.
2
Superior PerformanceKnauf Insulation set the industry standard for performance, by combining superior control and installation ease over heat loss and gain into such products as Knauf Insulation Earthwool® 1000° Pipe Insulation with ECOSE® Technology, which outperforms traditional rock mineral wool products in many applications.
Ease of InstallationEvery product we manufacture is designed to make installation easier, faster and more convenient. For large pipe or tank projects, the flexibility of our Earthwool Pipe & Tank Insulation makes it easier for installers to get a proper fit and a smooth, professional finish, especially on curved or irregular surfaces. And the unique manufacturing process we use for our Earthwool 1000° Pipe Insulation results in highly consistent density and a “layered” construction—making it easier to cut, notch out, and install.
Readily AvailableUnlike conventional industrial insulation materials, Knauf Insulation glass mineral wool products typically are in stock in our centrally located manufacturing plant, even our non-standard pipe insulations are available in less than 14 days from receipt of order. Distributors are located in every key market across North America.
3. Earthwool 1000° Pipe Insulation
5. Earthwool Redi-Klad® 1000° Pipe Insulation
7. Earthwool Pipe & Tank Insulation
9. KwikFlex® Pipe & Tank Insulation
11. Elevated Temperature Series
13. Elevated Temperature Blanket 1000°
14. Elevated Temperature Batt 1000° and HD Blanket 1000°
15. Elevated Temperature Panel 1000°
16. Elevated Temperature Board 1000°
17. Case Study: Renova Energy Ethanol Plant
20. Precautions & Application Guidelines
Table of Contents
3
DescriptionKnauf Insulation Earthwool 1000° Pipe Insulation is a molded, one-piece insulation made from inorganic glass mineral wool bonded with ECOSE Technology. It is produced in 3' lengths with or without a factory-applied jacket.
Application Earthwool 1000° Pipe Insulation can be used to insulate iron, austenitic stainless steel and copper piping in industrial applications. Earthwool 1000° Pipe Insulation is suitable for hot, cold, concealed and exposed piping systems, operating at temperatures from 0°F to 1000°F (-18°C to 538°C).
SPECIFICATION COMPLIANCES
United States
ASTM C547; Type 1, Type IV, Grade A
ASTM C585
ASTM C795
ASTM C1136 (jackets); Type 1, II, III, IV, VIII
HH-I-558C; Form D, Type III, Class 12; Class 13 (to 1000°F, 538°C)
NFPA 90A and 90B
MIL-I-2234D (except pH requirements)
MIL-I-24244D
NRC Reg. Guide 1.36 (certification needs to be specified at time of order)
Conforms to Marine Equipment European 1408/13
USCG 164. 109/4/1 (Unfaced)
Canada
CAN/ULC S102-M88
CGSB 51-GP-9M
CGSB 51-GP-52Ma (jacket)
Earthwool® 1000° Pipe InsulationWith ECOSE® Technology
4
• The Knauf Insulation rotary manufacturing process produces insulation with concentric inside diameters and consistent wall thicknesses, while making it easy to cleanly notch out sections.
• Earthwool® 1000˚ Pipe offers an extended temperature range—for all applications from 0˚ to 1000˚F.
• ECOSE® Technology bio-based binder eliminates non-renewable petroleum-based ingredients. No formaldehyde, no phenol, no acrylics.
Features & Benefits
TECHNICAL DATA
Earthwool® 1000° Pipe Insulation
Surface Burning Characteristics
UL/ULC Classified
Does not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with UL 723, ASTM E84, CAN/ULC S102-M88 and NFPA 255
Non-Combustible (ASTM E136) Product is non-combustible when tested in accordance with ASTM E136
Temperature Limitation(ASTM C411 & ASTM C447)
Up to 1000°F (538°C) at a maximum recommended thickness of 6 inches
Corrosiveness (ASTM C665) Will not accelerate corrosion on steel, copper or aluminum
Corrosion (ASTM C1617) The corrosion rate in mils/yr will not exceed that of 1 ppm chloride solution
Microbial Growth (ASTM C1338) Does not promote microbial growth
Water Vapor Sorption (ASTM C1104) Less than 0.2% by volume
Linear Shrinkage (ASTM C356) Negligible
Earthwool® 1000° Pipe Insulation
5
DescriptionKnauf Insulation Earthwool Redi-Klad 1000° Pipe Insulation is a multi-purpose, molded, one-piece glass mineral wool insulation bonded with ECOSE® Technology. Earthwool Redi-Klad comes with factory applied 5-ply weather and abuse resistant jacketing with self-sealing lap. When properly installed, Redi-Klad jacket provides a zero permeability rating. Earthwool Redi-Klad is produced in convenient 3' lengths with a matching 4" butt strip furnished for each 3' section. The installed product offers a finished appearance comparable to embossed aluminum.
ApplicationKnauf Insulation Earthwool Redi-Klad 1000° Pipe Insulation is designed for indoor and outdoor installation on industrial mechanical systems piping. Typical applications include, but are not limited to steam, condensate, process, chilled, and domestic water piping for new or retro-fit power generation, petrochemical, pulp and paper, institutional, and educational construction projects operating at temperatures from 0°F to 1000°F (-18°C to 538°C).
Earthwool Redi-Klad Product Forms and SizesProduced in 3' (914 mm) sections:• For iron pipe from 2" to 24" nominal pipe size
(51 mm to 610 mm)• For copper tube from 1¹⁄8" to 6¹⁄8" (29 mm to 156 mm)• Wall thickness from 1" to 6" (25 mm to 152 mm) in single layer
(for most sizes)
Packaging• Four convenient carton sizes for easy ordering, inventory
tracking and storage• Reinforced carton handles for strength and easy lifting• Bar-coded cartons for accurate shipments and tracking• Color-coded labels
Earthwool® Redi-Klad® 1000°Pipe Insulation
6
TECHNICAL DATA
Earthwool Glass Mineral Wool Pipe Insulation
Surface Burning CharacteristicsDoes not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with ASTM E84, CAN/ULC S102-M88, NFPA 90A and 90B, NFPA 255 and UL 723
Resists Microbial Growth(ASTM C1338, G21)
Does not promote microbial growth
Corrosiveness (ASTM C665) Does not accelerate corrosion on steel, copper or aluminum
Corrosion (ASTM C1617) The corrosion rate in mils/yr will not exceed that of 1 ppm chloride solution
Water Vapor Sorption (ASTM C1104) Less than 0.2% by volume
Linear Shrinkage (ASTM C356) Negligible
Redi-Klad® Clad Jacket and Tape
Surface Burning CharacteristicsDoes not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with UL 723
Surface Temperature Range Maximum use continuous use 300°F (149°C)
Application Temperature -10°F to 300°F (-23°C to 149°C)
Water Vapor Permeability (ASTM E96-05)
Zero-perm
Puncture Resistance (ASTM D1000) 35.4 kg, 189.3 N
Thickness 14.5 mils (0.0145")
Tensile (PTS-31) 68 lb./inch width, 306 N (31 kg)/25 mm
• Offers excellent resistance to heat loss or gain,
which saves energy and lowers operating costs
• A low thermal conductivity of 0.23 k at 75°F
mean temperature (0.33 k (SI) at 24°C
mean temperature)
• Self-closure tape eliminates need for banding,
screws and caulk
• Lightweight and easy to handle
• Low maintenance costs
• No off-site fabrication required
• Safe installation
• Fast, easy installation reduces installed costs
versus standard aluminum jacketing systems
• Properly installed, Redi-Klad® jacket provides a
zero perm vapor barrier
Features & Benefits
Earthwool® Redi-Klad 1000° Pipe Insulation
7
DescriptionKnauf Insulation Earthwool Pipe and Tank Insulation with ECOSE Technology is a semi-rigid glass mineral wool board in roll form faced with a factory applied FSK, ASJ+ vapor retarder or a glass mat facing. The glass wool is adhered perpendicular to the jacketing for flexibility and easy installation.
ApplicationKnauf Insulation Earthwool Pipe and Tank Insulation is typically used on tanks, vessels and large-diameter pipes. It can be used for any curved or irregular surfaces that require finished characteristics of rigid glass mineral wool insulation.
SPECIFICATION COMPLIANCES
United States
ASTM C795
NRC Reg. Guide 1.36 (Certification needs to be specified at time of order)
MIL-I-24244C
ASTM C1136 Type I, II, III, IV (ASJ+)
ASTM C1136 -Type II, IV (FSK)
ASTM C1393, Category 1
HH-B-100B (jackets) Type I and II (ASJ+)
HH-B-100B (jackets) Type II (FSK)
HH-I-558C; Form A, Class 3
TECHNICAL DATA
Earthwool Pipe & Tank Insulation with ECOSE® Technology
Temperature Range (ASTM C411)
Operating temperature to 850°F (454°C)
Compressive Strength (ASTM C165)
Not less than 120 PSF (5.75 kPa) at 10% deformation
Water Vapor Transmission(ASTM E96, Procedure A)
FSK, ASJ+ vapor retarders have a maximum vapor transmission rate of 0.02 perms
Puncture Resistance(ASTM C1136)
FSK Facing: 25
ASJ+ facing: 120
Resists Microbial Growth (ASTM C1338)
Does not promote microbial growth
Corrosiveness (ASTM C665) Does not accelerate corrosion on steel
Corrosion (ASTM C1617)The corrosion rate in mils/yr will not exceed that of the 5 ppm chloride solution
Surface Burning CharacteristicsDoes not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with ASTM E84, CAN/ULC S102-M88, NFA 90A and 90B, NFPA 255 and UL723
Linear Shrinkage (ASTM C356) Negligible
Earthwool® Pipe & Tank InsulationWith ECOSE® Technology
8
Pipe & Tank Insulation
• Flexible
• Easy to handle and fabricate
• No need to stock multiple sizes
• Various thicknesses are available to meet all
your pipe and tank insulation needs.
• Tough and durable
• Resists damage in shipment, during and after
installation
• Excellent thermal properties
Features & Benefits
STRETCH-OUTS*
NominalIron Pipe Size
Iron PipeOutside Diameter
Thickness
1" 25mm 1½" 38mm 2" 51mm 3" 76mm
10" 254 mm 10¾" 273 mm 401⁄8" 1019 mm 43¼" 1099 mm 463⁄8" 1178 mm 525⁄8" 1337 mm
12" 305 mm 12¾" 324 mm 463⁄8" 1178 mm 49½" 1257 mm 52¾" 1340 mm 59" 1499 mm
14" 356 mm 14" 356 mm 503⁄8" 1280 mm 53½" 1359 mm 565⁄8" 1438 mm 62 7⁄8" 1597 mm
16" 406 mm 16" 406 mm 565⁄8" 1438 mm 59¾" 1518 mm 627⁄8" 1597 mm 691⁄8" 1756 mm
18" 457 mm 18" 457 mm 627⁄8" 1597 mm 66" 1676 mm 691⁄8" 1756 mm 75½" 1918 mm
20" 508 mm 20" 508 mm 691⁄8" 1756 mm 723⁄8" 1838 mm 75½" 1918 mm 81¾" 2076 mm
22" 559 mm 22" 559 mm 75½" 1918 mm 785⁄8" 1997 mm 81¾" 2076 mm 88" 2235 mm
24" 610 mm 24" 610 mm 81¾" 2076 mm 847⁄8" 2156 mm 88" 2235 mm 943⁄8" 2397 mm
26" 660 mm 26" 660 mm 88" 2235 mm 911⁄8" 2315 mm 943⁄8" 2397 mm 1005⁄8" 2556 mm
28" 711 mm 28" 711 mm 943⁄8" 2397 mm 97½" 2477 mm 1005⁄8" 2556 mm 1067⁄8" 2715 mm
30" 762 mm 30" 762 mm 1005⁄8" 2556 mm 103¾" 2635 mm 1067⁄8" 2715 mm 1131⁄8" 2873 mm
32" 813 mm 32" 813 mm 1067⁄8" 2715 mm 110" 2794 mm 1131⁄8" 2873 mm 119½" 3035 mm
34" 864 mm 34" 864 mm 1131⁄8" 2873 mm 116¼" 2953 mm 119½" 3035 mm 125¾" 3194 mm
36" 914 mm 36" 914 mm 119½" 3035 mm 1225⁄8" 3115 mm 125¾" 3194 mm 132" 3353 mm
38" 965 mm 38" 965 mm 125¾" 3194 mm 1287⁄8" 3273 mm 132" 3353 mm 138¼" 3512 mm
40" 1016 mm 40" 1016 mm 132" 3353 mm 1351⁄8" 3432 mm 138¼" 3512 mm 1445⁄8" 3673 mm
42" 1067 mm 42" 1067 mm 138¼" 3512mm 141½" 3594mm 1445⁄8" 3673mm 150 7⁄8" 3832mm
THERMAL EFFICIENCY (ASTM C177)
Mean Temperature k k(SI)
100°F 38°C 0.26 0.037
200°F 93°C 0.35 0.050
300°F 149°C 0.45 0.065
400°F 204°C 0.57 0.082
500°F 260°C 0.75 0.108
FORMS AVAILABLE
Thickness Width Length
1" 25 mm
36" 914 mm
48' 14.63 m
1½" 38 mm 32' 9.75 m
2" 51 mm 24' 7.32 m
3" 76 mm 16' 4.88 m
Ther
mal
Con
duct
ivit
y (S
l Uni
ts )
(W/m
• ºC
)
0.70
0.60
0.50
0.40
0.30
0.20
0.101
0.086
0.072
0.057
0.043
0.029
0 10038
20093
300149
400204
500260
(˚F) (˚C)
Mean Temperature
Ther
mal
Con
duct
ivit
y (B
TU-i
n./h
r • ft
2 ºF)
9
DescriptionKnauf Insulation Kwik-Flex Pipe & Tank Insulation is a 48" wide semi-rigid glass mineral wool blanket, 2.5 pcf density, in roll form. It is available faced with a factory-applied ASJ+, FSK or PSK vapor retarder jacket. The glass mineral wool orientation provides excellent compressive strength while maintaining flexibility for ease of installation.
ApplicationKnauf Insulation Kwik-Flex Pipe & Tank Insulation is typically used on tanks, vessels, and large-diameter (greater than 10" pipes.) It can be used for any curved or irregular surfaces that require finished characteristics of rigid glass mineral wool insulation.
SPECIFICATION COMPLIANCES
United States
UL/ULC Classified (ASJ and FSK only)
ASTM C1393 Types I, II, IIIA, IIIB Category 2
ASTM C795
NRC 1.36
MIL-I-24244D
TECHNICAL DATA
Kwik-Flex® Pipe & Tank Insulation with ECOSE® Technology
Temperature Range (ASTM C411)
Operating temperature to 850°F (454°C)
Compressive Strength (ASTM C165)
Not less than 25 PSF (1.2 kPa) at 10% deformation
Water Vapor Transmission(ASTM E96, Procedure A)
FSK, ASJ+ and PSK vapor retarders have a maximum rate of 0.02 perms
Puncture Resistance(ASTM C1136)
FSK and PSK facing: 25
ASJ+ facing: 120
Resists Microbial Growth (ASTM C1338)
Does not promote microbial growth
Surface Burning Characteristics
UL/ULC Classified (ASJ+ and FSK only)
25/50 per ASTM E84 for PSK
Does not exceed 25 Flame Spread, 50 Smoke Developed when tested according to UL 723 and ASTM E84
Linear Shrinkage (ASTM C356)
Negligible
Corrosiveness (ASTM C665) Will not accelerate the corrosion of steel, copper, or aluminum
Corrosion (ASTM C1617)The corrosion rate in mils/year will not exceed that of the 5 ppm chloride solution
Kwik-Flex® Pipe & Tank Insulation
10
• Knauf Insulation Kwik-Flex® Pipe & Tank Insulation offers a unique combination of flexibility and compressive strength in a blanket form.
• Tough and durable, yet easy to handle and fabricate.
• Can be used for any curved or irregular surfaces that require the finished characteristics of rigid glass mineral wool insulation.
• Kwik-Flex Pipe & Tank Insulation has excellent thermal properties, with low thermal conductivity ratings to 850˚F (454˚C).
• Wraps tightly around curved and spiral surfaces, making installation quick.
• No need to stock multiple sizes
Kwik-Flex® Pipe & Tank Insulation
Features & Benefits
STRETCH-OUTS*
NominalIron Pipe Size
Iron PipeOutside Diameter
Thickness
1" 25mm 1½" 38mm 2" 51mm 3" 76mm
10" 254 mm 10¾" 273 mm 401⁄8" 1019 mm 43¼" 1099 mm 463⁄8" 1178 mm 525⁄8" 1337 mm
12" 305 mm 12¾" 324 mm 463⁄8" 1178 mm 49½" 1257 mm 52¾" 1340 mm 59" 1499 mm
14" 356 mm 14" 356 mm 503⁄8" 1280 mm 53½" 1359 mm 565⁄8" 1438 mm 62 7⁄8" 1597 mm
16" 406 mm 16" 406 mm 565⁄8" 1438 mm 59¾" 1518 mm 627⁄8" 1597 mm 691⁄8" 1756 mm
18" 457 mm 18" 457 mm 627⁄8" 1597 mm 66" 1676 mm 691⁄8" 1756 mm 75½" 1918 mm
20" 508 mm 20" 508 mm 691⁄8" 1756 mm 723⁄8" 1838 mm 75½" 1918 mm 81¾" 2076 mm
22" 559 mm 22" 559 mm 75½" 1918 mm 785⁄8" 1997 mm 81¾" 2076 mm 88" 2235 mm
24" 610 mm 24" 610 mm 81¾" 2076 mm 847⁄8" 2156 mm 88" 2235 mm 943⁄8" 2397 mm
26" 660 mm 26" 660 mm 88" 2235 mm 911⁄8" 2315 mm 943⁄8" 2397 mm 1005⁄8" 2556 mm
28" 711 mm 28" 711 mm 943⁄8" 2397 mm 97½" 2477 mm 1005⁄8" 2556 mm 1067⁄8" 2715 mm
30" 762 mm 30" 762 mm 1005⁄8" 2556 mm 103¾" 2635 mm 1067⁄8" 2715 mm 1131⁄8" 2873 mm
32" 813 mm 32" 813 mm 1067⁄8" 2715 mm 110" 2794 mm 1131⁄8" 2873 mm 119½" 3035 mm
34" 864 mm 34" 864 mm 1131⁄8" 2873 mm 116¼" 2953 mm 119½" 3035 mm 125¾" 3194 mm
36" 914 mm 36" 914 mm 119½" 3035 mm 1225⁄8" 3115 mm 125¾" 3194 mm 132" 3353 mm
38" 965 mm 38" 965 mm 125¾" 3194 mm 1287⁄8" 3273 mm 132" 3353 mm 138¼" 3512 mm
40" 1016 mm 40" 1016 mm 132" 3353 mm 1351⁄8" 3432 mm 138¼" 3512 mm 1445⁄8" 3673 mm
42" 1067 mm 42" 1067 mm 138¼" 3512mm 141½" 3594mm 1445⁄8" 3673mm 150 7⁄8" 3832mm
Additional 2” (51mm) to 4” (102mm) should be added for lap.
FORMS AVAILABLE
Thickness Width Length
1" 25 mm
48" 1219 mm
52' 15.85 m
1½" 38 mm 30' 9.14 m
2" 51 mm 26' 7.92 m
2½" 64 mm 21' 6.40 m
3" 76 mm 18' 5.48 m
THERMAL EFFICIENCY (ASTM C177)
Mean Temperature k k(SI)
75°F 24°C 0.24 0.035
100°F 38°C 0.25 0.036
200°F 93°C 0.32 0.046
300°F 149°C 0.39 0.056
400°F 204°C 0.49 0.070
500°F 260°C 0.61 0.088
0 200 400.20
.30
.40
.50
.60
.70
MEAN TEMPERATURE
.101
.086
.072
.057
.043
.029
93 149300
204500 (°F)260 (°C)
10038
THER
MAL
COND
UCTI
VITY
(S
I Uni
ts) (
W/m
• °C
)
THER
MAL
COND
UCTI
VITY
(B
TU-in
/hr •
ft2 • °
F)
11
Elevated Temperature SeriesWith ECOSE® Technology
PRODUCT DESCRIPTION APPLICATION
ET Blanket1000°
Lightweight, thermal insulation blanket (1.1 PCF, 17.6 kg/m³) bonded by ECOSE Technology
Industrial heating equipment up to 1000°F (538C°), such as industrial furnaces, marine applications and irregular surfaces
HD Blanket 1000°
Semi-rigid, thermal insulation (1.6 pcf, 25.6 kg/m³) bonded with ECOSE Technology
High-temperature marine applications, industrial furnaces, boilers, vessels and industrial ovens, where lighter-weight insulation is needed or flexible and/or semi-rigid high-temperature
insulations are needed for irregular surfaces
ET Batt 1000°Semi-rigid, thermal insulation (1.6 pcf, 25.6 kg/m³)
bonded with ECOSE Technology
High-temperature marine applications, industrial furnaces, boilers, vessels and industrial ovens, where lighter-weight insulation is needed or flexible and/or semi-rigid high-temperature
insulations are needed for irregular surfaces
ET Panel 1000°Semi-rigid, thermal insulation
(2.4 pcf, 38.4 kg/m3) board-like bonded with ECOSE Technology
Industrial heating applications up to 1000°F (538°C), such as high-temperature panel systems for ducts and precipitators, boilers, H-Bar systems, vessels and industrial ovens. It is ideal for use
in metal mesh blankets
ET Board 1000°Semi-rigid, thermal insulation (2.8 pcf, 44.9 kg/m³)
board-like bonded with ECOSE TechnologyIndustrial heating applications up to 1000°F (538°C), such as boiler walls, hot precipitators, hot
ductwork, cylindrical tanks, prefabricated panel systems, towers, stacks and industrial ovens
12
Elevated Temperature Series
SPECIFICATION COMPLIANCES
ET Blanket 1000° HD Blanket 1000° ET Batt 1000° ET Panel 1000° ET Board 1000°
United States
HH-I-558C; Form B, Class 7, 8 HH-I-558C; Form B, Type I, Class 7, 8 HH-I-558C; Form B, Type I, Class 7, 8 HH-I-558C; Form A, Class 1, 3HH-I-558C (Amend. 3); Form A, Class
1, 2, 3
MIL-I-22023D (except for pH requirements)
MIL-I-24244C MIL-I-24244C MIL-I-24244CMIL-I-22023D, Type III
(except for pH requirements)
– – – – MIL-I-24244C
USCG 164.109/18/1 USCG 164/109/18/1 USCG 164/109/18/1USCG 164.109/17/1
USCG 164 109/15/1
NRC Reg. Guide 1.36. (Certification needs to be specified at time of order)
NRC Reg. Guide 1.36. (Certification needs to be specified at time of order)
NRC Reg. Guide 1.36. (Certification needs to be specified at time of order)
NRC Reg. Guide1.36. (Certification needs to be specified at time of order)
NRC 1.36 (Certification needs to be specified at time of order)
ASTM C1139 Type I Grade 2, Type II Grade 2
ASTM C 1139 Type I Grade 3, Type 2 Grade 3
ASTM C 1139 Type I Grade 3, Type 2 Grade 3
ASTM C 1139 Type I Grade 5, Type II Grade 5
ASTM C1139, Type III
ASTM C553 Type 1, II – – – –
– – – – ASTM C612; Type IA, IB, II- category 1, III
– – – – ASTM C795
Conforms to Marine Equipment European 1408/13
Conforms to Marine Equipment European 1408/13
Conforms to Marine Equipment European 1408/13
Conforms to Marine Equipment European 1408/13
Conforms to Marine Equipment European 1408/13
CanadaCAN/ULC S102-M88 CAN/ULC S102-M88 CAN/ULC S102-M88 CAN/ULC S102-M88 ULC Classified, CAN/ULC S102-M88
CGSB 51-GP-11M CGSB 51-GP-11M CGSB 51-GP-11M CGSB 51-GP-10M CGSB 51-GP-10M
TECHNICAL DATA
ET Blanket 1000˚ HD Blanket 1000˚ ET Batt 1000˚ ET Board 1000˚ ET Panel
Surface Burning Characteristics
Does not exceed 25 Flame Spread, 50 Smoke Developed when tested in
accordance with UL 723, ASTM E84, and CAN/ULC S102-M88
Does not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with UL 723, ASTM E84, CAN/ULC S103-M88, NFPA 90A and
90B and NFPA 255
Does not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with UL 723, ASTM E84, CAN/ULC S103-M88, NFPA 90A and
90B and NFPA 255
Does not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with UL 723, ASTM E84, CAN/ULC S102-M88 and NFPA 255
Does not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with UL &23, ASTM E 84, CAN/ULC S102-M88, NFPA 90A and
90B and NFPA 255
Water Vapor Sorption (ASTM C1104)
0.1% or less by volume 0.1% or less by volume 0.1% or less by volume – 0.1% or less by volume
Temperature Limit (ASTM C411)
Up to 1000°F (538°C) at a maximum recommended thickness of 6"
Up to 1000°F (538°C) at a maximum recommended thickness of 6"
Up to 1000°F (538°C) at a maximum recommended thickness of 6"
Up to 1000°F (538°C)Up to 1000°F (538°C) at a maximum
recommended thickness of 6 inches
Microbial Growth (ASTM C1338)
Does not promote microbial growth Does not promote microbial growth Does not promote microbial growth Does not promote microbial growth Does not promote microbial growth
Corrosiveness (ASTM C665)
Does not accelerate corrosion on steel, copper or aluminum
Does not accelerate corrosion on steel, copper or aluminum
Does not accelerate corrosion on steel, copper or aluminum
Does not accelerate corrosion on steelDoes not accelerate corrosion on
aluminum, steel or copper
Corrosion (ASTM C1617)
The corrosion rate in mils/yr will not exceed that of the 5 ppm chloride
solution
The corrosion rate in mils/yr will not exceed that of the 5 ppm chloride
solution
The corrosion rate in mils/yr will not exceed that of the 5 ppm chloride
solution
The corrosion rate in mils/yr will not exceed that of the 5 ppm chloride
solution
The corrosion rate in mills/yr will not exceed that of the 5 ppm chloride
solution.
13
Storage • Protect material from water damage or other abuse. • Protect from welding sparks and open flame. • The material may be stored outside if the packaging is not
damaged.
Preparation • Apply the product on clean, dry surfaces.
Application • There is no heat-up cycle required for Knauf ET Blanket 1000°.• The product should be secured with welded pins or studs and
covered with sheet metal. An alternate method entails covering the insulation with a metal mesh and insulating cement, canvassing and painting.
• Pins and washers shall be located a maximum of 4" (102 mm) from each edge and spaced no greater than 16" (406 mm) on center.
• Care should be taken to avoid over compressing the insulation with the retaining washer.
• For application of Knauf ET Blanket 1000° over 450°F (232°C), double layer application is recommended.
THERMAL EFFICIENCY (ASTM C177)
Mean Temperature k k(SI)
100°F 38°C 0.28 0.040
200°F 93°C 0.38 0.055
300°F 149°C 0.52 0.075
400°F 204°C 0.70 0.101
500°F 260°C 0.90 0.130
STANDARD SIZES (ROLLS)
Thickness Width Length
1" 25 mm
48" 1219 mm
75' 22.90 m
1½" 38 mm 50' 15.20 m
2" 51 mm 75' 22.90 m
2½" 64 mm 60' 18.30 m
3" 76 mm 50' 15.20 m
3½" 89 mm 45' 13.70 m
4" 102 mm 40' 12.20 m
MADE-TO-ORDER SIZES
Thickness Width Length
1" 25 mm
24"36"48"
610 mm
914 mm
1219 mm
Custom
1½" 38 mm
2" 51 mm
2½" 64 mm
3" 76 mm
3½" 89 mm
4" 102 mm
Elevated Temperature Blanket 1000°Application
0.70
0.60
0.50
0.40
0.30
0.20
0.101
0.086
0.072
0.057
0.043
0.029
0-18
10038
20093
300149
400204
500260
(ûF)(ûC)
0.1150.80
Mean Temperature
o
o
Ther
mal
Con
duct
ivity
(BT
U-in
./hr •
ft2 ºF
)
Ther
mal
Con
duct
ivity
(SI U
nits
) (W
/m •
ºC)
13
14
Storage • Protect material from water damage or other abuse. • Protect from welding sparks and open flame. • The material may be stored outside if the packaging is not
damaged.
Preparation • Apply the product on clean, dry surfaces.
Application • There is no heat-up cycle required for Knauf ET Batt 1000° and
Knauf ET HD Blanket 1000°. • The product should be secured with welded pins or studs and
covered with sheet metal. An alternate method entails covering the insulation with a metal mesh and insulating cement, canvassing and painting.
• Pins and studs shall be located a maximum of 4" (102 mm) from each edge and spaced no greater than 16" (406 mm) on center.
• Care should be taken to avoid over compressing the insulation with the retaining washer.
• For application of Knauf ET Batt 1000° and Knauf ET HD Blanket 1000° over 500°F (260°C), double layer appliction is recommended with staggered joints.
THERMAL EFFICIENCY (ASTM C177)
Mean Temperature k k(SI)
100°F 38°C 0.24 0.035
200°F 93°C 0.33 0.048
300°F 149°C 0.44 0.063
400°F 204°C 0.57 0.082
500°F 260°C 0.72 0.104
ET BATT 1000° FORMS AVAILABLE
Thickness Width Length
1½" 38 mm
24" 610 mm 48" 1219 mm
2" 51 mm
2½" 64 mm
3" 76 mm
3½" 89 mm
4" 102 mm
HD BLANKET 1000° FORMS AVAILABLE
Thickness Width Length
1½" 38 mm
48" 1219 mm
120' 36.6 m
2" 51 mm 80' 24.4 m
2½" 64 mm 70' 21.3 m
3" 76 mm 60' 18.3 m
3½" 89 mm 50' 15.2 m
4" 102 mm 40' 12.2 m
Elevated Temperature Batt 1000° and HD Blanket 1000°Application
0.70
0.60
0.50
0.40
0.30
0.20
0.101
0.086
0.072
0.057
0.043
0.029
0-18
10038
20093
300149
400204
500260
(ûF)(ûC)
Ther
mal
Con
duct
ivit
y (S
l Uni
ts )
(W/m
• ºC
)
Ther
mal
Con
duct
ivit
y (B
TU-i
n./h
r • ft
2 ºF)
o
o
Mean Temperature
Elevated Temperature Series
1515
Storage • Protect material from water damage or other abuse. • Protect from welding sparks and open flame. • Vacuum packaged material can be store outside if care is taken
not to puncture the poly bag.
Preparation • Apply the product on clean, dry surfaces.
Application • There is no heat-up cycle required for Knauf ET Panel 1000°. • The product should be secured with welded pins or studs and
covered with sheet metal. An alternate method entails covering the insulation with a metal mesh and insulating cement, canvassing and painting.
• Pins and studs shall be located a maximum of 4" (102 mm) from each edge and spaced no greater than 16" (406 mm) on center.
• Care should be taken to avoid over compressing the insulation with the retaining washer.
• In temperatures over 550°F (288°C) and designed thickness over 3" (76 mm) dual layer application with staggered joints is recommended.
• When using the products at 1000°F (538°C), it is recommended that no more than 6" (152 mm) thickness should be used.
THERMAL EFFICIENCY (ASTM C177)
Mean Temperature k k(SI)
100°F 38°C 0.25 0.036
200°F 93°C 0.32 0.046
300°F 149°C 0.40 0.058
400°F 204°C 0.52 0.072
500°F 260°C 0.68 0.098
ET BATT 1000° FORMS AVAILABLE
Thickness Width Length
1½" 38 mm
24" 48"
610 mm 1219 mm
48"120"
1219 mm3048 mm
2" 51 mm
2½" 64 mm
3" 76 mm
3½" 89 mm
4" 102 mm
Elevated Temperature Panel 1000° Application
0.70
0.60
0.50
0.40
0.30
0.20
0.101
0.086
0.072
0.057
0.043
0.029
0-18
10038
20093
300149
400204
500260
(ûF)(ûC)
Ther
mal
Con
duct
ivit
y (S
l Uni
ts )
(W/m
• ºC
)
Ther
mal
Con
duct
ivit
y (B
TU-i
n./h
r • ft
2 ºF)
o
o
o
Mean Temperature
16
Elevated Temperature Series
FORMS AVAILABLE
Thickness Width Length
1" 25 mm
24"48"
610 mm1219 mm
24" to 120"610 mm to 3048 mm
1½" 38 mm
2" 51 mm
2½" 64 mm
3" 76 mm
3½" 89 mm
4" 102 mm
THERMAL EFFICIENCY (ASTM C177)
Mean Temperature k k(SI)
100°F 38°C 0.25 0.036
200°F 93°C 0.33 0.048
300°F 149°C 0.40 0.058
400°F 204°C 0.49 0.071
500°F 260°C 0.57 0.082
0.70
0.60
0.50
0.40
0.30
0.20
0.101
0.086
0.072
0.057
0.043
0.029
0-18
10038
20093
300149
400204
500260
(°F)(°C)
Mean Temperature
Ther
mal
Con
duct
ivit
y (S
l Uni
ts )
(W/m
• ºC
)
Ther
mal
Con
duct
ivit
y (B
TU-i
n./h
r • ft
2 ºF)
Storage • Protect material from water damage or other abuse. • Cartons are not designed for outside storage. • Vacuum packaged material can be stored outside if care is
taken not to puncture the polybag.
Preparation • Apply the product on clean, dry surfaces.
Application • All insulation joints must be firmly butted. Mount flush against
surfaces to 1000°F (538°C) or use in panels mounted away from operating surface.
• Knauf Insulation Elevated Temperature Board 1000° is designed to be applied over welded pins and/or studs up to ½" (13 mm) in diameter. The board is to be held in place by speed washers, tension clips or metal mesh reinforcement.
• Installation method should not compress material beyond maximum of 5% at any point.
• Pins and studs shall be located a maximum of 4" (102 mm) from each edge and spaced no greater than 16" (406 mm) on center.
• In temperatures over 550°F (288°C) and designed thickness over 3" (76 mm) dual layer application with staggered joints is recommended. Install thickness recommended by Knauf Insulation or NAIMA 3E Plus program.
• Finish surface with metal cover, or with insulating cement and canvas.
PackagingVacuum packaging Knauf Insulation Elevated Temperature Board will reduce some mechanical properties of the insulation. By ordering vacuum packaged products, the customer acknowledges these reduced properties and assumes responsibilities for the fitness for use in their application.
Elevated Temperature Board 1000°Application
17 17
Case Study:Renova Energy Ethanol Plant
Knauf Insulation was brought to the Wyoming Ethanol project through a partnership between insulation contractor DP Industrial and distributor International Technifab. For the Wyoming Ethanol expansion, DPI used Knauf Insulation 1000° Pipe Insulation, Kiwikflex® Pipe and Tank Insulation and Elevated Temperature (ET) Board. Jim Dunks of DPI has been pleased with the performance of all of these products, singling out Knauf Insulation 1000° Pipe Insluation for helping his crews stay busy and within budget.
”We’ve used other products that haven’t performed nearly as well,” he said. ”The paper [facing] falls off or doesn’t line up, or it’s not perfectly round. It’s a huge thing. Without the right product, the quality looks bad and your labor costs go up. It’s hard to recover from a situation like that.””We don’t have those problems with Knauf [pipe insulation].”
A variety of piping and equipment sizes in the Wyoming Ethanol facility confronted DPI’s crews. Manufacturing ethanol, from corn to fuel, takes the product through a series of processing and holding tanks. At the Torrington facility, these ranged from 1' x 4' to 15' x 45', with the tallest vessels rising four stories to nearly 80'. Special scaffolding was erected and moved from tank to tank as DPI workers insulated the largest of these. Nearly 11,000 linear feet of new piping ran throughout the buildings and between and among the tanks and equipment.
During the project, the new pipe and equipment was installed in the existing plant as well as in newly-constructed space that expanded the total area of the facility by 40%. In many cases, it was more cost-effective to retrofit the new vessels without removing the old, leading to space constraints that challenged installers.
Fortunately, Knauf Insulation offers a mix of products that allowed a smooth installation for all of these circumstances. Knauf Insulation 1000° Pipe Insulation for the small and large-bore piping, Knauf Insulation Kwikflex Pipe and Tank Insulation for the smaller and mid-sized vessels, and 15,000 square feet of Knauf Insulation Elevated Temperature Board for the large tanks. DPI Project Manager Dan Tobin has seen all of these products first-hand during his 23 years in the business. He was impressed again during the course of this 16-week installation.
A Solution for Every Challenge
"Knauf's pipe insulation is great to work with. It cuts smooth, with no loose fibers. You can tell it's wound better than other pipe insulation too, so it goes on easily.
— Dan Tobin, DPI Project Manager
18
Thermal Efficiency at Mean TemperatureGlass mineral wool products are inherently efficient insulators. The thermal efficiency chart, or ‘k curve’ chart at the left indicated the thermal performance of Knauf Earthwool 1000° pipe insulation across a range of mean temperatures.
3E Plus – A Valuable ToolThe 3E Plus software program can be used to determine: • Personnel protection• Heat loss calculations• Associated energy savings• Optimum insulation thickness• Condensation control• Greenhouse gas reduction
Based on ASTM C680, this software can calculate all of the above and more for horizontal and vertical pipes, for duct work and for tanks and vessels. Please see your local Knauf Insulation Territory Manager for a demonstration of 3E Plus software.
0
0.1
0.2
0.3
0.4
0.5
0.6
Earthwool
C547
Mean Temperature
k Va
lue
100°F 200°F 300°F 400°F
19
Hot Pipe• May be installed while the system is in operation, at all
temperatures up to 1000°F (538°C).• Maximum surface temperature of ASJ+ should not exceed
150°F (66°C).
Cold Pipe• Use a continuous vapor retarder on piping operating below
ambient temperatures.• Seal all joints, surfaces, seams and fittings to prevent
condensation.• On below freezing applications, and in high-abuse areas, the
product should be protected with a PVC vapor retarding outer jacket. In addition, exposed ends of insulation shall be sealed with vapor barrier mastic installed per the mastic manufacturer's instructions. Vapor seals at butt joints shall be applied at 12' to 21' intervals; at the Engineer’s discretion and at each fitting to isolate any water incursion.
• On below ambient water systems operating in high humidity conditions, it is recommended that the same guidelines be followed as listed above for below freezing applications.
Outside Applications• Do not expose pipe insulation to weather. It must be covered
with appropriate jacketing, mastic or vapor retardant coatings.• All exposed surfaces must be protected.
Storage• Protect insulation from water damage or other abuse, welding
sparks and open flame.• Cartons are not designed for outside storage. • Vacuum packaging is available to maximize shipping. Vacuum
packaging Knauf Insulation Pipe Insulation will reduce some mechanical properties of the insulation. By ordering vacuum packaged products, the customer acknowledges these reduced properties and assumes responsibilities for the fitness for use in their application.
General Guidelines• All sections should be firmly butted. Seal circumferential joint
with a minimum 4" (102 mm) wide butt strip.
• All piping should have continuous insulation.• Position longitudinal lap at top to minimize dirt and
moisture accumulation.• Insulation thickness must be adequate to assure 150°F (66°C)
exterior surface temperature maximum for personnel protection.
Earthwool® 1000° Pipe Insulation & Earthwool® Redi-Klad® 1000° Pipe Insulation
Redi-Klad• Keep adhesive and contact surfaces free from dirt and water,
and seal immediately once adhesive is exposed Earthwool Redi-Klad 1000° Pipe Insulation should be installed in dry conditions with no moisture present.
• Apply when ambient and insulation surface temperatures are between 0°F and 130°F (-18°C and 54°C).
• If stored below 0°F or above 130°F, allow insulation cartons to stand within recommended temperature range for 24 hours prior to application.
• Do not store product below -20°F (-29°C) or above 150°F (66°C).
• When using Knauf Insulation's Redi-Klad closure system, make sure the longitudinal and circumferential joints are properly sealed by rubbing the closure firmly with a squeegee.
• When using Knauf Earthwool Redi-Klad 1000° Pipe Insulation, the surface temperature of the insulation should not exceed 150°F (66°C) during the life of the insulation.
Fittings and Hangers• Use metal, PVC, or Proto EXOD 225 CPVC fitting covers.
For below ambient piping systems, caution should be taken to prevent punctures, tears, or rips in Redi-Klad vapor barrier. Additionally, all fitting insulation surfaces must have independent, field applied vapor barriers. Prior to installing fitting insulation, all exposed ends of pipe insulation sections must be vapor sealed.
• Fittings should be insulated to same thickness as the adjoining insulation.
• Apply fittings per manufacturer's instructions.• When required by specification, a hard insert of sufficient
length should be used to avoid compression of the insulation.
Additional Precautions• Glass mineral wool may cause temporary skin irritation. Wear
long sleeved, loose-fitting clothing, head covering, gloves and eye protection when handling and applying material.
• Wash with soap and warm water after handling.• Wash work clothes separately and rinse washer.• Use a disposable mask/respirator designed for nuisance-type
dusts where sensitivity to dust and airborne particles may cause irritation to the nose or throat.
Preparation• Apply only on clean, dry surfaces.• Pipe or vessel should be tested and released before insulation is
applied.
Precautions & Application Guidelines
20
Elevated Temperature Series
Precaution • FSK and ASJ+ jackets should not be used if outer-surface
temperature exceeds 150°F (66°C).
Storage • Protect stored insulation from water damage or other abuse.• Protect from welding sparks and open flame.• Cartons are not designed for outside storage.
Preparation • Apply Knauf Insulation Earthwool Pipe and Tank Insulation on
clean, dry surfaces.
Application For easy installation of Knauf Insulation Earthwool Pipe and Tank Insulation, simply follow these guidelines.
• Refer to the Stretch-Out Chart to find the appropriate length to cut for the specific pipe size. Be sure to add an additional 2" (51 mm) to 4" (102 mm) for your staple flap.
• Cut your stretch-out length and wrap the material around the iron pipe to ensure the proper fit.
• Staple the lap on 3" (76 mm) centers with outward clinching staples.
• Butt edges shall be firmly secured, and butt strips matching the jacket shall be applied at each joint.
PackagingVacuum packaging Knauf Insulation Earthwool Pipe and Tank insulation will reduce some mechanical properties of the insulation. By ordering vacuum packaged products, the customer acknowledges these reduced properties and assumes responsibilities for the fitness for use in their application.
Precautions • ASJ, FSK and PSK jackets should not be used if outer-surface
temperature exceeds 150°F (66°C).
Storage • Protect stored insulation from water damage or other abuse.• Protect from welding sparks and open flame.• Packages are not designed for outside storage.
Preparation • Apply Knauf Insulation KwikFlex Pipe and Tank Insulation on
clean, dry surfaces.
Kwik-Flex® Pipe & Tank Insulation
Precautions & Application Guidelines
Pipe & Tank Insulation
Precuations & Application Guidelines
Precaution
• During initial heat-up to operating temperatures above 350°F (177°C), a slight odor and some smoke may be given off as a portion of the bonding material used in the insulation begins to undergo a controlled decomposition.
• If natural convection is not adequate in confined areas, forced ventilation should be provided in order to protect against any harmful fumes and vapors that might be generated.
Website
© 2016 Knauf Insulation, Inc.
www.knaufinsulation.us
Information [email protected]
Fax (317) 398-3675
Technical Support (800) 825-4434, ext. 8512
Sales (800) 825-4434, ext. 8300
Knauf Insulation, Inc.
One Knauf Drive
Shelbyville, IN 46176
Versions of this product have surface burning characteristics that are classified by Underwriters Laboratories and therefore subject to audition for fire performance compliance.
This product has been tested and is certified to meet the EUCEB requirements
This product has been tested and is certified to meet the US Coast Guard requirements
This product is covered by one or more U.S. and/or other patents. See patent www.knaufinsulation.us/patents.